MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring_ system control panel by the technician who performs the work. A copy ofthis form must be provided to the tank system owner /operator.
The owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: PANAMA BUENA VISTA U.S.D. Bldg. No.:
Site Address: 4200 ASHE RD. City: BAKERSFIELD Zip: 93313
Facility Contact Person: VICKI STALNAKER
Make/Model ofMonitoring System: TLS -350 INSP.- ESTER ON-SITE
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced:
Contact Phone No.:
Date of Testing/Servicing: 3/23/2012
Tank ID: REGULAR 87 Tank ID: DIESEL
In -Tank Gauging Probe. Model: MAGIn -Tank Gauging Probe. Model: MAG
Annular Space orVault Sensor. Model: 420 Annular Space or Vault Sensor. Model: 420
Piping Sump / Trench Sensor(s). Model: 208 Piping Sump/ Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: FX1V Mechanical Line Leak Detector. Model: FXiDV
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: MAG / E.O.A. Tank Overfill / High -Level Sensor, Model: MAG / E.O.A.
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank ID: WASTE OIL Tank ID:
In -Tank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: 420 Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: N/A Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: 112 Dispenser 1D: 314
Dispenser Containment Sensor(s). Model: 208 Dispenser Containment Sensor(s). Model: 208
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Ifthe facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy ofthe report; (check all that apply): ® System set -up Alarm history report
Technician Name (print): RYAN MASON Signature: 1
Certification No.: A27367 ICC# 8029371 -UT License. No.: 611 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 392 -8687
Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308 Date ofTesting/Servicing: 3/23/2012
Page 1 of 5
UN4M -1/4 www.unidomorg Rev. 01 /17/08
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 329.01
Complete the following checklist:
LraaLl f
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down ifthe piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; ® Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfiil warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? if so, at what percent of tank capacity does the alarm trigger? 90%
Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. Ifyes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, ifapplicable
Yes No* Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 5
UN -036 — 2/4 www.unidocs.org Rev. 01/17108
Monitoring System Certification
F. In -Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section trust be completed ifin -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. ]Line Leak Detectors (LLD):
Cmmnlete the following checklist:
Check this box if LLDs are not installed.
Yes No* For equipment start -up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: ® 3 g.p.h.; 0.1 g.p.h ; [10.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
N/A
Yes No* for electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion ofthe monitoring system malfunctions
N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
UN-036 — 3/4
Page 3 of 6
www.unidocs.org Rev. 01117/08
0-.. A':i ,. C,!. - I.: 1h 1- w -A. It, r. y1
A, -7:4 4
1A :s 7
77
ep.
7.
r. t! L7 iV 4:' Y! rill e-. i! F,
rt". 71 r.: 'f IJAIt
iv! Q 1. - J 4 M-ft" ..I
w
t:t -iz
Tf t? I I!'
ro P£
wp Y. k;
ly
tt 0; W A. 'a q 1i ot 'A a R 134 1T Y. "I k 4 'el
41
t 's
4 V 'di
T., 7 ;1% i4 1' 4 i A
1 1 ^R n 1. ( .0 .3 :S is S4
1; 7c tr. r,.; 1; 'A 01 1
A..
PP, t:i 1. :6 tl W. 3- :1 7, t
er
5:A.-
Aid$
1 --20e, %-
RICH ENVIRONMENTAL
3305 BRITTAN ST. BAKERSFIELD, CA. 93308
OFFICE (661)326 -8402 FAX (661)326 -8934
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
W /0 #:
FACILITY NAME: PANAMA BUENA VISTA SCHOOL DISTRICT
FACILITY ADDRESS: 4200 ASHE RD. BAKERSFIELD, CA.
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL87 L/D TYPE : FXl V
YES 10 P.S.I. PASS
SERIAL # 1783
DIESEL L/D TYPE: FX1DV
YES 10 P.S.I. PASS
SERIAL # 7883
L/D TYPE: _ PASS
YES
SERIAL # FAIL
L/D TYPE: PASS
YES
SERIAL # FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED 1S TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RYAN MASON
SIGNATURE: i DATE: 3/23/12
p.
S -6Z-1 fSWRCB, January 2006
Spill Bucket 'Testing Report Form
Thisform is intendedfor use by contractors performing annual testing of USTspill containment structures. The completedform and
printoutsfrom tests (tfapplicable), should beprovided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACiQ.ITY INFORMATION
Facility Name: PANAMA BUENA VISTA U.S.D. Date ofTesting: 3/23/2012
Facility Address: 4200 ASHE RD. BAKERSFIELD, CA. 93313
Facility Contact: VICKI STALNAKER Phone:
Date Local Agency Was Notified ofTesting:
Name of Local Agency Inspector (ifpresent during testing): ESTER
Y 1 YY: _ M 7a1 19T 7.7JE`IYCe7 1
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RYAN MASON
Credentials: 0 CSLB Contractor X ICC Service Tech. SWRCB Tank Tester 0 Other (Specify)
License Number(s): 8029371 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum 0 Other
Test Equipment Used: VISUAL Equipment Resolution: 0
Identify Spill Bucket (By Tank
N,ulnber, $tored Product, etc.
1
REGULAR 87 -FILL
2
WASTE OIL
3
DIESEL FILL
4
Bucket Installation Type: X Direct Bury
0 Contained in Sump
X Direct Bury
Contained in Sump
X Direct Bury
0 Contained in Sump
Direct Bury
0 Contained in Sum
BucketDimneter. 12" 12" 12"
c]cpt,Llepth; 14" 14" 14"
Wait time between applying
vacuum/water and start oftest: 30 MIN 30 MIN 30 MIN
Test Start Time (T): 0900 1000 0900
Initial Reading (RO: 12" 12" 12"
Test End Time (TF): 1000 1100 1000
Final Reading. (RF): 12" 1211 12"
Test•Duration (TF — TO: 1 -HOUR 1 -HOUR 1 -HOUR
Change in Reading (RF - Ri): 0 0 0
Pass/Fail Threshold or
Criteria: 0.00 0.00 0.00
X Pass Fail X Pass Fail X Pass Fail Pass Fail
C_+ Offiffients — (include information on repairs made prior to testing, andrecommendedfollow -up forjailed tests)
Ar .
w
C-FR41FICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
1 herdby cw* that all the information contained in this report is true, accurate, and Infull compliance with legal requirements.
i
Tophnician's Signature:` Date: 323/12
i.. State laws and regulations do nWcurrently require testing to be performed by a qualified contractor. However, local requirements66niorestringent.
g
COMMUNICATIONS •SETUP - - IN-TANK SETUP- _
V_ _ - -
T 1 :DIESEL
SOFTWARE REVISION LEVEL
PORT SETTINGS: PRODUCT CODE 1
THERMAL COEFF :.000450
VERSION 329.01 COMM BOARD : 5 (RS -485) TANK DIAMETER 95.00
TANK PROFILE : 20 PTSSOFTWARE# 346329 - 100 -BCREATED - 09:01.29.15.44
BAUD RATE 2400
PARITY EVEN FULL VOL : 12153
STOP BIT : 1 STOP 90.3 INCH VOL : 11926
NO SOFTWARE - MODULE DATA LENGTH: 7 DATA 85.5 INCH VOL : 11520
80.8 INCH VOL 11016SYSTEMFEATURES:
PERIODIC IN -TANK TESTS
RS -232 SECURITY
CODE : DISABLED 76.0 INCH VOL 10423
ANNUAL IN -TANK TESTS 71.2 INCH VOL 9770
66.5 INCH VOL 9087COMMBOARD6 (RS -232)
BAUD RATE 1200 61.7 INCH VOL : 8355
PARITY ODD 57.0 INCH VOL 7614
STOP BIT : 1 STOP 52.2 INCH VOL : 6841
DATA LENGTH: 7 DATA 47.5 INCH VOL 6076
42.7 INCH VOL : 5295RS -232 SECURITY
CODE : DISABLED 38.0 INCH VOL : 4539
33.2 INCH VOL : 3782
28.5 INCH VOL 3066
SYSTEM SETUP AUTO TRANSMIT SETTINGS: 23.7 INCH VOL 2368
19.0 INCH VOL 1730
AUTO LEAK ALARM LIMIT 14.2 INCH VOL 1136
MAR 23. 2012 12 :02 PM DISABLED 9.5 INCH VOL : 633
4.7 INCH VOL 224AUTOHIGHWATERLIMIT
DISABLED
SYSTEM UNITS AUTO OVERFILL LIMIT
DISABLED FLOAT SIZE: 4.0 IN.
U.S.
SYSTEM LANGUAGE AUTO LOW PRODUCT
DISABLED LATER WARNING : 2.0
ENGLISH AUTO THEFT LIMIT HIGH WATER LIMIT: 3.0
SYSTEM DATE /TIME FORMAT DISABLED.
MON DD YYYY HH:MM:SS xM AUTO DELIVERY START MAX OR LABEL VOL: 12153
DISABLED OVERFILL LIMIT
953
PANAMA BUENA VISTA AUTO DELIVERY END 10937
4200 ASHE RD DISABLED HIGH PRODUCT
937
BAKERsFIELD CA AUTO EXTERNAL INPUT ON 1154545DISABLEDDELIVERYLIMIT
AUTO EXTERNAL INPUT OFP 1215
SHIFT "TIME.1 : 1:00 AMSHIFT; TIME 2 : DISABLED
DISABLED
AUTO SENSOR FUEL ALARM LOW PRODUCT : 10U0
SHIFT TIME 3 : DISABLED DISABLED IOC
ROC
LIMIT: 50
SHIFT TIME 4 : DISABLED AUTO SENSOR WATER ALARM SUDDEN LOSS LIMIT: 50
DT TANK TILT 0.25
TANK PER TST NEEDED WRN AUTOTO SENSOR OUT ALARM PROBE OFFSET 0.00
DISABLED DISABLED
TANK ANN TST NEEDED WRNDISABLED SIPHON MANIFOLDED TANKS
Ti9: NONE
LINE RE- ENABLE METHOD LINE MANIFOLDED TANKS
PASS LINE TEST T#: NONE
LINE PER TST NEEDED WRNDISABLED' LEAK M i N PER IODI.01. 3390
LINE ANN TST NEEDED WRN RS -232 END OF MESSAGE 4010
DISABLED DISABLED LEAK MIN ANNUAL 501
PRINT TC VOLUMES 6076
ENABLED
TEMP. COMPENSATION PERIODIC TEST TYPE
VALUE:(DEG F ): 60.0 STANDARE
STICK HEIGHT OFFSET
DISABLED ANNUAL TEST FAIL
iULLAGE:. 90%. ALARM DISABLEI
tklrPROTOCOL'DATA FORMAT PERIODIC TEST FAIL
HEIGHT •" ALARM DISABLEI
SAVING TIMEENABLED GROSS TEST FAIL
START DATE ALARM DISABLE:
WEEK 2 SUNSTASTARRT .'fI ME ANN TEST AVERAGING: OF
2:00 AM PER TEST AVERAGING: OF
END DATE
NOV WEEK I SUN TANK TEST NOTIFY: OF
END TIME
2:00 AM TNK TST SIPHON BREAK:OF
RE- DIRECT LOCAL PRINTOUT DELIVERY DELAY : 3 MI
DISABLED PUMP THRESHOLD 10.00
EURO PROTOCOL PREFIX
T 2:UNLEADED T 3:WASTE OIL
PRODUCT CODE 3
TRHERMAL CODEFF :.000700 THERMAL COEFF :.000470
TANK DIAMETER 95.00 TANK DIAMETER
TANK PROFILE
46.00
1 PTTANKPROFILE20PTS
FULL VOL 12153 FULL VOL 550
90.3 INCH VOL 11928
85.5 INCH VOL
INCH.VOL
11520
11016 FLOAT SIZE: 4.0 IIN.
76.0 INCH VOL
71.2 INCH VOL
10423
9770 WATER WARNING 5.0
66.5 INCH VOL 9087 HIGH WATER LIMIT: 5.0
61.7 INCH VOL 8355
57.0 INCH VOL 7614 MAX OR LABEL VOL:
OVERFILL LIMIT
550
90/152.2 INCH VOL 6841
47.5 INCH VOL 6076 495
42.7 INCH VOL 5295 HIGH PRODUCT 95%
38.0 INCH VOL : 4539 52% 33.2 I.NCH VOL 3782. DELIVERY LIMIT
28.5 INCH VOL 3066 5
23.7 INCH VOL 2368
1.0 INCH VOL 13 LOW PRODUCT I
144.2 INCH VOL 111366 LEAK ALARM LIMIT: 99
5 INCH VOL 633 SUDDEN LOSS LIMIT: 99
44.7 INCH VOL : 224 TANK TILT 0.00
PROBE OFFSET 0.00
FLOAT SIZE: 4.0 IN. SIPHON MANIFOLDED TANKS
WATER WARNING 2.0 Tit: NONE
HIGH WATER LIMIT: 3.0 LINE MANIFOLDED TANKS
TO: NONE
MAX OR LABEL VOL: 12153
OVERFILL LIMIT 90%
10937 LEAK MIN PERIODIC: 0%
HIGH PRODUCT 95% 0
11545
DELIVERY LIMIT 10% LEAK MIN ANNUAL 0%
1215 0
LOW PRODUCT 1000
LEAK-ALARM LIMIT: 50 PERIODIC TEST TYPE
SUDDEN LOSS LIMIT: 50 STANDARD
TANK TILT 1.25
PROBE 'OFFSET 0.00 ANNUAL TEST FAIL
ALARM DISABLED
SIPHON MANIFOLDED TANKS PERIODIC TEST FAIL
TO: NONE ALARM DISABLED
LINE MANIFOLDED TANKS
TO* NONE FAILGROSSTEST
ALARM DISABLED
LEAK MIN PERIODIC: 33% ANN TEST AVERAGING: OFF
4010 PER TEST AVERAGING: OFF
LEAK. MIN ANNUAL 50% TANK TEST NOTIFY: OFF
6076 TNK TST SIPHON BREAK:OFF
PERIODIC TEST TYPE DELIVERY DELAY 1 MIN
STANDARD PUMP THRESHOLD : 10.00%
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 3 MIN
PUMP - THRESHOLD 10.00%
LEAK _TEST METHOD
TEST ON DATE : ALL TANK
JAN 29. 2009
START TIME : DISABLED
TEST
DURATION :0220HOURS
TST EARLY STOP:DISABLED
LEAK TEST REPORTNFORMAT
LIQUID SENSOR- SETUP-
L 1:UNLEADED ANNULAR
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 2:UNLEADED STP SUMP
TRI-STATE (SINGLE
SUMP
L 3:DIESEL ANNULAR
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 4:DIESEL STP SUMP
TRI-STATE (SINGLE
UM
L 5 :DISPENSER 1 2
TRI-STATE
CATEGORY DISPENSER PAN
L 6:DISPENSER 3 4
CATEGORY : (SINGLE
DISPENSERPAP
L 7:WASTE OIL
TRI -STATE (SINGLE FLOAT'.
CATEGORY : OTHER SENSOR
a W&T VQTR TTMP -S
ALARM HISTORY REPORT ALARM HISTORY REPORT
OUTPUT RELAY SETUP
SYSTEM ALARM - - - -- IN -TANK ALARM -
PAPER OUT
R 1:UNLEADED SHUTDOWN OCT 24, 2011 1:04 PM T 2:UNLEADED
TYPE: PRINTER ERROR
STANDARD DEC 23, 2011 12:18 PM HIGH PRODUCT ALARM
NORMALLY CLOSED MAR 4, 2011 9:08 AM
MAR 18, 2010 9 :20 AM
IN -TANK ALARMS PROBE OUT
T 2:HIGH WATER ALARM MAR 31, 2011 2:36 PM
T 2:LOW PRODUCT ALARM MAR 4, 2011 9:09 AM
MAR 4, 2011 9:08 AM
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 6:FUEL ALARM DELIVERY NEEDED
L 2:SENSOR OUT ALARM END * * * MAY 24, 2010 4:09 PM
L 6:SENSOR OUT ALARM
MAX PRODUCT ALARM
PMC ALARMS MAR 4, 2011 9:08 AM
VP PRESSURE FAIL MAR 18, 2010 9:20 AM
R 3:
TYPE:
STANDARD
NORMALLY CLOSED
IN -TANK ALARMS ALARM HISTORY REPORT
T 1:HIGH WATER ALARM
T 1:LOW PRODUCT ALARM IN -TANK ALARM - - - --
LIQUID SENSOR ALMS T 1:DIESEL END
L 4:FUEL ALARM
L 5:FUEL ALARM LOW PRODUCT ALARM
L'4:SENSOR OUT ALARM OCT 5. 2010 3:50 PM
L.5:SENSOR OUT ALARM
HIGH PRODUCT ALARM
R•4:. MAR 4, 2011 9:13 AM
TYPE: MAR 18, 2010 9:20 AM
STANDARD
NORMALLY CLOSED PROBE OUT
MAR 31, 2011 2:28 PM
MAR 30, 2011 12:04 PM
IN -TANK ALARMS MAR 30, 2011 3:16 AM ALARM HISTORY REPORT
ALL:OVERFILL ALARM
ALL:H:IGH PRODUCT ALARM IN -TANK ALARM - - --
ALL:MAX PRODUCT ALARM DELIVERY NEEDED
OCT 5, 2010 11:25 AM T 3:WASTE OIL
MAX PRODUCT ALARM
MAR 4, 2011 9:13 AM
MAR 18, 2010 9:20 AM
SMARTSENSOR SETUP
END x *a
s 1 :CCVP
CATEGORY VAPOR VALVE
x* x x* END X*** X
s 2:PRESSURE SENSOR
CATEGORY VAPOR PRESSURE
s 8-:ATM
CATEGORY ATM P SENSOR
ALARM HISTORY REPORT
SENSOR ALARM - --
L 1:UNLEADED ANNULAR
ANNULAR SPACE
FUEL ALARM
MAR 23, 2012 9:49 AM
SENSOR OUT ALARM
MAR 4, 2011 9:22 AM
PMC SETUP
FUEL RM
PMC VERSION: 01.02 MAR 42011 9:07 AM
VAPOR PROCESSOR TYPE
VEEDER -ROOT POLISHER
a W&T VQTR TTMP -S
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 2:UNLEADED STP SUMP
STP SUMP
FUEL ALARM
MAR 23, 2012 9:48 AM
FUEL ALARM
OCT 14, 2011 8:57 AM
SENSOR OUT ALARM
MAR 4. 2011 9:22 AM
END # x x * 4
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:DIESEL ANNULAR
ANNULAR SPACE
FUEL ALARM
MAR. 23. 2012 9:52 AM
SENSOR OUT ALARM
OCT 24, 2011 1:04 PM
FUEL ALARM
OCT 24. 2011 1:03 PM
END * * * * *
ALARM HISTORY REPORT
SENSOR ALARM --
L 4:DIESEL STP SUMP
STP SUMP
FUEL ALARM
MAR 23. 2012 9:51 AM
SENSOR OUT ALARM
MAR .4. 2011 9:22 AM
FUEL ALARM
MAR 4. 2011 9:17 AM
ALARM HISTORY REPORT y -J-6 L-1
SENSOR ALARM - - - --
L 5:DISPENSER I 2
DISPENSER PAN
FUEL ALARM
MAR 23, 2012 10:20 AM
FUEL ALARM
MAR 23, 2012 9:50 AM
SENSOR OUT ALARM
MAR 4. 2011 9:22 AM
A * * * * END * * * *
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 6:DISPENSER 3 4
DISPENSER PAN
FUEL ALARM
MAR 23, 2012 10:14 AM
FUEL ALARM
MAR 23, 2012 9:50 AM
SENSOR OUT ALARM
MAR 4, 2011 9 :22 AM
A * * * * END * * * * *
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 7:WASTE OIL
OTHER SENSORS
FUEL ALARM
MAR 23, 2012 9:57 AM
FUEL ALARM
MAR 4. 2011 10:59 AM
SENSOR OUT ALARM
MAR 4. 2011 9:22 AM
4ssIA ///
MONITOR CERT. FAILURE REPORT
SITE NAME : PANAMA BUENA VISTA U.S.D. DATE: 3/23/12
F.Tia
THE FOLLOWING COMPONENTS WERE REPLACED/REP,iRED 7 COMPLETE
TESTING.
REPAIRS: NONE
LABOR: NONE
PARTSINTALLED: NONE
NAME: TITLE:
SIGNATURE:
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.