MONITORING SYSTEM CERTIFICATION
For Use ByAll: Jurisdictions Within the State ofCalifornia
Authority Cited. • Chapter 6.7; Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used - to document .testing and servicing of monitoring equipment A ;separate certification or iCD A Rlt t, be pramEgg for each
monitoring system contrDl Mel by the technician who performs the work. A copy ofthis form must.be provided to the tank system owner /operator.
The owner /opemor must submit a copy ofthis.form to, the local agency regulating UST`systems within 30 days oftest date. 4
A. General Information
Facility Name: PANAMA BUENA VISTA U.S.D.
Site Address: 4200 ASHE RD. City: BAKERSFIELD Zip: 93313
Facility Contact Person: VICKI 'STALNAKER Contact Phone No.: )
Make/Model of Monitoring System: TLS.350 INSP.- ESTER AND ERNIE Date ofTesting/Servicing: 3/412011
Bldg. No.:
B. Inventory of Equipment Teste&Certified
rh"k the annrnnrisatp hmpt to in&"tp sneeIrw enninment tnmeeted /aprviovd:
Tank ID: REGULAR 87 Tank 1[D: DIESEL
In-Tank Gauging Probe. Model: MAG in -Tank Gauging Probe. Model: MAG
Annular Space or Vault Sensor. Model: 420 AnnularSpace;or VaultSensor. Model :_ 420
Piping Sump/ Trench Smsor(s). Model: 208 Piping Sump / Trench Sensor(s). Model; 208
Fill Sump Sensor(s). model. Fill Sump Sensor(s). Model•
Mechanical Line leakDeuoctor. Model: FX1V Mechanical Liao LeakDetector. Model: FX1 D1/
Electronic Line Leak Detector. Model: Electronic LineLeak Detector.. Model:
0-Tank Overfill / Hiigh -Level Sensor. Model: MAGI E.OA Tank Overfill / High -Level Sensor. Model: MAGI E.O.A.
Other (specify equipment type and model in Section E on Page,2). Other. (specify equipment type and model in,Section E on Page2).
Tank ID: WASTE OIL TankID:
In -Tank Gauging Probe. Model: MAG In-Tank Gauging Piobi:. Model: .
Annular Space or Vault Sensor. Model: 420 Annular Space orVaultSensor. Model:
Piping Sump / TrenchSensor(s). Model: Piping Sump / Trench Sensor(s). Model:
THFSump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model: .
Electronic Line Leak Detector. Model` Electronic Line Leak Detector. Model:
Tank Overfill /.High-Level Sensor. Model: WA Tank Overfill / High -Level Sensor. Model:
Other (specify equipmenttype and model in Section E on Page4 Other (specify equipment type and model in Section E,on Page 2).
Dispenser ID: 112 Dispenser ID : 314
Dispenser ContainmentSensor(s). Model: 208 Dispenser Containment Sensor(s). Model: 208.
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). DispenserContainment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: DispenserContainment Sensor(s). Model:
C] ShearValve(s). ShearValve(s).
C] Dispenser Containment Float(s) and Chain(s). Dispemsor Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). ShearValve(s).
DispenserContainment.Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s)..
Ifthe facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at -the facility.
C. Certification.- I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information' (e g.. manufacturers' checklists) necessary to verify that this information is
correct and a PlotPlan showing the:layout of monitoring a uipment. For any. equipment capable of generating: such reports. I have also
attached a copy of the report; (chmk allthat apply): System set -up , Alarm history report
Technician Name (prim): STEVEN OBERT Signature:
Certification No.: A2M1 18029980 -UT License. No.: C611 D40 '809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 326.8402
Testing Company Address: 3305 BRfTTAN RD. BAKERSFIELD, CA. 93308 Date ofTesting/Serdicing: 3/4/2011
Page 1 of 6.
UN -036 — 114 www.unidocs.org Rev. 01117/08
Monitoring System Certification
D. Results ofTesting/Servicing
Software Version Installed: 329.01
rmmnlete the tntlnwino ehoekl st!
o3lb
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point ofsecondary containmcnt_and positioned so that other equipment will
not interferemith their, proper operation?
Yes No* If alarms are relayed . to a remote monitoring station,. is all communications equipment' (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or.is electrically disconnected? ,if yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; ® Dispenser Containment Sensors.
Did you confirm positive shut =down due to leaks —and sensor. failure/disconnection? ® Yes; .No.
Yes No* For tank systems "that utilize "the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill - warning alarm, visible and audible at the tank
fill point(s) and operatingproperly? Ifso, at what.percent oftank capacity does.the alarm trigger?. W/o
Yes* No Was any monitoring equipment replaced? Ifyes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. Ifyes, describe causes in Section E, below.
Yes No Was monitoring system. set -up reviewed to ensure proper settings? Attach set up reports,_if applicable
Yes 1.0 No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 5
UN -036 — 2/4 www.unidoes.org Rev..Ot/17/08
Monitoring System Certification
tJo31b
F. In -Tank Gauging / SIR Equipment: ®Check.this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed ifin -tank gauging equipment is used to perform leak detection. monitoring.
Complete the following. checklist:
Yes No* Has all input wiring been inspected :for proper- entry and termination, including testing for ground faults?
Yes p No* Were all tank gauging.probes visually inspected for,damage . and residue buildup?
Yes No* Was accuracyofsystem product level readings tested?
Yes No* Was accuracy of system water level readings tested ?.
Yes No* Were all probes. reinstalled.properly?
Yes No* Were all items on the equipment manufacturer's. maintenance checklist completed?
In Sectiowl%. below, describe bow and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): [] Check :this•box ifLLDs are not installed
Comnlete the fnlinwina eherkliat!
Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: 19 3 g.p.h.; [:10. 1 : g p.h ; 02 g.p.h.
Yes No* Were all LLDs confirmed operational.and accurate within regulatory. requirements?
Yes No* Was the testing apparatus properly calibrated?
g Yes No* For mechanical LLDs, does theLLD restrict product -flow ifit detects a leak?
N/A
Yes No* For electronic. LLDs, does -the turbine automatically shut offifthe LLD detects a leak?
g NIA
Yes No* For electronic LLDs,.does the turbine automatically shut off if any portion ofthe monitoring:system is disabled
g N/A . or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off ifany portion ofthe monitoring system malfunctions
g N/A or fails a test?
Yes No* For electronic LLDs; have all accessible wiring connections been visually inspected?
g N/A
Yes No* Were all items on the equipment manufacturer'smaintenance checklist completed?
In Section H, below, describe how and when these •deficiencies .were or will be corrected:
H. Comments:
Page 3 of 5
UN-036 -314 www.unidomorg Rev. 01/17/08
Monitoring,System Certification Form: Addendum for Vacuum/Pressu"re Interstitial Sensors
I. Results of Vacuum/Pressure Monitoring Equipment Testing
90110
This page should be used to document testing and 'servicing of vacuum and pressure interstitial sensors. A. copy of
this form must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner /operator: The owner /operator must submit a copy of the Monitoring System Certification Form to the
local agency regulating UST systems within 30. days oftest date.
Manufacturer: NIA Model: System Type: Pressure; [] Vacuum
Sensor ID
Component(s) Monitored bythis Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication T est:Result Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result :. []'Pass; [ Fail Interstitial Communication TestResult: Q Pass; Fail
Component(s) Monitored, by this Sensor:
Sensor Functionality Test Result: Pass; Fail:. Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:,
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Mterstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Resul Pass; [:].Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: . Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result[] Pass; . Fail Interstitial'Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor.
Sensor.Functionality Test Result:. Pass; E] Fail Interstitial Communication Test. Result El Pass; El Fail
How was interstitial communication verified?
Leak Introduced at Far End.of Interstitial Space;' Gauge; Visual Inspection; Other (Describe 1h Sec. J, below)
Was vacuum/pressure restored to operating levels in all interstitial spaces? Yes No (Ifno, describe in Sec. J, below)
J. Comments: NONE OF THESE.SENSORS ARE PRESENT AT THIS SITE.
Page 4 of 5
If the sensor succcessfully detects a simulated vacuum /pressure; leak introduced in the interstitial space at the fiirthest point from thesensor, vacuumtpressure has been demonstirated to be communicating throughout the interstice.
UN -036A -4/1 www.unidocLorg Rev. 0112GJ06
UST Ntbo MWIYU4
U ", R
A ) 04L
i 40:
WOt -A
t. It". T t, i hi Fa .1
1: 'F f it f:; a 0. P! J, Y lz }x Y -'s 7, :,J: 4 A 14 c A 'w
K tf. J, Jt I I Ai
wi i`j .. ,r i
41, liy J' N. :1 fit -M 't r I A
if
IL it r. I P v
A wC;i 4' il,
I :v ;Z: Z7
io, el 6
71! S j V, if. if it il
K A
4 W
K V9
4 K-
71.
t
it
ui
it 1 1, e
t4t.
te
I v It
w 3 %i,;
Z t Ji Ti t w j" O,A, t
it 1;
yv it :t wo 4 1 A 4 all
ME
t
RICH ENVIRONMENTAL
3305 BRITTAN ST. BAKERSFIELD, CA. 93308
OFFICE (661)326 -8402 FAX (661)326 -8934
PRODUCT LINE LEAK DETECTOR TEST
WORKSHEET
W /0#•
FACILITY NAME: PANAMA BUENA VISTA SCHOOL DISTRICT
FACILITY ADDRESS: 4200 ASHE RD. BAKERSFIELD, CA.
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAKDETEC"rOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL$7 L/D TYPE : FX1V
10 P.S:I. PASS
SERIAL #
1783S
DIESEL L/D TYPE • FX1DV
YES 10 P.S,L PASS
SERIAL # 7883
LID TYPE:..- PASS
YES
SERIAL # FAIL
L/D TYPE: PASS
YES
SERIAL # FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON, THIS DATE ACCORDING TO.RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND'LEMTATIONS.
THE MECHANICAL LEAK DETECTOR 'TEST PASS / FAIL IS DETERMINED BY USING.A.
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THATALLDATA COLLECTED IS TRUE AND CORRECT TO "THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: STEVENOBERT
SIGNATURE: DATE: 314111
403516
t
SWRCB, January 2006'
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annualtesting ofUSTspill containment structures. The completedform and
printoutsfrom tests (ifapplicable); should beprovided to thefacility owner /operatorfor submittal to the local regulatory agency.
1: FACILITY INFORMATION
Facility Name: PANAMA BUENA VISTA U:S.D. Date ofTesting: 3/411011'
Facility Address: 4200 ASHE RD. BAKERSFIELD, CA. 93313
Facility Contact: VICKI STALNAKER: Phone:
Date Local Agency Was Notified ofTesting: 1!27/2011
Name ofLocal Agency Inspector (rfpresent duringtesting}: ERNIE AND ESTER
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: STEVEN OBERT
Credentials: CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s): :80299MUT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Vacuum ,Other
Test Equipment Used: VISUAL Equipment Resolution: 0
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
1
REGULAR 87-FELL
2
WASTE OIL
3
DIESEL FILL
4
Bucket Installation Type: X Direct Bury
Contained in Sum
X Direct Bury
Contained inSum
X -Direct Bury
Contained in,Surnp
0,Direct.Bury
Contained in Sump,
Bucket Diameter. 12" 12" 12" .
Bucket Depth: 14" 14" 14"
Wait: time between applying
vacuum/water and start oftest: 30 MIN 30 MIN 30 MIN
Test Start Time (TO: 0900 1100 0900
Initial Reading (IQ: 12" 12" 12"
Test End Time (TF): 1000 1200 1000
Final Reading (RF): 12" 12"
Test Duration (TF — TO: 1 -HOUR 1 -HOUR 1 -HOUR
Change in Reading (RF - R 0 1.1 ' /:" 0
Pass/Fail Threshold or
Criteria: 0:00 0.00, 0.00
CERTMCATION OF TECHMCIAN RESPONSIBLE FOR CONDUCTING TMS TESTING
Ihereby certify that all the injornurtlon contained in this report . true, accurate,.and infull conWfiance with legal requirements.
Technician's Signature: Date: 3/4/11
State laws and regulations do not currently require testing.to be performed by a qualified contractor. However, local requirements
may be more stringent.
T I:DIESEL
1000
PRODUCT CODE 1THERMALCOEFF000450TANKDIAMETER
90%
95:00TANKPROFILE20PTS
11
10% 10%
FULL VOL 121 -5390.3 INCH VOL 1192885.5 INCH VOL 1152080.8 INCH VOL 1:101676.0 INCH VOL 1042371.2 INCH VOL 977066,5 INCH VOL 908761.7 INCH VOL 835557,0 INCH VOL 761452.2 INCH VOL 684147.5 INCH VOL 607642.7 INCH VOL 529538.0 INCH VOL 4539
33,2 INCH VOL 378228.5 INCH VOL 306623,7 INCH VOL 236819.0 INCH VOL 173014.2 INCH VOL 1136' 9.5 INCH VOL 633
4.7 INCH VOL 224
FLOAT SIZE: 4.0 IN.
WATER WARNING
1000
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 12153OVERFILLLIMIT90%
HIGH PRODUCT 10937
95 %;
DELIVERY LIMIT 11
10% 10%
121.5
LOW PRODUCT 1000LEAKALARMLIMIT: 50SUDDENLOSSLIMIT: 50TANKTILT0.25PROBEOFFSET0.00
SIPHON MANIFOLDED TANKST#: NONE
LINE MA'NIFOLDED TANKSTtt: NONE
LEAK MIN PERIODIC: .33%
OW
LEAK MIN ANNUAL 50,E
6076.
PERIODIC TEST TYPE
STANDARD
ANNUAL EST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST OFFPERTESTAVVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 3 MINPUMPTHRESHOLDc10.00.0
COMMUNjCATIONS SETUP — —
PORT SETTINGS:
COMM BOARD : 5 (RS -485)
BAUD RATE :•.2400
PARITY EVEN
STOP BIT 1,STOP
DATA: LENGTH: 7 DATA
RS -232 SECURITY.
CODE : DISABLED
COMM BOARD : 5 (RS -232)
BAUD RATE '1200
PARITY ODD
STOP BIT 1 STOP
DATA LENGTH: 7 DATA
RS -232 SECURITY
CODE : DISABLED
AUTO TRANSMIT SETTINGS:
AUTO LEAK ALARM LIMIT
DISABLED
AUTO.HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT
DISABLED
AUTO THEFT LIMITDISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL. INPUT OFF
DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM
DISABLED,
AUTO SENSOR OUT ALARM
DISABLED
RS -232 END OF MESSAGEDISABLED
SYSTEM :SETUP
MAR 4. 2011 10:57 AM
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMAT
MON DD YYYY HH:MM:SS xM
PANAMA..BUENA VISTA
4200 ASHE RD
BAKERSFIELD CA
SHIFT TIME .1 1:00 AM
SHIFT TIME 2 ; DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME A : DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE— ENABLE METHOD
PASS LINE TEST
LINE PER TST NEEDED WRN
DISABLED
LINE ANN TST NEEDED WRN
DISABLED
PRINT TC VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEG F ): 60.0
STICK HEIGHT OFFSET
DISABLED
ULLAGE 90%
H— PROTOCOL DATA FORMAT
HEIGHT
DAYLIGHT SAVING TIME
ENABLED
START DATE
MAR WEEK 2 SUN
START 'TIME
2:00 AM
END. DATE
NOV WEEK 1 SUN
END TIME
2:00 .AM
RE— DIRECT'LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
SYSTEM SECURITY
CODE : 000000
MA I NTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
SERVICE NOTICE
DISABLED
ISO 3166 COUNTRY
CODE:
MASS /DENSITY
DISABLED
c • uiva.cn+va.0
CODE
5.0
ERMMAAL 000700
MAX OR LABEL VOL:
aNK DIAMETER
OVERFILL LIMIT
95.00
NK PROFILE 20 PTS
HIGH 4ODUCT
FULL VOL 12153
90.3 INCH VOL : 11928
85.5 INCH VOL : 11520
80.8 INCH VOL : 11016
76.0 INCH VOL 10423
71.2 INCH VOL 9770
66.5 INCH VOL 9087
61.7 INCH VOL 8355
57.0 INCH VOL 7614
52.2 INCH VOL 6841
47.5 INCH VOL 6076
42.7 INCH VOL 5295
38.0 INCH VOL 4539
33.2 INCH.VOL 3782
28.5 INCH VOL : 3066
23.7 INCH VOL 2368
19.0 INCH VOL 1730
14.2 INCH VOL 1136
9.5 INCH VOL 633
4.7 INCH VOL 224
LOAT SIZE: 4.0 IN.
4TER WARNING : 2.0
IGH WATER LIMIT: 3.0
AX OR LABEL VOL: 12153
VERFILL LIMIT. : 90%
10937
IGH PRODUCT
11545
ELIVERY LIMIT
111
OW PRODUCT : 1000
EAK ALARM LIMIT: 50
UDDEN LOSS LIMIT: 50
ANK TILT 1.25
ROSE OFFSET 0.00
IPHON MANIFOLDED TANKS
NONE
INE MANIFOLDED TANKS
NONE
1 J ;wm '!t V1L
PRODUrm CODE I 3
THERM Is COEFF :.00'0470
TANK .DIAMETER 46.00
TANK PROFILE 1 PT.
FULL VOL '550
FLOAT SIZE: 4.0 IN.
WATER WARNING 5.0
HIGH WATER LIMIT: 5.0
MAX OR LABEL VOL: 550
OVERFILL LIMIT 90'%
495
HIGH 4ODUCT 95%
522
DELIVERY LIMIT 1%
5
LOW PRODUCT i
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99.
TANK TILT 0.00.
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
T#: NONE
LINE MANIFOLDED TANKS
T#: NONE
LEAK MIN PERIODIC: 0%.
LEAK MIN ANNUAL 0%
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL.
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL:
ALARM DISABLED
EAK MIN PERIODIC:
4010 'PER TEST AVFRAGING: OFF
EAK MIN ANNUAL 509
6076
ERIODIC TEST TYPE
STANDARD
NNUAL TEST FAIL
ALARM DISABLED
ERIODIC TEST FAIL
ALARM DISABLED
ROSS TEST FAIL
ALARM DISABLED
NN TEST AVERAGING': OFF
ER TEST AVERAGING: OFF
ANK TEST NOTIFY: OFF
NK TST SIPHON BREAK:OFF
SLIVERY DELAY 3 MIN
UMP THRESHOLD 10.00%
TANK, TES14,,NOT I FY: OFF
TNK TST SIPHON BREAK :OFF
DELIVERY DELAY . 1 MIN
PUMP THRESHOLD : 10.00%
ALARM HISTORY REPORT
SENSOR ALARM
L 3:DIESEL ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
MAR 4, 2011 9:22 AM
FUEL ALARM
MAR 4, 20.11 9:10 AM
FUEL ALARM..
MAR 4, 2011 9:10 AM
x x x END x x x x x
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 4:DIESEL STP SUMP
STP SUMP
SENSOR OUT ALARM
MAR 4, 2011 9:22 AM
FUEL ALARM
MAR 4, 2011 9:17 AM
SENSOR OUT ALARM.
MAR 18. 2010 9:32 AM
i
r
END
ALARM -HISTORY REPORT
SENSOR ALARM --
L 5:DTSPENSER 1. 2
DISPENSER PAN
SENSOR OUT ALARM
MAR 4, 2011 9:22 AM
FUEL ALARM
MAR 41: 2011 9:21 AM
SENSOR OUT ALARM
MAR 18, 2010 9:32 AM
LARM HISTORY REPORT
SENSOR ALARM{-
6 :DISPENSER 3 4
lISPENSER PAN
TENSOR OUT ALARM
IAR 4, 2011 9:22 AM
UEL ALARM
1AR 4. 2011 9:20 AM
TENSOR OUT ALARM
1AR 18, 2010 9:32 AM
xx*xx END *.*xx
ALARM FIISTORY REPORT
SENSOR ALARM - --
L,7:WASTE OIL
OTHER SENSORS.
FUEL ALARM
MAR' 4, 2011 10:59' AM
SENSOR OUT ALARM
MAR 4. 2011 9:22 AM
SENSOR OUT ALARM
MAR L8. 2010 9:32 AM
xx *:x x. END xxxx
ALARM HISTORY REPORT
SENSOR ALARM - --
L 8:
OTHER SENSORS
x*xxx END xx*x
EAK TEST METHOD
ST ON DATE : ALL TANK
AN 29, 2009
CART TIME : DISABLED
ST RATE :0.20 GAL /HR
JRATION 2 HOURS
3T EARLY STOP-.DISABLED
OAK TEST REPORT FORMAT
NORMAL
IQUID SENSOR'SETUP
1:UNLEADED ANNULAR
RI -STATE (SINGLE FLOAT)
4TEGORY : ANNULAR SPACE
2:UNLEADED STP SUMP
RI -STATE (SINGLE FLOAT)
4TEGORY :.STP SUMP
3:DIESEL ANNULAR
RI -STATE (SINGLE FLOAT)
ATEGORY : ANNULAR SPACE
4:DIESEL STP SUMP
RI -STATE (SINGLE.FLOAT)
ATEGORY STP SUMP
5:D PENSER 1 2
RI -S TE (SINGLE FAT)
ATEG : DISPENEi PAN
b:
RI -
0
iL.YS I S T
E. 9:0
AV MI NI I'
SHUTDOWN.
00bL 1 HISTORY REPORT
I1 .44 -- I'N -TANK ALARM
T 2:UNLEADED
TESTS HIGH PRODUCT ALARMZ $ MAR 4, 2011 9::08 PJ1
MAR 18, 2010 9:20 AM
PROBE OUT
MAR 4, 2011 9:09 AM
MAR 4. 2011 9:08 AM
l
DELIVERY NEEDED
MAY 24, 2010 4:.09 PM
MAX.PRODUCT ALARM
MAR 4, 2011 9:08 AM
MAR 18, 2010 9:20 AM
X x x x* END * x x* X
XXXx * END * ***
ALARM HISTORY REPORT
SENSOR ALARM --
L 1. :UNLEADED ANNULAR
ANNULAR SPACE ,
SENSOR .OUT ALARM
MAR 4, 2011 9:22 AM
FUEL ALARM
MAR 4, 2011 9:07 AM
SENSOR OUT ALARM.
MAR .18. 2010 .9:32 AM
Xx*x * END **xx
ALARM HISTORY REPORT
SENSOR ALARM --
L 2:UNLEADED STP SUMP
STP SUMP
SENSOR OUT ALARM
MAR 4. 2011 9:22 AM
FUEL ALARM
MAR 4, 2011 9:18 AM
SENSOR OUT ALARM
MAR 18, 2010 9:32 AN
MONITOR CERT. FAILURE REPORT
SITE NAME: PANAMA BUENA VISTA U.S.D. DATE: 3/4/11
ADDRESS: 420WASHE.RD. TECHNICIAN: STEVEN OBERT
THE FOLLOWING COMPONENTS WERE REPLACED/REPAIRED
TESTING.
REPAffl : 11 WASTE OIL BUCKET TORN NEEDS TO BE REPLACED. .
LABOR: NONE
PARTS INTALLED • NONE
NAME: TITLE
SIGNATURE:
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL. FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON- COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON- SITEFOR YOUR
CONVIENENCE.