MONITORING SYSTEM CERTIFICATION
For Use By All JW1sdldfons Within the State ofCalifornia
Authority Cited: Chapter 6.7; Health acidSafety Code; Chapter 16, Division 3, Tale 23, California Code ofRegulations
This form must be used to document testing and servicing ofmonitoring equipment. A gong gotification or art mast be Rrmgmd for each
ttmnitorina system controlpanel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator.
The owns /operator must submit a copy ofthis tbrm to the local agency regulating UST systems within 30 days oftest date.
A. General Information
Facility Name: PANAMA BUENA VISTA U.S.D. Bldg. No.:
Site Address: 4200 ASHE RD. City: BAKERSFIELD Zip: 93313
Facility Contact Person: VICKI STALNAKER Contact Phone No.: i }
Make/Model ofMonitoring System: TLS-= INSP.- ESTER AND ERNIE Date ofTestiiig/Servicing: 3/4/2011
B. Inventory of Equipment Tested/Certified
Cheek the anmmnrlate hmen toindieate anedfic eaornment htwmetedhwPvlred: l
Tank ID: REGULAR 87 Tank ID: DIESEL
1n -Tank Ganging Probe. Model: 1AAG In -TankGaugingProbe. Model: MAG
Annular Space or Vault Sensor. Model; 420 Annular Space or Vault Sensor. Model: 420
Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model: 208
Fill Sump Sensor(,). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: FX1V Mechanical Line Leak Detector. Model: FX1 DV
Electronic Line Leak Detector. Model: Electronic Line LeakDetector. Model:
Tank Overfill / High -Level Scum. Model: MAGI E.OA Tank Overtill / High-Level Sensor. Model: MAGI E.OA
Other (specify equipmenttype and model in Section E on Pagg2). Other (specify equipment type and model in Section Eon Page 2).
Tank ID: WASTE OIL Tank ID:
In -Tank Gauging Probe. Model: NM In-TankGauging Probe. Model:
Annular Space or Vault Sensor. Model: 420 Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Seosar(s). Model:
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Lace Leak Detector. Model: Mechanical Line Leak Detector. Model:
ElectronicLine Leak Detector. Model: Electronic Line Leek Detector. Model:
Tank Overfill / High -Level Sensor. Model: WA Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (speedy equipmenttype and model in Section E on Page 2).
Dispenser ID: 112 Dispenser ID: 314
Dispenser Containment Sensor(s). Model: 208 Dispenser Containment Sessor(s). Model• 208
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) andChain(s). Dispenser Containment Float(s) andChain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: DispenserContainment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) andChain(s).
Dispenser ID: Dispenser ED:
Dispenser Containment Sensor(s). Model• Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Vahro(s).
Dispenser Containment Float(s) and Cham(s). Dispenser Containment Float(s) andChain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected/serviced In accordance with the manufacturers'
guldelines. Attacbed to this Certification is information (e g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring ulpmettt. For any equipment capable of generating such reports, I have also
attached a copy of the report; (chwk aQ that apply): System set -up ® Alarm history report
Technician Name (prim): STEVEN OBERT Signature:
Certification No.: A28531 t8029880-UT License. No.: CM11 D40 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 326-W2
Testing Company Address: 3305 BRITTAN RD. BAKERSFIELD, CA. 93308 Date of Testing/servicing: 31412011
Page 1 of 5
UN4% -1 /4 www.unldocs.org Rev. 01n7M
43w
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 329.01
Comnlete the followina checklist!
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point ofsecondary containment and positioned so that other equipment will
not interfere with their proper 'on?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? Ifyes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; ® Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks lgId sensor f Ldureldisconnection? ® Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? Ifso, at what percent oftank capacity does the alarm trigger? 90%
Yes* No Was any monitoring equipment replaced? Ifyes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* IM No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. Ifyes, describe causes in Section E, below.
Yes No* Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, ifapplicable
IS Yes No* Is all monitoring operational M manufacturer's specifications?
In Section E below, describe how and when these deffelencies were or will be corrected.
E. Comments:
Page 2 of 5
UN-M-2/4 w".unldomorg Rev. OV17/08
Monitoring System Certification yObi b
F. In -Tank Ganging / SIR Equipment: ® Check this box if tank gauging is used only for inventory control.
Check this box ifno tank gauging or SIR equipment is installed
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy ofsystem product level readings tested?
Yes No* Was accuracy ofsystem water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
C'mmnlete the fnllmvtna eharklkt-
Check this box ifI I are not installed
Yes No* For equipment start -up or annual equipment certification, was a leak 'simulated to verify LLD performance?
NIA Check all that apply) Simulated leak rate: ® 3 g.p h.; 0.1 g.p.h ; 02 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow ifit detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off ifthe LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off ifany portion of the monitoring system is disabled
tg N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off ifany portion of the monitoring system malfimctions
N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
FL Comments:
L'N -036 - 3/4
Page 3 of b
www.enldomorg Rev. NAM$
Monitoring System Certification Form: Addendum for Vacuum /Pressure Interstitial Sensors
I. Results of Vacuum/Pressure Monitoring Equipment Testing
This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of
this form must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner /operator. The owner /operator must submit a copy ofthe Monitoring System Certification Form to the
local agency regulating UST systems within 30 days oftest date.
Manufacturer. N/A Model: System Type: Pressure; Vacuum
Sensor 1D
Component(s) Monitored by this Sensor.
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor-
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result Pass; Fail
Components) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail . Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor.
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial. Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: . Pass; Fail
Component(s) Monitored by this Sensor.
Sensor Functionality Test Result Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Fumctionality Test Result: Pass; Fail Interstitial Communication Test Result Pass; Fail
How was interstitial communication verified?
Leak Introduced at Far End ofInterstitial S ;1 G ; Visual 'on; Other (Describe in Sea J, below)
Was vacuum/pressure restored to operating levels in all interstitial spaces? Yes No ffno, describe in Sec. J, below)
J. Comments: NONE OF THESE SENSORS ARE PRESENT AT THIS SITE.
Page 4 of 5
If the sensor sugcessfidly detects a simulated
tev
cupmfpressure le *mtrod d m the interstitial space at the furthest point from the
sensor, unto sure has been demoastr$ W be commumi throughout the interstice.
UN-WA -1/1 wwwmddemorg Rev. 01!16/06
AVW
m Or
JI
10
Mk BINH
5, w 6t t. A IM. t, V, f, 'r q :A.e P%: Y. 11
t 14 Af :i 4! ;(1 -J: litit. il f Qv
21
U, -4, hi ;1 4 4 A 0 i,
v -Z .;i i-v 11 m '7 '41% tr. fit -.S. ti -f V
It .4; 1? T^
it. .';I .A! 1, VV T. . Ik :1 4.
4i •4 f, :w
I M M '41 .4
t, K ly
4 M1
IL 't
V ,
e
x..
it, 71 v I v
i: A It
itF' i, It ri. I. it 7t ;1 :1 t T.
z
W I 1f N 40'A :X' - w I 't
1 17l7lw. al `1.- 11 5, I
fio ;4 t 'A
It
T. f fr
V Y, Z:
It 74 -A f:. -f %F !-ta t-
iz -,r; 'k -v iA ihle7-: r- . 4
mot.
LL
7e ok, 'A is -1(5 i4 t, m. it
V o. j, !Z! N
14
fe t, 1;
l, A
r4
i
Y 4 T 71
k,. w • .6 k. R1, -.W 4 a;
J,: j. I:
WAN
RICH ENMONMENTAL
3305 BRTTTAN ST. BAKERSFIELD, CA. 93308
OFFICE (661)326 -8402 FAX (661)326 -8934
PRODUCT LINE LEAK DETECTOR TEST
1: 1 4 " l
W/0#:
FACILITY NAME: PANAMA BUENA VISTA SCHOOL DISTRICT
FACILITY ADDRESS: 4200 ASHE RD. BAKERSFIELD, CA.
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL&7 L/D TYPE: 'FXIV
YES 10 P.S.I. PASSSERIAL # _3
DIESEL L/D TYPE FX1DV
YES 10 P.S.L PASS
SERIAL # 7 q
IJD TYPE: _ PASS
YES
SERIAL # FAEL
L/D TYPE: PASS
YES
SERIAL. # FAEL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THOS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMLTATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 PAL I
ACKNOWLEDGE THATALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: STEVEN OBERT
SIGNATURE: DATE: 3/4611
SWRCB, January 2006 /
N `
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUSTspill containment structures. The completedform and
printoutsfrom tests (tf `applicable), shouldbe provided to thefacility owner /operatorfor submittal to the local regulatory agency.
is FACILITY INFORMATION
Facili Name: PANAMA BUENA VISTA U.S.D. Date ofT 3/4/2011
Facility Address: 4200 ASHE RD. BAKERSFIELD, CA. 93313
Facility Contact: VICKI STALNAKER Phone:
Date Local Agency Was Notified ofTesting : 1 /27 /2011
Name ofLocal Agency Inspector Wpresent during testing): ERNM AND ESTER
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: STEVEN OBERT
Credcnfials': CSLB Contractor X ICC Service Tech: SWRCB Tank Tester ' Other ecify)
License Number(s): 8029980 -UT
3. SPILL BUCKET ,TESTING INFORMATION
Comments — ('include i* mation on repairs madeprior to testing, andrecommendedfoll w -upforfailed tests)
WASTE OIL BUCKET IS TORN AND LEAKING WILL NEED TO BE
REPLACED.
CERTIFICATION OF TECEMICIAN RESPONSIBLE FOR CONDUCTING TSIS TESTING
I hereby ceA j+ that aQ the infonnadon contabted In this report h true, accurate, and Inf fi covVWwece with legalrequhwnentL
Technician's Signature: Co ` = Date: 3/4/11,,..
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
T I:DIESEL
2.0
PRODUCT CODE 1THERMALCOEFF000450TANKDIAMETER95.00TANKPROFILE20PTS
DELIVERY LIMIT
FUL VOL 1215390.3 INCH VOL 1192885.5 INCH VOL 11520
80.8 INCH VOL 11016
76.0 INCH VOL 1042371.2 INCH VOL 977066.5 INCH VOL 908761.7 INCH VOL 835557.0 INCH VOL 7614
52.2 INCH VOL 684147.5 INCH VOL 607642.7 INCH VOL 5295
38.0 INCH VOL 4539
28.5 INCH
VOL
3066
23.7 INCH VOL 2368
19.0 INCH VOL 173014.2 INCH VOL 1136' 9.5 INCH VOL 633
4.7 INCH VOL 224
FLOAT SIZE: 4.0 IN.
WATER WARNING 2.0HIGHWATERLIMIT: 3.0
MAX OR LABEL VOL: 12153OVERFILLLIMIT90%
HIGH PRODUCT 1095%
DELIVERY LIMIT 1504X5
1215
LOW PRODUCT 1000LEAKALARMLIMIT: 50SUDDENLOSSLIMIT: 50TANKTILT0.25PROBEOFFSET0.00
SIPHON MANIFOLDED TANKSTit: NONE
LINE MANIFOLDED TANKST#: NONE
LEAK MIN PERIODIC: 43.3%
LEAK MIN ANNUAL 5O
6076.
PERIODIC TEST TYPE
STANRARD
ANNUAL WT FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFFPERTESTAVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERYRESHHOOLD i 10. DO%
COMMUNICATIONS SETUP -
y
PORT SETTINGS:
COMM BOARD : 5 (RS -485)
BAUD RATE :..2400
PARITY : EVEN
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS -232 SECURITY
CODE : DISABLED
COMM BOARD : 6 (RS -232)
BAUD RATE : 1200
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS -232 SECURITY
CODE : DISABLED
AUTO TRANSMIT SETTINGS:
AUTO LEAK ALARM LIMIT
DISABLED .
AUTO.HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT
D I.SABLED
AUTO THEFT LIMIT
DISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM
DISABLED
AUTO SENSOR OUT ALARM
DISABLED
RS -232 END OF MESSAGE
DISABLED
SYSTEM SETUP - l+Vrt, [
MAR -4. 2011 10:57 AM
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
PANAMA BUENA VISTA
4200 ASHE RD
BAKERSFIELD CA
SHIFT TIME 1 : 1:00 AM
SHIFT TIME 2 DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE- ENABLE METHOD
PASS LINE TEST
LINE PER TST NEEDED WRN
DISABLED
LINE ANN TST NEEDED WRN
DISABLED
PRINTTO VOLUMES
TEMP COMPENSATION
VALUE (DEG F ): 60.0
STICK DIGHT OFFSET
ULLAGE : 90%t
H- PROTOCOL DATA FORMAT
HEIGHT
DAYLIGHT SAVING TIME
ENABLED
START DATE
MAR WEEK 2 SUN
START TIME
2:00 AM
END DATE
NOV WEEK I SUN
END TIME
2:00 AM
RE- DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
S
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
SERVICE NOTICE
DISABLED
ISO 3166 COUNTRY
CODE:
MASS /DENSITY
DISABLED
c • uivicn• -
CODE
5.0
JERMAL
5.0
000700
aNK DIAMETER
OVERFILL LIMIT
95.00
3NK PROFILE 20 PTS
FULL VOL 12153
90.3 INCH VOL 11928
85.5 INCH VOL 11520
80.8 INCH VOL 11016
76.0 INCH VOL 10423
71.2 INCH VOL 9770
66.5 INCH VOL 9087
61.7 INCH VOL 8355
57.0 INCH VOL 7614
52.2 INCH VOL 6841
47.5 INCH VOL 6076
42.7 INCH VOL 5295
38.0 INCH VOL 4539
33.2 INCH.VOL 3782
28.5 INCH VOL 3066
23.7 INCH VOL 2368
19.0 INCH VOL 1730
14.2 INCH VOL 1136
9.5 INCH VOL 633
4.7 INCH VOL 224
LOAT SIZE: 4.0 IN.
ATER WARNING 2.0
IGH WATER LIMIT: 3.0
AX OR LABEL VOL: 12153
VERFILL LIMIT, : 90%
10937
IGH PRODUCT 956
11545
ELI VERY LIMIT : 10%
1215
OW PRODUCT 1000
EAK ALARM LIMIT: 50
UDDEN LOSS LIMIT: 50
ANK TILT 1.25
ROBE OFFSET 0.00
IPHON MANIFOLDED TANKS
0: NONE
INE MANIFOLDED TANKS
NONE
EAK MIN PERIODIC: 33%
4010
EAK MIN ANNUAL 50%
6076
ERIODIC TEST TYPE
STANDARD
NNUAL TEST FAIL
ALARM DISABLED
ERIODIC TEST FAIL
ALARM DISABLED
ROSS TEST FAIL
ALARM DISABLED
NN TEST AVERAGING: OFF
ER TEST AVERAGING: OFF
ANK TEST NOTIFY: OFF
NK TST SIPHON BREAK:OFF
SLIVERY DELAY : 3 MIN
UMP THRESHOLD : 10.00%
1 J;wm 11r V1L
THERM COEFF :.010470
TANK DIAMETER 46.00
TANK PROFILE I PT
FULL VOL `550
FLOAT SIZE: 4.0 IN.
WATER WARNING 5.0
HIGH WATER LIMIT: 5.0
MAX OR LABEL VOL: 550
OVERFILL LIMIT 90%
r
HIGH 40DUCT
495
5
DELIV AY LIMIT 1%
5
LOW PRODUCT 1
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 0%
0
LEAK MIN ANNUAL 0%
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL.
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFFPERTESTAVERAGING: OFF
TAW TEErZ NOTIFY : OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 1 MIN
PUMP THRESHOLD : 10.00%
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:DIESEL ANNULAR
ANNULAR SPACE
SENSOR OUT ALARMMAR4, 2011 9:22 AM
FUEL ALARM
MAR 4, 2011 9:10 AM
FUEL ALARM
MAR 4. 2011 9:10 AM
x x x x x END x x x x x
F
ALARM HISTORY REPORT
SENSOR ALARM - - - -- L 4:DIESEL STP SUMP
STP SUMP
SENSOR OUT ALARMMAR4. 2011 9:22 AM
FUEL ALARM
MAR 4, 2011 9:17 AM
SENSOR OUT ALARMMAR18: 2010 9:32 AM
i
x x x END x x x x x
ALARM HISTORY REPORT
SENSOR ALARM - - - -- L S:DISPENSER 1 2
DISPENSER PAN
SENSOR OUT ALARM
MAR 4. 2011 9:22 AM
FUEL ALARM
MAR 4. 2011 9:21 AM
SENSOR OUT ALARM
MAR 18, 2010 9:32 AM
LARM HISTORY REPORT
SENSOR ALARMf
6:DISPENSER 3 4
ISPENSER PAN
TENSOR OUT ALARM
IAR 4, 2011 9:22 AM
UEL ALARM
1AR 4. 2011 9:20 AM
SENSOR OUT ALARM
IAR 18, 2010 9:32 AM
xxxx9 END xxxx
HISTORY REPORT
SENSOR ALARM - --
L 7:WASTE OIL
OTHER SENSORS.
FUEL ALARM
MAR 4, 2011 10:59 AM
SENSOR OUT ALARM
MAR 4. 2011 9:22 AM
SENSOR OUT ALARM
MAR 18. 2010 9:32 AM
xxxxx END xxxx
ALARM HISTORY REPORT
SENSOR ALARM - --
OTHER SENSORS
xxxxxENDxxxx
EAK TEST METHOD
EST ON DATE : ALL TANK
iN 29. 2009
CART TIME : DISABLED
EST RATE :0.20 GAL/HR
JRATION : 2 HOURS
3T EARLY STOP:DISABLED
FAK TEST REPORT FORMAT
NORMAL
IAUID SENSOR SETUP
1:UNLEADED ANNULAR
RI -STATE (SINGLE FLOAT)
4TEGORY : ANNULAR SPACE
2 :UNLEADED STP SUMP
RI -STATE (SINGLE FLOAT)
4TEGORY : STP SUMP
3:DIEBEL ANNULAR
RI -STATE (SINGLE FLOAT)
ATEGORY : ANNULAR SPACE
4:DIESEL STP SUMP `
RI -STATE (SINGLE FLOAT)
ATEGORY : STP SUMP
5:DISPENSER 1 2
AT : (DISPENSPAN
b:
RI-
0
SHUTDOWN
00- 7--'f-tb?L HISTORY REPORT
1;.44 - - -- IN -TANK ALARM -
T 2:UNLEADED
TES HIGH PRODUCT ALARMESTSMAR4. 2011 9:08 AM
MAR 18. 2010 9:20 AM
PROBE OUT
MAR 4, 2011 9:09 AM
MAR 4. 2011 9:08 AM
DELIVERY NEEDED
MAY 24, 2010 4:09 PM
MAX PRODUCT ALARM
MAR 4. 2011 9:08 AM
MAR 18. 2010 9:20 AM
x x x x x END x x x x x
xxxxx END xxxx
ALARM HISTORY REPORT
SENSOR ALARM --
L I:UNLEADED ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
MAR 4. 2011 9:22 AM
FUEL ALARM
MAR 4. 2011 9 :07 AM
SENSOR OUT ALARM
MAR 18. 2010 9 :32 AM
xxxxx END xxxx
ALARM HISTORY REPORT
SENSOR ALARM --
L 2:UNLEADED STP SUMP
STP SUMP
SENSOR OUT ALARM
MAR 4. 2011 9:22 AM
FUEL ALARM
MAR 4. 2011 9:18 AM
SENSOR OUT ALARM
MAR 18, 2010 9:32 W
MONITOR CERT. FAILURE REPORT
ADDRESS : 4,200 ASHE RD. TECHNICIAN: STEVEN OBERT
THE FOLLOWING COMPONENTS WERE REPLACED/REPAIRED.TO COMPLETE
TESTING.
REP : D WASTE OIL BUCKET TORN NEEDS TO BE REPLACED. .
1! a M no
NAME • TITLE
SIGNATURE:
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMENTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON —SITE FOR YOUR
CONVIENENCE.