HomeMy WebLinkAbout402 CHESTER (2)SWRCB, January 2002 Page --1— of 17 Secondary Containment Testing Report Form Thisform is intendedfor use by contractors performing periodic testing ofUST secondary containment systems. Use the appropriate pages ofthisform to report resultsfor all components tested The completedform, written -test procedures, and printouts from tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION 2. TESTING CONTRACTOR INFORMATION Company Name: Rich Environmental Pass Technician Conducting Test: RICH PHILLIPS Not Tested Credentials: X CSLB Licensed Contractor SWRCB Licensed Tank Tester License Type: C61040 A HAZ License Number: 809850 Manufacturer Manufacturer Training Component(s) Date Training Expires INCON TS -STS 6/11/2012 3. SUMMARY OF TEST RESULTS Component Pass Fail Not Tested Repairs Made Component Pass Fail Not Tested Repairs Made UNL87 ANNULAR X PREM91 ANNULAR X 0 D 0 UNL887 SEC PIPE X EI 0 1 0 PREM 91 SEC PIPE X UNL87 STP SUMP X D 0 PREM91 STP SUMP X UDC # 1/2 X UDC #3/4 X D UNL87 FILL SUMP X 0 PREM 91 FILL SUMP X a UNL87 VPR BOX X PREM 91 VPR BOX X p n Ifhydrostatic testing was performed, describe what was done with the water after completion of tests: CERTIFICATION OF TEC -IAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best ofmy knowledge, thefacts s this document are accurate and infull compliance with legal requirements Technician's Signature: Date: 08/18/11 SWRCB, January 2002 4. TANK ANNULAR TESTING Page 2— of Test Method Developed By: Tank Manufacturer X Industry Standard Professional Engineer Other (Specify) Test Method Used: Pressure X" Vacuum Hydrostatic Other (Specify) Test Equipment Used: 4" DIAL GAUGE Tank 487 Tank #91 Is Tank Exempt From Testing ?` Yes XNo Yes X No Equipment Resolution: Tank # Tank # Yes No Yes No Tank Capacity: 12000 8000 Tank Material: STEEL STEEL Tank Manufacturer: UNKNOWN UNKNOWN Product Stored: UNL87 PREM91 Wait time between applying pressure /vacuum/water and starting test: 30MIN 30MIN Test Start Time: 9:30 10:45 Initial Reading (Rj): IOHG IOHG Test End Time: 10:30 11:45 Final Reading (RF): 10140 IOHG Test Duration: 60 MIN 60 MIN Change in Reading (RF -R,): 00 00 Pass/Fail "threshold or Criteria: 00 00 i. I r r i4 `.!t,l =1;" re!! t' f• 1, 'i s i r j'jr i i j tfi Was sensor removed for testing? X Yes No NA X Yes No NA Yes 0 No NA Yes No NA Was sensor properly replaced and verified functional after testing? X Yes Q No NA X Yes No NA Yes No NA Yes No NA Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment testing. {California Code of Regulations, Title 23,, Section 2637(a)(6)) tk 3Z\ 1 SWRCB, January g2002Page S of 5. SECONDARY PIPE TESTING Test Method Developed By: C Piping Manufacturer X Industry Standard Professional Engineer Other (Specify) Test Method Used X Pressure Vacuum G Hydrostatic Other (Specify) Test Equipment Used: 4" DIAL GAUGE Equipment Resolution: .5% Piping Run #87 Piping Material: PLASTIC Piping Run #91 Piping Run # Piping Run # PLASTIC Piping Manufacturer: APT APT Piping Diameter: 1.5" 1.5" Length of Piping Run: 75' 75' Product Stored: UNL87 PREM91 Method and location of piping-run isolation: BOOT IN SUMP BOOT IN SUMP Wait time between applying pressure /vacuum /water and starting test: 30 MIN 30 MIN Test Start Time: 10:45 10 :45 Initial Reading (RI): 5.5 5.5 Test End Time: 11:45 11 :45 Final Reading (Fr): 5.5 5.5 Test Duration: 60 MIN 60 MIN Change in Reading (RF -Rj): 00 00 Pass/Fail Threshoid or Criteria: s tS IL : 0 PSI t -' n! ' 1 P0 i 0 PSI t Comments (include information on repairs made prior io testing, andrecommendedfollow -upforfailed tests) 437A r c fSWRB, January 2402 Page of / 6. PIPING SUMP TESTING Test Method Developed By: 0 Sump Manufacturer X Industry Standard Professional Engineer D Other (Spec) Test Method Used: 0 Pressure Vacuum X Hydrostatic D Other (Spec) Test Equipment Used: INCON TS -STS Equipment Resolution: Sump #87 Sump #91 Sump # Sump # Sump - Diameter: 37" 37" Sump Depth: 60" 60" Sump Material: FIBERGLASS FIBERGLASS Height from Tank Top to Top of Highest Piping Penetration: 26" 23" Height from Tank Top to Lowest Electrical Penetration: 21" 21" Condition of sump prior to testing: CLEAN CLEAN Portion of Sump Tested' 28" 25" Does turbine shut down when sump sensor detects liquid (both product and water ?* Yes No C NA 0 Yes No DNA Yes No NA Yes No NA Turbine shutdown response time Is system p ogrammed for fail -safe shutdown? 0 yes D No DNA 0 Yes 0 No DNA 0 Yes D No D NA 0 Yes 0 No NA Was fail -safe verified to be o erational ?* 0 Yes No O NA Yes No DNA Yes No NA 11 Yes 0 No NA Wait time between applying pressure /vacuum/water and starting test: 30 MIN 30 MIN Test Start Time: Initial Reading (Rj): Test End Time: Final Reading (RF): Test Duration: 15MIN 15MIN 15MM 15MIN Change in Reading (RF -Ri): Pass/Pail Threshold or Criteria: etRcult• .,..' ;t _ .,, 4i.i' 0 Yes No NA rHi. Yes No NA lot r,,;i' Yes No NA C Yes C No NAWassensorremovedfortesting? Was sensor properly replaced and verified functional after testing? 0 yes D No D NA 0 Yes 0N NAF Yes L No DNA ED Yes No ONA FAILING UNDER PRODUCT LINE PENETRATION If the entire depth ofthe sump is not tested, specify how much was tested. If the answer to AU of the questions indicated with an asterisk ( *),is "NO" or "NA ", the entire sump must be tested. (See SWRCB LG -160) SWRCB, January 2402 7. UNDER - DISPENSER CONTAINMENT (UDO TESTING 4 :)u l Page 61" of l Test Method Developed By: UDC Manufacturer X Industry Standard Professional Engineer Other (Spec) Test Method Used: Pressure Vacuum X Hydrostatic Other (Spec) Test Equipment Used: INCON TS-STS Equipment Resolution: UDC #1/2 UDC #3/4 UDC # UDC # UDC Manufacturer: TCI TCI UDC Material: PLASTIC PLASTIC UDC Depth: 30" 30" Height from UDC Bottom to Top of Hi hest Piping Penetration: 12" 12" Height from UDC Bottom to Lowest Electrical Penetration: 14" 14" Condition of UDC prior to testing: CLEAN CLEAN Portion of UDC Tested 14" 14" Does turbine shut down when UDC sensor detects liquid (both product and water)?* Yes No NA Yes No NA Yes No NA Yes No NA Turbine shutdown response time Is system programmed for fail- safe shutdown ?* Yes No NA C Yes C No NA Yes No NA Yes No NA Was fail -safe verified to be o rationial ?* Yes C No NA Yes No NA Yes No NA Yes No NA Wait tim6 between applying pressure /vacuum /water and starting test 30MIN 30MIN Test Start Time: Initial Reading Test End Time: Final Reading Rr): Test Duration: 15MIN 15MIN 15MIN 15MIN Change in Reading (RF -RI): Pass/Fail Threshold or Criteria: Yes No NA 7Yes . PP! . Was sensor removed for testing? No NA Yes No C NA Yes No 7-1 NA Was sensor properly replaced and verified functional after testin ? C Yes No NA Yes C No C NA Yes No NA Yes No NA Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) If the entire depth of the UDC is not tested, specify how much was tested. If the answer to anv ofthe questions indicated with an asterisk (") is "NO" or "NA ", the entire UDC must be tested. (See SWRCB LG -160) SWRCB, January 2002 8. FILL RISER CONTAINMENT SUMP TESTING Lk D LA t Page 6 .. of Facility is Not Equipped With Fill Riser Containment Sums Fill Riser Containment Sumps are Present, but were Not Tested 0 Test Method Developed By: Sump Manufacturer X Industry Standard Professional Engineer Other (Specify) Test Method Used: Pressure Vacuum X Hydrostatic Other (Specify) Test Equipment Used -, TNCON TS -STS Fill Sum # Fill Sum p# Sump Diameter: Equipment Resolution: Fill Sumg # Fill Sump # Sump Depth: Height from Tank Top to Top of Highest Piping Penetration: Height from Tank Top to Lowest Electrical Penetration: Condition of sump prior to testing; Portion,of Sump Tested Sump Material: Wait time between applying pressure /vacuum/water and starting test: 30MIN 30MIN 30MIN 30MIN Test Start Time: Initial Reading (Rj ): Test End Time: Final Reading (Ry)! Test Duration: 15MIN 15MIN 15MIN 15MIN 15MIN 15MIN 15MIN 1. 15MIN in Reading (RF -R, ): Change Pass/FaiI Threshold or Criteria: s:., .:;;; : ::.::::::.:, s :::f,:..,. is z;n;• ti r iii'.;;. d,liili;)!ii;i35i!Y,'k`li 'Ui'..,i:!'` s there a sensor in the sump? nt •r ijj .+ Yes No e i. ; . Yes No fi• 0 Yes No r. a+ +.1 : j +; Yes No Does the sensor alarm when either product or water is detected? 0 Yes No NA Yes No NA O Yes G No NA Yes No NA Was sensor removed for testing? C Yes No NA Yes No NA Yes D No NA Yes No DNA Was sensor properly replaced and verified functional after testin ? Yes No NA Yes No NA Yes No NA Yes No NA Comments (include information on repairs made prior (o testing, and recommendedfollow -upfor failed tests) N® FILL SUMPS SWRCB, January 2002 9. SPILIJOVERFELL CONTAINMENT BOXES r) u [ Page of 13 Facility is Not Equipped With S itl /Overfill Containment Boxes Spill /Overfill Containment Boxes are Present, but were Not Tested 0 Test Method Developed By: Spill Bucket Manufacturer X Industry Standard Professional Engineer 0 Other (Specify) Test Method Used: 0 Pressure Vacuum X Hydrostatic Other (Spec) Test Equipment Used: TNCON TS -STS Equipment Resolution: Spill Box #87 SPILL Bucket Diameter: 12" Spill.Box #87 VPR Spill Box #91 SPILL Spill Box 991 VPR 12" 12" 12" Bucket Depth: 16" 16" 16" 16" Wait time. between applying pressure /vacuum/water and starting test: 30MIN 30MIN 30MIN 30MTN Test Start Time: 10:17 10:34 10:17 10:34 Initial Reading (Rt): 2.688 2.688 5.473 5.473 Test End Time: 10 :32 10:49 10:32 10:49 Final Reading (RF): 2.688 2.688 5.473 5..473 Test Duration: 15MIN I SMIN 15MIN 15MIN 15MIN 15MIN 15MIN 15MIN Change in Reading (RF -RJ):. 000 000 000 000 Pass /Fail Threshold or Criteria: 002 002 002 002 @ t` !?:i,,;'.'tti, Y' i lit l• , .c i,i ' : [ 't ANT i • iii : i t ;t Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) s SUMP LEAK h s: T ;,.,T FAF 1'E' Oc'•! 10 1 1 klillV' LEUE.!. 1.7245 4D TiME tNU 0OTE os /1$ /* Ill', a:4 RF.SUL r I=HXL TEST S'fAR TED TWST TFiK't Ell 08 1$!21011 FS t_I^ :E JrL 1.r15 •iN L!y0 TTME 1:27' Pt1 END DATE 0B/18/2a qD _tUFL :..4277 1N LEAK THREHOLD a.00 Ih i r=A1LL' t? SB989 TESTING FAILURE REPORT SITE NAME: ONE STOP MOBIL DATE: 8/18/11 THE FOLLOWING COMPONENTS WERE REPLACED/REPAIRED TO COMPLETE TESTING. LABOR: PARTS INSTALLED: NAME: TITLE: SIGNATURE: THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR THE AB IFABOVELISTEDPROBLEMSANDNOTYING RICH ENVIRONMA.NTAL FOR ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE. A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR CONVIENENCE.