HomeMy WebLinkAbout11400 MING AVENUE (3)r _" Appendix VI Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http: //www.swrcb.ca.gov.) MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Informatio / / 9 Facility Name: 7'/e/l%t/. Ikmwi,n Bldg. No.: Site Address: /?2 '00 % z < Cicy:230 - /J 21p: Facility Contact Person: .-090 Y .L11 //iQi Contact Phone No.: 6/) Make/Model of Monitoring System,0952) SiCA= 7% S'- ?_4W& Date of Testing/Servicing:/0 h2i'91 D// B. Inventory of Equipment Tested/Certified Check the annrooriate boxes to indicate specific eauioment Insoectad/serviced: Tank ID Tank ID', IC In -Tank Gauging Probe. Model: W In -Tank Gauging Probe. Model: Annular space or Vault Sensor. Model: Ir Annular Space or Vault Sensor. Model: r!r Piping Sump/ Trench Sensor(s). Model: e' Piping Sump / Trench Sensor(s). Model: Y Fill Sump Sensor(s). Model: W Fill Sump Sensor(s). Model: 5r Mechanical Line Leak Detector. Model: /'V C Mechanical Line Leak Detector. Model: Electronic Line Leak Detector. Model, Electronic Line Leak Detector. Model: V Tank Overfill / High -Level Sensor. Mode • D U Tank Overfill / High -Level Sensor. Model' Other (MgU 2quipment to and model in SectIOWE on Pa 2). fr Other (specify e u ment and model in Section E on Page 21. Tank ID: Tank ID: V In -Tank Gauging Probe. Model: In -Tank Gauging Probe. Model: Annular Space orVault Sensor. Model: Annular Space or Vault Sensor. Model: hr Piping Sump / Trench Sensor(s). Model: - Piping Sump / Trench Sensor(s). Model: I'f Fill Sump Sensor(s). Model: - D Fill Sump Sensor(s). Model: 1 Mechanical Line Leak Detector. Model: A nical Line Leak Detector. Model: Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: X Tank Overfill / High -Level Sensor. Model; 9 Tank Overfill /. High -Level Sensor. Model: Other uI ment and model in Section E on Pa e 2 . Others 29WE2ent = and model In Section E on Page 2). Dispenser ID: DispenserlD: if Dispenser Containment Sensor(s). Model: - OS Nr Dispenser Containment Sensor(s). Model: hr Shear Valve(s). I" Shear Valve(s). Dispenser Contai meat Floats and Chain(s). Disperaw Contain ent Floats and Chaln s . DispenserlD Dispenser to W Dispenser Containment Sensor(s). Model: r Dispenser Containment Sensor(s). Model: id Shear Valve(s). X Shear Valve(s). Dispenser Contai nt Floats and Chain(s). Dispenser Contaiivnent Floats and Chain(s). Dispenser ID: Dispenser ID: W Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model: m Shear Valve(s). Shear Vatve(s). 0IsE2nserContainment Floats and Chains Dispenser Containment Floats and Chain(s). If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the tacility. C. CertMcation - I certify that the equipment Identified In this document was Inspected/serviced In accordance with the manufacturers' guidelines. Attached to this Certification is information (e.g. manufacturers' check) F;:rge"narstlng ry to verify that this Information is correct and a Plot Plan showing the layout of monitoring equipment For any equlpme such reports, 1 have also attached a copy of the report; (check aft that apply): 5rSystem set-up KAla h Technician Name (print) -1V A %LY.F Signature. Certification No.: Aj5ZU2 se. No.: Testing Company Name Phone No.: to Testing Company Address: Date ofTesting/Servicing: A2ev1 =?Q// Monitoring system Certification Page 1 of4 12107 2/21/07 Appendix VI Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at httb: //www.swrcb.ca.Qov.) MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State ofCalifornia Authority Cited. Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This foam must be used to document testing. and servicing of monitoring. equipment A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days oftest date. A. General Information Facility Name: Site Address: Facility Contact Person: City. Contact Phone No.: Bldg. No.: Zip: Make/Model of Monitoring System: Date of Testing/Servicing: I I B. Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment Inspected/serviced: Tank ID: Tank ID: In -Tank Gauging Probe. Model: In -Tank Gauging Probe. Model: Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model: Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model: Fill -Sump Sensor(s). Model: Fill. Sump Sensor(s).. Model: Mechanical Una Leak Detector. Model: Mechanical Una Leak Detector. Model: Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: Tank Overfill I High -Level Sensor. Model: Tank Overfill I High -Level Sensor. Model: Other (specify equipment type and model in Section E on Page 2). Other (se2a equipment!Me and model in Section E on P 2). TanklD• TanklD• In -Tank Gauging Probe. Model: in -Tank Gauging Probe. Model: Annular Space or Vault Sensor. Model:. Annular Space or Vault Sensor. Model: Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model: Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model: Mechanical Una Leak Detector. Model: Mechanical Una Leak Detector. Model: Electronic Una Leak Detector. Model: Electronic Una Leak Detector. Model: Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model: Other equiEmega and model in Section E on Pa e 2 . Other equipment DE and model in Section E on Pa 2). Dispenser ID: Dispenser 11): W Dispenser Containment Sensor(s). Model; d- Dispenser Containment Sensor(s). Model: r Shear Valve(s). Shear Valve(s).. Dispenser Contain nt Floats and Chains . Dispenser Containment Floats and Chain(s). Dispenser ID: Dispenser ID: Nr' Dispenser Containment Sensor(s). Model: ,? Dispenser Containment Sensor(s). Model: X Shear Valve(s). Shear Valve(s). 0 Dispenser Containment Floats and Chains . Dispenser Containment Floats and Chain(s). Dispenser ID: Dispenser ID: Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model: Shear Valve(s). Shear Valve(s). Dispenser Containment Floats and Chaln s Dispenser Containment Roat(!j and Chains . Ifthe facility contains more tanks ordispensers, copy this forth. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment Identified in this document was Inspected/serviced In accordance with time . manufacturers' guidelines. Attached to this Certification Is information (e.g. manufacturere. the A of ry to verfythat this fMormatfon.ts coandaPlotPlanshowingthelayoutofmonitoringequipment. For any equip rating such report', I have also attached a copy of the report; (check all that apply): System set-up Alarm h Technician Name (print): Signature: Certification No.: U No.; Testing Company Name: Testing Company Address: Monitoring System Certification Page 1 of 4 Phone No.:(___ ) Date of Testing/Servicing: 12107 2/21/07 D. Results of TesatlnglServicing Software Version Installed:,? '' Comolete the followina checklist Yes ' No' Is the audible alarm operational? Yes No' Is the visual alarm operational? Yes No' Were all sensors visually Inspected, huxbonally tested, and confirmed operational? j Yes . No' Were all sensors installed at lowest point of secondary containment and positioned so that otherequipmentwill not interfere with their proper operation? Yes No' If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? JC WA Yes NW For pressurized piping systems, does the turbine automatically shut down If the piping secondary containment monitoring system N/A detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut -down? (Check all that apply) X Sump/Trench Sensors; )( Dispenser Containment Sensors. Did you confirm positive shut -down due to leaks and sensor failure/disoonnection? r e; No. Yes No' For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill prevention N/A valve is installed), is the overfill warning a visible and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm er? % Yes' No Was any monitoring equipment replaced? If yes, identity specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes' No Was liquid found Inside any secondary containment systems designed as dry systems? (Check all that apply) Product Water. if es, describe causes in Section E below. Yes No- Was monitoring system set -up reviewed to ensure propersettings? Attach set up reports, if applicable Yes No- Is all monitoring equipment operational per manufacturer's specifications? In Section E below, describe how and when these deficiencies were or will be corrected. E. Comments: Monitoring System Certification Page 2 of4 72/07 2/21/07 F. InTank Gauging / SIR Equipment: 13' Check this box iftank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in -tank gauging equipment is used to perform teak detection monitoring. Complete thefollowing checklist Yes No' Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No* Were all tank gauging probes visually inspected for damage and residue buildup? Yes No' Was accuracy of system product level readings tested? Yes No' Was accuracy ofsystem water level readings tested? Yes No' Were all probes reinstalled properly? iYes :d No* Were all items on the equipment manufacturers maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): Check this box if LLDs are not installed. Complete the following checklist: Yes No' For equipment start -up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all N/A that apply) Simulated leak rate: )C3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h. Yes No' Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No' Was the testing apparatus properly calibrated? Yes No' For mechanical LLDs, does the LLD restrict product flow if it detects a leak? WA Yes No• For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? N/A Yes No' For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or X- WA disconnected? Yes No' For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or N/A fails a test? Yes No' For electronic LLDs, have all accessible wiring connections been visually inspected? N/A Yes No* Were all items on the equipment manufacturers maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: Monitoring System Certification Page 3 of 4 14107 3 2/21/07 Monitoring System Certification Monitoring Site Plan Site Address: r.DR : tar*t' R RugC :: :: : STS . Sue1:E1?• : : : : : ANNGua2S G JLQSbiL. IO.60oCsA1: URC'SEtJ50R TRoK - LL D, fpwK PiggdLAR . . . . . . . . . ................. . LLD .. . AILL St 1nP MPS FrAA P R . . . . O. . . . . . Llidl EN . . . . . . . . . . . NU p1R . . . . . . . . . . . . 2t;. 000' i+i . . . . . . . . . . . . . . . ANNULI SfJtLSb C S/1Lri0(b ItDL3El: LL' D'fAN. :AiVi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . gip l.... 1p ±....... ,...... ! . -.. . 11.% ..................... ipENs:`iN : t :: Ar,InaLmz- Sc-wsb l; • -%NP bFS 1H-p13...1O.pc4::::.bp6:--..q.D3---- VCR, F... . ILL ........... .... ... . ...... .. . ........ .. ..... ............... jLMIr ................ ............................... COLiNTEk .. . . . . . . . . . . . . . . . . . AKKEJ ................ Date map was drawn: la lay Instructions If you already have a diagram that shows all required information, you may include it rather than this page, with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the space provided, note the date this Site Plan was prepared. Monitoring System Certification Page 4 of4 12!07 4 2/21/07 SYSTEM —SETUP — — — — — — NOV 1, 2011 1 : 46 FIM SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE./TIME FORMAT M iN DD YYYV HH:MM:SS, xll GRAND ISLA'1D CHEVRON 11400 M I NiG AVE. BAKERSD I ELD . i :A 93311 SHIFT TIME 1 IiISABLED SHIFT TINE 2 DISABLED SHIFT TIME 3 DISABLED SHIFT TIME 4 DISABLED TANK PER TST NEEDED WRN DISABLED TANK PNN TST NEEDED t.JRN DISABLED LINE RE— ENABLE METHOD PASS LINE TEST LINE PER TST NEEIiED WRN DISABLED LINE ANN TST NEEDED WRIV DISABLED PRINT TG VOLUMES ENABLER TEIIP iCONPENSAT I OIV VALUE (DEG F ): 60.0 STICK HEIGHT OFFSET DISABLED ULLA E : 90% H— PROTOCOL DATA FORMAT HEIGHT DA` i'LIGHT SAVING TIME ENABLED START DATE MAR WEEK '? SUN START TIME 2:00 AM END DATE NOV WEEK I SUN END TIME 2:00 AM RE— DIRECT LOCAL PRINTOUT D I :SABLED EURO PROTOCOL PREFIX S SYSTEM SEC: UR I TY' C!)DE : 000000 MAINTENANCE HISTORY ENABLED TANK [CHART SECURITY DISABLED CIJ13TOI "I ALARMS DISABLED 3ERV I CE NOT I CE DISABLED ISO 3166 COUNTRY ODE: VAPOR MOtl I TOR I NG TYPECARBISD I°IASS. DENS I T'Y` DISABLED COMMUNICATI0NS SETUP PORT SETTINGS COMM BOARD : 1 tEDIM ? RS -232 SECURITY CODE : DISABLED COMM BOARD 2 tRS -232} BAUIi RATE 9600 PARITY NONE STOP BIT I STOP DATA LENGTH: 8 DATA RS-232' SECURITY CODE : DISABLED AUTO TRANSMIT SETTINGS: AUTO LEAK ALARf'1 Lit-III' DISABLED AUTO HIGH WATER LIMIT DISABLED PUTO OVERFILL LIMIT DISABLED AUTO LOW PRODUCT DISABLED AUTO THEFT LIMIT DISABLED AUTO DELIVER`; START DISABLED AUTO DELIVERY END DISABLED AUTO EXTERNAL INPUT Ofd DISABLED AUTO EXTERNAL INPUT OFF DISABLED AUTO SENSOR FUEL ALARM DISABLED AUTO SENSOR WATER ALARI1 DISABLED AUTO SENSOR OUT ALA01 D I SABLED RS -232 END OF MESSAiGE ri I RABLED IN —TANK SETUP T I:UNLEADED PRODUCT CODE 1 THERMAL COEFF :.000700 TA14K DIAMETER 120.00 TANK PROFILE I PT FULL VOL 220000 FLOAT SIZE: 4.0 IN. MATER LJARN I NG 2.0 HIGH WATER LIMIT: 3.0 I:JATER ALARM FILTER: LOIA Mi:;X OR LABEL VOL: 20000 OVERFILL LIMIT 90% 18000 HIGH PRODUiCT 951". 19000 DELIVERY LIMIT 10% 2000 LOW PRODUCT t 000 LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 TANK TILT 0.00 PROBE OFFSET 0.00 SIPHON I IAN I FOLDED TANKS Ttt: NONE LINE HANIFOLDED TANKS I TO: NONE LEAK MIN PERIODIC: 1% 200 LEAK MIN ANNUAL 1:-v vUU PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARII Ii I SABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY 1 MIN T 2::-UPREME PRODUCT CODE 2 THERMAL COEFF :.000700 TANK DIAMETER : 120.00 TANK PROFILE I PT FULL VOL 12000 FLO"IT SIZE: 4.0 IN. WATER WARNING : U HIGH WATER LIMIT: 3.0 WATER ALARM F I LTER : LOW mA°. OR LABEL VOL: 120001 OVERFILL LIMIT 90 %t 10800 HIGH PRODUCT 9510 11400 DELIVERY LIMIT 10 %0 1200 LOW PRODUCT 1000 LEAK ALARM L I M I T: 99 SUDDEN LOSS LIMIT: 99 TONK TILT 0.00 PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS TO: NONE LINE MANIFOLDED TANKS TO: NONE LEAK MIN. PERIODIC 1 ,, 130 LEAK MIN ANNUAL I% 120 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED( ANN TEST AVERAGING: OFF F'ER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK. TST SIPHON BREAK:OFF DELIVERY DELAY 1 MIN T 3:DIESEL PRODUCT CODE :3 THERMAL i—OEFF :.000450 TANK DIAMETER : 120.00 TANK PROFILE 1 PT FULL VOL 10000 I FLOAT SIZE: 4.0 IN. WATER WARNING 2.0 I HIGH WATER LIMIT: 3.0 WATER ALARM FILTER: LOW MAX OR LABEL VOL: 10000 OVERFILL LIMIT 9001. 9000 HIGH PRODUCT 95°r„ 9500 DELIVERY LIMIT 10% 1000 LOW PRODUCT 1000 LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 TANK TILT 0.00 PROBE OFFSET 0.00 i SIPHON MANIFOLDED TANKS s TO: NONE LINE MANIFOLDED TANKS TO: NONE LEAK MIN PERIODIC: 0i 0 LEAK MIN ANNUAL : 0% L PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLEF? GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TAN1' TEST NOT iF`Y : OFF TNK TST SIPHON BREAY:OFF DELIVERY DELAY I MIN PU°1P THRESHtiLD 10.00 "i: LEAK TEST METHOD TEST ON DATE : ALL TANK JAN 2, 2012' START TIME : 2:00 f4l l TEST RATE :0.20 GAL/HR DURATION 2 HOURS: i TST EARL, STOP: ENABLED LEAK TEST REPORT FORMAT I NORMAL LIQUID SENSOR SETUP L I:DISP. 1 DW SUMP —1 CATEGORY DISPENSER PAN L ' '2:DISP. 3 -4 DW Sump —1 CATEGORY DISPENSER PAN L 3:DISP. 5 -6I j DW SUMP —1 i CATEGORY : DISPENSER PAN i L 4:DISP. 7 -8 DI,,[ SUMP 2 --1 CATEGORY : DISPENSER PAN L S:DISP. 9 -10 DW SUMP —1 CATEGORY : DISPENSER PAN L 6:DISP.11 -12 DW SUMP 2 -1 CATEGORY : DISPENSER PAN L 7:DISF'. 13-14 DW SUMP 2 -1 CATEGORY DISPENSER PAN L S:D1SP. 15 -16 DW SUMP —1 CATEGORY : DISPENSER PAll L 9:UNL. STP TRI —STATE eSINGLE FLOAT) CATEGORY : STP SUMP LIO:UNL.NTP ANN TRI —STATE (SINGLE FLOAT) iATEGORY : ANNULAR SPACE LI1:UNL. FILL TRI —STATE (SINGLE FLOAT) CATEGORY : OTHER SENSORS L 12 : I INL . FILL ANN TRI —STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE L 13 : SUPREME STP TRI —STATE (SINGLE FLOAT) CATEGORY : STP SUMP 1-14:SUPREME STP ANN TRI —STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE L15:SUPREME FILL TRI —STATE (SINGLE FLOAT) CATEGORY : STP SUMP 1-16:6UPREME FILL ANN TRI —STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE LI ?:DIESEL STP TRI— STATE (SINGLE FLOAT) CATEGORY : STP SUMP OUTPUT RELAY SETUP R I:UNLEADED TYPE: PUh9P CONTROL OUTPUT TANK 0: 1 LIQUID SENSOR ALMS L I :FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4 :FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L B:FUEL ALARM L 9:FUEL ALARM L13:FUEL ALARM L 1:SENS0R OUT ALARM L 2:SENSOR OUT ALARM L 3 :SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENS0R OUT ALARM L 6:SENS0R OUT ALARM L 7:SENS0R OUT ALARM IV B :SENSOR OUT ALARM L 9 :SEN2,,OR OUT ALARM 1_13 SENSOR OUT ALARM L I:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SH0RT ALARM L 5:SH0RT ALARM L 6:SH0RT ALARM L 7:SH0RT ALARM L 8 : SHORT ALARI°I L 9:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL R 2:SUPREME TYPE: PUMP CONTROL OUTPUT TANK # : 2 LIQUID SENSOR ALMS L I:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L B:FUEL ALARM L 9:FUEL ALARM L13:FUEL ALARM L I:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L B:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3 :SHORT ALARM L SHORT ALARM L 5:SHORT ALARM L 6:SH0RT ALARM L SHORT ALARM L 8:SH0RT ALARM L 9:SHORT ALARM L13:SH0RT ALARM ISD SITE ALARMS ISD GROSS PRIES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK. FAIL R 3: Ii I ESEL TYPE: PUMP CONTROL OUTPUT TANK #: 3 LIQUID SENSOR ALI-IS L 1:FUEL ALARM L B:FUEL ALARM L17:FUEL ALARM L I:SENSOR OUT ALARM L B:SENSOR OUT ALARM L17:SENS0R OUT ALARM L i:SHORT ALARM L B:SHORT ALARM L17:SH0RT ALARM R 4:OVER -FILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #!: NONE IN -TANK ALARMS ALL :OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM SMARTSENSOR SETUP s 1 : UNL . PRODUCT CATEGORY VAC SENSOR PUMP #1: R 1:UNLEADED VOLUME: 100.0 GALLONS RELIEF VALVE: : 110 s 2: VAPOR CATEGOR`! VAC SENSOR PUMP #1: R 1:UNLEADED VOLUME: 100.0 GALLONS RELIEF VALVE: : NO s 3:UNL TANK ANN CATEGORY VAC SENSOR PUMP #: R 1:UNLEADED VOLUME: 100.0 GALLONS RELIEF VALVE: : NO 5 4 :UNL VENT CATEGORY VAC SENSOR PUMP 0: R I:UNLEADED VOLUME: 100.0 GALLONS RELIEF VALVE: : NO s 5:SUPREINIE PRODUCT CATEGORY VAC SENSOR PUMP 0: R 2:SUPREME VOLUME: 100.0 GALLONS RELIEF VALVE: : NO s 6:SUPREME VENT CATEGORY VAC SENSOR PUMP d: R 2:SUPREME VOLUME: 100.0 GALLONS RELIEF VALVE: : NO s 7:SUPREME TANI ANNISDHOSEALARMS ALL:GROSS COLLECT FI L CATEGORY VAC SEV50F ISD HOSE ALARI°S r PUMP 0: ALL:GROSS C:ULLECT FAIL ALL:DEGRD COLLECT FAIL R 2:SUPREME ALL : DEGRD COLLECT FAIL ALL :FLOW COLLECT FAIL VOLUME: 100.0 GALLONS ALL : FLOW COLLECT FAIL RELIEF VALVE: : NO s 8: ATM FUEL GRADE CATEGOR'; ATM P SENSOR s 9:DIESEL VENT CATEGORY VAC SENSOR PUMP #: FP MHH MHH HHHR3:DIESEL VOLUME: 100.0 GALLONS RELIEF VALVE: : NO s10:DIESEL PRODUCT CATEGORY VAC SENSOR PUMP #: 105 005 205 R 3:DIESEL VOLUME: 100.0 GALLONS RELIEF VALVE: : NO sl7:DISP. 1 -2 CATEGORY AIR FLOW METER s18:DISP. 3 -4 CATEGORY AIR FLOW METER s19:DISP. 5 -6 CATEGORY AIR FLOW METER s20:DISP. 7 -8 CATEGORY AIR FLOW METER s21:DISP. 9 -10 CATEGORY A I R FLOl. +1 METER 522 :DISP. 11 -12 CATEGORY AIR FLOW METER s23:DISP. 13 -14 CATEGORY AIR FLOW METER s24:DISP. 15 -16 CATEGORY VAPOR PRESSURE s25:DISP. 15 -16 CATEGORY AIR FLOW METER I SD FUEL GRADE HOSE MAP 02 1 2 3 4 02 34 FP MHH MHH HHH MHH AA 00 104 004 204 U U 2 O1 105 005 205 U U 3 f 02 106 006 206 U U 3 03 107 007 207 U U 4 04 108 008 208 U U 4 05 109 009 209 U U 5 06 110 010 210 U U 5 07 111 011 211 U U b- 08 112 012 212 U U 6 09 113 013 213 U U 7 10 114 014 214 U U 7 11 115 015 215 U U 8 32 116 016 216 U U 8 33 101 001 201 U U 1 34 102 002 202 U U 1 35i 103 003 203 U U 2 LABEL TABLE 16 02 08 1: UNASSIGNED BLENDS 3: REGULAR 4: MID GRADE 5: PREM I UI°I 6: GOLD 7: BRONZE 8: SILVER 9: BLEND2 10: BLEND4 PMC SETUP PMC VERSION: 01.04 VAPOR PROCESSOR TYPE NONE PROCESSOR CONTROL LEVEL: NONE EVR ISD SETUP EVR T' 'PE : VACUUM ASSIST VACUUM ASSIST TYPE HEALY VAC NOZZLE A.iL RANGE MkX : 1 .15 1 °1I PJ : 0.95 VAPOR PROCESSOR TYPE NONE ANALfSI3 TIMES TIME: 10:00 AM DELAY MINUTES: 1 ACCEPT HIGH ORVR : DISABLED ISD HOSE TABLE ID FP FL HL AA RR 01 U3 01 02 UI 02' 02 34 02 02 01 02 03 35 03 02 02 0' 04 00 04 02 02 02 05 01 05 02 03 02 06 02 06 02 03 02 07 03 07 02 04 02 08 04 08 02 04 02 09 05 09 02 05 02 10 06 10 02 05 02 11 07 11 02 06 02 12 08 12 02 06 02 13 09 13 02 07 02 14 10 14 02 07 02 15 11 15 02 08 02 16 32 16 02 08 02 I SD A I RFLOW METER MAP ID SERIAL NUM LABEL 1 41339 DISP. 1 -2 2 41325 DISP. 3 -4 3 41332 DISP. 5 -6 4 41333 DISP. 7 -8 5 54619 DISP. 9 -10 6 54620 DISP. 11-1 7 54617 DISP. 13 -1 8 41338 DISP. 15 -1 ALARM HISTORY REPORT IN-TANK ALARM - T I:UNLEADED SETUP DATA WARNING OCT 11. 2011 1 :25 PI'1 HIGH WATER ALARM OCT 21. 201 1 1 :53 P11 OVERFILL ALARM 0CT 21. 2011 2:01 PH DOT 21 . 2011 9::37 41 LOW PRODUCT ALARM 1:53 OCT 91. 2011 1:48 PM OCT 21. 9011 9:35 AM OCT 19. 201l 7:41 All SUDDEN LOSS ALARM OCT 21, 2011 9:35 AM OCT 19, 2011 7:41 All HIGH PRODUCT ALARM 1:41 OCT 21, 2011 9:37 AM INVALID FUEL LEVEL OCT 11, 2011 OCT 11. 2011 1:25 Ptl PROBE OUT I :56 Pt °1 00'T 21 . 2011 2: 02 PM OCT 19, 2011 7:41 All OCT 17. 2011 7:44 All HIGH WATER WARNING OCT 21. 2011 1 :53 Pill ALARM HI S'L.')R1` REP'.>R1 IN -TANK ALARM - T '_' : SUPREI "IE HIGH WATER ALARM OCT 2l. 2011 1 :55 P11 OCT 17, ' 201 1 12:56 P11 ! OVERFILL ALARM OCT 21. 2011 1:58 PM LOW PROIiUCT ALARM OCT 21. 2011 1:58 Pll OCT 21.. 2011 1:50 PI °1 OCT 19. 2011 7:58 All SUDDEN LOSS ALARM OCT 19, 2011 7:38 At °l OCT 17. 2011 9:47 All INVALID FUEL LEVEL OCT 21, 2011 2:O3 Phl iOCT19. 2011 7:43 AM OCT 11, 2011 12:23 PM PROBE OUT OCT 21. 2011 2:02 PM OCT 19, 2011 7:59 AM OCT 19, -'011 7:54 AM HIGH WATER WARNING OCT 21 . 2011 1:55 PH OCT It. 2011 2:'--)l PM DELIVERY NEEDED f OCT 21 . 20 T 1 1 :58 PrIl OC:T 21. 2011 1 :50 Pt °I OCT 19. '2'011 7:58 All i 1. DELIVERYSER1` h1EELiED LOW TEMP' WARNINGDEL ' i . ?Oil ? : 01 PI °I OCT 19. '?O 1 1 y : 5'' All OCT 21, 2011 9:44 All OCT 19, 2011 7:56 AM OCT I1. 2011 1:25 PM END x x ri ALARM H I STOR'f REPORT IN-TANK ALARM - T 3:DIESEL SETUP DATA WARNING OCT 11. 2011 1:41 Phi OVERFILL ALARM OCT 21. 2011 1:55 Pt °1 OCT 21, 2011 1:53 PM LOW PRODUCT ALARM OCT 21, 2011 1:57 Pll OCT 21. 2011 1 •52 PP1 OCT 1 1 . 21011 1 : 41 P11 HIGH PRODUCT ALARM OCT 21. 2011 1:53 Pil INVALID FUEL LEVEL OCT :' 1 . 2011 1:55 PH OCT 1l. _011 1:41 PrI PROBE OUT OCT '21. '2011 2:04 PM OCT 11, 2011 1:10 P11 HIGH WATER WARNING OCT 21. 201.1 I :56 Pt °1 DELIVERY NEEDED OCT 21. 2011 1:57 PM OCT 21 . 2011 1 :51 PH OCT 1 1 . 2011 1 :41 Pt °l n END x z ALARM H 1 STOR ", REPORT SENSOR ALARI'l - - - -- L 1:DISP. 1 DISPENSER PAN SENSOR OUT ALARM 0C 21. 2011 2'21 8 PM LOW L I GU I D ALARM OCT ' 21 . 2011 1 :215 P11 FUEL ALARM OCT 21, 2011 1 : 20 Pt°l x * * n ; END n * * x ALARM HISTORY REPORT SEN'SOR ALARM L 2:DISP. 3--4 DISPENSER PAN SENSOR OUT ALARM OCT 21. 2011 2:28 PM LOW LIQUID ALARM OCT '- 1 . 201 1 1 .27 Pi1 17UEL ALARM UCT 2A . '20 1 1 1: 19 PM ALARM H12TORY REPORT SENSOR ALARM L '-':DISP. 5-6 DISPENSER PAN SENSOR OUT ALARM OCT 211.- 2011 2:28 PH LOU LIQUID ALARM OCT 21. 2011 1:26 PH FUEL ALARM OCT 21, 2011 1:18 PM x * X ENE) * * * * * ALARM HISTORY REPORT DISPENSER PAN SENSOR OUT ALARM OCT 21. 2011 2:28 PH LOW LIQUID ALARM OCT 21. 2011 1:'26 PM FUEL ALARH OCT - 201 1 1 : 18 Pill Al-ARM HISTOR'L` REPORT L 5:DISP. 9-10 DISPENSER PAN SENSOR OUT ALARM OC :T 21. 2011 2:28 PI " I LOW L I OU I D ALARM OCT 21, 2011 1:25 Pll FUEL ALARM OCT 21 o 2011 1 17 Pll X * * ;Y, * END '* x * x - ALARM HISTORY REPORT SENSOR r-iLARIII L 6:DISP.11-12 DISPENSER PAN SENSOR OUT ALARM- OCT 21. 2011 21:2-18 PH LOW LIOUID ALARM OCT '21. 2011 1 PH FUEL ALARM 0 (" T 21 - '201 1 1: 17 PH bARll HISTOR',' REPORT SENSOR ALARM L 7:DISP. 13-14 DISPENSER PAN SENSOR OUT r`lI-A'RM DCT 21, -011 2:28 PH LOW LIOUID ALARI'l OCT 21, 2011 1 :25 Pll FUEL ALARM i OCT 21, 2011 1:16 PI'l x * END -* x ' ALARM HISTORY' REPOR'l SENSOR ALARM L b'DISP. 15-16 DISPENSER PAN SENSOR m',UT ALARM OCT 21 - 2011 LOW LIQUID ALARM CT 2 1 - 'DO 1OAT 1 1 :25 PH FUEL ALARM OCT - 2011 t : 15 PH hl-ARt"l H I STORY REPORT SENSOR ALARM L 9:UNL. STP STP SUMP SENSOR OUT Al-iiRfl OCT 21. 2011 '2 28 PM FUEL ALARM OCT 21, 2011 1: 1 PH FUEL. ALARM OCT 14, 2011 1 :10 PM x f * x 'w, E- I.JL) * * * * X ALARM HIl-n-`f()R','l REPORT SENSOR ALmRll LIO:(JNI-.STP ANN ANNULAR SPACE SENSOR OUT ALARM 0CT , 220 1 1 2:28 Pl-,l FUEL ALARM 0CT 21 - 201 1 1 : '24 F ' I'l Al-HRH HISTORY REP)P*I' SENSOR ALARM LII:UNL. FILL OTHER SENSORS SENSOR OUT ALARM OCT 21. 2011 2: 28 F11 FUEL ALARM OCT 14, 2011 1:12 Rl k x X x END *. .( x x .t ALARH HISTORY REPORT SENSOR ALARM L12:UNL. FILL ANN ANNULAR SPACE SENSOR OUT ALARM OCT 21, 2011 2:20 I'M FUEL ALARM 0(,'T 21. 2011 1 :24 Ffl x x x* END X :t x * ri ALARM HISTORY REPQR'I' SEI*25op ALARI,.i L 13: SUPREME 'STP STP SUMP SENSOR OUT ALARM T 21 - 2, 011 2-27 -Pi-1 FUEL Al-ARI-i IIII OCT 21, 2011 1 :20 Pt"I FUEL ALAR11 OCT 14, 2011 1 :10 Pm vk ;k x END * * 3' ,, * AI-PiR[lt HISTORY REP OR, ALARM 1-10SUPREHE STP ANN SENSOR OUT ALARM OCT -"1.. 2011 2:28 P11 FUEL ALARM OCT 21, 2011 1 : _'4 PH FUEL ALARM OCT 2-1, 2 01 1 1 :2,31 F-1•1 x * * * END x 7,; k '* 1ilJiRr1 HI STS R"Y REPORT SENSOR NI -ARll L15:SUF-PEI-JE FILL STP SUMP SENSOR OUT ALARH OCT 21. 2011 2:2-8 Pil FUEL ALARM OCT 14, 2011 1 :1 1 Pf,-1 x * END * * x j-- * ALARM HISTOR',-' REP = >R7' SENSOR ALARM 1-16:0-UPRE11E FILL ;)I'•IN ANNULAR SPACE FUEL ALARM OCT 24. 2011 11:42 AN SENSOR OUT ALARM OCT 21, 2011 2: 28 Pfl FUEL ALARM OCT 21. 2011 1 :24 Prl t , X x :* END * * * -, * HDARll HISTORY REPORT SENSOR ALARf-1 L 17: Lj I ESEL STP STP SUMP SENSOR OUT ALARM CICT 21- 2011 2:27 PH FUEL ALARM OCT 21, 2011 1 12 PH FUEL ALARM OCT 14, 2011 1 :10 pf°j i END * . X , A ALARM HISTOR-,,i REPORT SENSOR ALARt-1 LIG:lJIESEL STP ANN ANNULAR SPACE SENSOR OUT ALARM 0,-'T 21. 2011 2:27 pm FUEL ALARM OCT 21. 2011 1 22 PH FUEL ALAR(-j OUT 21, 2011 8:0a Al.1 x END ALARM HISTORY REPORT ALARM HISTORY REPORTALARMHISTORYREPORT SENSOR ALARM 1_19:DIESEL FILL OTHER SENSORS SENSOR OUT ALARM OCT 21 - 2011 2:228 Pf"I FUEL ALARM OCT 14, 2011 1 : I I PH SENSOR OUT ALARM OCT ll. 2011 1 : 41 PM x X. ik A. x END ;k 4; 4 W, ALARM HISTOR-,,' REPORT SENSOR ALARll L'DO:DIE---EL FILL ANN ANNULAR SPACE SENSOR OUT ALARM OCT 21. 2011 2:28 P111 FUEL ALARM OC-T 21, 2011 1 : 2:3 P11 FUEL ALARM o('T 21.. 2011 11 :43 Al'•1 x -X END * * x *, * ALARM HIST(_>RY REPORT SW'IRTSENSOR ALARM -- I : UNL. PRODUCT VACUUM WARNING 0 'T 29 P11U21 HIGH LIQUID ALARM OCT 21, "Oil 2,;06 PM HIGH LIQUID ALARM OCT 21. 2011 1:44 PH END ALARM HISTORY REPORT SMr_1RTSENSOR ALARM 5 _-':VAPOR HIGH LIQUID ALARM OCT 21- 2011 1:44 P'll PJO VACUUM "'LHRM OCT 21, 2011 1:44 Ftl NO VACUUM ALARM OCT 21. 2011 1 30 ftl x* * x * END )k x x A *. SMARTSENSOR ALARM -- s 3: UNL TANK A14N NO VACUUM ALARM OCT 221 '210-11 1 :32 F11 SENSOR FAULT ALARM OCT 21. '2011 9:59 AM NO VACUUM ALARM 0C. T 21 ^01 1 9: 18 AM X X I( x* END * * t* x ALARM HISTORY REPORT SMARTSENSIOR ALARM -- s 4:UNL VENT HIGH LIQUID ALARH OCT 21, 2011 1:45 P11 110 VACUUM ALARM OCT '21, 2011 1 : 44 PM NO VACUUM ALARM 0C :T 2 1. - 20 1 1 1 :'31 Pri x 'A * * x END x )t *: w X SM"'ARTSEN2::"0R 5: SUPREME PRODUCT NO VACUUM ALARM OCT 26. 2011 1 150 Flm NO 'v'ACUUN ALARM OCT 226, 2011 1 50 F-M HIGH LIQUID ALARM OCT 211, "11011 121:14 pt"1 t t* x END * A 'k *. s ALARM HISTORY REPORT SHHRTSENSIOR ALARM 3 b:SWPREME VENT HIGH LIQUID ALARM OCT 221, 2011 2:11 PH 1 HIGH LIQUID ALARM OCT 21.. 2011 2:11 PM NO VACUUM (ALARM 0 'CT '-'1, X011 1:46 PM or, END ALARM HISTORY REPORT SMARTSENSOR ALARM -- i 9 :a1 E1 VENT HIGH LIQUID ALARM T 21. 2011 1 :49 P11 Q VACUUM ALARM T 21. 2011 1 :48 P NO Cur ALARM T 21. 2011 1 :86 P X X * EN « k * y * A M HISTORY REPORT SMARTSENSOR ALARM -- siO :DIEE PRODUCT HIGH LIQUID ALARM T 21. 2011 2 :18 F HIGH LIQUID ALARM T 21. 2011 2 :17 ! 140 VACUUM ALARM T 21. 2O!! 1 :48 PH k * * * E l X * * * * ALARM HISTORY REPORT SMARTSENSOR ALARM 7 :SUPPEME TANK ANN N VAc.UUM ALARM T 21, 2011 1 :a4 ,t SETUP DHT WARNING T II, 2011 1 :10 N VACUUM ALARM T ll, 2011 1 :02 E t ARM H1: 0 REPORT AkeEms§ oR ALARM -- s B: ATM EN * * * * *