July 3, 2012
VIA FED EX 7985 8202 1504
Bakersfield Fire Department
2101 H Street
Bakersfield CA 93301
Re: Secondary Containment Testing
AT&T Corporation
1520 20th STREET, BAKERSFIELD, CA
GEOPAR: CAK010
To Whom it May Concern:
2' >... Dt,po,0 r.;::... An,h,,im, CA 92x:6
Enclosed are the results for the following tests completed on June 29, 2012:
Secondary Containment Testing Report Form
Please do not hesitate to call me if you have any questions.
Program Manager
CA I+co 588098 ± AZ Ilc? 095984 ; NV I c 0049666 ! 7X hc4 CR0000041.
Secondary Containment Testing Report Form
Thisfornt is intendedforusehy contractors perfortningperiodic testing ofUSTsecondarycontaintnetit systems. Use the
appropriate pages ofthis form to report resultsfor all components tested The completedform, written test procedures, and
printouts from tests (ifapplicable), should be provided to the facility owner /operatorforsubmittal to the local regulatory agency.
I. FACILITY INFnRMAT1(1N Farilitv In• CA i<nio
Facil it Name: AT&TCorporation Date of Testin : 6/29/2012
Facility Address: 152020TH ST, BAKERSFIELD, CA 93301
Facility Contact: Grant Armstrong Phone: (661) 327 -6903 r Initial r Repair Test
Date Local Agency Was Notified Of Testing: 6/18/2012 F 6 Month r Other
Name of Local Agency Inspector (if present during testing): Ernie Medina Triennial
2. TESTING CONTRACTOR INFORMATION
Company Name: Tait Environmental Services
Pass
Technician Conducting Test: Adolfo Aguilar
Not
Tested
Credentials: CSLB Licensed Contractor f— SWRCB Licensed Tank Tester r, ICC UST Service Technician
License Type: A B AS C -10 HAZ I License Number: 588098
Not
Tested
Man ufactu rer Training
Annular #CAKOI OU00I
Manufacturer Component(s)
r
Date Training Expires
ICC Technician 5238610 -UT
r
2/7/2013
Incon TS -STS 1732573702
i
8/4/2012
Blueline CA -1870 8/4/2013 _
j— r— F—
Piping Sump #CAK0100001
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not
Tested
Repairs
Made Component Pass Fail Not
Tested
Repairs
Made
Annular #CAKOI OU00I f7 r r r r r r
Fill Swap #CAKO10U001 i r- r— r r— j— r— F—
Piping Sump #CAK0100001 i— r- f- I f- r
Trans. Sump #CAKO10U001 r F F F r r r r
Sply Sec. Line #CAKO10U001 17 r— F fv j` f— F- f-
Ret. Sec. Line #CAKO10U001 f7 f— r F7 f— f— r r
Vent Sec. Line #CAKOl0U00I f f" C" F f— F f— F-
r r f—
r r F- f—
r r f- r f- r
If hydrostatic testing was performed, describe what was done with the water after completion of tests:
ITook Non -Haz. Test Water To Tait Shop.
For any equipment capable ofgenerating a print out of test results, you must attach a copy of the test report to this
certification f System printout attached.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best ofmy knowledge, thefacts stated in this documen tare accurate and in full compliance with legal requirements
Technician's Signature: f,,,,r%, Date: 6/29/2012
4. TANK ANNULAR TESTING
Test Method Developed By: r Tank Manufacturer r Industry Standard r Professional Engineer
F Other(Specify)
Test Method Used: F Pressure Vacuum r Hydrostatic
F Other(Specify)
Test Eciuinment Used: 4" Dial Gauee Eauinment Resolution: .2
ikl, L - A a ®' Tank
Annular#ICAKOIOUDOI
Tank Tank Tank
Is Tank Exempt From Testing? 0) r Yes F No r Yes r No r Yes r No r Yes r No
Tank Capacity: 8,000 Gallons
Tank Material: Steel / Clad
Tank Manufacturer. Joor
Product Stored: Diesel
Wait time between applying
pressure /vacuum/waterand
starting test:
1 Hour
Test Start Time: 10:00 AM
Initial Reading (Rt): 10 HG
Test End Time: 11:00 AM
Final Reading (RF): 10 HG
Test Duration: 1 Hour
Change in Reading (RF -R,): 0
Pass/Fail Threshold or Criteria: 0
Test Result: 1 Pass r Fail r Pass r Fail r Pass r Fail r Pass r Fail
Was sensor removed for testing'? I' 1g r No 1 NA r Y. I I N° r NA r Y. 1 1 N° r NA vg r N° r NA
Was sensor properly replaced and
verified functional after testing'? r– rYaNO Nn r r rYesNo NA r rrYaNo NA r r rYesN° NA
Comments – (include information on repairs made prior to testing, mid recommendedfollow -tipforfailed tests)
Reinstalled Sensor To Lowest Point But Not'l'ested.
1) Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary
containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic
containment testing. { Cali forniaCode of Regulations, Title 23, Section 2637(a)(6)1
5. SECONDARY PIPE TESTING
Test Method Developed By: r Piping Manufacturer F Industry Standard r Professional Engineer
F Other(Specify)
Test Method Used: F Pressure r Vacuum r Hydrostatic
F Other(Specify)
Test Equipment Used: 4" Dial Gauge Equipment Resolution: X'
Piping Run
Supply #CAKOIOU00I
Piping Run
Return #CAKOIOU00I
Piping Run
Vent #CAK0100001
Piping Run
Piping Material: Poly Poly Fiberglass
Piping Manufacturer: Western Fiberglass Western Fiberglass Ameron
Piping Diameter: 1" 1.50" 2"
Length of Piping Run: 120' 120' 35'
Product Stored: Diesel Diesel Diesel
Method and location ofpiping -run
isolation: rest Boot Test Boot Test Boot
Wait time between applying
pressure/vacuum/waterand
starting test:
15 Minutes 15 Minutes 15 Minutes
Test State Time: 1:10 PM 1:10 PM 9:25 AM
Initial Reading (R1): 5 PSI 5 PSI 5 PSI
Test End Time: 2: 10 PM 2:10 PM 10:25 AM
Final Reading (R1): 5 PSI 5 PSI 5 PSI
Test Duration: I Hour 1 I -lour I Hour
Change in Reading (RF"R1): 0 0 0
Pass/Fail Threshold or Criteria: 0 0 0
Fest Result: rv—' Pass r Fail F Pass r Fail F Pass r Fail r Pass r Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow-up forfailed tests)
lReplaced Supply Sec. Line Test Boot & Return Sec. Line Test Boot In The Transition Piping Sump, Re- tested & Passed.
6. PIPING SUM PTESTING
Test Method Developed By: r Sump Manufacturer F Industry Standard r Professional Engineer
r Other(S eci )
Test Method Used: F Pressure r Vacuum Hydrostatic
r Other(Specify)
test Equipment Used: In -font "fS -STS Equipment Resolution: .0006
Sump ump Sump umpx--, ` F ' Piping #CAK0100001 Trans. #CAK0100001
Sump Diameter: 42" 30" X 24"
Sump Depth: 34" 33"
Sump Material: Fiberglass Fiberglass
Height li•om Tank Top to "fop of
Highest Piping Penetration: 17 16"
Height from Tank "fop to Lowest 20" N/AElectricalPenetration:
Condition ofsump prior to Good Good
testing :
Portion ofSump Tested (1) 2" above penetration 2" above penetration
Does turbine shut down when
sump sensor detects liquid (both r Ya r r
No I- NA
r rr
1 Ya 1 No I- NA r1 Ya No NA
r r
Ya I No 1 NA
product and water) ?*
Turbine shutdown response time N/A N/A
Is system programmed for fail- r Ya r No IV NA r r r1YesINoI_ NA r r rIYa1NoI NA r- f Yes I No F NAsafeshutdown ?*
Was fail -safe verified to be Ya r No NA r Ya r r No 1V NA Ir Ya 1r No I NA f Ya f No 1r NAoperational ?*
Wait time between applying
pressure/vacuum/water and 15 Minutes 15 Minutes
starting test:
Test Start Time: 1:33 PM 1:56 PM 1:56 PM 2:13 PM
Initial Reading (RI): 5.2121 5.2115 5.1153 5.1150
Test End Time: 1:48 PM 2:12 PM 2:12 PM 2:28 PM
Final Reading (RI): 5.2116 5.2113 5.1 150 5.1150
Test Duration: 15 Min. 115 Min. 15 Min. 115 Min.
Change in Reading (RF"Rt): 0005 0002 0003 0000
Pass/Fai I "Threshold or Criteria: 002 1.002 002 1.002
Test Result: r rPass Fail r' rPass Fail rrPass Fail rrPass Fail
Was sensor removed for testing? F Ya r No r NA r Ys r Nor NA r Ya r No r NA r Yes r Nor NA
Was sensor properly replaced and r 1'a I "o r "A rr1'a P "o r "A r Yes r "o r "A r 1'a r "of r NAverifiedfunctionalaftertesting?
Comments — (include information on repairs made prior to
Re
testing, and recommendedfollow -rip for failed tests)
talledins Sensor To Lowest Point But Not Tested.
mm ..._.___
A t
1) Ifthe entire depth of the sump is not tested, specify how much was tested. Ifthe answer to any of the questions indicated
with an asterisk ( *) is "NO" or "NA', the entire sump must be tested. (See SWRCB LG -160)
8. FILL RISER CONTAINMENT SUMP TESTING
Facility is Not Equipped With Fill Riser Containment Sumps r
Fil I Riser Containment Sumps are resent, but were Not Tested r
Test Method Developed By: (— Sump Manufacturer r--' Industry Standard r Professional Engineer
F Other(Specify)
test Method Used: (— Pressure r Vacuum F-00 Hydrostatic
r Other(Specify)
Test Equipment Used: Incon TS -STS E ui ment Resolution: .0006
e Fill Sum p
Fill KAK010000I
Fill Sum p Fill Sum p Fill Sump
Sump Diameter: 42"
Sump Depth: 36"
Height from Tank Top to Top of
Highest Piping Penetration: N/A
Height from Tank Top to Lowest
13lectrical Penetration: 24„
Condition of sump prior to
testing :
Fair
Portion of Sump Tested: 2" Above Colllar
Sump Material: Fiberglass
Wait time between applying
pressure /vacuum /water and
starting test:
15 Minutes
Test Start Time: 12:01 PM 12:16 PM
Initial Reading (R1): 3.1731 3.1733
Test End Time: 12:16 PM 12:31 PM
Final Reading (RF): 3.1733 3.1736
Test Duration: 15 Min. 115 Min.
Change in Reading (RF"R1): 0002 0003
Pass/Fai I Threshold or Criteria: 002 1.002
Test Result: r Pass r Fail r Pass r Fail r Pass r— Fail r Pass r Fail
Is there a sensor in the sump'? r Ym No F Ym F No F Y. (— No F Y. No
Does the sensor alarm when either
product or water is detected?
F
Yes '- No F NA F Y. F No F NA F Yes f— No r- NA
F
Yes j No F- NA
Was sensor removed for testing? I- Y. I No I NA rI Y. r- No F NA r r rIYg1NoIr NA rI Yes No NA
Was sensor properly replaced and
veri tied functional after testing? r 'g "° NAFF F F No r NAYes r Yes r No I NA
r-
rF
F Yes I No 1 NA
Comments — (include information on repairs made prior to testing, and recommendedfollow -up forfailed tests)
sorTrip In Alarm During Testing, Reinstalled Sensor To Lowest Point.
ATT CAKO10
1520 20TH ST,
BAKERSFIELD
CALIFORNIA
TAIT ENVIRONMENTAL
06/29/2012 1:48 PM
SUMP LEAK TEST REPORT
PIPING
TEST STARTED 1:33 PM
TEST STARTED 06/29/2012
BEGIN LEVEL 5,2121 IN
END TIME 1:48 PM
END DATE 05/29/2012
END LEVEL 5,2116 IN
LEAK. THRESHOLD 0,002 IN
TEST RESULT PASSED
TRANSTN
TEST STARTED ' 1:56 PM
TEST STARTED 06/29/2012
BEGIN LEVEL 5,1153 IN
END TIME 2:12 PM
END DATE 06/29/2012
END LEVEL 5.1150 IN
LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED
ATT CAK010
1520 20TH ST,
BAKERSFIELD
CALIFORNIA
TAIT ENVIRONMENTAL
06/29/2012 2:12 PM
SUMP LEAK TEST REPORT
PIPING
TEST STARTED 1:56 PM
TEST STARTED 06/29/2012
BEGIN LEVEL 5,2115 IN
END TIME 2:12 PM
END DATE 06/29/2012
END LEVEL 5,2113 IN
LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED
TRANSTN
TEST STARTED 2:13 PM
TEST STARTED 06/29/2012
BEGIN LEVEL 5,1150 IN
END TIME 2:28 PM
END DATE 06/29/2012
END LEVEL 5.1150 IN
LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED
I
TEST DATE: 6/29/2012 CLIENT: AT &T GEOPAR: CAKO10 PAGE J- OF P-
ATT CAKO10
1520 20TH ST, ATT CAKO10
1520 20TH ST, BAKERSFIELD
CALIFORNIA BAKERSFIELD I
TAIT ENVIRONMENTAL CALIFORNIA
TAIT ENVIRONMENTAL
06/29/2012 12:16 PM
06/29/2012 12:31 PM
SUMP LEAK TEST REPORT
SUMP LEAK TEST REPORT
i
FILL
r
FILL
TEST STARTED 12:01 PM
TEST STARTED 06/29/2012 '" TEST STARTED 12:16 PM
BEGIN LEVEL 3,1731 IN TEST STARTED 06/29/2012
END TIME 12:16 PM BEGIN LEVEL 3,1733 IN
END DATE 06/29/2012 E.ND,TIME 12:31 PM
END LEVEL 3,1733 IN END DATE 06/29/2012
LEAK THRESHOLD 0,002 IN END LEVEL 3,1736 IN
TEST RESULT PASSED LEAK THRESHOLD 0,002 IPJ
TEST RESULT PASSED
TEST DATE: 6/29/2012 CLIENT: AT &T GEOPAR: CAK010 PAGE cv?- OF '