January 31, 2012
VIA FED EX 7931 7737 6584
Bakersfield Fire Department
2101 H Street
Bakersfield CA 93301
Re: Monitoring System Certification
Spill Bucket Testing
AT&T Corporation
1520 20th STREET, BAKERSFIELD, CA
GEOPAR: CAK010
To Whom it May Concern:
r3,'l
213. 4 I.h,pont D. ,e, A-lh m,, CA Y;206
Enclosed are the results for the following tests completed on January 27, 2012:
Monitoring System Certification Report Form
Spill Bucket Testing Report Form
Please do not hesitate to call me if you have any questions.
Very Truly
Matthew L. Denison
Program Manager
CA ic.# 588098; A2Ilc 095984 NV I,cx 01049666,`TX hca CR0000041
I
Appendix VI
Copies of Monitoring System Certification form and UST M onitoring Plot Plan available at http: / /www.waterboards.ca.gov .)
MONITORING SYSTEM CERTIFICATION
For Use By AllJurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6.7, Health andSafe v Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs die work. A copy of this form must be provided to the tank system owner /operator
owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days oftest date.
A. General Information
Facility Name: AT &T Corporation BuildingNo.: CAK010
Site Address: 1520 20TH ST City: BAKERSFIELD Zip: 93301
Facility Contact Person: Grant Anrnstrong Contact Phone No.: (661) 327 -6903
Make /Model of Monitoring System: Veeder -Root / TLS -350 Date ofTesting/Servicing: 1/27/2012
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to indicate specific eauipment inspected /serviced:
The
Tank ID: CAKOIOU001 i Tank ID: Dierel #CAKOIOA002
F' In -Tank Gauging Probe. Model: 846390 -105 i In -Tank Gauging Probe. Model: 847390 -301
F Annular Space or Vault Sensor. Model: 794390420 P Annular Space or Vault Sensor. Model.. 794380 -208
F Piping Sump/ Trench Sensor(s). Model: 794380 -208 F Piping Sump/ Trench Sensor(s). Model• 794380 -208
F Fill Sump Sensor(s). Model: 794380 -208 r Fill Sump Sensor(s). Model:
F Mechanical Line Leak Detector. Model: r Mechanical Line Leak Detector. Model:
F Electronic Line Leak Detector. Model: r Electronic Line Leak Detector. Model:
P_' Tank Overfill / High -Level Sensor. Mode]• 790091-001 F Tank Overfill / High -Level Sensor. Model: 790091 -001
F Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank ID: Tank ID:
F In -Tank Gauging Probe. Model: r In-TankGauging Probe. Model:
F Annular Space or Vault Sensor. Model: r Annular Space or Vault Sensor. Model:
F Piping Sump/ Trench Sensor(s). Model: r Piping Sump/ Trench Sensor(s). Model:
F Fill Sump Sensor(s). Mode] r Fill Sump Sensor(s). Model:
r Mechanical Line Leak Detector. Model: r Mechanical Line Leak Detector. Model:
F Electronic Line Leak Detector. Model: r Electronic Line Leak Detector. Model:
F Tank Overfill/ High -Level Sensor. Model' r Tank Overfill/ High -Level Sensor. Model:
r Other (specify equipment type and model in Section E on Page 2). r Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: Dispenser ID:
F Dispenser Containment Sensor(s). Model: r Dispenser Containment Sensor(s). Model:
r Shear Valve(s). r Shear Valve(s).
F Dispenser Containment Float(s) and Chain(s). r Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
r Dispenser Containment Sensor(s). Model: r Dispenser Containment Sensor(s). Model:
F Shear Valve(s). r Shear Valve(s).
F Dispenser Containment Float(s) and Chain(s). r Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information forevery tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is correetand
a Plot Plan showing the layout of monitoring equipment For any equipment capable of generating such reports, 1 have also attached a copy of
the report; (check all that apply) : r System set -up r Alarm history report
Technician Name (print): Adolfo Aguilar /
Signature: OL
Certification No.: A20066 License. No.: 588098
Testing Company Name: TAIT ENVIRONMENTAL SERVICES Phone No.: 714560 -8222
Testing Company Address: 2131 S0UTHDUPONTCRwkANAHSrmtcnm- -806 Date ofTesting/Sery icing: 1/27/2012
D. Results of Testing /Servicing
Software Version Installed: 120.00
Complete the following checklist:
Yes No* Is the audiblealarm operational?
Yes r No* Is the visual alarm operational?
Yes r No * Were all sensors visually inspected, functionally tested, and confinned operational?
Yes r.
NoM.__
Were all sensors installed at lowest point of secondary containment and positioned so that ofpY1her equipment
will not interfere with their
proper operation?
F Yes F No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem)
F N/A operational?
r No* F Yes For pressurized piping systems, does the turbine automatically shut down if the piping secondary
F containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: whichN/A sensors initiate positive shut -down? (Check all that apply)
F Sump /Trench Sensors; r Dispenser Containment Sensors. Did you confirm positive shut -down
clue to leaks and sensor failure /disconnection?
F Yes; r No.
F Yes No * F tank_____. or systems that utilize the monitoring system as the primary tank overfill waming device (i.e. no
echanical overll prevention valve is installed), is the overll waming alam visible and audible at themfifir
N/A tank fill point(s) and operating properly? If so, at what percent of tank capacity does the a lane trigger?
Yes* F No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or otherequipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
r Yes* R No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that
FTNo*
apply) r Product; r Water. If yes, describe causes in Section E, below.
Yes Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
F Yes F No* Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Other Sensors From Page 1:
L6: Piping Box Sensor 794380- 208 - Certified- (Replaced L6: Piping Box Sensor 794380 -208 Like For Like - Certified.)
LT Remote Pump Cabinet 794380 -208- Certified.
Fill Port With A Mechanical Overfill Prevention Drop -Tube Valve.
F. In -Tank Gauging / SIR Equipment:
F Check this box iftank gauging is used only for inventory control.
F Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): P_ Check this box if LLDs are not installed.
Complete the following checklist:
F Yes
No* Has all input wi ring been inspected for proper entry and tennination, including testing for ground faults'?
Ir Yes r No* Were all tank gauging probes visually inspected fordamageand residue buildup?
F Yes r No* Was accuracy of system product level readings tested?
Yes r No* Was accuracy of system water level readings tested?
Yes r No* Were all probes reinstalled properly?
r Yes r No* Were all items on the equipment manufactuer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): P_ Check this box if LLDs are not installed.
Complete the following checklist:
F Yes r No* For equipment start -up or annual equipment certification, was a leak simulated to veri fy LLD performance ?(Check
F N/A n// that apply) Simulated leak rate: r 3 gp.h.; r 0.1 g.p.h ; r 02 g.p.h.
Yes r No* Were all LLDs confirmed operational and accurate within regulatory requirements?
F_ Was the testing apparatus properly calibrated?
F For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
F A
o._..___
u
For electronic LLDs, does the turbine automatically shut off ifthe LLD detects a leak?
JeFo*
A
For electronic LLDs, does the turbine automaoticallyshutoffifanyportionofthemonitoringsystemisdisabledor
A disconnected?
o* For electronic LLDs, does the turbine automatically shut offifany portion of the monitoring system malfimctions or
A
fai Is a test?
Forelectronic LLDs, have all accessiblewiring connections been visually inspected? es o*
F N/A
F Yes r No* Were all items on the equipment manufacturer's maintenance checklist completed?
IntheSection H, below, describehow and when these deficiencies were or will becorrected.
H. Comments:
Suction System.
S ite Address : 1520 20TI-I S "r, BAKERSFIELD, 93301
aW
UST Monitoring Site Plan
Monitoring Plan Site Map
BusirdassNlarne__. Pacific Be4lTelcphoneCo. dhaA.TUT Cal. ?04,0 10
USinyc5 Addr_5_:
ATG Probe 846390 -105
Z.!"M 3 ,- Rdrq Slam H
794380 -208 ..,......,.
11`,
rt'' 794380 -208
B!G laT C2sr:
794390.420
790091--------- ,<----------- - - - -,f
V_ F 363 m
xr
S p Cayyank
W/ ATG 847390 -301
L4; Gay Tank annular
Sensor 794380 -208
4 "Fccr
E, nr Accm
C, riv; irg rN0T t SwIe
Tae:L ca Fitmm
kse%a'(E6) 794380.2013
4T] :&%k
N: F,rmr (C7) 794380 -208
AT &T building
E3: Day Tank Rupture Basin
Sensor 794380 -208
Date map was drawn: 1/27/2012
Instructions
N
W+ E
S
Ifyou already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System
Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if
installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spi II containers, or other
secondary containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the
space provided, note the date this Site Plan was prepared.
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors petforming annual testing of USTspill containment structures. The completedform and
printouts from tests (ifapplicable), should be provided to the facility owner /operatorfor submittal to the local regulatory agency.
FACILITY INFORMATION Facility ID: CAKO10
Facility Name: AT &T Corporation Date of Testing: 1 /27/2012
Facility Address: 1520 20TH ST, BAKERSFIELD, CA 93301
Facility Contact: Grant Armstrong Phone: (661) 327 -6903
Date Local Agency Was Notified of Testing: 1/12/2012
Name of Local Agency Inspector (ifpresent during testing): Ernie Medina
TESTING CONTRACTOR INFORMATION
Company Name: TAIT Environmental Services, Inc.
Technician Conducting Test: Adolfo Aguilar
Credential 1 : r CSLB Contractor I-' ICC Service Tech. r SWRCB Tank Tester r Other (Specify)
License number(s): A B ASB C -10 HAZ License Number 588098 : ICC Technician 5238610
SPILL BUCKET TESTING INFORMATION
Test Method Used: r1-1 Hydrostatic r Vacuum r Other
Test Equipment Used: Visual, Measured & Marked Equipment Resolution: 1/16"
Identify Spill Bucket (By Tank
Number, Stored Product, etc. 1 #CAK010U001 2 3
Bucket Installation Type: r Direct Bury
F7' Contained in Sump
r On top of AST
F Direct Bury
F- Contained in Siunp
r On top of AST
r Direct Bury
r Contained in Sump
r On top of AST
r Direct Bury
Contained in Sump
On top of AST
Bucket Diameter: 11.00"
Bucket Depth: 13.00"
Wait time between applying
vacuum /water and start of test:
15 Minutes
Test Start Time (TI): 9:15 AM
Initial Reading (RI): 13.00"
Test End Ti me (TI,): 10:15 AM
Final Reading (RF): 13.00"
Test Duration (TF -TI): 1 Hour
Change in Reading (RI: -RI): 0
Pass /Fail Threshold or
Criteria:
0
Test Result: F Pass F Fail I- Pass F Fail F- Pass F- Fail F- Pass f- Fail
Comments - (include information on repairs made prior to testing, and recommendedfollow -up forfailed tests)
Spill Bucket Is 4.8 Gallon Capacity (Does Not Hold 5 Gallons). Lake Test Passed The Hour Test. Took Non- I-laz. Test Waer To TES(Contraaor) Shop Properly Labled
Secured
CERTIFICATION OF TECH NICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance vith legal requirements.
Technician's Signature: "V - Date: 1/27/2012
150301
JAN 31, 2012 9:24 AM
1:BKFDCA01 CAKO10 T -S
M
M
I50302
JAN 31, 2012 9:24 AM
2:1520 20TH ST
M
M
I5D3D3
JAN 31, 2012 9:24 AM
3:BAKERSFIELD,CA 93301
M
M
I50304
JAN 31, 2012 9:24 AM
4:661 -869 -1846
M
M
I51700
JAN 31, 2012 9:24 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMAT
MON DD YYYY HH :MM:SS xM
M
M
I50F00
JAN 31, 2012 9:24 AM
MON DD YYYY HH:MM:SS xM
M
M
110200
JAN 31, 2012 9:24 AM
BKFDCA01 CAKO10 T -S
1520 20TH ST
BAKERSFIELD,CA 93301
661 - 869 -1846
SYSTEM CONFIGURATION
SLOT BOARD TYPE
1 4 PROBE / G.T.
2 INTERSTITIAL BD
3 UNUSED
4 UNUSED
5 UNUSED
6 UNUSED
7 UNUSED
8 UNUSED
9 RELAY BOARD
10 COMBO I/O BOARD
11 UNUSED
12 UNUSED
13 UNUSED
14 UNUSED
15 UNUSED
16 UNUSED
COMM 1 FAXMODEM BC)ARD
COMM 2 UNUSED
COMM 3 UNUSED
COMM 4 UNUSED
COMM 5 UNUSED
COMM 6 UNUSED
M
M
I60100
JAN 31, 2012 9:25 AM
TANK CONFIGURATION
POWER ON RESET CURRENT
162295 162373
201439 201582
15000000 15000000
15000000 15000000
15000000 15000000
15000000 15000000
15000000 15000000
15000000 15000000
14933 14956
9929 9945
15000000 15000000
15000000 15000000
15000000 15000000
15000000 15000000
15000000 15000000
15000000 15000000
40571 40582
15000000 15000000
15HHH 150DDDDD
15000000 15000000
15000000 15000000
15000000 15000000
DEVICE LABEL CONFIGURED
1 DIESEL TK #CAKO10U001 ON
2 DIESEL TK #CAKO10A002 ON
3 OFF
4 OFF
A
A
I60200
JAN 31, 2012 9:25 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK #CAKO10U001
2 DIESEL TK #CAKO10A002
3
4
A
A
I60300
JAN 31, 2012 9:25 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK #CAKO10U001 1
2 DIESEL TK #CAKO10A002 1
3
TK #CAKO10A002
3
4 4
A
4
A
0.00
A
160400
JAN 31, 2012 9:25 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #CAKO10U001 8002
2 DIESEL TK #CAKO10A002 250
3 0
4 0
A
A
I60700
JAN 31, 2012 9:25 AM
191uMarau12vr21 :i
TANK PRODUCT LABEL INCHES
1 DIESEL TK #CAKO10U001 82.00
2 DIESEL TK #CAKO10A002 30.00
3
NONE
0.00
4
A
0.00
A
I62100
A
2012 9:25 AM
TANK LOW PRODUCT LIMIT
I60900
TANK PRODUCT LABEL GALLONS
JAN 31, 2012 9:25 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1
1 DIESEL TK #CAKO10U001 0.000450
2 DIESEL TK #CAKO10A002 0.000450
3
NONE
0.000000
4
A
0.000000
A
I62100
A
2012 9:25 AM
TANK LOW PRODUCT LIMIT
I61200
TANK PRODUCT LABEL GALLONS
JAN 31, 2012 9:25 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL MANIFOLDED TANKS
1 DIESEL TK #CAKO10U001 NONE
2 DIESEL TK #CAKO10A002 NONE
3 NONE
4 NONE
A
A
I62100
JAN 31, 2012 9:25 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #CAKO10U001 4000
2 DIESEL TK #CAKO10A002 105
3 0
4 0
A
A
I62200
JAN 31, 2012 9:25 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #CAKO1OU001 7601
2 DIESEL TK #CAKO10A002 237
3 0
4 0
A
A
162300
JAN 31, 2012 9:25 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #CAKO10U001 7201
2 DIESEL TK #CAKO10A002 225
3 0
4 0
A
A
I62400
JAN 31, 2012 9:25 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK #CAKO1OU001 2.0
2 DIESEL TK #CAKO10A002 2.0
A
A
I62800
JAN 31, 2012 9:25 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #CAKO10U001 8002
2 DIESEL TK#CAKO10A002 250
3 0
4 0
A
A
162900
JAN 31, 2012 9:25 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #CAKO10U001 4000
2 DIESEL TK #CAKO10A002 125
3 0
4 0
A
A
I70300
JAN 31, 2012 9:25 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 FILL SUMP TRI -STATE (SINGLE FLOAT)
2 PIPIN SUMP TRI -STATE (SINGLE FLOAT)
3 DAYTANK RUPTURE BASN TRI -STATE (SINGLE FLOAT)
4 DAY TANK ANNULAR TRI -STATE (SINGLE FLOAT)
5 ANNULAR TRI -STATE (SINGLE FLOAT)
6 PIPING BOX TRI -STATE (SINGLE FLOAT)
7 REMOTE PUMP CABINET TRI- STA,SOB
AJv3*4H #LOAT)
8 TRI -STATE (SINGLE FLOAT)
A
I90200
JAN 31, 2012 9:25 AM
SOFTWARE REVISION LEVEL
VERSION 120.00
SOFTWARE# 346120 -100 -A
CREATED - 00.07.28.15.33
S- MODULE# 330160 -002 -A
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
CSLD
A
A
I11100
JAN 31, 2012 9:25 AM
BKFDCA01 CAKO10 T -S
1520 20TH ST
BAKERSFIELD,CA 93301
661 - 869 -1846
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK DIESEL TK #CAKO10A002 HIGH WATER ALARM CLEAR 1 -27 -12 11:22AM
T 2 TANK DIESEL TK #CAKO1OA002 PROBE OUT CLEAR 1 -27 -12 11:22AM
T 2 TANK DIESEL TK #CAKO1OA002 PROBE OUT ALARM 1 -27 -12 11:21AM
T 2 TANK DIESEL TK #CAKO10A002 MAX PRODUCT ALARM CLEAR 1 -27 -12 11:20AM
T 2 TANK DIESEL TK #CAKO10A002 HIGH WATER ALARM ALARM 1 -27 -12 11:16AM
T 2 TANK DIESEL TK #CAKO10A002 MAX PRODUCT ALARM ALARM 1 -27 -12 11:13AM
T 2 TANK DIESEL TK #CAKO10A002 PROBE OUT CLEAR 1 -27 -12 11:10AM
T 2 TANK DIESEL TK #CAKO10A002 PROBE OUT ALARM 1 -27 -12 11:07AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM CLEAR 1 -27 -12 11:O1AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM ALARM 1 -27 -12 11:O1AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM CLEAR 1 -27 -12 10:54AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM ALARM 1 -27 -12 10:53AM
L 6 PIPE PIPING BOX FUEL ALARM CLEAR 1 -27 -12 10:34AM
L 6 PIPE PIPING BOX FUEL ALARM ALARM 1 -27 -12 10:31AM
L 6 PIPE PIPING BOX SENSOR OUT ALARM CLEAR 1 -27 -12 10:30AM
L 6 PIPE PIPING BOX SENSOR OUT ALARM ALARM 1 -27 -12 10:27AM
T 1 TANK DIESEL TK #CAKO10U001 HIGH WATER ALARM CLEAR 1 -27 -12 10:03AM
T 1 TANK DIESEL TK #CAKO10U001 MAX PRODUCT ALARM CLEAR 1 -27 -12 10:03AM
T 1 TANK DIESEL TK #CAKO10U001 PROBE OUT CLEAR 1 -27 -12 10:02AM
T 1 TANK DIESEL TK #CAKO1OU001 PROBE OUT ALARM 1 -27 -12 10:02AM
T 1 TANK DIESEL TK #CAKO10U001 MAX PRODUCT ALARM ALARM 1 -27 -12 9:58AM
T 1 TANK DIESEL TK #CAKO10O001 OVERFILL ALARM CLEAR 1 -27 -12 9:57AM
T 1 TANK DIESEL TK #CAKO10U001 OVERFILL ALARM ALARM 1 -27 -12 9:55AM
T 1 TANK DIESEL TK #CAKO10U001 LOW PRODUCT ALARM CLEAR 1 -27 -12 9:52AM
T 1 TANK DIESEL TK #CAKO10U001 HIGH WATER ALARM ALARM 1 -27 -12 9:51AM
T 1 TANK DIESEL TK #CAKO10U001 LOW PRODUCT ALARM ALARM 1 -27 -12 9:46AM
T 1 TANK DIESEL TK #CAKO10O001 PROBE OUT CLEAR 1 -27 -12 9:46AM
T 1 TANK DIESEL TK #CAKOl0U001 PROBE OUT ALARM 1 -27 -12 9:44AM
L 7 OTHER REMOTE PUMP CABINET FUEL ALARM CLEAR 1 -27 -12 9:31AM
L 7 OTHER REMOTE PUMP CABINET FUEL ALARM ALARM 1 -27 -12 9:25AM
L 2 PIPE PIPIN SUMP FUEL ALARM CLEAR 1 -27 -12 9:21AM
L 2 PIPE PIPIN SUMP FUEL ALARM ALARM 1 -27 -12 9:13AM
L 1 STP SUMP FILL SUMP FUEL ALARM CLEAR 1 -27 -12 9:05AM
L 1 STP SUMP FILL SUMP FUEL ALARM ALARM 1 -27 -12 9:05AM
L 5 ANNULAR ANNULAR FUEL ALARM CLEAR 1 -27 -12 9:O1AM
L 5 ANNULAR ANNULAR FUEL ALARM ALARM 1 -27 -12 9:OOAM
T 1 TANK DIESEL TK #CAKO10U001 LEAK ALARM CLEAR 10 -11 -11 6:15AM
T 1 TANK DIESEL TK #CAKO10U001 LEAK ALARM ALARM 10 -11 -11 6:08AM
T 1 TANK DIESEL TK4CAKO10U001 OVERFILL ALARM CLEAR 9 -01 -11 11:33AM
T 1 TANK DIESEL TK #CAKO10U001 OVERFILL ALARM ALARM 9 -01 -11 11:30AM
L 7 OTHER REMOTE PUMP CABINET FUEL ALARM CLEAR 2 -10 -11 1:04PM
L 7 OTHER REMOTE PUMP CABINET FUEL ALARM ALARM 2 -10 -11 1:OOPM
L 6 PIPE PIPING BOX FUEL ALARM CLEAR 2 -10 -11 10:57AM
L 6 PIPE PIPING BOX FUEL ALARM ALARM 2 -10 -11 10:52AM
T 2 TANK DIESEL TK #CAKO10A002 HIGH WATER ALARM CLEAR 2 -10 -11 10:28AM
T 2 TANK DIESEL TK #CAKO10A002 PROBE OUT CLEAR 2 -10 -11 10:27AM
T 2 TANK DIESEL TK #CAKO10A002 PROBE OUT ALARM 2 -10 -11 10:27AM
T 2 TANK DIESEL TK #CAKO10A002 HIGH WATER ALARM ALARM 2 -10 -11 10:26AM
T 2 TANK DIESEL TK #CAKO10A002 OVERFILL ALARM CLEAR 2 -10 -11 10:23AM
T 2 TANK DIESEL TK #CAKO10A002 OVERFILL ALARM ALARM 2 -10 -11 10:21AM
A
A
111200
JAN 31, 2012 9:26 AM
BKFDCA01 CAKO10 T -S
1520 20TH ST
BAKERSFIELD,CA 93301
661 -869 1846
NON- PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK DIESEL TK #CAKO10A002 SETUP DATA WARNING CLEAR 1 -27 -12 11:50AM
T 2 TANK DIESEL TK #CAKO10A002 SETUP DATA WARNING ALARM 1 -27 -12 11:49AM
T 2 TANK DIESEL TK #CAKO10A002 HIGH WATER WARNING CLEAR 1 -27 -12 11:22AM
T 2 TANK DIESEL TK #CAKO10A002 HIGH PRODUCT ALARM CLEAR 1 -27 -12 11:22AM
T 2 TANK DIESEL TK #CAKO10A002 HIGH WATER WARNING ALARM 1 -27 -12 11:16AM
T 2 TANK DIESEL TK #CAKO10A002 HIGH PRODUCT ALARM ALARM 1 -27 -12 11:11AM
T 2 TANK DIESEL TK #CAKO10A002 DELIVERY NEEDED CLEAR 1 -27 -12 11:10AM
T 2 TANK DIESEL TK #CAKO10A002 INVALID FUEL LEVEL CLEAR 1 -27 -12 11:10AM
DIESEL TK #CAKO10A002 INVALID FUEL LEVEL ALARM 1 -27 -12 11:10AM
DIESEL TK #CAKO10A002 DELIVERY NEEDED ALARM 1 -27 -12 11:07AM
DIESEL TK #CAKO10U001 HIGH WATER WARNING CLEAR 1 -27 -12 10:03AM
DIESEL TK #CAKO10U001 HIGH PRODUCT ALARM CLEAR 1 -27 -12 10:03AM
DIESEL TK #CAKO10U001 HIGH PRODUCT ALARM ALARM 1 -27 -12 9:55AM
DIESEL TK #CAKO10U001 DELIVERY NEEDED CLEAR 1 -27 -12 9:52AM
DIESEL TK #CAKO10U001 HIGH WATER WARNING ALARM 1 -27 -12 9:51AM
DIESEL TK #CAKO10U001 DELIVERY NEEDED ALARM 1 -27 -12 9:46AM
PRINTER ERROR CLEAR 9 -14 -11 9:06AM
LOW PRODUCT ALARM
PAPER OUT CLEAR 9 -14 -11 9:06AM
PAPER OUT ALARM 9 -14 -11 9:05AM
PRINTER ERROR ALARM 9 -14 -11 9:05AM
SUDDEN LOSS ALARM
PAPER OUT CLEAR 8 -31 -11 8:31AM
PAPER OUT ALARM 8 -21 -11 2:16PM
PRINTER ERROR CLEAR 7 -27 -11 9:50AM
HIGH PRODUCT ALARM
PAPER OUT CLEAR 7 -27 -11 9:50AM
PROBE OUT
PRINTER ERROR ALARM 7 -27 -11 9:49AM
PAPER OUT ALARM 7 -23 -11 1:46PM
PRINTER ERROR CLEAR 6 -22 -11 9:04AM
HIGH WATER WARNING
PRINTER ERROR ALARM 6 -22 -11 9:04AM
PAPER OUT CLEAR 6 -22 -11 9:04AM
PAPER OUT ALARM 6 -22 -11 8:56AM
DELIVERY NEEDED
PRINTER ERROR CLEAR 6 -22 -11 8:51AM
PAPER OUT CLEAR 6 -22 -11 8:51AM
PAPER OUT ALARM 6 -22 -11 8:51AM
PAPER OUT CLEAR 6 -22 -11 8:51AM
PRINTER ERROR ALARM 6 -22 -11 8:50AM
PAPER OUT ALARM 6 -22 -11 8:50AM
PRINTER ERROR CLEAR 5 -31 -11 9:16AM
PAPER OUT CLEAR 5 -31 -11 9:16AM
PAPER OUT ALARM 5 -31 -11 9:16AM
PAPER OUT CLEAR 5 -31 -11 9:15AM
PRINTER ERROR ALARM 5 -31 -11 9:15AM
PAPER OUT ALARM 5 -31 -11 9:15AM
DIESEL TK #CAKO1OA002 HIGH WATER WARNING CLEAR 2 -10 -11 10:28AM
DIESEL TK #CAKO1OA002 HIGH WATER WARNING ALARM 2 -10 -11 10:26AM
DIESEL TK #CAKO10A002 HIGH PRODUCT ALARM CLEAR 2 -10 -11 10:21AM
DIESEL TK #CAKO10A002 HIGH PRODUCT ALARM ALARM 2 -10 -11 10:21AM
DIESEL TK #CAKO10A002 DELIVERY NEEDED CLEAR 2 -10 -11 10:20AM
DIESEL TK #CAKO10A002 INVALID FUEL LEVEL CLEAR 2 -10 -11 10:20AM
DIESEL TK #CAKO10A002 INVALID FUEL LEVEL ALARM 2 -10 -11 10:18AM
DIESEL TK #CAKO1OA002 DELIVERY NEEDED ALARM 2 -10 -11 10:18AM
A
A
I20600
JAN 31, 2012 9:27 AM
BKFDCA01 CAKO10 T -S
1520 20TH ST
BAKERSFIELD,CA 93301
661 - 869 -1846
TANK ALARM HISTORY
TANK 1 DIESEL TK #CAKO10U001
LEAK ALARM OCT 11, 2011 6:08 AM
OCT 14, 2010 2:44 PM
OCT 13, 2010 11:06 AM
HIGH WATER ALARM JAN 27, 2012 9:51 AM
FEB 10, 2011 9:52 AM
FEB 19, 2010 10:16 AM
OVERFILL ALARM JAN 27, 2012 9:55 AM
SEP 1, 2011 11:30 AM
FEB 10, 2011 9:47 AM
LOW PRODUCT ALARM JAN 27, 2012 9:46 AM
FEB 10, 2011 9:43 AM
FEB 19, 2010 10:05 AM
SUDDEN LOSS ALARM APR 4, 2010 3:43 PM
FEB 19, 2010 10:08 AM
FEB 19, 2010 10:05 AM
HIGH PRODUCT ALARM JAN 27, 2012 9:55 AM
PROBE OUT JAN 27, 2012 10:02 AM
JAN 27, 2012 9:44 AM
FEB 10, 2011 9:56 AM
HIGH WATER WARNING JAN 27, 2012 9:51 AM
FEB 10, 2011 9:52 AM
FEB 19, 2010 10:16 AM
DELIVERY NEEDED JAN 27, 2012 9:46 AM
FEB 10, 2011 9:43 AM
FEB 19, 2010 10:05 AM
MAX PRODUCT ALARM JAN 27, 2012 9:58 AM
CSLD INCR RATE WARN DEC 10, 2008 9:38 AM
SEP 18, 2008 10:06 AM
SEP 18, 2008 6:58 AM
LOW TEMP WARNING APR 4, 2010 3:48 PM
TANK 2 DIESEL TK #CAKO10A002
SETUP DATA WARNING JAN 27, 2012 11:49 AM
HIGH WATER ALARM JAN 27, 2012 11:16 AM
FEB 10, 2011 10:26 AM
OVERFILL ALARM FEB 10, 2011 10:21 AM
APR 11, 2008 1:50 PM
LOW PRODUCT ALARM FEB 10, 2011 10:18 AM
FEB 19, 2010 9:55 AM
APR 6, 2009 11:07 AM
SUDDEN LOSS ALARM OCT 12, 2010 8:39 PM
FEB 19, 2010 9:55 AM
APR 28, 2009 11:13 AM
HIGH PRODUCT ALARM JAN 27, 2012 11:11 AM
FEB 10, 2011 10:21 AM
FEB 19, 2010 9:58 AM
INVALID FUEL LEVEL JAN 27, 2012 11:10 AM
FEB 10, 2011 10:18 AM
FEB 19, 2010 10:01 AM
PROBE OUT JAN 27, 2012 11:21 AM
JAN 27, 2012 11:07 AM
FEB 10, 2011 10:27 AM
HIGH WATER WARNING JAN 27, 2012 11:16 AM
FEB 10, 2011 10:26 AM
DELIVERY NEEDED JAN 27, 2012 11:07 AM
FEB 10, 2011 10:18 AM
FEB 19, 2010 9:57 AM
MAX PRODUCT ALARM JAN 27, 2012 11:13 AM
FEB 19, 2010 9:58 AM
FEB 19, 2010 9:57 AM
A
A
I30200
JAN 31, 2012 9:27 AM
BKFDCA01 CAKO10 T -S
1520 20TH ST
BAKERSFIELD,CA 93301
661 -869 -1846
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 FILL SUMP
JAN 27, 2012 9:05 AM FUEL ALARM
FEB 10, 2011 9:30 AM FUEL ALARM
FEB 19, 2010 9:18 AM FUEL ALARM
2 PIPIN SUMP
JAN 27, 2012 9:13 AM FUEL ALARM
FEB 10, 2011 9:35 AM FUEL ALARM
FEB 19, 2010 9:22 AM FUEL ALARM
3 DAYTANK RUPTURE BASN
JAN 27, 2012 10:53 AM FUEL ALARM
FEB 10, 2011 10:04 AM FUEL ALARM
FEB 19, 2010 9:44 AM FUEL ALARM
4 DAY TANK ANNULAR
JAN 27, 2012 11:01 AM FUEL ALARM
FEB 10, 2011 10:11 AM FUEL ALARM
FEB 19, 2010 9:50 AM FUEL ALARM
5 ANNULAR
JAN 27, 2012 9:00 AM FUEL ALARM
FEB 10, 2011 9:25 AM FUEL ALARM
FEB 19, 2010 9:14 AM FUEL ALARM
6 PIPING BOX
JAN 27, 2012 10:31 AM FUEL ALARM
JAN 27, 2012 10:27 AM SENSOR OUT ALARM
FEB 10, 2011 10:52 AM FUEL ALARM
7 REMOTE PUMP CABINET
JAN 27, 2012 9:25 AM FUEL ALARM
FEB 10, 2011 1:00 PM FUEL ALARM
MAR 2, 2010 10:42 AM FUEL ALARM