HomeMy WebLinkAbout1700 MT. VERNON AVENUEMONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6 7, Health andSafety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator.
The owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: KERN MEDICAL CENTER
Site Address: 1700 MT VERNON AVENUE -k
Facility Contact Person:
Make /Model of Monitoring System: TLS -350
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected /serviced:
City: BAKERSFIELD
Bldg. No.:
Zip:
Contact Phone No.: ( )
Date of Testing/Servicing: 1/9/2012
Tank ID: TK -1 1500 DIESEL AGT Tank ID: TK -2 10K DIESEL
In -Tank Gauging Probe, Model: N/A In -Tank Gauging Probe. Model: BMAG -1
Annular Space or Vault Sensor. Model: 208 Annular Space or Vault Sensor. Model: 208
Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical LineLeak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank ID: TK-3 2K DIESEL AGT Tank 1D: TK-41 K DIESEL AGT
In -Tank Gauging Probe, Model: MAG -1 In -Tank Gauging Probe. Model.
Annular Space or Vault Sensor. Model: 208 Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model:
Other (specify equipmenttypeand model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2),
Dispenser 111): Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Ifthe facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification -1 certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy ofthe report; (check all that apply): ® System set -up ® Alarm ory report
Technician Name (print): RICH PHILLIPS Signature:
Certification No.: A2908411036169 -UT License. No.: _ 611 D40 809850
Testing Company Name: RICH ENVIRONMENTAL
Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308
UN -036 — I/4
Page 1 of 5
www.unidoes.org
Phone No.: (661) 392 -8687
Date ofTesting/Servicing: 11912012
Rev. 01 /17/08
Ni
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 324.03
6n fn11n rinn n1.nn41icH
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? ifyes: which sensors initiate
positive shut -down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks Wo sensor failure /disconnection? Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? 90%
Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
El Comments: SUMP SYSTEM IS SUCTION 208 SENSOR
I
I
I
M
Page 2 of 5
UN -036 — 2/4 www.uaidomorg Rev. 01/17 /08
Monitoring System Certification
Lk53iz A`
4
F. In -Tank Gauging / SIR Equipment: Check this box iftank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLDs are not installed.
Cmmnlete the fallnwinu checklist-
El Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; [10.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Ej Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion ofthe monitoring system malfunctions
N/A or fails a test?
p Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
p Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
IL Comments: SUCTION SYSTEM -NO LEAK DETECTORS
VN -036 — 3/4
Page 3 of 5
www.unidm.org Rev. OIA7 /08
u
Monitoring System Certification Form: Addendum for Vacuum/Pressure Interstitial Sensors
I. Results of Vacuum[Pressure Monitoring Equipment Testing
This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of
this form must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner /operator. The owner /operator must submit a copy of the Monitoring System Certification Form to the
local agency regulating UST systems within 30 days of test date.
Manufacturer: NONE Model: System Type: Pressure; ® Vacuum
Sensor 1D
A kWSS
n: • ' ,_ s.., -,
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: [] Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
How was interstitial communication verified?
Leak Introduced at Far End of Interstitial Space;' Gauge; Visual Inspection; Other (Describe in Sec. J, below)
Was vacuum/pressure restored to operating levels in all interstitial spaces? Yes No (Ifno, describe in Sec. J, below)
J. Comments: NONE OF THESE SENSORS ARE PRESENT AT THIS SITE.
Page 4 of 5
If the sensor successful) detects a simulated vacuum/pressure le i e
sensor, vacuum/pressurehas been demonstrated to be communicating, throughout the intetrstice.
space at the furthest point from th
UN -036A -1/1 www.unidoes.org Rev. 01126/06
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intendedfor use by contractors performing annual testing ofUSTspill containment structures. The completedform and
printoutsfrom tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: KERN MEDICAL CENTER I Date of Testing: 1/9/12
Facility Address: 1700 MT VERNON AVENUE, BAKERSFIELD
Facility Contact: Phone:
Date Local Agency Was Notified of Testing: 10/31/11
Name ofLocal Agency Inspector (fpresent during testing): ERNIE
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials: CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s): 1035169 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used. VISUAL Equipment Resolution: 0
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
l DIESEL 10K 2 3 4
Bucket Installation TType: Direct Bury
X Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
11 Direct Bury
Contained in Sum
Bucket Diameter: 12"
Bucket Depth: 14"
Wait time between applying
vacuum/water and start oftest: 30 MIN
Test Start Time (Ti): 9:45
Initial Reading (Rj): 14"
Test End Time (TF); 10:45
Final Reading (RF): 14"
Test Duration (TF — Tj): 1 -HOUR
Change in Reading (RF - Rj): 0
Pass/Fail Threshold or
Criteria: 0.00
Test Result: X Pass Fail Pass Fail Pass Fail Pass Fail
COMMent3 — (include information on repairs made prior to testing, andrecommendedfollow -upfor failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the Informado, ntained In this report is true, accurate, and infull compliance with legal requirements.
Technician's Signature: Date: 1/9/12
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
ys3t1.'
RICH ENVIRONMENTAL
5643 BROOKS CT. BAKERSFIELD, CA. 93308
OFFICE (661)392 -8687 FAX (661)392 -0621
PRODUCT LINE LEAD DETECTOR TEST
WORK SHEET
FACILITY NAME: KERN MEDICAL CENTER
FACILITY ADDRESS: 1700 MT VERNON AVENUE, BAKERSFIELD
PRODUCT LINE TYPE: SUCTION SYSTEM
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
l
L/D TYPE:_
SERIAL #_
YES
NO
PASS
FAIT.
L/D TYPE: _ YES PASS
SERIAL # _ NO FAIL
L/D TYPE: _ YES PASS
SERIAL # _ NO FAIL
L/D TYPE:_ YES PASS
SERIAL # _ NO FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICH PHIL
SIGNATURE: DATE: 1/9/12
f"
SOFTWARE REVISION LEVEL
VERSION 324.03
SOFTWARE# 346324 -100 -D
CREATED - 05.06.06.15.41
NO SOFTWARE MODULE
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
f,
SYSTEM SETUP
JAN 9. 2012 9:01 AM
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
KERN MEDICAL CENTER
1.830 FLOWER ST.
BAKERSFIELD.CA 93305
661- 326 -2482
SHIFT TIME I DISABLED
SHIFT TIME 2 DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE- ENABLE METHOD
ALARM ACKNOWLEDGE
LINE PER TST NEEDED WRN
DISABLED
L 114E ANN TST NEEDED WRN
DISABLED
PRINT TC VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEG F ?: 60.0
STICK HEIGHT OFFSET
DISABLED
DAYLIGHT SAVING TIME
ENABLED
START DATE
APR WEEK 1 SUN
START TIME
2:00 AM
END DATE
OCT WEEK 6 SUN
END TIME
2:00 AM
0
SYSTEM SECURITY
CODE : 000000
CUSTOM ALARM LABELS
DISABLED
COI °1MUNICATIONS SETUP
PORT SETTINGS:
NONE FOUND
RS -232 END OF MESSAGE
DISABLED
IN-TANK SETUP-
T 1:DIESEL
PRODUCT, CODE 1
THERMAL COEFF :.000450
TANK DIAMETER 36.00
TANK PROFILE 1 PT
FULL VOL 1502
FLOAT SIZE: 4.0'IN.
WATER WARNING 2.5
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 1502
OVERFILL LIMIT 909
1351
HIGH PRODUCT 95%
1426
DELIVERY LIMIT 50%
751
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 1.70
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
TG: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 0%
0
LEAK MIN AN14UAL 0%
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY I MIN
PUMP THRESHOLD 10.00`%.
N
exuoUCT CODE 2
THERMAL COEFF :.000450
TANK DIAMETER 96.00
TANK PROFILE 4 PTS
FULL VOL 9726
72.0 INCH VOL 8246,
48.0 INCH VOL 5149
24.0 INCH VOL 1935
FLOAT SIZE: 4.0 IN,
T 3:2000 DIESEL
PRODUCT CODE 3
THERMAL COEFF 000450
TANK DIAMETER 60.00
TANK PROFILE 4 PTO
FULL VOL 2000
45.0 INCH VOL 1500
30.0 INCH VOL 1000
15.0 1N0- WIT. 500
WATER WARNING 2.5 FLOAT S1"F: 4.0 IN.
HIGH WATER,, LIMIT: 3.0 WATER WARNING 2.0
MAX QR LABEL VOL: 9728 HIGH WATER LIMIT: 3.0
OVERFILL LIMIT 90%
8755 MAX OR LABEL VOL: 2000
HIGH PRODUCT 95% OVERFILL LIMIT : 90%
9241 1800
DELIVERY LIMIT 25% HIGH PRODUCT 950%
2432 1900
DELIVERY LIMIT 25%
LOW PRODUCT 1000 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99 LOW PRODUCT 500
TANK TILT 0.00 LEAK ALARM LIMIT: 99
PROBE OFFSET 0.00 SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
T#' NONE
LINE MANIFOLDED '. NYS SIPHON MANIFOLDED TANKS
TO*. NONE TO: NONE
LINE MANIFOLDED TANKS
T#: NONE
LEAK MIN PERIODIC: 0%
0.' LEAK MIN PERIODIC: 0%
LEAK MIN ANNUAL 0% 0
0 LEAK MIN ANNUAL : 0%
0
PERIODIC TEST TYPE
STANDARD PERIODIC TEST TYPE
ANNUAL TEST FAIL STANDARD
ALARM DISABLED ANNUAL TEST FAIL
PERIODIC TEST FAIL ALARM DISABLED
ALARM DISABLED PERIODIC TEST FAIL
GROSS TEST FAIL. ALARM DISABLED
ALARM DISABLED GROSS TEST FAIL
ANN TEST AVERAGING: OFF ALARM DISABLED
PER TEST AVERAGING: OFF ANN TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF PER TEST AVERAGING: OFF
TNK TOT SIPHON BREAK:OFF TANK TEST NOTIFY: OFF
DELIVERY DELAY I MIN TNK TOT SIPHON BREAK:OFF
PUII1V THRESHOLD 10.004 DELIVERY DELAY I MIN
PUMP THRESHOLD 10.00%
q6-vl-- t
Z,
LEAK TEST METHOD
TEST MONTHLY : ALL TANK
WEEK. 1 MON
START TIME : 2:00 AM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TOT EARLY STOP:DISABLED
LEAK TEST REPORT FORMAT
NORMAL
LIQUID SENSOR SETUP
L 1 :TANK 1 ANNULAR SPACE
NORMALLY CLOSED
CATEGORY : ANNULAR SPACE
L 2:FILL SUMP
TRI -STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 3:MID SUMP
TRI -STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 4:END SUMP
TRI -STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 5:2000 ANNULAR SPACE
NORMALLY CLOSED
CATEGORY : ANNULAR SPACE
L 7 :DT 100
TRI -STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
REPORTALARMHISTORY
OUTPUT RELAY SETUP
ALARM HISTORY REPORT SENSOR ALARM
L 4:END SUMPMPSENSORALARM -- OTHER SENSORSL1:TANK I ANNULAR SPACE FUEL ALARMR1:T3 2000 DIESEL ANNULAR SPACE JAN 9, 2012 9:42 AMTYPE: FUEL ALARM
STANDARD JAN S. 2012 9:07 AM FUEL ALARMNORMALLYOPENJAN9, 2012 9:39 AMFUELALARM
IN -TANK ALARMS
NOV 2. 2010 8:57 AM FUEL ALARM
ALL:OVERFILL ALARM FUEL ALARM
NOV 2. 2010 8:48 AM
ALL:LOW PRODUCT ALARM JUL 29..2010 10:58 AM
ALL:HIGH PRODUCT ALARM
LIQUID OENSOR ALMS
L 5:FUtL ALARM
R 2:10.000 HORN ALARM HISTOR`! REPORT
TYPE:
STANDARD SENSOR ALARM - - - --
NORMALLY OPEN ALARM HISTOR'. REPORT 5 :2000 ANNULAR SPACELSPACE
1N -TANK ALARMS
SENSOR ALARM - - - --
L 2:FILL SUMP FUEL ALARMFUE
9, 2012 9:08 AM
ALL:OVERFILL ALARM OTHER SENSORS JAN
ALL:LOW PRODUCT ALARM FUEL ALARM FUEL ALARMALL:HIGH PRODUCT ALARM JAN 9. 2012 9:47 AM NOV 2. 2010 9:02 AM
R 3:T1 FUEL ALARM Fes, ALARMTYPE: JAN 9, 2012 9:47 AM JUL 30, 2010 6:19 AM
STANDARD
NORMALLY OPEN FUEL ALARM
SEP 10, 2011 6:04 Pt -1
IN -TANK ALARMS
III I ALL:OVERFILL ALARM
ALL:LOW PRODUCT ALARM
ALL:HIGH PRODUCT ALARM
T 1 :MAX PRODUCT ALARM ALARM HISTORY REPORT
LIQUID SENSOR ALMS SENSOR ALARM - - - -- L 1:FUEL ALARM
ALARM HISTORY REPORT
r L 6:DT 325
OTHER SENSORSR4:DAY TANK 100
TYPE: ALARM - - - -- SENSOR OUT ALARM
STANDARD L 3:MIDES mp DEC 28. 2011 10 :27 AM
NORMALLY CLOSED OTHER SENSORS
FUEL ALARM SENSOR OUT ALARM
NO ALARM ASSIGNMENTS - JAN 9. 2012 9:45 AM DEC 1. 2011 12:44 PM
FUEL ALARM SENSOR OUT ALARM
NOV 2, 2010 8 :50 AM DEC 1, 2011 12:42 PM
FUEL ALARM
AUG 12. 2009 8:30 AM
HISTORY REPORT
ALARM
SENSOR ALARM _' - --
Lr? :
DT X100
OTHER SENSORS -
NOV ALARM 8:4? AM
2010
SENSOR OUT LARM31
JUL 30•
SENSOR OUT ALARM 30 AM
JUL .3 2010
MONITOR CERT. FAILURE REPORT
SITE NAME: /n iccL G[/ DATE:— S -J --
ADDRESS: 17o D M 7' A1-4:r TECHNICIAN: RICHIE PHILLIPS
CITY: .6A 1666 -Lj /'`'` / yA SIGNATURE:
REPAIRS:
NONE
PARTSINSTALLED:
NONE
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMENTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON- COMPLYANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.