HomeMy WebLinkAbout215 21ST STREET (8)Tan nol®
11000 N. MoPac Expressway, Suite 500
Austin, Texas 78759
Phone: (512) 451 -6334
Fax: (512) 459-1459
BAKERSFIELD FIRE DEPARTMENT
OFFICE OF ENVIRONMENTAL SERVICES
INSPECTOR CRAIG PERKINS
1501 TRUXTUN AVE.
BAKERSFIELD, CA 93301
Test Date: 5/31/2012
Order Number: 3402244
i
Date Printed and Mailed: 6/21/2012
i , Dear Regulator,
Enclosed are the results of recent testing performed at the followin g
PEPSI COLA #3040 ; 1
215 EAST 21ST STREET
BAKERSFIELD, CA 93305
Testing performed:
ATG
IMPACT. VALVE
LEAK DETECTOR
SPILL BUCKET TEST
Sincerely,
Y
a srrY'-
Dawn Kohlmeyer
Manager, Field Reporting
I
t:
i
4
i
it. • b:
rf '
T,
I
I
TAnknology
Work Order: 3402244
Site Name / ID: PEPSI COLA #304
Address: 215 EAST 21ST ST
City: BAKERSFIELD
LDT 5000 Field Test Apparatus
Line Leak Detector Test
Date: 5/31/2012
i
Page 1 of 1
r
State: CA Zip: 93305
I
Tank ID 1
Product Diesel
Product Line 1
Tested From 1
Existing /New Existing
Mechanical /Electronic Mechanical
Manufacturer /Model Red Jacket FX1D
Serial No. 308082873
Pump Operating Pressure (psi) 28.00
Calibrated Leak (mllmin) 189.0
Calibrated Leak (gph) 3.00
Holding PSI
NIA for Electronic Lo's 11.00
Resiliency (ml)
N/A for Electronic Lo's 50.00
Metering PSI
N /A for Electronic Lo's
Opening Time (sec)
N /A for Electronic LD's 2
est Results Pass
Technician Name: Edgar Sotomayor Certification #: 1950 •"
Technician Signature:
Environmental Compliance for Petroleum Systems
2010Tankndogy Inc., Austin, TX. All rights reserved, tankndogy.com Ir
i
Tanknology Impact Valve
Inspection
Impact Valve Operational
Inspection
Work Order: X402244 Date: 5/31/2012
Site Name /ID: PEPSI COLA #3040
Address: 215 EAST 21ST STREET
City: 13AKERSFIELD State:
y
i
Appendix VI
Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http.: / /www.swrcb.Ca.gov.)
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of
Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring
system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The
owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. {
A. General Information I
4 .
Facility Name: PEPSI COLA #3040 Bldg. No.: 3040'" {
Site Address: 215 EAST 21ST STREET City: BAKERSFIELD Zip: 93305
Facility Contact Person: CASEY BLAIR Contact Phone No.: 201 -6963
Make /Model of Monitoring System: Veeder Root Simplicity Date of Tiist14servicing: 5/31/2012
B. Inventory of Equipment Tested /Certified {
ChPrk tha nonronriatn hmrac to Indiratn cnnrlflr anidnmant Incnartadloa 1~1-
Tank ID: Tl: DIESEL FUEL - Diesel Tank ID:
R, In -Tank Gauging Probe. Model: Mag r In -Tank Gauging Probe. Model:
r` Annular Space or Vault Sensor. Model: 302 rl Annular Space or Vault Sensor. Model:
i f Piping Sump / Trench Sensor(s). Model: 352 r Piping Sump / Trench Sensor(s). Model: l'
r FIII Sump Sensor(s), Model: r Fill Sump Sensor(s). Model: I
Mechanical Line Leak Detector. Model: Red Jacket FX1DV r Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. _Model: r Electronic Line Leak Detector. Model: i
r Tank Overfill / High -Level Sensor: Model: Flapper r Tank Overfill / High -Level Sensor. Model:
Other (specify ui ment type and model in Section E on Page 2). ri Other (soecify equipment and model in Sectlon E on Pa e 2).
Tank ID: j Tank ID:
r In -Tank Gauging Probe. Model: r In -Tank Gauging Probe. Model: I
r Annular Space or Vault Sensor. Model: N Annular Space or Vault Sensor. Model: !
Piping Sump / Trench Sensor(s). Model: 17! Piping Sump / Trench Sensor(s). Model: { Y'
r FIII Sump Sensor(s), Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model r Mechanical Line Leak Detector. Model:
r Electronic Line Leak Detector. -Model: r Electronic Line Leak Detector, Model: {
Tank Overfill / High -Level Sensor. Model Tank Overfill /High -Level Sensor. Model: I
Other (specify equipment and model in Section E on Page 2). rj Other (specify equipment a and model in Section on Pa e 2).
Dispenser 1/2 Dispenser
ID: ID: {.
Dispenser Containment Sensor(s). Model: r Dispenser Containment Sensor(s).;Model:
R Shear Valve(s). Shear Valve(s). I
P7 Dispenser Containment Float(s) and Chaln(s). Dispenser Containment Float(s) and Chain(s).
Dispenser Dispenser i4. ID: ID:
r Dispenser Containment Sensor(s). Model: r Dispenser Containment Sensor(s). Model:
F Shear Valve(s), r Shear Valve(s).
r Dispenser Containment Floats and Chain(s ). Dis enser Containment Floats and Chain(s).
Dispenser Dispenser
ID: ID: '}
T7. Dispenser Containment Sensor(s). Model: r Dispenser Containment Sensor(s). Model:
r Shear Valve(s). rl Shear Valve(s).
r Dispenser Containment Float(s) and Chain(s). r Dispenser Containment Float(s) and Chain's).
r the raclllty contains more tanks or dispensers, copy this form. include information for every tank and dispenser at the facility. ? -
C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the,manufactu ers' uidelines'' Attached to
this Certification is Information (e.g. manufacturers' checklists) necessary to verify that this information is correct and a Plot Plan showing,the layout of
monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report; (check all tha' apply) :.r System set-
up r Alarm history report
Technician Name (print): Edgar Sotomayor
Certification No.: 836950'
Testing Company Name: Tanknology
Testing Company Address: 11000 N. MoPac Expressway Suite 500
Signature:
License. No.: 743160 Class 'A' "
Phone No.: (800) 800-4633 E
Monitoring System Certification Page 1 of
i
k
D. Results of Testing /Servicing i
Software Version Installed: 119.05
Complete the following checklist:
f` Yes C No* Is the audible alarm operational?
i,
f i
is Yes No* Is the visual alarm operational?
C Yes No* Were all sensors visually Inspected, functionally tested, and confirmed operational?
JJ
i.
is Yes t? No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not Interfere with
Monitoring System Certification Page 2 of 3 12/07
i
their proper operation? ' I
r Yes 7 No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operatlorial?
4, ; t:
r N/A f
i
G Yes r No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring
Ii
C. N/A system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors Initiate positive shut -down? (Check
all that apply) P Sump/Trench Sensors; r Dispenser Containment Sensors. j
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? (o Yes; r No
r Yes r No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill
prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) andoperating.properly? IfrN/A so at what percent of tank capacity does the alarm trigger? %
fYes* 0. No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E below, t
Yes* t No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply),:
F Product; r Water. If yes, describe causes in Section E below. i
IT-' Yes 0y, No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, If applicable
r Yes i > No* Is all monitoring equipment operational per manufacturer's specifications?
in section r Deiow, descnoe now and when these deticiencies were or will be corrected. .
E. Comments:
i,
f i
I removed a small amount of rain water from the STP /piping sump. I '
4
JJ
i.
Monitoring System Certification Page 2 of 3 12/07
i
4, ; t:
t
Ii
t
i
F. In -Tank Gauging / SIR Equipment: r 1 Check this box if tank gauging is used only for Inventory control.
r' Check this box if no tank gauging or SIR equipment is Installed.
This section must be completed if In -tank gauging equipment Is used to perform leak detection monitoring. ; f
I
Complete the following checklist:
Yes r No* Has all Input wiring been Inspected for proper entry and termination, Including testing for ground fauits7
Yes rO No* Were all tank gauging probes visually inspected for damage and residue buildup?
r Yes r No* Was accuracy of system product level readings tested?
r Yes M No* Was accuracy of system water level readings tested?
r Yes 00 No* Were all probes reinstalled properly?..
r Yes Ir No* Were all items on the equipment manufacturer ?s maintenance checklist completed? I
in the bection H, Deiow, aescrIbe now and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): r Check this box If LLDs are not Installed. i.
k
Complete the following checklist:
r Yes r No* For equipment start-up or annual equipment certification was a leak simulated to verify LLD performance? (Check all that
M, N/A apply) Simulated leak rate: WA g.p.h.; r 0.1 g.p.h; 0.2 g.p.h. y I
r Yes C, No* Were all LLDs confirmed operational and accurate within regulatory requirements? I
Yes r No* Was the testing apparatus properly calibrated?
r Yes r No* For mechanical LLDs, does the LLD restrict product Flow if it detects a leak?
ry N/A
r Yes G"' No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? ?
N/A
Yes OP No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system'is °disabled or. disconnected?
r Yes r No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or.falls a test?
7- N/A
r Yes r= No* For electronic LLDs, have all accessible wiring connections been visually Inspected?
N/A j
r Yes r No* Were all Items on the equipment manufacturer's maintenance checklist completed?
in Lne Jeuiun r1, Deiow, oescrioe now ano when Cnese aehaencies were or Wnl be correctea. 1
i
f
SWRCB, January 2002 Page 1 of 1
Secondary Containment Testing Report Form
This form is intendedfor use by contractors performing periodic testing of UST secondary containment systems. Us'e the appropriate
pages ofthis form to report resultsfor all components tested. The completedform, written test procedures,. and printoutsfrom tests
ifapplicable), should be provided to thefacility owner /operator for submittal to the local regulatory agency.`
1. FACTT.TTV TNFnRMATTnN
Facility Name: PEPSI COLA #3040 Date of Testing: 5/31 /2012 1 ..
Facility Address: 215 EAST 21ST STREET , BAKERSFrELD, CA 93305
Facility Contact: CASEY BLAIR Phone: 201 -6963
Date Local Agency Was Notified of Testing: 5/22/2012
Name ofLocal Agency Inspector (if present during testing): Ernie Medina j
2. TF,STTNC. CONTRACTOR INFORMATION
Company Name: TANKNOLOGY INC.
Technician Conducting Test: Edgar Sotomayor j
Credentials: CSLB Licensed Contractor r SWRCB Licensed Tank Tester
License Type: A ILicense Number: 743160
M ._ ..... -, _......., ._. -., w .. - .. .....,. ,
Manufacturer Training
Manufacturer Component(s) Date Training
l'
Expires
OPW VR 102 2/21/2014°
l
f:
3. SUMMARY OF TEST RESULTS I
Not Repair Not RepairsComponentPassFailComponentPass. Fail r!::? Tested Made ; .:, Tested Made
Spill Box TI: DIESEL FUEL diesel fill j(
F
If hydrostatic testing was performed, describe what was done with the water after completion of tests:
I,
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING , ., z .:. a
To the best ofmy knowledge, the facts stated in this document are accurate and infull compliance with legal requirements
Technician's Signature: Date: 5/31/2012
WO: 3402244
iti
i
7
Page 1 of 1
I
SPILL /OVERFILL CONTAINMENT BOXES
Facility is Not Equipped With Fill Riser Containment Sumps rJ
Fill Riser Containment Sumps are Present, but were Not Tested r
Test Method Developed By: r Spill Bucket Manufactured, Industry Standard 0 Professional "Engineer
t' Other (Specify): i
Test Method Used By: r7 Pressure r Vacuum C Hydrostatic -:
l" Other (Specify):
Test Equipment Used: LAKE TE T Equipment Resolution: 0.062 in.
Offi 1, , r4. 4 fix= si
5`III Box # V
t
z r Tank TS DIE$EL FUEL Dlesel v SpIII Boxy # 9 RSpIII7Box #i Er k F Spill Bon #7
S FIII Direct+
W0: 3402244
broa
Bucket Diameter: 11.00
a:,
Irj
i
I7
i
Bucket Depth: 12.00 I
Wait time between
I
applying
pressure /vacuum /water 10 min min min min
and starting test I
Test Start Time: 09:00:00
Initial Reading ,>Sy. 5.50 In. i
Test End Time: 10:00:00
Final Reading oyl: 5.50 In. i ' ." .
Test Duration: 1 hr
Change in Reading rAfyl: 0.00 In,
i
Pass /Fall Threshold or
Criteria: 0.00
Pas E
w.
G
Comments ? (include information on repairs made prior to testing, and recommended follow- up 'for fpiledtests) '.
i
i
t 5..
W0: 3402244
tr
a:,
Irj
i
I7
Site DiagramUnknology' This site diagram is for reference only and is not drawn to scale)
Work Order: 3402244 Date: 5/31/2012
Site ID / Name: 3040 /PEPSI COLA #3040
Address: 215 EAST 21ST STREET
City: BAKERSFIELD State: CA ;Zip, .93305
ST
DSL
TL 4 r t/
80
p
ENTRANCE
VENT
C
LI 0
Bravo
Lu
L2 Float
V`
80
p
ENTRANCE
1
t•
1
N. Lu
V`
1
t•
1
W.O.# SCI- 3402244 i
SHIFT TIME 1 6:00 AM
SHIFT TIME 2 DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED .
SHIFT BIR PRINTOUTS
DISABLED
108689 PEPSI SITE 9 DAILY BIR PRINTOUTS j
215 EAST STREET DISABLED21ST
BAKERSFIELD.CA 93305 TICKETED DELIVERY AUTO DIAL TIME SETUP
81152324905001 DISABLED
TANK PER TST NEEDED WRN NONE I,
MAY 31, 2012 7:27 AM DISABLED
TANK ANN TST NEEDED WRN jDISABLED
SYSTEM STATUS REPORT LINE RE- ENABLE METHOD
PASS LINE TEST
ALL FUNCTIONS NORMAL 1
LINE PER TST NEEDED WRN
INVENTORY REPORT DISABLED
LINE ANN TST NEEDED WRN y
DISABLED i
T 1:DIESEL FUEL RS -232 SECURITY i
VOLUME - 5888 GALS PRINT TC VOLUMES CODE 000000
ULLAGE - 9214 GALS ENABLED 1k% ULLAGE- 7703 GALS
TC VOLUME a 5844 GALS TEMP COMPENSATION
HEIGHT - 49.64 INCHES VALUE (DEG F ): 60.0
WATER VOL - 0 GALS STICK HEIGHT OFFSET j
WATER - 0.00 INCHES DISABLED RS -232 END OF MESSAGE..]
TEMP - 76.8 DEG F DISABLEDH- PROTOCOL DATA FORMAT 5
HEIGHT AUTO DIAL ALARM SETUP,,:,!
x x * * END x x x * x DAYLIGHT SAVING TIME
ENABLED
START DATE
MAR WEEK 3 SUN
START TIME
2:05 AM
END DATE
NOV WEEK 1 SUN
END TIME
2:00 AM
REDIRECT LOCAL PRINTOUT,
SOFTWARE REVISION LEVEL DISABLED 1N -TANK SETUP I'
VERSION 119.05.
SOFTWARE# 346119 -100 -F EURO PROTOCOL PREFIX T,.
CREATED - 00.02.25.12..15 S T 1:DIESEL FUEL j
PRODUCT CODES- MODULE# 330160 -105-A THERMAL COEFF :.000450. SYSTEM FEATURES: TANK DIAMETER'' : 119 '.50PERIODICIN -TANK TESTS SYSTEM SECURITY TANK PROFILE 4 PT$. ANNUAL IN -TANK TESTS CODE 000000 FULL VOL 151'02' CSLD 89.6 INCH VOL, 12290, BIR 59.8 INCH VOL 7580
FUEL MANAGER 29.9 INCH VOL 2836,..
METER DATA YES
END FACTOR: HEM ISPHER:
CAL UPDATE: IMMEDIATE)
FLOAT SIZE: 4.0 IN 8496!,.
WATER WARNING 1,. 5 ;
COMMUNICATIONS SETUP HIGH WATER LIMIT: 20(.;
SYSTEM SETUP MAX OR LABEL VOL: 15102!
OVERFILL LIMIT aMAY31, 2012 7:27 AM PORT SETTINGS: 2H13289]
HIGH PRODUCT
COMM BOARD 2 (FXMOD) 138931BAUDRATE2400DELIVERYLIMIT` SYSTEM UNITS PARITY ODD 3020 "' U.S. STOP BIT I STOP
SYSTEM LANGUAGE DATA LENGTH: 7 DATA LOW PRODUCT 1000
ENGLISH DIAL TYPE TONE LEAK ALARM LIMIT: 241
SYSTEM DATE /TIME FORMAT ANSWER ON 1 RING SUDDEN LOSS LIMIT: 501
MON DD YYYY HH:MM:SS_xM TANK TILT 1'.511:
Y
i
4
W.O. #,SCI - 3402244
LEAK MIN PERIODIC: 0%
0 LIQUID SENSOR SETUP
LEAK MIN ANNUAL 0% RECONCILIATION SETUP
0 L 1:ANNULAR SPACE
DUAL FLOAT HYDROSTATIC
CATEGORY ANNULAR SPACE MDIM 1: TTGG
PERIODIC TEST TYPE
STANDARD AUTOMATIC DAILY CLOSING, 'yTIME: 2:00 AM
ANNUAL TEST FAIL L 2:TURBINE SUMP
ALARM DISABLED DUAL FLT. HIGH VAPOR AUTO SHIFT 01 CLOSING ' tCATEGORYSTPSUMPTIME: DISABLED
PERIODIC TEST FAIL
ALARM DISABLED AUTO SHIFT 02 CLOSING
TIME: DISABLED•
GROSS TEST FAIL
ALARM DISABLED AUTO SHIFT 03 CLOSING
TIME: DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF AUTO SHIFT 04 CLOSING,.,.;
TIME: 6:00 AM i
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF PERIODIC RECONCILIATION, ! OUTPUT RELAY SETUP MODE: MONTHLY
DELIVERY DELAY 5 MIN ALARM: DISABLED 4
R 2:POSITIVE SHUTDOWN TEMP COMPENSATION
TYPE: STANDARD
STANDARD
NORMALLY CLOSED BUS SLOT FUEL METER TANK;:j
2 10 0 0 1` l"
IN -TANK ALARMS 2 10 1 0
ALL:LEAK ALARM
ALL:SUDDEN LOSS ALARM
LIQUID SENSOR ALMS I
LEAK TEST METHOD L 1:FUEL ALARM
L 2:FUEL ALARM
TEST CSLD ALL..TANK L I :SENSOR OUT ALARM i
Pd a 99%c L 2 :SENSOR OUT ALARM
CLIMATE FACTOR :MODERATE L 1 :SHORT ALARM
L 2:SHORT ALARM
L 1:HIGH LIQUID ALARM i.
LEAK TEST REPORT FORMAT L 1:LOW LIQUID ALARM
NORMAL
i
108889 PEPSI SITE 9
215 EAST 21ST STREET
BAKER$FIELD.CA 93305
81152324905001
MAY 31. 2012, . 728,AM i k'
FUEL MANAGEMENT SETUP
t,t
DELIVERY WARN DAYS; 0.4 F
AUTO PRINT: DISABLED
T 1:DIESEL FUEL
AVG SALES -SUN: 0 GAL l
AVG SALES -MON: 218 GAL
AVG SALES -TUE: 365 GAL
AVG SALES -WED: 372 GAL
nun onrco_•ruoo A150 /`_Ar
4
W.O.# SC1- 3402244
108889 PEPSI SITE 9
215 EAST 21ST STREET
AKERSFIELD.CA 93305
81152324905001
MAY 31. 2012 . 9:33 AM
SYSTEM- STATUS_REPORT -
D 8:ALARM CLEAR WARNING
ALARM HISTORY REPORT
IN -TANK ALARM - - - --
T I:DIESEL FUEL
HIGH WATER ALARM
MAY 31, 2012 8:37 AM
JUN 14. 2011 9:34 AM
JUN 30, 2010 8:36 AM
OVERFILL ALARM
MAY 31, 2012 8:26 AM.
JUN 14. 2011 9:44 AM
JUN 30, 2010 9:21 AM
LOW PRODUCT ALARM
MAY 31, 2012 8:25 AM
JUN 14, 2011 9:30 AM
JUN 30, 2010 8:31 AM
HIGH PRODUCT ALARM
MAY 31. 2012 8 :26 AM
JUN 14. 2011 9:46 AM
JUN 30, 2010 9:22 AM
INVALID FUEL LEVEL
MAY 31. 2012 8:26 AM
JUN 14, 2011 9:,30 AM.'';
JUN 30, 2010 8:32 AM
PROBE OUT
MAY 31, 2012 8:43 AM
MAY 31, 2012 8:32 AM
MAY 31, 2012 8:19 AM
HIGH WATER WARNING
MAY 31, 2012 8:36 AM
JUN 14, 2011 9:34 AM
JUN 30, 2010 8:36 AM
DELIVERY NEEDED.
MAY 31, 2012 8:31 AM
MAY 31. 2012 8:25 AM
MAY 11, 2012 5:32 PM
MAX PRODUCT ALARM
MAY 31, 2012 8:27 AM
JUN 14. 2011 9:46 AM.,
JUN 30, 2010 9:22 AM
ACCU -CHART CAL WARN
JUL 30, 2001 11:30 AM
RECON WARNING
JAN 27, 2003 9:30 AM
JAN 20, 2003 2:30 PM
JAN 13. 2003 2:30 PM
RECON ALARM
JAN 27, 2003 1:30 PM
JAN 20, 2003 3 :30 PM
JAN 13, 2003 2:30 PM
LOW TEMP WARNING
JUL 17, 2009 9:38 AM
AUG 4. 2008 11:47 AM
MAY 19, 2005 1:33 PM
xxxxx END xxxx
ALARM HISTORY REPORT
SENSOR ALARM - --
L 1:ANNULAR SPACE
ANNULAR SPACE
LOW LIQUID ALARM
MAY 31. 2012 8:50 AM
HIGH LIQUID ALARM
MAY 31, 2012 8:50 AM
LOW LIQUID ALARM
MAY 31, 2012 8:50 AM
xxxxxENDxxxx
ALARM HISTORY REPORT
SENSOR ALARM - --
L 2 :TURBINE SUMP
STP SUMP
FUEL ALARM
MAY 31, 2012 8:51 AM
SENSOR OUT ALARM
MAY 31, 2012 8:47 AM
SENSOR OUT ALARM
MIN 1d. 9nii 4:1a AM
108889 PEPSI SITE 9
215 EAST 21ST STREET
BAKERSFIELD.CA 93305
81152324905001
MAY 31. 2012 8:47 AM
SYSTEM STATUS REPORT
D 8:ALARM CLEAR WARNING
SENSOR ALARM - - - -=
L 2:TURBINE SUMP
STP SUMP
SENSOR OUT ALARM
MAY 31, 2012 8:47 AM
SENSOR ALARM ------
L 1:ANNULAR SPACE
ANNULAR SPACE
SENSOR OUT ALARM
MAY 31. 2012 8:47 AM
x x x x x END x x x x x
108889 PEPSI SITE 9
215 EAST 21ST STREET
BAKERSFIELD.CA 93305
81152324905001
MAY 31, 2012 9:33 AM
SYSTEM- STATUS REPORT -
D B:ALARM CLEAR WARNING
i.
i
i
I
I
i
i
I
i
i,
i