HomeMy WebLinkAbout2524 OSWELL STREET (7)MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each f
monitoring system control panel by the technician who performs the work. A copy ofthis form must be provided to the tank system owner /operator.
The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days oftest date.
A. General Information
Facility Name: MOBIL
Site Address: 2524 OSWELL ST. City: BAKERSFIELD
Bldg. No.:
Zip: 93304
Facility Contact Person: LONGE CHAO Contact Phone No.: ( )
Make/Model of Monitoring System: TLS -350 Date of Testing/Servicing: 41512012
B. Inventory of Equipment Teste&Certified
Check the annronriate boxes to indicate specific eauinment insnected/serviced:
Tank ID: UNL87 Tank ID: PREM91
In -Tank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model: MAG
Annular Space or VaultSensor. Model: 420 Annular Space or Vault Sensor. Model: 420
Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model: 208
Q Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: RED JACKET Mechanical Line Leak Detector. Model: RED JACKET
Electronic Line Leak Detector. Model: Electronic Line leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (specifyequipment type and model in Section E on Page 2). Q Other (specify equipment type and model in Section E on Page 2).
Tank rD: DIESEL Tank ID:
In -Tank Gauging Probe. Model: MAG Q In -Tank Gauging Probe. Model:
Annular Space orVault Sensor. Model: 420 Q Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model:
QQFiII Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector, Model: RED JACKET Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: ' 1 -2 Dispenser ID: 3-4
Dispenser Containment Sensor(s). Model: 001 Dispenser Containment Sensor(s). Model: 001
Shear Valve(s). Shear Valve(s).
Q Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 54 Dispenser ID: 7-8
Dispenser Containment Sensor(s). Model: 001 Dispenser Containment Sensor(s), Model: 001
Shear Valve(s). Shear Valve(s).
Q Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 9 -10 Dispenser ID:
Dispenser Containment Sensor(s). Model: BEAUDREAU Q Dispenser Containment Sensor(s). Model:
Shear Valve(s). Q Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Q DispenserContainment Float(s) and Chain(s).
Itthe facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
Correct. and a Plot Plan showing the layout of monitoring equipment, For any equipment capable of ge rating such reports, I have also
attached a copy of the report; (check all that apply): ® System set -up ® Alarm hilt eport
Technician Name (print): RICH PHILLIPS Signature:
Certification No.: A2908411035169 -UT License. No.: C611 D40 809850
Tesfing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 392 -8687
Testing ;Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308 Date ofTesting/Servicing: 4!512012
1JN -03G —1 /A .
Page 1 of 5
www.unidocs.org Rev. 01/17/08
Monitoring System Certification
A Results of Testing/Servicing
Software Version Installed:
fmmnipta thn fnllnwina rhnr1r1icf-
Yes I No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
ID N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? %
Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No* Is all monitoring equipment operational per manufacturer's specifications?
In Section:E below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 5
UN -036 — 2/4 www.unidocs.org Rev. 01117/08
Monitoring System Certification
F. In -Tank Gauging / SIR Equipment: lR Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLDs are not installed.
Comnlete the fnllnwinu checklist:
Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: ® 3 g.p.h.; [10. 1 g.p.h ; 0.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow ifit detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off ifthe LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion ofthe monitoring system malfunctions
g N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yesj No* Were all items on the equipment manufacturer's maintenance checklist completed?
Xn Section H, below, describe how and when these deficiencies were or will be corrected.
IU :Comments:
IN-036 — 3/4
Page 3 of 5
www.unidocs.org Rev. 01/17/08
Monitoring System Certification Form: Addendum for Vacuum/Pressure Interstitial Sensors
Y. Results of Vacuum/Pressure Monitoring Equipment Testing
This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of
this form must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner /operator. The owner /operator must submit a copy of the Monitoring System Certification Form to the
local agency regulating UST systems within 30 days oftest date.
Manufacturer: N/A Model: System Type: Pressure; Vacuum
Sensor ID
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: [] Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
How was interstitial communication verified?
Leak Introduced at Far End ofInterstitial Space;' Gauge; Visual Inspection; Other (Describe in Sec. J, below)
EWas vacuum/pressure restored to operating levels in all interstitial spaces? [I Yes No (Ifno, describe in Sec. J, below)
J. Comments: NONE OF THESE SENSORS ARE PRESENT AT THIS SITE.
Page 4 of 5
If the sensor successfully detects a simulated vacuum/pressure leak introduced in the interstitial space at the furthest point from the
sensor, vacuum/pressure has been demonstrated to be communicating throughout the interstice.
UN -66A -1/1 www.unidws.org Rev. 01/26106
LISITVT
SWRCB, January 2006 .
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUSTspill containment structures. The completedform and
printouts from tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: MOBIL I Date of Testing: 4/5112
Facility Address: 2524 OSWELL ST, BAKERSFIELD 93304
Facility Contact: LONGE CHAD Phone: 661 - 345 -b208
Date Local Agency Was Notified ofTesting: 3/2/12
Name of Local Agency Inspector (fpresent during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials: CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other (Spec)
License Number(s): 1035169 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic 0 Vacuum Other
Test Equipment Used: VISUAL I Equipment Resolution: 0
1 .. ...... ... z
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
I REG 87 -FILL 2 PREM91 -FILL 3 DIESEL FILL 4
Bucket Installation Type: X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
Direct Bury
Contained in Sum
ucket Diameter. 12" 12" 12"
Bucket Depth: 14" 14" 14"
Wait.time between applying
vacuum/wafer and start oftest: 30 MIN 30 MIN 30 MIN
Test Start Time (Tj): 1:00 1:00 1:00
Initial Reading (Ri): 14" 14" 14"
Test End Time (TF): 2:00 2:00 2:00
Final Reading (RF): 14" 14" 14"
Test Duration (TF— Tj): I -HOUR 1 -HOUR I -HOUR
Change in Reading (RF - R,): 0" 0" 0"
Pass/Fail Threshold or
Criteria: 0.00 0.00 0.00
Test Resalt: X Pass Fail X Pass Fail X Pass Fail Pass D Fail
Comments — (include information on repairs made prior to testing, andrecommendedfollow -upforfailed tests)
CERTIFICATION OF TECH IAN RESPONSIBLE FOR CONDUCTING THIS TESTING
IYiereby certify that all the Information co aimed to this report is true, accurate, and infull compliance with legal requirements.
Technician's Signature: Date: 4/5/12
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
x}5991 f
RICH ENVIRONMENTAL
5643 BROOKS CT. BAKERSFIELD, CA. 93308
OFFICE (661)392 -8687 FAX (661)392 -0621
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
FACILITY NAME: MOBIL
W /0 #:
FACILITY ADDRESS: 2524 OSWELL ST, BAKERSFIELD 93304
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL87 L/D TYPE: RED JACKET
NO 12 FAIL
SERIAL # MECHANICAL
pREM91 L/D TYPE: RED JACKET
YES 11 PASS
SERIAL # MECHANICAL
DIESEL L/D TYPE: RED JACKET
YES 11 PASS
SERIAL # MECHANICAL
RE -TEST L/D TYPE : RED JACKET
UNL87 YES 12 PASS
SERIAL # MECHANICAL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICH Pm4ls
SIGNATURE: DATE: 4/5/12
DISABLED
CUSTOM
SECURIn,
TANK 'PER TST NEEDED WRN COMMUNICATIONS SETUP
DISABLED
UINAELEDANN TST NEEDED WRNTANK
DISABLED
DISABLED
ISO 3166 COUNTRY
LANGUAGE CODE:
PORT SETTINGS:
LINE RE-ENABLE METHOD
MASS /DENSITY
PASS LINE COMM BOARD 1 tSDIM >
3IL LINE PER TST NEEDED WRN
N -232 SECURITY
CODE : DISABLED
4 OSWELL ST.
FR CA 93306 DISABLEDLINEANN TST NEEDED WRN COMM BOARD' 2 (RS -232)
DISABLED 13AUD RATE 1200
PARITY ODD
5, 2012 12:49 PM PRINT TC VOLUMES STOP BIT : I STOP
ENABLED DATA LENGTH: 7 DATA
RS -232 SECURITY
TEMP CoMpENSATION CODE : DISABLED
YSTEM STATUS , REPORT.
r VALUE (DEC F 1 60.0
OFFSET
3LL FUNCTIONS NORMAL STICK HEIGHT
DISABLED AUTO TRANSMIT SSETTINGS:
ULLAGE: 90%'
H--PROTOCOL DATA FORMAT
AUTO LEAK ALARM LIMIT
DISABLED
HEIGHTDAYLIGHT SAVING TIME
AUTO HIGH WATER LIMIT
DISABLED
ENABLED AUTO OVERFILL LIMIT
START DATE DISABLED
MAR WEEK 2 SUN AUTO LOW PRODUCT
TWARE REVISION LEVEL START TIME
2:00 AM
DISABLED
AUTO THEFT LIMIT
RSION 330.01
TWARE# 346330-100 -B END RATE
NOV WEEK 1 SUN A
TT
DE
AUTOO DELIVERY START
TEDj - 10.07.23.17.25 END TIME DISABLED
2'40 AM AUTO DELIVERY END
10DULE# 33(1160 -064 -a
STEM FEATURES: RE- DIRECT LOCAL PRINTOUT
DISABLED
AUTO EXTERNAL INPUT ON
ERIODIC IN-TANK TESTS DISABLED DISABLEDUALIN-TANK TESTS PREFIX
AUTO EXTERNAL INPUT OFF
ISD E PROTOCOL DISABLED
AUTO SEOR FUEL. ALARMSENSOR
1J .
1(I AUTO DISABLED
20 REPETITIV AUTO SENSOR WATER ALARM
DISABLED
3.10 AUTO SYSTEM SECURITY AUTO SENSOR OUT ALARM
3.20 REPETITIV CODE :000000 DISABLED
MAINTENANCE HISTORY
D I BA13L.ED
DISABLED
CUSTOM
SECURIn,
IFT TIME I : DISABLED
IFT TIME 2 : DISABLED
IFT TIMETIMM 4 : DISABLED
RS-232 END OF MESSAGE
DISABLEDCUSTOMALARMS
STEM SETUP DISABLED
5. 2012 12:49 PM
SERVICE NOTICE
DISABLED
STEM UNITS
S. ISO 3166 COUNTRY
LANGUAGE CODE:
VGLISH
3TEM DATE /TIME FORMATVDDYYYYHH:W'SS xM MASS /DENSITY
DISABLED
24LOSWELL ST.
CERPFIELD CA 93306
IFT TIME I : DISABLED
IFT TIME 2 : DISABLED
IFT TIMETIMM 4 : DISABLED
RS-232 END OF MESSAGE
DISABLED
TANK. SETUP
I :UNL -87
DUCT CODE i
3RMAL COEFF :.000700
VK DIAMETER 113.75
VK PROFILE 1 PT
FULL VOL 15023
SAT SIZE: 4.0 IN.
rER WARNING 2.0
3H WATER LIMIT: 3.0
OR LABEL VOL: 15023ERFILLLIMIT90%
135203HPRODUCT95%
14271
LIVERY LIMIT 1014
1502
A PRODUCT 500
AX ALARM LIMIT: 99
DDEN LOSS LIMIT: 99NKTILT0.00OBEOFFSET0.00
PHON MANIFOLDED TANKS
NONE
NE MANIFOLDED TANKS
NONE
AK MIN PERIODIC: 0%
0
AK MIN ANNUAL 0%
0
RIODIC TEST TYPE,
STANDARD
INUAL TEST FAIL
ALARM DISABLED
RIODIC TEST FAIL
ALARM DISABLED
OSS TEST FAIL
ALARM DISABLED
IN TEST AVERAGING: OFFRTESTAVERAGING: OFF
NK TEST NOTIFY: OFF
IX TST SIPHON BREAK:OFF
LIVERY DELAY 15 MINIMPTHRESHOLD10.0014
T 2:PREM -91
PRODUCT CODE 2
THERMAL COEFF :.000700
TANK DIAMETER 90.00
TANK PROFILE 1 PT
FULL VOL 11550
FLOAT SIZE: 4.0 IN.
WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 11550
OVERFILL LIMIT 90%
10395
HIGH PRODUCT 95%
10972
DELIVERY LIMIT 10•
1155
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 0%
0
LEAK MIN ANNUAL 0%
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY : 15 MIN
PUMP THRESHOLD : 10.00%
T 3 :DIESEL
PRODUCT CODE 3
THERMAL COEFF :.000450
TANK DIAMETER 90.00
TANK PROFILE 1 PT
FULL VOL 11550
FLOAT SIZE: 4.0 IN.
WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
OR LABEL VOL: 11550MAX
OVERFILL LIMIT 90'•6
10395
HIGH PRODUCT 951%
10972
DELIVERY LIMIT 10%
1155
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
T;I: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 06/6
0
LEAK MIN ANNUAL 0%
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 15 MIN
PUMP THRESHOLD 10.00%
A
fS9 `r1
AK Ti ST METHOD I
rOUTPUT RELAY SETUP
ST ON DATE : ALL TANK
N 29, 2009
3 36136
ART TIME : DISABLED I.R 1:87 STP
ST RATE :0,20 GAi HR TYPE:
RATION 2 HOURS STANDARD
NORMALLY CLOSED
T EARLY STOP:DISABLID
0: 1
AK TEST REPORT FORMAT
NORMAL.
LIQUID SENSOR ALMS
a L 1:FUEL ALARM
L 1:SENSOR OUT ALARM
ISD S I TE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
QUID SENSOR SETUP ISD HOSE ALARMS
ALL:FLOW COLLECT FAIL
1:87 STP sR 2:91 STP
I —STATE (SINGLE FLOAT) TYPE:
TEGORY : STP SUMP STANDARD
NORMALLY CLOSED
2:57 ANNULAR TANK #: 2
I —STATE (SINGLE FLOAT)
TEGORY : ANNULAR SPACE
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 4:FUEL ALARM
3:91 PROBE SUMP L 3:SENSOR OUT ALARM
I —STATE (SINGLE FLOAT) L 4:SENSOR OUT ALARM
TEGORY : PIPING SUMP
ISD SITE ALARMS
ISD GROSS PRES FAIL
4:91 STP ISD DEGRD PRES FAIL
I —STATE (SINGLE FLOAT) ISD VAPOR LEAK FAIL `
TEGORY : STP SUMP ISD VP PRES FAIL
ISD VP STATUS FAIL
5:91 ANNULAR ISD HOSE ALARMS
I —STATE (SINGLE FLOAT) ALL:FLOW COLLECT FAIL
TEGORY : ANNULAR SPACE
R 3:DIESEL STP
s•TYPE: STANDARD
6:DIESEL PROBE SUMP NORMALLY CLOSED
I —STATE (SINGLE FLOAT)
TEGORY : PIPING SUMP TANK 4: 3
7:DIESEL STP LIQUID SENSOR ALMS
I —STATE (SINGLE FLOAT) L 6:FUEL ALARM
TEGORY : STP SUMP L 7:FUEL ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
8:DIESEL ANNULAR
I —STATE (SINGLE FLOAT) R 4:REMOTE ALARM
TEGORY : ANNULAR SPACE TYPE:
STANDARD
NORMALLY CLOSED
TANK #: NONE
NO ALARM ASSIGNMENTS —
9 i
SMARTSENSOR SETUP- - - -
s 1:CARBON CANISTER
CATEGORY VAPOR VALVE
s 2:PRESSURE SENSOR
CATEGORY VAPOR PRESSURE
s 3 :DISP._ 3 -4
CATEGORY AIR FLOW METER
s 4:DISP 1 -2
CATEGORY AIR FLOW METER
is 5:DISP 5 -6
CATEGORY AIR FLOW METER
s 6:DISP 7 -8
CATEGORY AIR FLOW METER
s 7:DISP 9 -10
CATEGORY AIR FLOW METER
s 8:ATM
CATEGORY ATM P SENSOR
EVR /ISD SETUP
EVR TYPE: BALANCE
BALANCE NOZZLE TYPE
VST
VAPOR PROCESSOR TYPE
VEEDER -ROOT POLISHER
ANALYSIS TIMES
TIME: 10:00 AM
DELAY MINUTES: 1
ACCEPT HIGH ORVR:
ENABLED
ISD HOSE TABLE
ID FP FL HL AA RR
01 01 01 02 02 02
02 02 02 02 02 02
03 03 03 02 01 02
04 04 04 02 01 02
05 UU 05 02 03 02
06 06 06 02 03 02
07 07 07 02 04 02
08 08 08 02 04 02
09 09 09 02 05 02
10 16 10 02 05 02
ISD AIRFLOW METER MAP
ID SERIAL NUM LABEL
1 41517 DISP 3 -4
2 41519 DISP 1 -2
3 36136 DISP 5 -6
4 34956 DISP 7 -8
5 35821 DISP 9 -10
D FUFL GRADE HOSE MAP
1 2 3 4
MHH MHH MHH MHH AA
101 201 901 U U 2
102 202 902 U U 2
103 203 903 U U 1
104 204 904 U U 1
I U 9 U 2 0 0 0 0
906 106 206 U U 3
207 907 3 U 107 4
208 908 3 U 108 4
109 209 909 3 U 5
110 210 910 3 U 5
BEL TABLE
r--- - - - - --
UNASSIGNED
BLEND3
REGULAR
MID GRADE
PREMIUM
GOLD
BRON2E
SILVER
BLEND2
BLEND4
10 SETUP
1C VERSION: 01.03
3POR PROCESSOR TYPE
EDER -ROOT POLISHER
ARM HISTORY REPORT
1N -TANK ALARM -
JERFILL ALARM
PR 1, 2012 8:26 AM
4R 27, 2012 2:58 PM
aR 11, 2012 3:02 AM
OW,PRODUCT ALARM
PR 2, 2011 2:54 PM
IGH PRODUCT ALARM
OV 9, 2011 2:50 AM
NVALID FUEL LEVEL
PR 2, 2011 2 :42 PM
ELIVERY NEEDED
PR 2, 2011 11:27 AM
OW TEMP WARNING
EC 15, 2011 4:32 AM
EC 10, 2011 5:57 AM
F.0 8, 2011 3:30 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 1:87 STP
STP SUMP
SENSOR OUT ALARM
APR 5, 2012 1:41 PM
FUEL ALARM
APR 5, 2012 1:20 PM
SENSOR OUT ALARM
APR 6, 2011 9:43 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 2:87 ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
APR 5. 2012 1 :41 PM
FUEL ALARM
APR 5, 2012 1:21 PM
SENSOR OUT ALARM
APR 6, 2011 9:43 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:91 PROBE SUMP
PIPING SUMP
SENSOR OUT ALARM
APR 5, 2012 1:41 PM-
SENSOR OUT ALARM
APR' G. 2011 9:43 AM
FUEL ALARM
APR 6, 2011 9 :30 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - -- L 4 :91 STP
STP SUMP
SENSOR OUT ALARMAPR5, 2012 1:41 PM
FUEL ALARMAPR5. 2012 1:22 PM
SENSOR OUT ALARMAPR6, 2011 9:43 AM
SENSOR ALARM - - - --
L 5:91 ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
APR 5, 2012 1:41 PM
FUEL ALARM
APR 5. 2012 1:23 PM
SENSOR QUT .ALARM
APR 6, 2011 9:43 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 6:DIESEL PROBE SUMPPIPINGSUMP
SENSOR OUT ALARMAPR5, 2012 1:41 PM
SENSOR OUT ALARM
APR 6. 2011 9:43 AM
FUEL ALARM
APR 6, 2011 9:29 AM
ALARM HISTORY REPORT
SENSOR ALARM -----
L 7:DIESEL STP
STP SUMP
SENSOR OUT ALARM
APR 5, 2012 1:41 PM
FUEL ALARM
APR 5, 2012 1:23 PM
SENSOR OUT ALARM
APR 6, 2011 9:43 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - -- L 8:DIESEL ANNULARANNULARSPACE
SENSOR OUT ALARM
APR 5, 2012 1:41 PM
FUEL ALARM
APR 5, 2012 1:23 PM
SENSOR OUT ALARMAPR6, 2011 9:43 AM
T
MONITOR CERT. FAILURE REPORT
SITE NAME: MOBIL DATE: 4/5/12
THE FOLLOWING COMPONENTS WERE REPLACED/REPAIRED TO COMPLETE
TESTING.
REPAIRS: UNL87 LEAK DETECTORS FAILED - REPLACED AND RE- TESTED -
PASSED
LABOR:
PARTS INSTALLED: REPLACED 1 -RED JACKET FX1V AND TESTED
NAME : TITLE:
SIGNATURE•
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICK ENVIRONMENTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.