MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work A copy of this form must be provided to the tank system owner /operator.
The owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: JOHNNYS ARCO
Site Address: 2612 BUCK OWENS BLVD
Facility Contact Person: JOHNNY
Make/Model ofMonitoring System: TLS -350
B. Inventory of Equipment Tested/Certified
Checktheanorouriate boxes to indicate saecific equipment inspected /serviced:
City: BAKERSFIELD
Bldg. No.:
Zip:
Contact Phone No.: ( )
Date of Testing/Servicing: 11/30/2011
Tank ID: UNL87 Tank ID: UNL 87 SIPHON
InTank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model: MAG
Annular Space or Vault Sensor. Model: 409 Annular Space or Vault Sensor. Model: 409
Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: RED JACKET DIAPHRAM Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank ID: PREM 91 Tank ID:
In -Tank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: 409 Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: RED JACKET Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: 1 -2 Dispenser ID: 3-4
Dispenser Containment Sensor(s), Model: 406 Dispenser Containment Sensor(s). Model: 406
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). El Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 5-6 Dispenser ID: 7-8
Dispenser Containment Sensor(s). Model: 406 Dispenser Containment Sensor(s). Model: 406
IR Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of grating such reports, I have also
attached a copy of the report; (check all that apply): ® System set -up ® Alarm hilt report
Technician Name (print): RICH PHILLIPS Signature:
Certification No.: A2908411035169 -UT License. No.: 1/ D40 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 392 -8687
Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308 Date ofTesting/Servicing: 11130/2011
Page 1 of 5
UN -036 —1/4 www.unidoes.org Rev. 01/17/08
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 329.01
Complete the following checklist:
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks gDA sensor failure/disconnection? ® Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? Ifso, at what percent oftank capacity does the alarm trigger? %
Yes* No Was any monitoring equipment replaced? Ifyes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. Ifyes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes 1 No* Is all monitoring equipment operational per manufacturer's ecifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 5
UN-036 — 2/4 www.unidomorg Rev. 01/17/08
Monitoring System Certification
F. In -Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
a Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
Complete the following checklist:
Check this box if LLDs are not installed.
Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: ® 3 g.p.h.; 0.1 g.p.h ; 02 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow ifit detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off ifany portion of the monitoring system malfunctions
N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
UN -036 — 3/4
Page 3 of 5
www.unidocs.org Rev. 01 /17/08
Monitoring System Certification Form: Addendum for Vacuum/Pressure Interstitial Sensors ` 1 `
1. Results of Vacuum/Pressure Monitoring Equipment Testing
This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of
this form must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner /operator. The owner /operator must submit a copy of the Monitoring System Certification Form to the
local agency regulating UST systems within 30 days of test date.
Manufacturer: NONE Model: System Type: Pressure; ® Vacuum
Sensor ID
Components) Monitored by this Sensor:
Sensor Functionality Test Result: El [3 Fail Interstitial Communication Test Result: Pass; Fail
Components) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Components) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: [] Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor.
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
How was interstitial communication verified?
Leak Introduced at Far End of Interstitial Space;' Gauge; Visual Inspection; Other (Describe in Sec. J, below)
Was vacuum/pressure restored to operating levels in all interstitial spaces? Yes No (Ifno, describe in Sec. J, below)
J. Comments: NONE OF THESE SENSORS ARE PRESENT AT THIS SITE.
Page 4 of 6
If the sensor successfully detects a simulated vacuum/pressure leak introduced in the interstitial space at the furthest point from the
sensor, vacuum/pressure has been demonstrated to be communicating throughout the interstice.
UN -036A - t/1 www.unidoes.org Rev. 01/26/06
Monitoring System Certification
UST Monitoring Site Plan
Site Address: LV? BUCA OWENS BLVD. BAKERSFIELD, CA. 9330$
6
u
C
0.
date map was drawn- ;: 1:2019.
111tstruc6s.m.
If you already have a diagran:::,at shoe u: wd "r-nation, vn,, m- ! -0- it, rather than this page. with your Monitoring
System Certtficc.ion. On your site plan, snow the gene ai layou-' u` tanks .u, n }. Clearly identify Ic;atiuns nl thr Wu-wing
equipment, if it :.,fled: nivahuring system control :acts; sensors r ovi.,;6 annular spaces, stu,ips, dispenser pans, spill
containers, or other secondary containment areas: [mechanical or electronic li le leak detectors; and in -tank liquid level probes (if used
for leak detection). ,„ ; ?.; space provided, note the date this Site Plan was prepai , 1.
pape 4 of 4
l;\ -036 -3/i www.anidoch.j-,; Rev. WP/(iit
COO
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractorsperforming annual testing ofUSTspill containment structures. The completedform and
printoutsfrom tests (rfapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: JOHNNY'S ARCO Date of Testing: 11/30/11
Facility Address: 2612 BUCK OWENS BLVD, BAKERSFIELD
Facility Contact: JOHNNY Phone:
Date Local Agency Was Notified of Testing:
Name of Local Agency Inspector (fpresent during testing): ERNIE MEDINA
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials: CSLB Contractor X ICC Service Tech. 0 SWRCB Tank Tester 0 Other (Specify)
License Number(s): 1035169 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic 0 Vacuum 0 Other
Test Equipment Used: VISUAL Equipment Resolution: 0
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
1 REG87 -FILL 2 UNL87 SIPHON -FILL 3 PREM91 -FILL 4
Bucket Installation Type: X Direct Bury
Contained in Sump
X Direct Bury
0 Contained in Sump
X Direct Bury
0 Contained in Sump
0 Direct Bury
Contained in Sum
Bucket Diameter: 12" 12" 12"
Bucket Depth: 14" 14" 14"
Wait time between applying
vacuum/water and start oftest: 30 MIN 30 MIN 30 M1N
Test Start Time M: 9:30 9:30 9:30
Initial Reading (RD: 10" 10" 10"
Test End Time (TF): 10:30 10:30 10:30
Final Reading (RF): 9" 9" 9"
Test Duration (TF -TO: 1 -14OUR 1 -HOUR 1 -HOUR
Change in Reading (RF - Rj): 0 0 0
Pass/Fail Threshold or
Criteria: 0.00 0.00 0.00
Test Result: X Pass 0 Fail X Pass Fail X Pass 0 Fail Pass 0 Fail
Comments— (include information on repairs made prior to testing, and recommendedfollow -up forfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby cen* that all the information coast ' din this report is true, accurate, and in fullcompliance with legal requirements.
Technician's Signature: Date: 11/30/11
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
RICHENVIRONMENTAL
5643 BROOKS CT. BAKERSFIELD, CA. 93308
OFFICE (661)392 -8687 FAX (661)392 -0621
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
Wro #:
FACILITY NAME: JOHNNY'S ARCO
FACILITY ADDRESS: 2612 BUCK OWENS BLVD, BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
87 LID TYPE: RED JACKET
YES 11 PASS
SERIAL # 6776
91 L/D TYPE: RED JACKET
YES 10 PASS
SERIAL # 3486
L/D TYPE: PASS
YES
SERIAL # FAIL
L/D TYPE: PASS
YES
SERIAL # FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICH PHILL
SIGNATURE: DATE: 11/30/11
ISO 3166 COUNTRY
CODE:
MASS /DENSITY
SYSTEM SETUP DISABLED
NOV 30, 2011 8:35 AM
Lf"l —T l
RECEIVER SETUP: "'
NONE
AUTO DIAL TIME SETUP:
NONE
SYSTEM UNITS
SYSTEM SECURITY
CODE : 000000
U.S.
MAINTENANCE HISTORY
30FTWARE REVISION LEVEL DISABLED
ERSION 330.01
3OFTWARE4 346330 -100 -H
TREATED - 10.07.23.17.25 TANK CHART SECURITY
ENGLISH
DISABLED
MODULE# 330160 -004-'a
SYSTEM DATE/TIME FORMAT
3YSTEM FEATURES:
PERIODIC IN -TANK TESTS CUSTOM ALARMS
ANNUAL IN -TANK TESTS DISABLED
ISD
SERVICE NOTICE
COMMUNICATIONS SETUP
DISABLED
ISO 3166 COUNTRY
CODE:
MASS /DENSITY
SYSTEM SETUP DISABLED
NOV 30, 2011 8:35 AM
Lf"l —T l
RECEIVER SETUP: "'
NONE
AUTO DIAL TIME SETUP:
NONE
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH RS -232 END OF MESSAGE
SYSTEM DATE/TIME FORMAT DISABLED
MON DD YYYY HH:MM:SS XM
COMMUNICATIONS SETUP AUTO DIAL ALARM SETUP
ARCO81360
2612 Huck Owens Blvd
Bakersfield
CA 93308 PORT SETTINGS:
SHIFT TIME 1 10:00 PM COMMCOMM BOARD 1 (EDIMSHIFTTIME2DISABLED232SECURITYSHIFTTIME3DISABLEDCODEDISABLEDSHIFTTIME4DISABLED
TANK PER TST NEEDED WRN COMM HOARD 2 (RS -232)
bISABLED BAUD RATE 1200
TANK ANN TST NEEDED WRN PARITY ODD
STOP BIT 1. STOP N- TAtdfC SETUP
DISABLED DATA LENGTH: 7 DATA
LINE RE- ENABLE METHOD RS -232 SECURITY
CODE : DISABLED T 1:U R
PASS LINE TEST PRODUCTCT CODECODE 1
THERMAL COEFF :.000700
LINE PER TST NEEDED WRN AUTO TRANSMIT SETTINGS: TANK DIAMETER 92.00
DISABLED TANK PROFILE 4 PTS
LINE ANN TST NEEDED WRN AUTO LEAK ALARM LIMIT FULL VOL 11627
DISABLED DISABLED 69.0 INCH VOL 9438
PRINT TC VOLUMES AUTO HIGH WATER LIMIT 46.0 INCH VOL
23.0 INCH VOL
5814
2190
ENABLED DISABLED
AUTO OVERFILL LIMIT
ITEMP COMPENSATION DISABLED
AUTO LOW PRODUCT FLOAT SIZE: 3.0 IN.
VALUE (DEC F ): 60.0 DISABLEDSTICKHEIGHTOFFSETAUTOTOTHEFT LIMIT WATER WARI4I NG 2.0
DISABLED DISABLED NIGH WATER LIMIT: 3.0
ULLAGE: 90% AUTO DELIVERY START MAX OR LABEL VOL: 11627
H- PROTOCOL DATA FORMAT AUTOAUTO DELIVERY END OVERFILL LIMIT 90%
HEIGHT DISABLED 10464
SAVING TIME AUTO EXTERNAL INPUT ON HIGH PRODUCT
DIYYLIGHT
DISABLED 11045
RE- DIRECT LOCAL PRINTOUT AUTO EXTERNAL INPUT OFF DELIVERY LIMIT 10%
DISABLED DISABLED 1162
EURO PROTOCOL PREFIX AUTO SENSOR FUEL ALARM
DISABLED LOW PRODUCT 500
S AUTO SENSOR WATER ALARM LEAK ALARM LIMIT: 99
DISABLED SUDDEN LOSS LIMIT: 50
AUTO SENSOR OUT ALARM TANK TILT
PROBE OFFSET
0.00
0.00DISABLED
G
VAPOR PROCESSOR TYPE
SMARTSENSOR SETUP
L3 :91 STP
VEEDER -ROOT POLISHER
TRI -STATE SINGLE FLOAT) s 1:VAPOR PRESSURECATEGORY : STP SUMP CATEGORY VAPOR PRESSURE
L 4:87 ANN I s 2:CANISTER
CATEGORY VAPOR VALVE
TRI -STATE SINGLE FLOAT)
3 42039
CATEGORY : ANNULAR SPACE s 3:DISP 1 -2
ISD GROSS PRES FAIL
s 6:DISP
CATEGORY
CATEGORY AIR FLOW METER
OUTPUT RELAY SETUP
R 1:87 STP EVR!ISD SETUP
TYPE'.
STANDARD
NORMALLY CLOSED EVR TYPE: BALANCE
TANK #: NONE BALANCE NOZZLE TYPE
VST
LIQUID SENSOR ALMS VAPOR PROCESSOR TYPE
s 4:DISP 3 -4
VEEDER -ROOT POLISHER
L 5:87 ANN 2 CATEGORY AIR FLOW METER
TRI -STATE SINGLE FLOAT)
1 42020
L 2:8ENSOR OUT ALARM
CATEGORY : ANNULAR SPACE s 5:DISP 5 -6
TIME: 11:59 PM
3 42039
CATEGORY AIR FLOW METER
L 6:91 ANN
ISD GROSS PRES FAIL
s 6:DISP
CATEGORY
7 -8
AIR FLOW METERTRI -STATE SINGLE FLOAT)
ISD VAPOR LEAK FAIL
CATEGORY : ANNULAR SPACE s B:ATM .
ENABLED
ALL:FLOW COLLECT FAIL
ISD VP STATUS FAIL
CATEGORY ATM P SENSOR
OUTPUT RELAY SETUP
R 1:87 STP EVR!ISD SETUP
TYPE'.
STANDARD
NORMALLY CLOSED EVR TYPE: BALANCE
TANK #: NONE BALANCE NOZZLE TYPE
VST
LIQUID SENSOR ALMS VAPOR PROCESSOR TYPE
1
L 1:FUEL ALARM VEEDER -ROOT POLISHER
ISD
L 2:FUEL ALARM
L 3:SENSOR OUT ALARM ID SERIAL
L 1:SENSOR OUT ALARM
ISD SITE ALARMS 1 42020
L 2:8ENSOR OUT ALARM ANALYSIS TIMES
2 42045 DISP 3 -4
TIME: 11:59 PM
3 42039
ISD SITE ALARMS DELAY MINUTES: 1
42018
ISD GROSS PRES FAIL
ISD VP PRES FAIL
ISD DEGRD PRES FAIL
ISD VP STATUS FAIL
ISD VAPOR LEAK FAIL ACCEPT HIGH ORVR: ISD VP PRES FAIL ENABLED
ALL:FLOW COLLECT FAIL
ISD VP STATUS FAIL
ISD HOSE TABLEISDHOSEALARMSI- FL AA RR
ALL:FLOW COLLECT FAIL
FP --
01 01 01 02 01 02R2:91 STP 02 02 02 02 01 02
TYPE: 03 03 03 02 02 02
STANDARD 04 04 04 02 02 02
NORMALLY CLOSED 05 05 05 02 03 02
06 06 06 02 03 02
TANK #: 3 07 07 07 02 04 02
08 08 08 02 04 02
LIQUID SENSOR ALMS
UNASSIGNED
1 2 3 N
L 3:FUEL ALARM ISD AIRFLOW METER MAPL3:SENSOR OUT ALARM ID SERIAL NUM LABEL
ISD SITE ALARMS 1 42020 DISP 1 -2
ISD GROSS PRES FAIL 2 42045 DISP 3 -4
ISD DEGRD PRES FAIL 3 42039 DISP 5 -6ISDVAPORLEAKFAIL442018DISP7 -8ISDVPPRESFAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:FLOW COLLECT FAIL
q'i -
14L
ISD FUEL GRADE HOSE MAP
UNASSIGNED
1 2 3 N
FP MHH MHH MHH MHH AA - --
01 - 101 501 901 U U 1
102
03
102
103
502 902 U U
503 303 U U 2
04 104 504 304 U U 2
U 305105505905U306106506906UU07107507307UU4
0S l0a 508 308 U U 4
LABEL TABLE
1: UNASSIGNED
2: BLEND3
3: REGULAR
4: MID GRADE
5: PREMIUM
6: GOLD
7: BRONZE
8: SILVER
9: BLEND2
10: BLEND4
PMC SETUP
pMC VERSION: 01.03
VAPOR PROCEOR TYPE
VEEDER -ROOTPOLISHER
SIPHON PIANIFOLDED TANKSTO: NONE
LINE MANIFOLDED TANKST#: NONE
LEAK MIN PERIODIC: 10%
1162
LEAK MIN ANNUAL IQ9
1162
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM• D I SABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFFPERTESTAVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY : 15 MINPUMPTHRESHOLD : 10.003;
LEAK MIN PER I Ob I C: 10%
1162 LEAK MIN PERIODIC: 10%
1162 '
LEAK. MIN ANNUAL : 10%
1162 LEAK MIN A14NUAL 10%
1162
PERIODIC TEST TYPE
STANDARD PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 15 MIN
PUMP THRESHOLD 10.00%
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
AN14 TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 15 MIN
PUMP THRESHOLD 10.00%
LEAK TEST METHOD
TEST 014 DATE : ALL TANK
JAN 29. 2009
START TIME : 12:00 AM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
LEAK TEST REPORT FORMAT
NORMAL
LIQUID SENSOR SETUP
L 1:67 1
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 2:87 2
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
T 3: UL PREMIUM
PRODUCT CODE 3
THERMAL COEFF :.000700
TANK DIAMETER 92.00
TANK PROFILE 4 PTS
T 2:UNLEADED R FULL VOL 11627
PRODUCT CODE 1 69.0 INCH VOL 9438
THERMAL COEFF :.000700 46.0 INCH VOL 5814
TANK DIAMETER 92.00 23.0 INCH VOL 1170
TANK PROFILE 4 PTS
FULL VOL
69.0 INCH VOL
11627
9438 FLOAT SIZE: 3.0 1N,
46.0 INCH VOL
23.0 INCH VOL 5814
2190 WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
FLOAT SIZE: 3,0 IN. MAX OR LABEL VOL: 11627
OVERFILL LIMIT 90%
WATER WARNING 2,Q 10464
HIGH WATER LIMIT: 3.0 HIGH PRODUCT 9
110455
MAX OR LABEL VOL: 11627 DELIVERY LIMIT 10%
OVERFILL LIMIT : 90% 1162
HIGH PRODUCT 10464
95% LOW PRODUCT 500
LEAK ALARM LIMIT: 99
DELIVERY LIMIT 11045 SUDDEN LOSS LIMIT: 50
1162 TANK TILT 3.50
PROBE OFFSET 0.00
LOW PRODUCT 500LEAKALARMLIMIT:
SUDDEN LOSS LIMIT: 99 SIPHON MANIFOLDED TANKS
TANK TILT
PROBE OFFSET
50
4.50
T#: NONE
LINE MANIFOLDED TANKS0.00 Tit: NONE
SIPHON MANIFOLDED TANKST#: NONE
LINE MANIFOLDED TANKST#: NONE
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
AN14 TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 15 MIN
PUMP THRESHOLD 10.00%
LEAK TEST METHOD
TEST 014 DATE : ALL TANK
JAN 29. 2009
START TIME : 12:00 AM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
LEAK TEST REPORT FORMAT
NORMAL
LIQUID SENSOR SETUP
L 1:67 1
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 2:87 2
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
SENSOR ALARM -- - --
T, 1:8? 1
STP sump
FUEL ALARM 1:11 PMNOV30
SENSOR OUT ALARM Pd•1
NOV 30. 2011
FUEL ALARM 9:31 AMNOV30, 2011
ALARM HISTORY REPORT
SENSOR ALARM - --
L 2:87 2
STP SUMP
SENSOR OUT ALARM
NOV 30. 2011 9:46 AM
FUEL ALARM
NOV 30. 2011 9:31 AM
ALARM HISTORY . RI:pO r ..
L 3 1 STSENOR ALARMSTPgI' --
SENSORONOV30. 011. 9:46 AMFUELALANOV30, 011 9:30 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 4:87 ANN 1
ANNULAR SPACE
SENSOR OUT ALARM
NOV 30. 2011 9:46 AM
FUEL ALARM
NOV 30. 2011 9:36 AM
FUEL ALARM
NOV 30, 2011 9:35 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 5:87 ANN 2
ANNULAR SPACE
SENSOR OUT ALARM
NOV 30. 2011 9:46 AM
FUEL ALARM
NOV 30, 2011 9:37 AM
FUEL ALARM
NOV 30. 2011 9:37 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 6:91 ANN
ANNULAR SPACE
SENSOR OUT ALARM
NOV 30. 2011 9:46 AM
FUEL ALARM
NOV 30. 2011 9:38 AM
FUEL ALARM
NOV 30. 2011 9:38 AM
MONITOR CERT. FAILURE REPORT
S6N"'1
SITE NAME: DATE: 130 -1
ADDRESS: 9-- %Y `' 4ra J TECHNICIAN: RIME PWLLIPS
CITY: 1k1 J,
REPAIRS:
NONE
PARTS INSTALLED:
J
NONE
SIGNATURE:
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBII ITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.