Secondary Containment Testing Report Form
This form is intendedfor use by contractors performing periodic testing ofUSTsecondary containment systems. Use the
appropriate pages ofthisform to report resultsfor all components tested. The completedform, written test procedures, and
printoutsfrom tests (fapplicable), should beprovided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: OSWELL CHEVRON . Date of Testing: 10 -28 -10
Facility Address: 2700 OSWELL ST BAKERSFIELD, CA 93306
Facility Contact: Phone:
Date Local Agency Was Notified of Testing:
Name of Local Agency Inspector (fpresent during testing): ERNIE MEDINA
2. TESTING CONTRACTOR INFORMATION
Company Name: Rich Environmental
pass
Technician Conducting Test: RYAN MASON ICC# 8029371 -UT
Credentials: X CSLB Licensed Contractor D SWRCB Licensed Tank Tester
License Type: C61/D40 A HAZ
Manufacturer
License Number: 809850
Manufacturer Training
Com onen s ) Date Training Expires
1NCON TS -STS 8 -11 -11
Repairs
Made
UNL887 ANNULAR X
3. SUMMARY OF TEST RESULTS
Component pass Faii Not
Tested
Repairs
Made Component Pass Fail Not
Tested
Repairs
Made
UNL887 ANNULAR X UDC 7 -8 X
PREM91 ANNULAR X UNL87 FILL SUMP X
DIESEL ANNULAR X PREM91 FILL SUMP X D.
UNL87 SEC. PIPE X DIESEL FILL SUMP X
PREM91 SEC. PIPE X UNL87 VAPOR BUCKET X
DIESEL SEC. PIPE X PREM91 VAPOR BUCKET X
UNL87 STP X DIESEL VAPOR BUCKET X
PREM91 STP X
DIESEL STP X
UDC 1 -2 x
UDC 3-4 x 0
UDC 5-6 X
Ifhydrostatic testing was performed, describe what was done with the water after completion of tests:
RECYCLE AND REUSE
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best ofmy knowledge, thefacts stated in this document are accurate and infull compliance with legal requirements
Technician's Signature: Z,,--v Date: 10 -28 -10
0 0
SWRCB, January 2002
4. TANK ANNULAR TESTING
I el-
Page - of _7
Test Method Developed By: i I Tank Manufacturer X Industry Standard I Professional Engineer
l ' Other (Speck)
Test Method Used: 1.1 Pressure X Vacuum i I t lydrostatic
i.I Other (Specify)
Test Equipment Used: Equipment Resolution:
Is Tank Exempt From Testing ?'
Tank Capacity:
Tank # 87 Tank # 91 Tank # DIESEL Tank
X Yes I I No X Yes U No X Yes No
SINGLE.
I I Yes I I No
SINGLE SINGLE
Tank Material: WALL WALL WALI.
Tank Manufacturer: TANK TANK TANK
Product Stored:
Wait time between applying
pressure /vacuum/water and
starting test:
30MINS 30MINS 30MINS 30MINS
Test Start. Time:
Initial Reading (R,):
Test End Time:
Final Reading, (R,:):
Test Duration: 60 MINS 60 MINS 60 MINS 60MINS
Change in Reading (R,, -R,):
Pass. Fail Threshold or Criteria: 0" HG V HG 0" HG 0" HG
Test Resin "t Q Piss : ;t3'I+1 Pstss =rCJ Fail,' 0 Pass;.. C]: Fail D I?ass: D V it
Was sensor removed for testing ?. X Yes ! !No t I NA X Yes I! No ; 1NA X Yes I No ! iNA X Yes No I I NA
Was sensor properly replaced and.
verified functional after testing? X Yes `` =i No I NA X Yes 11 No 1.4 NA X Yes LNo I .NA X Yes !'No I NA
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
NOT TESTED SINGLE WALL TANKS
Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary
containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment
testing. (California Code of Regulations, Title 23, Section 2637(a)(6);
SWRCB, January 2002
5, SECONDARY PIPE TESTING
Page. . 3 of- 7-
Test Method Developed By: 1 Piping Manufacturer X Industry Standard' I Professional Engineer
1'!. Other (Specify)
Pest Method Used: X Pressure 1.1 Vacuum : I Hydrostatic
i I Other (SpeciifY)
Test Equipment Used: Equipment Resolution: _
Piping Material:
Piping Run # 87 Piping Run # 91 Piping Run # DSL Piping Run #
FIBERGLASS FIBERGLASS FIBERGLASS
Piping Manufacturer: SMITH SMITH SMITH
4,; —•—
200'
Piping Diameter: 4,. 4,.
Length of Piping Run: 200' 200'
Product Stored:
Method and location of
piping-run isolation:
UNL87
BOOT IN.SUMP
PREM91
BOOT IN SUMP
DIESEL
BOOT 1N SUMP BOOT IN SUMP
Wait time between applying
pressure /vacuum /water and
starting test:
30 MINS 301MINS 30 MINS 30 MINS
Test Start Time: 9:30AM 9:30AM 9:30AM
Initial Reading (R,): 5 PSI 5 PSI 5 PSI .
Test End Time: 10:30AM 10:30AM . 10:30AM
Final Reading (R,:): 5 PSI 5 PSI 5 PSI
Test Duration: 60 MINS 60 MINS 60 MINS 60 MINS
Change in Reading (Ri -R,): 0 PSI . 0 PSI 0 PSI
Pass/Fail Threshold or
Criteria: O PSI 0 PSI 0 PSI U PSI
Tlest Result: ' X P Ss QFa 1 X f' ss i t7 Fait :! X :::Pass Fail:. D. :Pass Et Fail
Comments — (include information on repairs made prior to testing, and recommended.jolloia, -up fi)rfailed tests) _
SWRC13,1anuary 2002
6. PIPING SUMP TESTINC
7S (LL
Page. 4 of 7
Test Method Developed By: I I Sump Manufacturer X Industry Standard i I Professional Engineer
w
1 Other (Spec)
Test Method Used: I i Pressure i I Vacuum X Hydrostatic
I I Other (Specify)
Test Equipment Used: iNCON Equipment Resolution: ,002"
Sump Diameter:
Sump # 87 Sump# 91 Sump # DSL Sump #
48" 48" 48"
Sump Depth: 53" 53" 53"
Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS.
Height from Tank Top to Top of
Highest Piping Penetration: 24" . 24" 24"
I leight from Tank Top to Lowest
Electrical Penetration: 26" 26" 26"
Condition of sump prior to testing: CLEAN CLEAN CLEAN
Portion of Sump Tested' 2.6 26" 26"
Does turbine shut down when
sump sensor detects liquid (both
product and water)?
X Yes .,I No I .I NA X Yes L I No I: I NA X Yes I ; No U NA I I Yes I No I ' NA
Turbine shutdown response time 5 SEC 5 SEC 5 SEC
Is system programmed for:fail -safe
shutdown?* . X Yes i 1 No t.! NA X Yes i. I No ! `NA X Yes I No I .I NA i Yes I ' No I ; NA
Was fail -safe verified to he
operational ?
o X.Yes !.I No I I NA X Yes . t I No l .! NA X Yes I ! No i ! NA Yes I : No I I NA
Wait time between applying
pressureivacuum /water and starting
test:
30 MINS. 30 MINS 30 MINS 30 MINS
Test Start Time: 12:15P .M 12:31PM 11:21AM I I:39AN1 10:30AM 10 :47AM
Initial Reading (R,): sA(AIN 5.4641N 4A341N 4.4341N 55071N 5.5071N
Test End Time: 12:30PM 12:46PM 11:36AM 11:54AN1 10.45AM 11:03,%N1
Final Reading (R,:): 5.4651N 5.4641N 4.4331N 4.4331N 5.5081N. 5.508IN
Test Duration: 15MINS . 15NIINS 15MINS 15MINS ISMINS 15MINS 15MINS 15NIINS C
Change in Reading (R, : -R,): 001IN .0001N 0011N 0011N AIII IN 0011N
Pass /Fail Threshold or Criteria: 0021N .0021N 0021N 0021N 0021±5 0021N 0021N 0021'N
j
Testesut 4X Isass ,Q,FiI`: 7{' Past :::, 0 iFali' X Pass:: L7Fai1 Pass U;ai.l
Was sensor removed for testing? X Yes ' Il No f I NA X Yes ' ,)No f ' NA X Yes 1 !No i I NA X Yes ].!No , NA
Was sensor properly replaced and
verified functional after testin ? X Yes., I :1 No I NA X Yes '.'INo I I NA X Yes 11No : INA X Yes i 1No NA
Comments — (include information can repairs made ,prior to !sling; and recommended Jallorr-up for fulled tests)
If the entire depth ofthe sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an
asterisk ( *) is "NO" or "NA ", the entire sump must be tested. (See SWRCB LG -160) .
SWRCB, January 2002
7. 11N1)FR= n1SPF.N1.9FR CONTAINMFNT (110CI TFCT(Nf:
66 Z Z-Z-
Page _ 5 of - 7.
test Method Developed By: I.1 UDC Manufacturer X Industry Standard ': I Professional Engineer
i-1 Other (Speci))
Test Method Used: I I Pressure l : vacuum X I lydrostatic
I. i Other (.Spec)
Test Equipment Used: INCON EEquipment Resolution: .002"
UDC # 1 -2 UUDC # 3 -4 UU DC # 5 -6 UUDC # 7 -8
UNKNOWN UUNKNOWN UUNKNOWN UUNKNOWNJOCManufacturer: U
UDC Material: FFIBERGLASS FFIBERGLASS FFIBERGLASS FFIBERGLASS
UDC Depth: 228" . 228" 228" 228"
Height from UDC Bottom to Top . 8;, 88„ 88" 88 ' of Highest Piping Penetration :.
6" . Ileight from UDC Bottom to 6 b - Lowest Electrical Penetration: 6" 66' b
Condition of UDC prior to CCLEAN CCLEAN CCLEAN CCLEAN
testin,:
Portion of U DC "Tested 110" 110" 110" 110"
Does turbine shut down when
UDC sensor detects liquid (both XX Yes .I No L.1 NA XX Yes :J No t NA XX Yes : i No ' ; NA XX Yes : INo I.± AN
roduct and water)"` -
Turbine shutdown response time 55 SEC 55 SEC S 5 SEC;
Is system programmed for fail-
Comments - (include: information on repairs made prior to leslii g, and recommended follow -upforfailed le_ts} _V ,
If the entire depth ofthe UDC is not tested, specify how much was tested. If the answer to any of the. questions indicated with an
asterisk ( *) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160)
SWRCB, January 2002
R_ F'11,1,11IRVR CONTAINMENT SIIMP TF'CTINC:
t)b k cz_: 1Page, G_ of - 7
Facility is Not Equipped With Fill Riser Containment Sums LI
Fill Riser Containment Sumps are Present, but were Not Tested ;
Test Method Developed By: 1.? Sump. Manufacturer X Industry Standard I Professional Engineer 1
i I Other (Specify)
Test Method Used: 1 Pressure t I Vacuum X Hydrostatic
I Other. (Specif ) _
test Equipment Used: INCON. Equipment Resolution: .002"
Fill Sump # 87 Fill Sum # 91 Fill Sump # DSL Fill Sump #
Sump Diameter: 42" 42" 42"
Sump Depth: 52" 52" 52"
Height from Tank Top to Top of, 24" 24" 24"
Hi hest Piping Penetration:
Height from Tank lop to Lowest
Electrical Penetration: 28" 28" 28"
Condition of sump prior to CLEAN CLEAN CLEANtesting:
Portion of Sump Tested 26" 26" 26"
Sump Material: FIBERGLASS . FIBERGLASS FIBERGLASS
Wait time between applying
pressurervacuum /water and. 30MINS . 30MINS 30MINS 30MINS
starting test:
Test Start Time: 11:214M 11:39AM 10 :30AM 10:47AM 9e-42AM 9:57AM
Initial Reading, (R,): 3.986IN 3.989IN . 3.0031N 3.0031N 4.1751N 4.1751N
Test End Time: 11:36AM 11:54AM 10:45AM 11:03AM 9:57AM I0:12AM
Final Reading R +): 3.9871N 3.990IN 3.0031N 3.0031N 4.175IN 4.1751N
Test Duration: 15MINS 15MINS 15MINS 15MINS 15MINS IWINS I NINS 15MINS
Change in Reading (R1 -111): 0011N 0011N. 0001N MOIN 0001N 0001N
Pass/Fail Threshold or Criteria: 0021N 0021N 002IN 0021N 0021N 0021N ot121N oo21N
Test 12esult Ofat] Kass :: Fail :.
Is there a sensor in the sump? X Yes I No X Yes l.; No X Yes 1 ! No X Yes No
Does the sensor alarm when
either product or water is X Yes I1 No F1 NA' X Yes PNo ! !NA X Yes ' 1 No ;NA X Yes i I No !:NA
detected?
Was sensor removed for testing? X Yes CI No L.I NA X Yes I "INo t. NA X Yes ; INo I tNA X Yes i INo !'NA
Was sensor properly replaced and
verified functional after testing? X Yes t.. No P NA X Yes .INo L:: ?NA X Yes ! 'No I INA X Yes '. No I!NA
Comments — (include irrfortnation on repairs made prior to lesling, and recommendedfollow -terpalled 1cst,S%
SWRCB, January 2002.
9. SPILL/OVERFILL CONTAINMENT BOXES
j f LL
Page _ 7_ of 7_
Facility is Not Equipped With Spill /Overfill Containment Boxes
Spill /Overfill Containment Boxes are.Present, but were Not Tested
Test Method Developed By: r; Spill Bucket Manufacturer . I I Industry Standard .1 Professional Engineer
I. I Other ( Specif})
Pest Method Used: ;" I Pressure I : Vacuum i Hydrostatic
I I Other (.Specify)
Test Equipment Used: Equipment Resolution:
Bucket Diameter:
Spill. Box # 87 VPR Spill Box #91 VPR Spilt Box # DSL VPR Spill Box #
12" 12" 12"
Bucket Depth: 16" 16" I6"
Wait time between applying
pressure /vacuum /water and
starting test:
30MINS 30MINS 30MINS 30MINS
test Start Time: 10:30AM 10:47AM 9 :42AM 9 :57AM 9:42AM 9:57AM
Initial Reading (R,): 5.6801N .5.6801N 4.7481N 4.7471N 6.2431N 6.2431N
Test End Time: 1.0:45AM 1 1:03AM 9;57AM 10:12AM 9:571M 10:12AM
Final Reading (110. 5.680IN 5.680IN 4.747IN 4.7461N 6.2431N 6.2431N
Test Duration: ISMINS ISMINS ISMINS 15MINS 15MINS 15MINS 15MINS 1541I N5
Change in Reading (R,wR,): 001 IN .0001N 0011.N oonN AOOIN 000114
Pass/Fail Threshold or
Criteria: 0021N 0021N 0021N A021N 0021N O(121N 102IN .0021N
Test Resr,li X Pass ail X P9SS 0:2i V Pas$ ' :El Fail 63 pass. ' 11 Fail
Comments -- (include information on repairs madeprior io testing, and recommended follow -upfqrfailed tests)
t2iZ.'
OSWELL CHEVRON
O8WELL CHEVRON 2700 OSWELL
2700 OSWELL BAKERSFIELD
BAKERSFIELD
10.282010 1h: i3 AM
10/28/25i0 9:57 AM
SUMP LEAK TEST REPORT
SUMP LEA!{ TEST REPORT'
GSLkiPR
DSLVPR
TEST STARTED 9:57 AM
TEST STARTED 9:42 AM TEST STARTED 10/28/2010
TEST STARTED 10282010 BEGIN LEVEL 6.2436 IN
LEVEL 6.
9438
AM END TIME 101-12 AM,
END TIMEEND END DATE 10/28/2010
ENV) DATE 10/292010 END LEVEL 6.2434 IN
END LEVEL 6.2435 IN LEAK THRESHOLD 0.002 IN
LEAK THRESHOLD 0.002 IN TEST RESULT PASSED
TEST RESULT PASSED
91VPR
91VPR
TEST STARTED 9:57 AM
TEST STARTED 9:42 AM TEST STARTED 10/28/2010
TEST STARTED 10/28/2010 BEGIN LEVEL__. 4.7475_IN _
BEGIN LEVEL 4.7481 IN END TIME 10:12 AM
END TIME 9- 57 AM END DATE 10/28/2010
END DATE 10/28/2010 END LEVEL 4.7468 IN
END LEVEL 4.7475 IN LEAK THRESHOLD 0.002 IN
LEAK THRESHOLD 0.002 IN TEST RESULT PASSED
TEST RESULT PASSED
87VPR
8?UPR
TEST STARTED 9:57 AM
T TARTER 9. TEST STARTED 19/28/2010
T RTED 1 10 BEGIN LEVEL 4.9422 IN
BEG 46 IN END TIME 10:12 AM
END TIME 9:57 AM END DATE 10/28/2010
END DAM 010 END LEVEL 4.9418 IN
END 4• LEAK THRESHOLD 0.862 IN
LE .RESHOLD 0.062 TEST RESULT PASSED
RESULT INCREASED
DSLFSMP
DSLFSMP
TEST STARTED 9:57 AM
TEST STARTED 9:42 AM TEST STARTED 10/28/2010
TEST STARTED 10/28/2010 BEGIN LEVEL 4.1753 IN
BEGIN LEVEL 4.1755 IN END TIME 10:12 AM
END TIME 9'57 AM END DATE 10/28/2010
END DATE 10/28/20.10 END LEVEL 4.1751 IN
END LEVEL 4.1753 IN LEAK THRESHOLD 0.002 IN
LEAK THRESHOLD 0.602 IN TEST RESULT PASSED
TEST RESULT PASSED
OSWELL CHEVRON
2700 OSWELL
86KERSF IELD
1 w1"28120 10 11:36 Atn
SUMP LEAK TEST REPORT
91STP
TEST STARTED 11:21 AMTESTSTARTED16/28/2610BEGINLEVEL4.434/ .INENDTIME11:36 AMENDDATE10/28/2010ENDLEVEL4.4339 IN
LEAK THRESHOLD 0.002 INTESTRESULTPASSED
87FSNP
TEST STARTED 11121 AM
TEST STARTED 16/28/2010
BEGIN LEVEL 3. %65 IN
END TIME 11:35 AM
END DATE 16/28/2010
END LEVEL 319874 IN
LEAK THRESHOLD 61.002 INTESTRESULTPASSED
OSWELL CHEVRON
2700 OSWELL
BAKERSFIELD
10/28/2010. 11:54 AM
SUMP LEAK TEST REPORT
91STP
TEST STARTED 11:39 AMTEST .STARTED 16120/2010
BEGIN LEVEL 4.4334 INENDTIME11:54 Ali
END DATE 16/28/2010
END LEVEL 4.4,'031 IN
LEAK THRESHOLD 0.802 INTESTRESULTPASSED
87FSMP
TEST STARTED 11:39 AMTESTSTARTED10/28/2010
BEGIN LEVEL. 3.9893 INENDTIME11:54 AMENDDATE28/28!2010ENDLEVEL3.5901 IN
LEAK THRESHOLD 0.002 INTESTRESULT ' PASSED.
OSWELL CHEURC0
2700 OSWELL
BAKERSFIELD
10/28/2010 i1:03 AM
SUMP LEAK TEST REPORT
DSLSTP
TEST STARTED 10:47 AM
TEST STARTED 16/28/2010
BEGIN LEUEL 5.5081 IN
END TIME 11:03 Ali
6D DATE to/28/2610
END LEVEL 5.5081 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED
91FSMP
TEST STARTED 10 :47 AM
TEST STARTED 101281"1010
BEGIN LEVEL 3.0036 IN
END TIME 11:03 AM
END DATE 10/28/2010
END LEVEL 3.0037 IN
LEAK THRESHOLD 0.00: IN
TEST RESULT PASSED
87UPR
TEST STARTED 10:47 AM
TEST STARTED 10/28/2016
BEGIN LEVEL x.6886 IN
END TIME 11:03 AM
END GATE 10/28/2010
END LEVEL 5.6508 IN
LEAK THRESHOLD 9,002 IN
TEST RESULT PASSED
SWELL CHEVRON2700OSWELL
9AKERSFIELD
10/28/201)-4 1@:46 AN.
SUMP LEAK TEST REPORT
DSLsTF'
TEST STARTED 10:30 AMTESTSTARTED10/20/2010BEGINLEVEL5.5078 INENDTIME10:4` AmENDDATE10/23/2020ENDLEVEL5.5080 INLEAKTHRESHOLD0.002 INTESTRESULTPASSED
91FSMP
TEST STARTED
TEST STARTED 10:36 AM
18/28/2010BEGINLEVEL
DID TIME 3.0034 IN
END DATE 10;45 AM
10/28/2010ENDLEVEL
LEAK THRESHOLD 3.0035 IN
6.002 INTESTRESULTPASSED
87UPR
TEST STARTED 10 :36 AMTESTSTARTED
BEGIN LEVEL 1012EV2010
5.6818 INENDTI.Me.
END DATE 10:45 Am
10128/2010ENDLEVEL
LEAK THRESHOLD 5.6807 IN
0.002 INTESTRESULTPASSED
TEST STARTED 2:53 PM
TEST STARTED 16/28/2010 3-4
SWELL +.HEVRON
BEGIN LEVEL .
END TIME
3.6290 IN
3:08 PM
276E DSIELD
TEST STARTED
OSWELL CHEVRON i AKERSFIcLO
16/28/2010
2700 OSWELL
TEST STARTEDBENIN 16/28/2010
BAKERSFIELD 10/28/2010 1:57 PM
IDSWEiL CHEVRON, LEVEL
END TIME 3.6658 IN
OSWELL CHEVRON
0/28/20le 3 :88 Pm SUMP LEAK TEST REPORT 2790 05WELL.
12 :30 PM
TEST RESULT
BRKERSFIELD
SUMP LEAK TEST REPORT 2 16/28 ./2816
TEST STARTED 10/26/20lq
12: 30 PPt
5 -6 TEST STARTED 1:42 PM
TEST UMP LEAK TEST REPORT
TEST STARTED 2:53 PM BEGIN 5.9642 IN
TEST RESULT
TEST STARTED 16/28/2010 c'OEL
END TIME 1:57 PM 8?STP
BEGIN LEVEL 4.1461 IN END DATE 10/28/2610 TEST STARTEDENDTIME3:08 PP1 END LEVEL 5.9631 IN 22:15 PMTESTSTARTEDENDDATE10/28/2019 LEAK THRESHOLD 9.602 10/28/2610BEGINLEVELENDLEVEL4.1445 IN EESTRESULTPASSED 5, END TIME 4640 INLEAKTHRESHOLD8.002 IN END DATE 12:36 PMTESTRESULTPASSED
END LEVEL 16/28/2010
70,T STARTED 16/28/2010
5.4654 INLZAKTHRESHOLD0.002 IN7 -8 ST RESULTTEST PASSED
TEST STARTED 2:53 PM
TEST STARTED 16/28/2010 3-4
END DATE 10/28/2019
BEGIN LEVEL .
END TIME
3.6290 IN
3:08 PM
50.002
TEST STARTED 12:15 PNi
END DATE 16/28/2010
16/28/2610 3 :27 PM
TEST STARTEDBENIN 16/28/2010ENDLEVEL3.6272 IN IDSWEiL CHEVRON, LEVEL
END TIME 3.6658 INLEAKTHRESHOLD6.002 IN 2706 OSWELL END DATE 12 :30 PM
TEST RESULT PASSED BAKERSFIELD
END LEVEL 102616
TEST STARTED 10/26/20lq
18/28/201 -0 2:32 Ph LEAK THRESHOLD 3.6844 IN
0.802 IN
TEST STARTED
TEST RESULT PASSED
16/28/2616BEGINLEVEL
SUMP L >_AK. TEST REPORT
5.4646 INENDTIME
1 -2
TEST STARTED 2:1.7 P(M
TEST STARTED 10/28/2010
BEGIN LEVEL 5.5604 IN
OSWELL CHEVRON END TIME 2:32 PM
2760 OSWELi END DATE 10/28/2019
BAKERSFIELD 50.002
LEAKGLEVEL
HRES,HOLD IN OSWELL CHEURON
16/28/2610 3 :27 PM TEST RESULT PASSED 2790 OSWELLSAKERSFIELD
SUMP LEAK TEST REPORT 10/28/2010 0L:4E PM
5-6
SUMP LEAK TEST REPORT
EST STARTED 3 :11 PM
TEST STARTED 10/26/20lq 87STP
BEGIN LEVEL 4.1432 IN TEST STARTEDENDTIME3:27 PM 12:31 PMTESTSTARTEDENDDATE16/28./2018 16/28/2616BEGINLEVELENDLEVEL4.1426 IN 5.4646 INENDTIMELEAKTHRESHOLD0.602 IN 12:46 PMENDDATETESTRESULTPASSED18/28/2816ENDLEVEL5.4649 INLEAKTHRESHOLD
8 0.002 INTESTRESULTPASSED
TEST STARTED 3:11 Ptl
70,T STARTED 16/28/2010 3 -4
r3E01K LEVEL 3.6272 IN TEST STARTED
END DATE 10/2R/2010 TEST STARTED 160604181
BEGININ +_EUfI. 3.6268 IN LEVEL 1 3.6044 IHENDTIMELEAKTHRESHOLD9.002 IN END DATE 12'46 PM
TEST RESULT PASSED END LEVEL 10/28 /2010
LEAK THRESHOLD 3.8035 IN
8'82 INTESTRESULTPASSED
SB989 TESTING FAILURE REPORT A
SITE NAME: OSWELL CHEVRON DATE: 10 -28 -10
ADDRESS: 2700 OSWELL ST TECHNICIAN: aYAN MA ON
CITY: BAKERSFIELD SIGNATURE:
1&4
REPAIRS:
NONE
PARTS INSTALLED:
NONE
NAME: TITLE:
SIGNATURE:
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY .OF NOTIFYING THE
APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR THE
ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTA.L FOR ANY
NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF ANY FINES
OR PENALTIES OCCURING.FROMNON- COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON-SITE FOR YOUR CONVIENENCE.