HomeMy WebLinkAbout2701 MING AVENUE (27)ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended bv CCR Title 19
Date Of Inspection, Testing, Maintenance: 11/30/2011 System Riser ID: 2485
Property Information:
Frequency Description
Type Of System: F CACName: Red Robin #244 x Wet Pipe Q
o 0
Address: 2701 Ming Ave Dry Pipe ,
1
lp
Preaction /terQ
Deluge .E"Mp
City: Bakersfield
12.4.3.1
Main Drain Test Results:
Initial Static Pressure: 70 (psi)
Residual Pressure: 60 (psi)
Restored Static Pressure: 70 (psi)
Abbreviation Key:
I = Inspection
T =Test
M = Maintenance
A -O = After Operation
MI = Per Manufacturer's Instructions
Item Activity Frequency Description NFPA 25
Reference Fail N/A Pass
1.1 1 Daily
Weekly
Preaction /Deluge Valves - Enclosure
temperature
12.4.3.1 X
1.2 I Daily
Weekly
Dry Pipe Valves - Enclosure
temperature
12.4.4.1.1 X
1.3 1 Quarterly
Gauges - (Dry, Preaction, Deluge
Systems)
5.2.4.2
5.2.4.3 X
1.4 1 Quarterly Control Valves 12.3.2.1 X
1.5 1 Quarterly Alarm Devices 5.2.6 X
1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X
1.7 1 Quarterly Hydraulic nameplate 5.2.7 X
1.8 1 Quarterly Pipe and Fittings 5.2.2 X
1.9 1 Quarterly Sprinklers 5.2.1 X
1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X
1.11 I Quarterly Fire Department Connections 12.7.1 X
1.12 I Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X
1.13 1 QuarterlyQuarter) Preaction /Deluge Valves - Exterior
Inspection 12.4.3.1.6 X
1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X
1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X
1.16 1 Quarterly Backflow Preventers 12.6.1 X
1.17 1 Annual Buildings 5.2.5 X
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended bv CCR Title 19
Frequency
Date Of Inspection, Testing, Maintenance: 11/30/2011 System Riser ID: 2485
Fail
Property Information:
Pass
Type Of System:
1
Name: _Bed Robin 244 Wet Pipe
yQ — Tc0Q. q
Address: 2701 Ming Ave Dry Pipe y
Annually Seismic Braces
Preaction
X
Deluge
I
City: Bakersfield
Hangers (Accessible concealed spaces) 5.2.3.3
Item Activity Frequency Description
NFPA 25
Reference Fail N/A Pass
1.18 1 Annually Hangers 5.2.3 X
1.19 I Annually Seismic Braces 5.2.3 X
1.20 I 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X
1.21 I 5 Years Seismic Braces (Accessible concealed
spaces)
5.2.3.3 X
1.22 1 5 Years Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3 X
1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X
1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X
1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X
1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X
1.27 1 5 Years Preaction /Deluge Valves - Interior
Inspection 12.4.3.1.7 X
1.28 1 5 Years Preaction/Deluge a ves - trainers,
filters, orifices 12.4.3.1.8 X
1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X
1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X
2.1 T Annually Alarm Devices (90 Sec) 5.3.3
12.2.7 X
2.2 T Annually Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3 T Annually Antifreeze Test 5.3.4 X
2.4 T Annually Control Valve - Position 12.3.3.1 X
2.5 T Annually Control Valve - Operation 12.3.3.1 X
2.6 T Annually Supervisory 12.3.3.5 X
2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X
2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X
2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 11/30/2011 System Riser ID: 2485
Property Information: Type Of System: F Cqo
Name: Red Robin #244 Wet Pipe ' :'°o,
Address: 2701 Mina Ave E] Dry Pipe
Preaction 4 P
Deluge iqEMp;
City: Bakersfield
NFPA 25
Item Activity Frequency Description Reference Fail N/A Pass
2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X
2.11 T Annuallyy ry Pipe Valve - Low Air Pressure 12.4.4.2.6 XAlarm
2.12 T Annuallyy ry Pipe Valve - Quick- Opening 12.4.4.2.4 XDevice
2.13 T Annually Dry Pipe Valve - Trip Test 12.4.4.2.2 X
2.14 T Annually Backflow Preventor Assemblies 12.6.2 X
2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X
2.16 T 5 Years Gauges 5.3.2 X
2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X
2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X
2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X
2.20 T 5 Years Sprinklers - Corrosive environment or 5.3.1.1.2 X
corrosive water
2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X
2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X
2.23 T 50 Years Sprinklers 5.3.1.1.1 X
2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X
2.25 T Sprinklers manufactured prior to 1920 5.3.1.1.1.1 X
Replace
3.1 M Annually Control Valves 12.3.4 X
3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X
3.3 M Annually Dry Pipe Valves /Quick- Opening 12.4.4.3.2 XDevices
3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X
3.5 M 5 Years Obstruction Investigation Chapter 13 X
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended bv CCR Title 19
Date Of Inspection, Testing, Maintenance:
Property Information:
Name: Red Robin #244
Address: 2701 Ming Ave
City: Bakersfield
11/30/2011 System Riser ID:
Type Of System:
x Wet Pipe
Dry Pipe
Preaction
E] Deluge
2485
pF Cq
ov9
9°
RE M
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
See Continuation Page(s)
x PASS
FAIL
Indicate the number of continuation pages)
1 11/30/2011
Signature Date
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5