January 27, 2011
VIA FED EX: 7931 2184 4292
Bakersfield Fire Department
2101 H Street
Bakersfield CA 93301
Re: Monitoring System Certification
Spill Bucket Testing
Pacific Bell Telephone Co. dba AT &T California
3221 S. H STREET, BAKERSFIELD, CA
CEOPAR: SA098
To Whom It May Concern:
Pd- SS
213! Dupwo LJure. Aw hr i n, CFA 92 06
Enclosed are the results for the following tests completed on January 10, 2012:
Monitoring System Certification Report Form
Spill Bucket Testing Report Form
Please do not hesitate to call me if you have any questions.
4Ve r You rs,
w L. Denison
Program Manager
CA UCf 596099 ; AZ 41C 095984 i NV hCA 0049665 1 TX til,4 CR0000041
Appendix V1
Copies of Monitoring System Certification form and USTMonitoring Plot Plan available at http: / /www.waterboards.ca.gov .)
MONITORING SYSTEM CERTIFICATION
For Use ByAll Jurisdictions Within the State ofCalifornia
Authority Cited. Chapter 6.7, Health andSafety Code, Chapter 16, Division 3, Title 23, California Code ofRegrdations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator
owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: Pacific Bell Telephone Co. dba AT &T California Building No.: SA098
Site Address: 3221 S. H STREET City: Bakersfield Zip: 93304
The
Facility Contact Person: Grant Anmstrong
Make /Model of Monitoring System: Veeder- Root/TLS -350
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to indicate specific equipment inspected
Tank ID: SA098U001
Contact Phone No.: (661) 327 -6903
Date of Testin g/S ervicing: 1/10/2012
serviced:
Tank ID
F_ In -Tank Gauging Probe. Model: 847390 -107 r In -Tank Gauging Probe. Model:
F Annular Space or Vault Sensor. Model: 794390 -420 F Annular Space or Vault Sensor. Model:
Piping Sump/ Trench Sensor(s). Model: 794380-208 r Piping Sump/ Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: 794380 -208 r Fill Sump Sensor(s). Model:
F Mechanical Line Leak Detector. Model: r Mechanical Line Leak Detector. Model:
F Electronic Line Leak Detector. Model: r Electronic Line Leak Detector. Model:
r Tank Overfill / High -Level Sensor. Model: 790091 -001 r Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). r Other (specify equipment type and model in Section E on Page 2).
Tank 1D: Tank ID:
F In -Tank Gauging Probe. Model: r In -Tank Gauging Probe. Model:
r Annular Space or Vauh Sensor. Model: r Annular Space or Vault Sensor. Model:
r Piping Sump/ Trench Sensor(s). Model: r Piping Sump/ Trench Sensor(s). Model:
F Fill Sump Sensor(s). Model: r Fill Sump Sensor(s). Model:
r Mechanical Line Leak Detector. Model: r Mechanical Line Leak Detector. Model:
F Electronic Line Leak Detector. Model: r Electronic Line Leak Detector. Model:
IF Tank Overfill/ High -Level Sensor. Model: r Tank Overfill/ High -Level Sensor. Model:
i r Other (specify equipment type and model in Section E on Page 2).
Dispenser
r Other (specify equipment type and model in Section E on Page 2).
ID: Dispenser 1D: :
W..
F Dispenser Containment Sensor(s). Model: r Dispenser Containment Sensor(s). Model:
F Shear Valve(s). r Shear Valve(s).
F Dispenser Containment Float(s) and Chain(s).
v_ _. ___
r Dispenser Containment Float(s) and Chain(s).
Dispenscr ID: Dispenser ID:
F Dispenser Containment Sensor(s). Model: r Dispenser Containment Sensor(s). Model:
F Shear Valve(s). r Shear Valve(s).
F Dispenser Containment Float(s) and Chain(s) r Dispenser Containment Floats) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is correctand
a Plot Plan showing the layout of monitoring equipment For any equipment capable of generating such reports, I have also attached a copy of
the report; (check all that apply) : P System set -up r Alarm history report
Technician Name (print): Adolfo Aguilar
Signature: 4
Certification No.: A20066 License. No.: 588098
Testing Company Name: TAIT ENVIRONMENTAL SERVICES Phone No.: 714560 -8222
Testing Company Address: 2131 sOUTttoUPONTMfVF ANAHEIM,cA92806 Date ofTesting/Sery icing: 1/10/2012
D. Results of Testing /Servicing
Software Version Installed: 324.01
Complete the following checklist:
Yes F No* Is the audiblealann operational?
Yes r No* Is the visual alarm operational?
EKYes_ F No* Were all sensors visually inspected, functionally tested, and confinned operational?
Yes r No* Were all sensors instal led at lowest point of secondary containment and positioned so that other equipment
will not interfere with their
proper operation?
F Yes F No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem)
r N/A operational?
r No* For pressurized piping systems, does the turbine automatically shut down ifthe piping secondaryYes
containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: whichN/A sensors initiate positive shut -down? (Check all that apply)
F Sump/Trench Sensors; r Dispenser Containment Sensors. Did you confirm positive shut -down
due to leaks and sensor failure /disconnection?
r Yes; (— No.
Yes N o* For tank systems that utilize the monitoring system as the primary tank overfill waming device (i.e. no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at theN/A tank fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger?
Yes* F No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
F Yes* r No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that
apply) r Product; r Water. If yes, describe causes in Section E, below.
Yes F No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
R_ Yes r No* Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Other sensors from page 1:
L4: Transition Sump Sensor 794380 -208 Certified.
L5: Piping Sump Sensor 794390 -420 Certified.
Fill Port With A Mechanical Overfill Prevention Drop -Tube Valve.
F. In -Tank Gauging / SIR Equipment:
F Check this box iftank gauging is used only for inventory control.
F Check this box if no tank gauging or SIR equipment is installed.
This section mustbe completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
r No* Has all input wiring been inspected for proper entry and termination, including testing for grownd faults? ffFY
No* Were all tank gauging probes visually inspected for damage and residue buildup?
F Yes
r No*
r No *
Was accuracy of system product level readings tested?
Was accuracy of system level readings tested? Y Y g. sted?
F Yes r No* Were all probes reinstalled properly?
F Yes r No* Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how andwhen these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): r Check this box if LLDs arenot installed.
Complete the following checklist:
F Yes r No* For equipment start -up orannual equipment certification, was a leak simulated to verify LLD performance ?(Check
F N/A n!lthatapply) Simulated leak rate: r 3gp.h.; r 0.1g.p.h; r 0.2g.p.h.
r Yes r No* Were all LLDs confirmed operational and accurate within regulatory requirements?
r Yes r No* Was the testing apparatus properly calibrated?
r Yes r No For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
F N/A
F Yes r No* Forelectronic LLDs, does the turbine automatically shut offifthe LLDdetects a leak?
F N/A
F Yes r No* Forelectronic LLDs, does the turbine automatically shut off i fany porti on of the monitoring system is disabled or
F N/A disconnected?
r Yes r No* Forelectronic LLDs, does the turbine automatically shut off ifany portion of the monitoring system malfunctions or
F N/A fai Is a test?
F Yes r No* Forelectronic LLDs, have all accessiblewiring connections been visually inspected?
r N/A
F Yes r No* Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
ion System.
LIST Monitoring Site Plan
Site Address: 3222 IS. H STREET, Bakersfield, 93304
r at &t Monitoring Plan Site Map
b'att'ing NOT to Scafe
Busi ')ess Name, Pacific Hell Telephone Co. diva AT &T Cal_ ,SA098)
Bti iness Address: 32'1 S. H Street Bd..ersfield
7aP. err.:
e'd 5
Pining Far
vr9
C•E IL2 f
I' 1 LII41 i
Date map was drawn: 1/10/2012
Instruetinns
N
rr
d
N
N
St +E
S
Ifyou already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System
Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if
installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other
secondary containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the
space provided, note the date this Site Plan was prepared.
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUSTspill containment structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to the facility owner /operatorfor submittal to the local regulatory agency.
FACILITY INFORMATION Facility ID: SA098
Facility Name: Pacific Bell Telephone Co. dba AT &T California Date of Testing: l /10/2012
Facility Address: 3221 S. H STREET, Bakersfield, CA 93304
Facility Contact: Grant Armstrong Phone: (661) 327 -6903
Date Local Agency Was Notified of Testing: 12/19/2011
Name of Local Agency Inspector (ifpresent during testing): Esther Duran
TESTING CONTRACTOR INFORMATION
Company Name: TAIT Environmental Services, Inc.
Technician Conducting Test: Adolfo Aguilar
Credential t : F CSLB Contractor r ICC Service Tech. r SWRCB Tank Tester r Other (Specify)
License number(s): A B ASB C -10 HAZ License Number 588098 : ICC Technician 5238610
SPILL BUCKET TESTING INFORMATION
Test Method Used: r Hydrostatic r Vacuum r Other
Test Equipment Used: Visual,Measured & Marked Equipment Resolution: 1/16"
Identify Spill Bucket (By Tank
Number, Stored Product,etc. 1 SA0980001
Bucket Installation Type: r Direct Bury
r7l Contained in Sump
r On top of AST
r Direct Bury
r Contained in Sump
r On top of AST
r Direct Bury
r Contained in Sump
r On top of AST
r Direct Bury
r Contained in Sump
r On top of AST
Bucket Diameter: 11.00"
Bucket Depth: 14.50"
Wait time between applying
vacuum /water and start of test:
15 Minutes
Test Start Time (TI): 9:15 AM
Initial Reading(RI): 14.25"
Test End Time (TI;): 10:15 AM
Final Reading (RI;): 14.25"
Test Duration (TF —TI): 1 Hour
Change in Reading (RF -RI): 0
Pass /Fail Threshold or
Criteria:
0
Test Result: F171 Pass r Fail r Pass r Fail r Pass r Fail r Pass r Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -upfor failed tests)
Took Non-Haz. Test Water To TES (Contractor) Shop Properly Labled & Seared.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
hereby certify that all the information contained in this report is true, accurate, and infull compliance with legal requirements.
Technician's Signature: ,.
f ? --
Date: 1/10/2012
250301
JAN 16, 2012 12:50 PM
1:BKFDCAI4 SA098 S -S
I50302
JAN 16, 2012 12:50 PM
2:3221 S. H ST.
I50303
JAN 16, 2012 12:50 PM
3:BAKERSFIELD,CA 93304
I50304
JAN 16, 2012 12:50 PM
4:661- 832 -8370
I51700
JAN 16, 2012 12:50 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMAT
MON DD YYYY HH:MM:SS xM
ISOF00
JAN 16, 2012 12:50 PM
MON DD YYYY HH:MM:SS xM
I10200
JAN 16, 2012 12:50 PM
BKFDCA14 SA098 S -S
3221 S. H ST.
BAKERSFIELD,CA 93304
661 - 832 -8370
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 163785 161997
2 INTERSTITIAL BD 200879 199692
3 UNUSED 10306571 10229885
4 UNUSED 10265262 10222197
5 UNUSED 10261818 10219418
6 UNUSED 10249310 10215672
7 UNUSED 10253984 10227519
8 UNUSED 10247323 10214233
9 RELAY BOARD 14983 14988
10 UNUSED 10251789 10216694
11 UNUSED 10242063 10220538
12 UNUSED 10251033 10216931
13 UNUSED 10239736 10214487
14 UNUSED 10246737 10225171
15 UNUSED 10242820 10213225
16 UNUSED 10238506 10216773
COMM 1 FAXMODEM BOARD 40172 40118
COMM 2 UNUSED 10240833 10223199
COMM 3 UNUSED 10246661 10221760
COMM 4 UNUSED 10237503 10211825
COMM 5 UNUSED 10242385 10224421
COMM 6 UNUSED 10240341 10215236
El
I60100
JAN 16, 2012 12:50 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK #SA098U001 ON
2 OFF
3 OFF
4 OFF
I60200
JAN 16, 2012 12:50 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK #SA098U001
0.000450
2
0.000450
3
0.000000
4
0.000000
I60300
JAN 16, 2012 12:50 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
SIPHON MANIFOLDED TANKS
1 DIESEL TK #SA098U001 1
2 2
3 3
4 4
I60400
JAN 16, 2012 12:50 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA098U001 6016
2 5036
3 0
4 0
I60700
JAN 16, 2012 12:50 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK #SA096U001 95.75
2 92.00
3 0.00
4 0.00
I60900
JAN 16, 2012 12:50 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK #SA098U001 0.000450
2 0.000450
3 0.000000
4 0.000000
I61200
JAN 16, 2012 12:50 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS
1 DIESEL TK #SA098U001 NONE
2 NONE
3 NONE
4 NONE
I62100
JAN 16, 2012 12:51 PM
LINE MANIFOLDED TANKS
NONE
NONE
NONE
NONE
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL
1 DIESEL TK #SA098U001
2
3
4
162200
JAN 16, 2012 12:51 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL
1 DIESEL TK #SA098U001
2
3
4
I62300
JAN 16, 2012 12:51 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL
1 DIESEL TK #SA098U001
2
3
4
I62400
JAN 16, 2012 12:51 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL
1 DIESEL TK #SA098U001
Ll
I62800
JAN 16, 2012 12:51 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL
1 DIESEL TK #SA098U001
2
3
4
I62900
JAN 16, 2012 12:51 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL
1 DIESEL TK #SA098U001
2
3
4
Fl
I70300
JAN 16, 2012 12:51 PM
LIQUID TYPE
SENSOR LOCATION
1 ANNULAR SPACE SENSOR
2 FILL SUMP SENSOR
3 PIPING SUMP SENSOR
4 TRANSITION SUMP
5 PIPING PAN
6 ANNULAR SPACE
7
8
I90200
JAN 16, 2012 12:51 PM
SOFTWARE REVISION LEVEL
VERSION 324.01
SOFTWARE# 346324 -100 -B
GALLONS
2000
3000
0
0
GALLONS
4784
4784
0
0
GALLONS
4532
4532
0
0
INCHES
2.0
GALLONS
6016
5036
0
0
GALLONS
3000
3525
0
0
TYPE
TRI -STATE (SINGLE FLOAT)
TRI -STATE (SINGLE FLOAT)
TRI -STATE (SINGLE FLOAT)
TRI -STATE (SINGLE FLOAT)
TRI -STATE (SINGLE FLOAT)
TRI -STATE (SINGLE FLOAT)
TRI -STATE (SINGLE FLOAT)
TRI -STATE (SINGLE FLOAT)
CREATED - 03.11.10.17.15
5- MODULE# 330160 -002 -A
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
CSLD
I11100
JAN 16, 2012 12:51 PM
BKFDCAI4 SA098 S -S
3221 S. H ST.
BAKERSFIELD,CA 93304
661 - 832 -8370
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK #SA098U001 HIGH WATER ALARM CLEAR 1 -10 -12 9:43AM
T 1 TANK DIESEL TK #SA098U001 MAX PRODUCT ALARM CLEAR 1 -10 -12 9:43AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT CLEAR 1 -10 -12 9:43AM
T 1 TANK DIESEL TK #SA098U001 OVERFILL ALARM CLEAR 1 -10 -12 9:41AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT ALARM 1 -10 -12 9:41AM
T 1 TANK DIESEL TK #SA098U001 MAX PRODUCT ALARM ALARM 1 -10 -12 9:40AM
T 1 TANK DIESEL TK #SA098U001 OVERFILL ALARM ALARM 1 -10 -12 9:38AM
T 1 TANK DIESEL TK #SA098U001 OVERFILL ALARM CLEAR 1 -10 -12 9:37AM
T 1 TANK DIESEL TK #SA098U001 OVERFILL ALARM ALARM 1 -10 -12 9:36AM
L 5 PIPE PIPING PAN FUEL ALARM CLEAR 1 -10 -12 9:30AM
L 5 PIPE PIPING PAN FUEL ALARM ALARM 1 -10 -12 9:30AM
L 5 PIPE PIPING PAN FUEL ALARM CLEAR 1 -10 -12 9:30AM
L 5 PIPE PIPING PAN FUEL ALARM ALARM 1 -10 -12 9:30AM
L 4 PIPE TRANSITION SUMP FUEL ALARM CLEAR 1 -10 -12 9:30AM
T 1 TANK DIESEL TK #SA098U001 HIGH WATER ALARM ALARM 1 -10 -12 9:25AM
L 4 PIPE TRANSITION SUMP FUEL ALARM ALARM 1 -10 -12 9:23AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT CLEAR 1 -10 -12 9:22AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT ALARM 1 -10 -12 9:19AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM CLEAR 1 -10 -12 9:16AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM ALARM 1 -10 -12 9:11AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM CLEAR 1 -10 -12 9:11AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM ALARM 1 -10 -12 9:06AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM CLEAR 1 -10 -12 9:05AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM ALARM 1 -10 -12 9:O1AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT CLEAR 1 -20 -11 10:18AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT ALARM 1 -20 -11 10:14AM
T 1 TANK DIESEL TK #SA098U001 HIGH WATER ALARM CLEAR 1 -20 -11 9:50AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT CLEAR 1 -20 -11 9:49AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT ALARM 1 -20 -11 9:48AM
T 1 TANK DIESEL TK #SA098U001 HIGH WATER ALARM ALARM 1 -20 -11 9:47AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT CLEAR 1 -20 -11 9:43AM
T 1 TANK DIESEL TK #SA098U001 OVERFILL ALARM CLEAR 1 -20 -11 9:42AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT ALARM 1 -20 -11 9:42AM
T 1 TANK DIESEL TK #SA098U001 OVERFILL ALARM ALARM 1 -20 -11 9:41AM
T 1 TANK DIESEL TK #SA098U001 LOW PRODUCT ALARM CLEAR 1 -20 -11 9:35AM
T 1 TANK DIESEL TK #SA098U001 LOW PRODUCT ALARM ALARM 1 -20 -11 9:35AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT CLEAR 1 -20 -11 9:35AM
T 1 TANK DIESEL TK #SA098U001 PROBE OUT ALARM 1 -20 -11 9:34AM
L 5 PIPE PIPING PAN FUEL ALARM CLEAR 1 -20 -11 9:30AM
L 5 PIPE PIPING PAN FUEL ALARM ALARM 1 -20 -11 9:27AM
L 4 PIPE TRANSITION SUMP FUEL ALARM CLEAR 1 -20 -11 9:26AM
L 4 PIPE TRANSITION SUMP FUEL ALARM ALARM 1 -20 -11 9:22AM
L 4 PIPE TRANSITION SUMP FUEL ALARM CLEAR 1 -20 -11 9:22AM
L 4 PIPE TRANSITION SUMP FUEL ALARM ALARM 1 -20 -11 9:22AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM CLEAR 1 -20 -11 9:21AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM ALARM 1 -20 -11 9:17AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM CLEAR 1 -20 -11 9:17AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM ALARM 1 -20 -11 9:13AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM CLEAR 1 -20 -11 9:12AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM ALARM 1 -20 -11 9:09AM
I11200
JAN 16, 2012 12:52 PM
BKFDCAI4 SA098 S -S
3221 S. H ST.
BAKERSFIELD,CA 93304
661 832 -8370
NON PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK #SA098U001 LOW TEMP WARNING CLEAR 1 -10 -12 9:45AM
T 1 TANK DIESEL TK #SA098U001 HIGH WATER WARNING CLEAR 1 -10 -12 9:43AM
T 1 TANK DIESEL TK #SA098U001 LOW TEMP WARNING ALARM 1 -10 -12 9:43AM
T 1 TANK DIESEL TK #SA098U001 HIGH PRODUCT ALARM CLEAR 1 -10 -12 9:43AM
T 1 TANK DIESEL TK #SA098U001 HIGH PRODUCT ALARM ALARM 1 -10 -12 9:38AM
T 1 TANK DIESEL TK #SA098U001 HIGH WATER WARNING ALARM 1 -10 -12 9:25AM
T 1 TANK DIESEL TK #SA098U001 LOW TEMP WARNING
T' 1 TANK DIESEL TK #SA098U001 LOW TEMP WARNING
T 1 TANK DIESEL TK #SA098U001 LOW TEMP WARNING
T 1 TANK DIESEL TK #SA098U001 LOW TEMP WARNING
T 1 TANK DIESEL TK #SA098U001 HIGH WATER WARNING
T 1 TANK DIESEL TK #SA098U001 HIGH WATER WARNING
T 1 TANK DIESEL TK #SA098U001 DELIVERY NEEDED
T 1 TANK DIESEL TK #SA098U001 INVALID FUEL LEVEL
T 1 TANK DIESEL TK4SA098U001 DELIVERY NEEDED
T 1 TANK DIESEL TK #SA098U001 INVALID FUEL LEVEL
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING
T 1 TANK DIESEL TK #SA098U001 LOW TEMP WARNING
T 1 TANK DIESEL TK #SA098U001 HIGH PRODUCT ALARM
T 1 TANK DIESEL TK #SA098U001 HIGH PRODUCT ALARM
T 1 TANK DIESEL TK #SA098U001 HIGH WATER WARNING
T 1 TANK DIESEL TK4SA098U001 HIGH WATER WARNING
SYSTEM PRINTER ERROR
SYSTEM PAPER OUT
SYSTEM PRINTER ERROR
SYSTEM PAPER OUT
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
SYSTEM PRINTER ERROR
SYSTEM PAPER OUT
SYSTEM PRINTER ERROR
SYSTEM PAPER OUT
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
SYSTEM PRINTER ERROR
SYSTEM PRINTER ERROR
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 6 OTHER ANNULAR SPACE SETUP DATA WARNING
L 6 OTHER ANNULAR SPACE SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING
I20600
JAN 16, 2012 12:52 PM
BKFDCA14 SA098 S -S
3221 S. H ST.
BAKERSFIELD,CA 93304
661 - 832 -8370
TANK ALARM HISTORY
TANK 1 DIESEL TK #SA098U001
SETUP DATA WARNING APR 26, 2004 3:45 PM
LEAK ALARM JUN 2, 2006 9:35 AM
HIGH WATER ALARM JAN 10, 2012 9:25 AM
JAN 20, 2011 9:47 AM
JAN 29, 2010 8:40 AM
OVERFILL ALARM JAN 10, 2012 9:38 AM
JAN 10, 2012 9:36 AM
JAN 20, 2011 9:41 AM
LOW PRODUCT ALARM JAN 20, 2011 9:35 AM
FEB 19, 2009 9:48 AM
APR 13, 2005 10:14 AM
SUDDEN LOSS ALARM JUN 2, 2006 9:04 AM
HIGH PRODUCT ALARM JAN 10, 2012 9:38 AM
JAN 29, 2010 9:35 AM
MAR 29, 2006 11:48 AM
INVALID FUEL LEVEL JAN 20, 2011 9:35 AM
FEB 19, 2009 9:48 AM
APR 13, 2005 10:13 AM
PROBE OUT JAN 10, 2012 9:41 AM
JAN 10, 2012 9:19 AM
JAN 20, 2011 10:14 AM
CLEAR 1 -20 -11 10:18AM
ALARM 1 -20 -11 10:18AM
CLEAR 1 -20 -11 9:51AM
ALARM 1 -20 -11 9:50AM
CLEAR 1 -20 -11 9:50AM
ALARM 1 -20 -11 9:47AM
CLEAR 1 -20 -11 9:35AM
CLEAR 1 -20 -11 9:35AM
ALARM 1 -20 -11 9:35AM
ALARM 1 -20 -11 9:35AM
CLEAR 1 -29 -10 9:40AM
ALARM 1 -29 -10 9:38AM
CLEAR 1 -29 -10 9:38AM
ALARM 1 -29 -10 9:35AM
CLEAR 1 -29 -10 8:41AM
ALARM 1 -29 -10 8:40AM
CLEAR 1 -07 -10 7:51AM
CLEAR 1 -07 -10 7:51AM
ALARM 1 -07 -10 7:30AM
ALARM 1 -07 -10 7:30AM
CLEAR 9 -28 -09 11:27AM
ALARM 9 -28 -09 11:26AM
CLEAR 9 -28 -09 11:26AM
ALARM 9 -28 -09 11:25AM
CLEAR 9 -28 -09 11:15AM
ALARM 9 -28 -09 11:14AM
CLEAR 9 -28 -09 11:14AM
ALARM 9 -28 -09 11:14AM
CLEAR 9 -28 -09 11:14AM
CLEAR 9 -28 -09 11:09AM
CLEAR 9 -28 -09 11:09AM
ALARM 9 -28 -09 11:09AM
ALARM 9 -28 -09 11:09AM
ALARM 9 -28 -09 11:09AM
CLEAR 9 -28 -09 11:09AM
ALARM 9 -28 -09 11:09AM
CLEAR 9 -28 -09 11:07AM
ALARM 9 -28 -09 11:04AM
CLEAR 9 -28 -09 10:58AM
ALARM 9 -28 -09 10:53AM
CLEAR 9 -28 -09 10:48AM
ALARM 9 -28 -09 10:46AM
CLEAR 9 -28 -09 10:45AM
ALARM 9 -28 -09 10:44AM
HIGH WATER WARNING JAN 10, 2012 9:25 AM
JAN 20, 2011 9:47 AM
9:01 AM
JAN 29, 2010 8:40 AM
DELIVERY NEEDED JAN 20, 2011 9:35 AM
ALARM
FEB 19, 2009 9:48 AM
8:59 AM
MAY 11, 2006 1:42 PM
MAX PRODUCT ALARM JAN 10, 2012 9:40 AM
MAR 29, 2006 11:48 AM
PERIODIC TEST FAIL JUN 14, 2006 1:38 AM
2011
JUN 3, 2006 9:55 AM
MAY 11, 2006 7:55 AM
CSLD INCR RATE WARN NOV 9, 2004 11:34 AM
SUMP SENSOR
OCT 23, 2004 10:39 AM
LOW TEMP WARNING JAN 10, 2012 9:43 AM
ALARM
JAN 20, 2011 10:18 AM
9:17 AM
JAN 20, 2011 9:50 AM
I30200
JAN 16, 2012 12:52 PM
BKFDCA14 SA098 S -S
3221 S. H ST.
BAKERSFIELD,CA 93304
661 - 832 -8370
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 ANNULAR SPACE SENSOR
JAN 10, 2012 9:01 AM FUEL ALARM
JAN 20, 2011 9:09 AM FUEL ALARM
JAN 29, 2010 8:59 AM FUEL ALARM
2 FILL SUMP SENSOR
JAN 10, 2012 9:06 AM FUEL ALARM
JAN 20, 2011 9:13 AM FUEL ALARM
JAN 29, 2010 9:05 AM FUEL ALARM
3 PIPING SUMP SENSOR
JAN 10, 2012 9:11 AM FUEL ALARM
JAN 20, 2011 9:17 AM FUEL ALARM
JUN 28, 2010 9:36 AM FUEL ALARM
4 TRANSITION SUMP
JAN 10, 2012 9 :23 AM FUEL ALARM
JAN 20, 2011 9:22 AM FUEL ALARM
JAN 20, 2011 9:22 AM FUEL ALARM
5 PIPING PAN
JAN 10, 2012 9:30 AM FUEL ALARM
JAN 10, 2012 9:30 AM FUEL ALARM
JAN 20, 2011 9:27 AM FUEL ALARM
C7