HomeMy WebLinkAbout3221 TAFT HWY (3)MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6.', Health andSafety Code: Chapter 16 Division 3, Title 23, California Code ofRegulalions
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitornte system control panel by the technician who performs the work. A copy of this form must be provided to the tank system ownerroperator.
The owner operator must submit a copy of this form to the local agency regulating UST systems within 30 days oftest date. {
A. General information
Facility Name: HAPPY GAS
Site Address: 3221 TAFT HWY
Facility Contact Person: AMITA
Make/Model of Monitoring System TLS -350
B. Inventory of Equipment Tested/Certified
Cheek the annrnnriate hnrPS to indientP snerifie wudnmont ingnertPd/aPrvirPd-
Bldg. No.:
City: BAKERSFIELD Zip:
Contact Phone No.: ( )
Date of Testing/Servicing: 8/29/2011
Tank 1D: RED DIESEL rank ID: UNL87
Z In -Tank Gauging Probe. Model: MAG Z In -Tank Gauging Probe. Model MAG
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
Z Piping Sump / Trench Sensor(s). Model 208 Z Piping Sump /Trench Sensor(s). Model: 208
Fili Sump Sensor(s). Model: 208 Fill Sump Sensor(s). Model. 208
Mechanical i.ine Leak Detector. Model: RED JACKET Mechanical Line Leak Detector. Model: RED JACKET
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill /High-Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER
Other kspeeify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank ID: PREM91 Tank ID: DIESEL
In-Tank Gauging Probe. Model: MAG Z In -Tank Gauging Probe. Model: MAG
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor, Model:
Z Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor( ,,). Model: 208
Z Fill Sump Sensor(s). Model: 208 Fill Sump Sensor( ,,). Model: 208
Z Mechanical Line Leak Detector. Model: RED JACKET Z Mechanical Litre leak Detector. Model: RED JACKET
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model.
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (.speciA, equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section F.. on Page 2).
Dispenser ID: 1/2 Dispenser ID: 314
Z Dispenser Containment Sensor(s). Model: BEAUDREAU Dispenser Containment Sensor(s). Model. BEAUDREAU
Z Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 516 Dispenser ID: 7/8
ES
Z Dispenser Containment Sensor(s). Model: BEAUDREAU Dispenser Containment Sensor(s). Model: SEAUDREAU
Z Shear Valve(s). Shear Valve(s).
Dispenser Containment Floa[(s) and Chain(s). Dispenser ContainmentFloat(s) and Chain(s).
Dispenser ID: 9 Dispenser ID:
Z Dispenser Containment Sensor(s). Model: BEAUDREAU Dispenser Containment Sensor(s). Modei:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Floats) and Chain(s). Dispenser Containment Floats) and Chain(s).
if the facility contains more tanks or dispensers. copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy of the report; (check all that apply): ® System set -up ® Alarm history report
Technician Name (print): RICHARD MASON Signature:
Certification No.: 5297857 -UT License. No.: CD40 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: k6 61) 326 -8402
Testing Company Address: 3305 BRITTAN RD. BAKERSFIELD, CA. 93308 Date ofTesting/Servicing: 8129/2011
Page 1 of 5
t -V -036 - V4 www.unidocs.org Rev. 01117i08
LE3 i Z
Monitoring System Certification I%
I D. Results of Testing/Servicing
Sotirware Version Installed: 14.01
Complete the followine checklist:
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational'?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere vx ith their broiler operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Fj Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sumpn'reneb Sensors; Dispcnser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes; No.
D Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? %
Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. Ifyes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No* Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments: 87 FILL SUMP SENSOR WAS BAD I REPLACED WITH NEW AND RETESTED. RED DIESEL WAS
OUT OF ORDER UNABLE TO TEST POSITIVE SHUTDOWN AND LEAK DETECTOR
Page 2 of 5
UN -036 — 2/4 www.unidoes.org Rev. 01117'08
Monitoring System Certification
F. In -Tank Gauging/ SIR ]Equipment:
L(bl- i
Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes j No* Has al l input wiring been inspected for proper entry and termination, including testing for ground faults'?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy ofsystem water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed? J
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
Comnletp the fhUnwina ehpi-Wkth
Check this box if LLDs are not installed.
Yes E) `No* i For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: ® : g.p.h.; 0.1 g.p.h; 0.2 g.p.h.
Yes Z No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes NO Was the testing apparatus properly calibrated?
0 Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
NA or disconnected?
Yes No* For electronic LLDs. does the turbine automatically shut off ifany portion of the monitoring system malfunctions
NA or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected? 4
N/A I i
0 Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed'?
in Section H, below, describe how and when these deficiencies were or will be corrected.
Page 3 of. 5
1a -036 - 3!4 www.unidnes.org Re%. 01/17/08
14")_7 _ _1
Monitoring System Certification Form: Addendum for Vacuum/Pressure Interstitial Sensors
1. Results of Vacuum/Pressure Monitoring Equipment Testing
This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of
this form must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner /operator. The owner /operator must submit a copy of the Monitoring System Certification Fonn to the
local agency regulating UST systems within 30 days oftest date.
Manufacturer: N/A Model: System Type: Pressure, Vacuum
Sensor ID
d Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
T
1 Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Components) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass: Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass-, Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
How was interstitial communication verified? 9
Leak- Introduced at Far End of Interstitial Space;' Gauge; Visual Inspection; Other (Describe in Sec. J, below)
Was vacuum /pressure restored to operating levels in all interstitial spaces? Yes No (Ifno, describe in Sec. J, belou)
J. Comments: NONE OF THESE SENSORS ARE PRESENT AT THIS SITE.
Page 4 of 5
If the sensor successfully detects a simulated vacuum/pressure leak introduced in the interstitial space at the furthest point from the
sensor, vacuum /pressure has been demonstrated to be communicating throughout the interstice.
UN-036A - 1/1 www.unidoes.org Rev. 01/26/06
431 -t1 /y
I'
System Certification
ST Monitoring Site-Plan
tU r •'1j3 ------------- •--- -.....
t-------- - - - - -1 - 3 - - -- -- - - - - - - - - - - - - - - ° -
r r - . • . - . . - r - • • - - - - - - - - w - • - . . • . r - - - - . • r - r
Date map was drawn: 19, )V/ A
s'-vctions
If you already have a diagram that shows all required information, you may include it, rather than this page, with your
Monitoring System Certification. On your site plan, show the general layout oftanks and piping. Clearly identifylocationsofthefollowingequipment, if installed: monitoring system control panels; sensors monitoring tank annularspaces, sumps, dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic line leak
detectors; and in -tank liquid level probes (if used for leak detection), In the space provided, note the date this Site Plan
was prepared.
Page r- of S
05100
i
SWRCB, January 2006
Spill ]Bucket 'Vesting Report Form
Thisform is intendedfor use by contractors performing annual testing of USTspill containment structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: HAPPY GAS Date of Testing: 8/29/2011
Facility Address: 3221 TAFT HWY, BAKERSFIELD
Facility Contact: AMITA Phone:
Date Local Agency Was Notified of Testing: 7/19/2011
Name of Local Agency Inspector (ifpresent during testing): ERNIE MEDINA
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Tec ician Conducting Test: RICHARD MASON
Credentials': L CSLB Contractor X 1CC Service Tech, G SWRCB Tank Tester G Other (Specify)
License Number(s): 5297857 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used: VISUAL Equipment Resolution: 0
MEW=
Identify Spill Bucket (By Tank
Number, Siored Product, etc.
TM0MM==MMTT
2
PREM 91 -FILL
3 4
DIESEL RED DIESEL
1
REG 87 -FILL
Bucket Installation Type: Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
L Direct Bury
X Contained in Sump I
E Direct Bury
X Contained in Sum
Bucket Diameter: 12" 12" 12" 12"
Bucket Depth: 14" 14" 14" 14"
Wait time between applying
vacuum /water and start of test:
30 MIN 30 MIN 30 MIN 30 MIN
Test Start Time (Ti): 1:00PM l :00PM 1:00PM 1:00PM
Initial Reading (Rj): 9" 9" 9" 9"
Test End Time (Tr): 2:OOPM 2:OOPM 2:00PM 2:OOPM
Final Reading (RF): 9" 9" 9" 9"
Test Duration (Tr' — Tj): 1 -HOUR 1 -HOUR 1 -HOUR I -HOUR
Change in Reading (Rr- Rj): 0_ 0 0 0
Pass /Fail Threshold or
Criteria: r'_ 0.00 0.00 0.00 0.00 i
i
7
h11.F
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certo that all the information contained in this report Is true, accurate, and infull compliance with legal requirements.
Technician's Signature: Date: 8/29/2011
State laws and regulations do not current!,,' require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
RICH ENVIRONMENTAL
3305 BRITTAN ST. BAKERSFIELD, CA. 93308
OFFICE (661)326 -8402 FAX (661)326 -8934
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
W /0 #:
FACILITY NAME: HAPPY GAS
FACILITY ADDRESS: 3221 TAFT HWY, BAKERSFIELD
PRODUCT LINE. TYPE: PRESSURE
LA 1nl
PRODUCT LEAK DETECTOR TYPE TEST i TRIP PASS
BELOW P.S.I. OR j
SERIAL NUMBER 3 G.P.H. FAIL
UNL87
I
LID TYPE: RED JACKET i YES i2 j
I
PASS
SERIAL # MECHANICAL
PREM91 LID TYPE: RED JACKET YES 12 PASS
SERIAL # MECHANICAL
i DIESEL L/D TYPE: RED JACKET YES 12
i
i PASS
SERIAL # MECHANICAL
RED LID TYPE: RED JACKET NO 0 NOT
DIESEL TESTED
SERIAL #MECHANICAL
I
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICHARD MASON
SIGNATURE: t DATE: 8/29/2011
IN -TANK SETUP
T 1:DIESEL RED pPRODUCTCODE1.000470THERMALCOEFF
TANK DIAMETER 95.00TANKPROFILE
FULL VOL : 11783
FLOAT SIZE: 4.0 IN. 8496
WATER WARNING : 2.0
HIGH WATER LIMIT: 4.0
MAX OR LABEL VOL: 11783
OVERFILL LIMIT 97%
11429
HIGH PRODUCT 95%
11193
DELIVERY LIMIT 17%
2003
LOW PRODUCT 330
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 0 00TA14KTILT
MAN IFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 0°i
LEAK MIN ANNUAL : 01/0
0
PERIODIC TEST TYSTAPJDAkD
ANNUAL TEST L
ALARM DISABLED
PERIODIC FARMAIL
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK :OFF
DELIVERY DELAY 3 MIN
BAUD RATE 9600
PARITY : ODD
STOP BIT : I STOP
DATA LENGTH: 7 DATA
AUTO TRANSMIT SETTINGS
AUTO LEAK ALARM LIMIT
DISABLED
AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODWT
DISABLED
AUTO THEFT LIMIT
DISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY E14D
DISABLED
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM
DISABLED
AUTO SENSOR OUT ALARM
DISABLED
RS -232 SECURITY
000000
SYSTEM SETUP
AUG 29, 2011 11:39 - -
SYSTEM UNITSU.S.
SYSTEM LANGUAGEENGLISH
SYSTEM DATEITIME FORMATMONDDYYYYHH:MM:SS
PUNKIN CENTER3221TAFTHwyBAKCA.93313
SHIFT TIMESHIFTTIME 2 . 4:35.AM
SHIFT TIME 3 DISABLED
SHIFT TIME q DISABLED
DISABLED
PERIODIC: TEST WARNINGSDISABLED
ANNUAL TEST WARNINGSDISABLED
PRINT TC VOLUMESENABLED
TEMP C :OMPENSATIONVALUECDEGF ) : 60.0
H- PROTOCOL DATA FORMATHEIGHT
P,E- DIRF'CT LOCAL PRINTOUTDISABLED
SYSTEM SECURITYCODE : 000onn
ainl4vmr%L 1. 6_'1"7
NORMALLY CLOSED 11 11
IN -TANK ALARMS
T 1:LEAK ALARM
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 2:SENSOR OUT ALARM
L I:SHORT ALARM
L 2 :SHORT ALARM
R 2:REG UNLEADED
TYPE:
STANDARD
NORMALLY CLOSED
IN--;TANK ALARMS " "'" :•
T 2 :LOW PRODUCT ALARM
ALL:HIGH PRODUCT ALARM
T 2:INVALID FUEL LEVEL
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 4:FUEL ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
R 3:SUPER UNLEADED
TYPE:
STANDARD
NORMALLY CLOSED
IN -TANK ALARMS
T 3:LOW PRODUCT ALARM
LIQUID SENSOR'ALMS
L 6 :FUEL ALARM
L 6:SENSOR OUT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
R 4:DIESEL 2
TYPE:
STANDARD
NORMALLY CLOSED
IN -TANK ALARMS
T 4:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 8:FUEL ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
R 5 :COUNTER LIGHT
TYPE:
STANDARD.
NORMALLY OPEN
IN -TANK ALARMS
ALL :LEAK ALARM
ALL:LOW PRODUCT ALARM
ALL:INVALID FUEL LEVEL
ALL:PROBE OUT
ALL:DELIVERY NEEDED
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
ALL:WATER ALARM
UU l BODE 3
THERMAL COEFF 000470
TANK DIAMETER 95.00
TANK PROFILE 1 PT
FULL VOL 11783
FLOAT SIZE: 4.0 IN. 8496
WATER WARNING 2.0
HIGH WATER LIMIT: 410
MAX OR LABEL VOL: 11783
OVERFILL LIMIT 97%
FULL VOL
11429
HIGH PRODUCT 95%
20
IZ
11193
DELIVERY LIMIT 17%
2003
LOW PRODUCT 330
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 0%
0
LEAK MIN ANNUAL 0%
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIf TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 3 MIN
T 3:0UPER UNL 92
PRODUCT CODE 6
THERMAL COEFF 000700
TANK DIAMETER 95.00
TANK PROFILE 1 PT
FULL VOL 11783
FLOAT SIZE: 4.0 IN. 8496
WATER WARNING 2.0
HIGH WATER LIMIT: 4.0
MAX OR LABEL VOL: 11783
OVERFILL LIMIT 97%
11429
HIGH PRODUCT 95n
11193
DELIVERY LIMIT 171,
2003
LOW PRODUCT 330
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0,00
MANIFOLDED TANKS
TO: NONE
83)171
T 2 :REG UNLEADED 87
PRODUCT CODE
THERMAL COEFF :.000701
TANK DIAMETER 95.0i
TANK PROFILE 1 P1
FULL VOL 1178:
FLOAT SIZE: 4.0 IN. 849E
WATER WARNING 2.i
HIGH WATER LIMIT: 4.1,
MAX OR LABEL VOL: 1176.
OVERFILL LIMIT 97 %
11429
HIGH PRODUCT 95%
11193
DELIVERY LIMIT 171
2003
LOW PRODUCT 330
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99,
TANK TILT 0.00
MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 0% LEAK MIN PERIODIC: 0:
0 0
LEAK MIN ANNUAL : 0°o LEAK MIN ANNUAL : 01%
0 0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON.BREAK:OFF
DELIVERY DELAY 3 MIN
PERIODIC TEST TYPE
STANDARD
AN14UAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNX TST SIPHON BREAK:OFF
DELIVERY DELAY 3 MIN
I FCY E^•DG F FCk F E"'
F r>
O
20
IZ
Qo
Z
ra]
Z T
iVli Ism01ws c
a lino cno mina riio avc
amino m'
u.• W „w`, wow.. nw.. w•• a1 w.. aw
w
Fd FOI
A JACKi Ll CPC WaC
DC CU
F- O
mmu
3GC
4. C7
Q
UJ C7 C4J] FU2 (n ill
I W m I W w w
cCC
I uJ
D'F
I W m F
1 aQ jR F J CJ
JET -
U
J , 3FLN 1F»0 1F
4 ALARtj HISTORY REPORT
L 7:plSE OR ALARMOTHERSENSORSDSL2
A G 29. 201 ALARM
FUEL ALARM
1 I3:54
AUG 29. 2011 12:55
FUEL ALARMDEC19. 2010 14:13
HISTORY
RRPoRT
LARM
CEOR ALARM
tT_
SENSORS
R ,A1:AR4...,...
AG. 29"'. . 23+ 1 13'
AUG 29 A011 12:55
FU'E" ALAR<21010 1 g . 03DBC19' ...
ALARM F,ISTOR'z REPORT
SENSOR ALARM - - --
1, - ;3.FEG FILL
OTHER SENSORS ARr1
SENSOR 2011 13:54AUGHUG49•
FUEL ALARIQ11 13:46AUG 'gig
SENSOR OUT ALARM
AUG 29, 2011 13:30
gLAF,M HISTrjRY REPORT
L 4:TpENSOR ALgRh1 ___ OTHER REG oft - SENSOR S NSORS
AUG 29, UT ALARM
L
2011 1 4
92pHUB2,
112: 52
AUG L qALARMM9' 201I 12:;8j
ALARM HISTORY REPORT
SENSOR ALARM - -- --
L5:FILL SUPER UNL
OTHER SENSORS
SENSOR OUT ALARM
AUG 29. 2011 13 :54
FUEL ALARM
AUG 29. 2011 13 :06
FUEL ALARM
FEB _26. 2011. . 1 : 04 , ...
ALARM HISTORY REPORT
SENSOR ALARM
L 6:STP SUPER SUMP
OTHER SENSORS
SENSOR.OUT ALARM
HUG 29. 2011 13:54
FUEL ALARM
AUG 29. 2011 12:53
SENSOR OUT ALARM
SEP 29. 2010 9:29
LEAK TEST METHOD "i n i
TEST WEEKLY ALL TANK
SUN
START TIME 1 :00 AM
TEST RATE :0.20 GAL; ,HR
DURATION : 2 HOURS
LEAK TEST REPORT FORMAT
ENHANCED
r'TWAREVER REVISION LEVELSION14.0ISOF'nIARE# 346014 - 100 -13CREATED - 97.03.12.20.41
NO SOFTWARE MODULESYSTEMFEATURES:
PERIODIC IN -TANK TESTSANNUALIN -TANK TESTS
ALA41 HISTORY REPORT
SENSOR ALARM
L 1:FILL RED DSL
OTHER SENSORS
SENSOR OUT ALARM
AUG 29. 2011 13:54
FUEL ALARM
AUG 29, 2011 13:02
FUEL-- ALARtl
DEC 25, 2010 22:50
ALARM HISTORY REPORT
SENSOR ALARM
L 2 :STP RED DSL
01 HER BE N$9F 1SENSOR ,OUT
AUG-Z9,- :201.1
FUEL ALARM
AUG 29, 2011 bs..
SENSOR OUT ALARM
SEP 29, 2010 9:29 "
Lk51 *`1
MONITOR CERT. FAILURE REPORT
SITE NAME : HAPPY GAS DATE: 8/29/2011
ADDRESS: 3221 TAFT HWY TECHNICIAN: RICHARD MASON
THE FOLLOWING COMPONENTS WERE REPLACED /REPAIRED TO COMPLETE
TESTING.
REPAIRS; 87 FILL SUMP SENSOR WAS BAD I REPLACED WITH NEW AND
RETESTED NEW ONE PASSED.
RED DIESEL WAS OUT OF SERVICE I WAS UNABLE TO TEST
POSITIVE SHUTDOWN AND LEAK DETECTOR
LABOR:
PARTS INSTALLED : 1- VEEDEROOT 208 SENSOR FOR 87 FILL SUMP.
NAME. TITLE:
SIGNATURE:
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMENTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.