MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6.7, Health andSafety Code; Chapter 16, Division 3, Title 23, California Code: ofRegulations
This form must be used to document testing and servicing of monitoring equipment A separate certifle4on.or report must be prepared for each
monitoring System control panel by the technician who performs the work A copy of this form must be provided to the tank system owner /operator.,
The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days oftest date.
A. General Information
Facility Name: C&M SHELL STATION Bldg. No.:
Site Address: 3605 ROSEDALE HWY. City: BAKERSFIELD Zip: 93308
Facility Contact. Person: CHOY Contact Phone No.: (661) 304 -7747
Make /Model.of Monitoring System: TLS -350 INSP.- ESTHER Date of TestinWServicing: 511812011 .
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to indicate specific equipment inspected /serviced:
Tank iD: REGULAR 87 Tank ID: PREMIUM 91
In -Tank Gauging Probe, Model: MAG In -Tank Gauging Probe: Model: MAG
Annular Space or Vault Sensor. Model: 301 Annular Space or Vault Sensor. Model: 302
Piping Sump./ Trench Sensor(s). Model: 208 Piping Sump /Trench Sensor(s). Model: 268
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: FX1V Mechanical Line Leak Detector. Model: FX1V
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill/ High - Level. Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (specify equipment type and model in Section E onPage2). Other (specify equipment type and model'in Section E on Page 2).
Tank ID: DIESEL Tank ID: VENT BOX
In -Tank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: 302 Annular Space or Vault Sensor. Model:
Piping Sump/ Trench Sensor(s). Model: 362 PipingSump/ Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: FX1DV Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: El Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specifyequipment type and model in Section E on Page 2).
Dispenser ID: 112 Dispenser ID: 314
Dispenser Containment Sensor(s). Model' 406 Dispenser Containment Sensor(s). Model: 406
Shear Valve(s). Shear Valve(s)..
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 516 Dispenser ID: 718
Dispenser Containmenf Sensor(s). Model: 351. Dispenser Containment Sensor(s). Model: 351
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s)..
Dispenser ID: 9110 Dispenser ID: 11112"
Dispenser Containment Sensor(s). Model: 406 DispenserContainment Sensor(s). Model: 406
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form Include information for every tank and dispenser at the facility.
C. Certification -I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers'
guidelines. Attached to this Certification Is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equi ment capable of generating such reports, I have.also
attached a copy of the report; (check aU that apply): ® System set -up term 'story report
Technician Name (print): RYAN MASON Signature:
CertificationNo.: A273671 8029371 -UT License. No.: V611 D 0 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: 661) 326 -8402
Testing Company Address: 5643 BROOKS CT. BAKERS FIELD, CA 93308 Date of Testing/Servicing: 511812011
Page 1 of 5
UN- 036 —1/4 www.unidoes.org Rev. 01117/08
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 330.01
Complete the followine checklist:
q24 r
Yes No* Is the audible alarm operational?
Yes No* is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
p N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; ® Dispenser Containment Sensors.
Did you confirm positive shutdown due to leaks and sensor failure /disconnection? 10 Yes; No.
Yes. No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed),, is the'overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so; at what percent of tank capacity does the alarm.trigger? %
Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacementparts in Section E, below.
Yes *' No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, ifapplicable
Yes No* Is all monitoring equipment operational .per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 5
UN -036 - 2/4 wwwxoidoeaorg Rev. 01/17/08
Monitoring System Certification
F. In -Tank Gauging / SIR Equipment: ® Check this box iftank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if.in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level.readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items. on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
Cmmnlete the fnllnwino checklist!
p Check this box ifLLDs are not installed.
Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate:. ® 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow ifit detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
Z. N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
N/A or disconnected?
Yes No* For electronic. LLDs, does the turbine automatically shut off if.any portion of the monitoring system malfunctions
N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yes No* Were all items on the equipment manufacturer's maintenance checklist. completed?
In Section H, below, describe how and when these deficiencies wereor will be corrected.
H. Comments:
Page 3 of 5
UN-036 — 3/4 www.nnidocs:org Rev. 01/17 /08
Sii,: ildress. t -A 6:3W 00 _133W
IC
4L dj
11"voij 91117'L6tiv have a:diagrarh that shows al :1 ,r;c 8qijrc8.. ritefti&', it'.:ratho IhAn piga. with:ypyr
ar y. Ss;,4611 uitmcatioh. : N yvar.... 'laypuv6ff_fik_s :4ti& C46 I identify, Iix ations -of [lie f0p0m: 014h,:O the mineral:
Odiobeft.* il' in§tjllc& qpk*;: dispenser parts: —,pi(Iwwr% mont ns. ivi1hr.
MMOenI- kd' and in -tank liquid. I" N.s 6fv-sed
for le;k, det&ti6n). th:th6 aic N Olt Odd-
UN;O36 - 414
Ps
ww.w;ijrtidk-Lorg tIkAs/fIN19
I/
q,ZA59 t
RICH ENVIRONMENTAL
3305 BRITTAN ST. BAKERSFIELD, CA. 93308
OFFICE (661)326 -8402 FAX (661)326 -8934
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
W /0#:
FACILITY NAME: C &M SHELL STATION
FACILITY ADDRESS: 3605 ROSEDALE HWY. BAKERSFIELD, CA.93308
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL87 LID TYPE: FX1V
YES 10 P.S.I. PASS
SERIAL # 9838
PREM91 L/D TYPE: FX1V
YES 10 P.S.I. PASS
SERIAL # 0874
DIESEL L/D TYPE: FX1DV
YES 10.P.S.I. PASS
SERIAL # 4746'
L/D TYPE: PASS
YES
SERIAL # FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE.AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A:
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE.BEST
OF MY KNOWLEDGE.
TECHNICIAN: RYAN MASON
SIGNATURE: DATE: 5/18/11
L4 z,451
SWRCB, January 2006
Spill Bucket Testing Report Form
Thuform is intendedfor use by contractors performing annual testing of USTspill containment structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1_ FACILITY INFORMATION
Facility Name: C&M SHELL STATION Date ofTesting: 5/13/10
Facility Address: 3605 ROSEDALE HWY. BAKERSFIELD, CA. 93308
Facility Contact: CHOY Phone: (661) 304 -7747
Date Local Agency Was Notified ofTesting: 4/28/10
Name of Local Agency Inspector (fpresent during testing): ERNIE MEDINA
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RYAN MASON
Credentials: CSLB Contractor X ICC Service Tech. "SWRCB Tank Tester Other (Spec)
License Number(s): 8029371 =UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used: VISUAL Equipment Resolution: 0
YA
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
1
REGULAR 87 -FILL
2 PREMIIUM 91-
FILL
3
DIESEL FILL
4
Bucket Installation Type: X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
X Direct Bury
O Contained in Sum
Direct Bury "
Contained in Sum
Bucket Diameter: 12" 12" 12"
Bucket Depth: 14" 14" 14"
Wait time between applying
vacuum/water and start oftest:
30 MIN 30 MIN 30 MIN
Test Start Time (T,): 0900 0900 0900
Initial Reading (R,): 12" 12" 12"
Test End Time (TF): 1000 1000 1000
Final Reading (RF): 12" 12" 12"
Test Duration (TF -- Ti): 1 -HOUR HOUR 1 -HOUR
Change in Reading (RF - Rj): 0 0 0
Pass/Fail Threshold or
Criteria: 0.00 0.00 0.00
UK • N91,
i
Comments — (include information on repairs made.prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certj& that all the information contained in dtls report Is true,. accurate, and infull compliance with legal requirements.
Technician's Signature: Date: 1 5118/11
1 State laws and regulations do not currently require testing to beperformed by a,qualified contractor. However, local requirements
may be more stringent.
1
SOFTWARE REVISION LEVELVERSIOIV330 .'01
SOFTWAREO 346330 -100 -BCREATED - 10,07,23,17.25
S- MODULE;! 330160 -004 -eSYSTEMFEATURES:
PERIODIC IN -TANK TESTSANNUAL•IN -TANK TI?STSISD
SYSTEM SETUP
T - - - -
MAY 18, 2011' 2:10 F'M
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMATMONDDYYYVHH :MM:SS M
SHELL
3605 ROSEDALE HWYBAKERSFIELDCA
SHIFT TIME 1 12:00 AMSHIFTTIME24:00 AMSHIFTTIME3.: DISABLEDSHIFTTIME4DISABLED
TANK PER TST NEEDED WRNDISABLED
TANK ANN TST NEEDED WRNDISABLED.
LINE RE- ENABLE METHODPASSLINETEST
LINE PER TST NEEDED WRNDISABLED
LINE ANN TST NEEDED WRNDISABLED
PRINT TC VOLUMESENABLED
TEMP COMPENSATIONVALUE (DEG F ): 60.0
STICK HEIGHT OFFSETDISABLED
ULLAGE: 90%
H- PROTOCOL DATA FORMATHEIGHT
DAYLIGHT SAVING TIME. DISABLED
RE- DIRECT LOCAL PRINTOUTDISABLED
EURO PROTOCOL PREFIXS
COMMUNICATIONS SETUP
IN -TANK SETUP
PORT SETTINGS:
COMM.BOARD : I (EDIM S T 1:87
RS -232 SECURITY PRODUCT CODE l
CODE : DISABLED THERMAL COEFF :.000700
TANK DIAMETER 92.00
COMM BOARD 2 (RS -232) TANK PROFILE I PT
BAUD RATE 1200 FULL VOL 972B
PARITY ODD
STOP BIT 1 STOP
DATA LENGTH: 7 DATA FLOAT SIZE: 4.0 IN.
RS -232 SECURITY
CODE *. DISABLED WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
COMM BOARD 3 (FXMOD)
BAUD RATE : 2400 MAX OR.LABEL VOL: 9728.
PARITY ODD OVERFILL LIMIT 90%
STOP BIT 1 STOP 8755
DATA LENGTH: 7 DATA HIGH PRODUCT 95i
RS -232 SECURITY 9241
CODE : DISABLED DELIVERY LIMIT 5%
DI AL .TY? : 496BONE ...,._:._.:...,
ANSWER
MODEM SETUP STRING LOW PRODUCT 500
LEAK ALARM LIMIT: 3
DIAL TONE INTERVAL: 32' SUDDEN LOSS LIMIT: 50
TANK TILT 2.20
PROBE OFFSET 0.00
AUTO TRANSMIT SETTINGS:
AUTO LEAK ALARM LIMIT SIPHON MANIFOLDED TANKS
DISABLED TO: NONE
AUTO HIGH WATER LIMIT LINE MANI.FOLDED TANKS
DISABLED TO: NONE
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT LEAK MIN PERIODIC: 0%
DISABLED 0
AUTO THEFT LIMIT
DISABLED LEAK MIN ANNUAL : 0%
AUTO DELIVERY START 0
DISABLED
AUTO DELIVERY END
DISABLED PERIODIC TEST TYPE
AUTO EXTERNAL INPUT ON STANDARD
DISABLED
AUTO EXTERNAL INPUT OFF ANNUAL TEST FAIL
DISABLED ALARM DISABLED
AUTO SENSOR FUEL ALARM
DISABLED PERIODJC TEST FAIL
AUTO SENSOR WATER ALARM ALARM DISABLED
DISABLED
AUTO SENSOR OUT ALARM GROSS TEST FAIL
DISABLED ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
RECEIVER SETUP:
TNK.TST SIPHON BREAK:OFF
NONE
DELI VERY . DELAY 5 KINN
PUMP THRESHOLD 10.00
AUTO DIAL TIME SETUP:
NONE
T 3:91T2:DIEBEL PRODUCT CODE 3 LEAK TEST METHODPRODUCTCODE2THERMALCOEFF :.000700 — — — — — — — THERMAL•COEFF :.000450 TANK DIAMETER 92.00 TEST ON DATE : ALL TANKTANKDIAMETER92.00 TANK PROFILE 1 PT JAN 29, 2009TANKPROFILE1PT" FULL VOL 9728 START 'TIME : DISABLEDFULLVOL9728TESTRATE :0.20 GAL /HR
FLOAT SIZE: 4.0 IN. FLOAT SIZE: 4.0 IN. DURATION : 2 HOURS
WATER WARNING 2 p WATER WARNING 2.0 TST EARLY. STOP :DISABLED
HIGH WATER LIMIT: 3,0 HIGH WATER LIMIT: 3.0 LEAK TEST REPORT FORMAT
MAX OR LABEL VOL: 9728 MAX LABEL 9.728
NORMAL
OVERFILL LIMIT' 90% OVERFILL LIMIT 90% 9755
8755 HIGH PRODUCT 95% HIGH PRODUCT 95% 9241
9241 DELIVERY LIMIT 10% DELIVERY LIMIT 144: 972
1361
LOW PRODUCT 500
LOW PRODUCT 500
LEAK ALARM LIMIT' 3 LEAK ALARM LIMIT: 3
SUDDEN LOSS LIMIT: 50
SUDDEN LOSS LIMIT: 50
TANK TILT 1.45 TANK TILT 2.44 LIQUID SENSOR SETUP
PROBE OFFSET
1.45 PROBE OFFSET 0100 _ — — _ _ _ _ — — — —
L 1 :87 STP
SIPHON MANIFOLDED TANKS SIPHON MANIFOLDED TANKS TRI —STATE (SINGLE FLOAT)
TO: NONE, Tat: NONE CATEGORY : STP SUMP
LINE MANIFOLDED TANKSLINEMANIFOLDEDTANKSTO: NONENONE L 2:DIESEL STP.
DUAL FLT. HIGH VAPOR
LEAK MIN PERIODIC: 0% LEAK MI14 PERIODIC: CATEGORY : STP SUMP
0
LEAK MIN ANNUAL Ogg
LEAK MIN ANNUAL 00 L 3 :91 STP
0 TRI—STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
PERIODIC TEST TYPE PERIODIC TEST TYPE
STANDARD
STANDARD L 4:87 ANN
NORMALLY CLOSED
ANNUAL TEST FAIL ANNUAL TESALARMLDISA,BLED CATEGORY ANNULAR SPACE
ALARM DISABLED
PERIODIC TEST FAIL PERIODIC TEST FAIL
ALARM-DISABLED ALARM DISABLED L.5:DIESEL ANN
DUAL POINT HYDROSTATIC
GROSS TEST FAIL GROSS TEST FAIL CATEGORY : ANNULAR SPACE
ALARM DISABLED ALARM DISABLED
ANN TEST AVERAGING: OFF ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
PER TEST AVERAGING: OFF L 6:91 ANN
DUAL,POINT HYDROSTATIC
TANK TEST NOTIFY: OFF TANK TEST NOTIFY: OFF CATEGORY ANNULAR SPACE
TNK TST SIPHON BREAK:OFF ?NK TST SIPHON BREAK ":OFF
DELIVERY DELAY 5"MIN DELIVERY DELAY • 5 MIN L 7 :VENT BOX
PUMP THRESHOLD 10.00% PUMP THRESHOLD 10.00% TRI —STATE (SI.NGLE FLOAT)
CATEGORY : OTHER.SENSORS
L e: NONE
NORMALLY CLOSED
CATEGORY I OTHER SENSORS
EVR /ISD SETUP
SMARTSEN$OR SETUP
OUTPUT .RELAY SETUP
5 1:VAPOR PRESSURE EVR TYPE: BALANCE
R 1:87 CATEGORY VAPOR PRESSURE
TYPE: BALANCE NOZZLE TYPE
STANDARD s 2:CANISTER VST
NORMALLY CLOSED CATEGORY VAPOR VALVE
VAPOR PROCESSOR TYPE
TANK 4:. 1 s 8' :ATM VEEDER -ROOT POLISHER
CATEGORY ATM P SENSOR
LIQUID SENSOR ALMS s 9;DISP 1 -2 ANALYSIS TIMES
L 1 :FUEL ALARM CATEGORY AIR FLOW METER TIME: 10 :00 AM
L 3:FUEL ALARM DELAY MINUTES: I
L 1:SENSOR OUT ALARM 510 :DISP 3 -4
L 3 :SENSOR OUT ALARM CATEGORY AIR FLOW METER
L 3:WATER ALARM ACCEPT HIGH ORVR:
L 1:HIGH LIQUID ALARM 511 :DISP 5 -6 ENABLED
L 3:LIQUID WARNING CATEGORY AIR FLOW METER
ISD HOSE TABLE
ISD SITE ALARMS 512:D1SP 7 -8 ID FP FL HL AA RR
ISD GROSS PRES .FAIL CATEGORY AIR FLOW METERISDDEGRDPRESFAIL 01 01 O1. 02 01 03
ISD VAPOR LEAK FAIL sl3.:DISP 9 -10 02 02 02 02 01 03
ISD VP PRES FAIL CATEGORY AIR FLOW METER 03 00 03 02 02 03
ISD VP STATUS FAIL 04 04 04 02 02 03
sl4:DISP 11 -12 05 05 05 02 03 03
ISD HOSE ALARMS CATEGORY AIR FLOW METER 06 06 06 02 03 03
ALL :FLOW COLLECT FAIL 07 '07, 07 02 04 03
08 08 08 02 04 03
R 2:DIESEL. 09 09 09 02 05 03
TYPE: 10 16 10 02 05 03
STANDARD 11 17' 11 02 06 03
NORMALLY CLOSED 12 16 12 02 06 03
TANK 0: 2
ISD AIRFLOW METER MAP
ID SERIAL NUM LABEL
LIQUID SENSOR ALMS
L 2:FUEL ALARM 134514 DISP 1 -2
L 2:SENSOR OUT ALARM 2 39498 DISP 3 -4
L 2 :HIGH LIQUID ALARM 3 38972 DISP 5 -6
4 37267 DISP 7 -8
R 3:91 5 36516 DISP 9 -10
TYPE:' 6 34444 DISP 11 -12
STANDARD
NORMALLY CLOSED
ISD FUEL GRADE HOSE MAP
TANK 4: 3 1 2 3 4
FP MHH MHH MHH MHH AA
LIQUID SENSOR ALMS 01101.30I 201 U U 1
L 3:FUEL ALARM 02 102 302 202 U'U 1.
L 3:SENSOR OUT ALARM 03 103 303 203 U U 2
04 104 304 204 U U 2
ISD SITE ALARMS PMG GETUP 05 105 305 205 U U 3
ISD GROSS PRES FAIL 06 106 306 206 U U 3
ISD DEGRD PRES FAIL C VERSION: ISD VAPOR LEAK FAIL 01,03 08 108.308 208 4 U 4
ISD VP PRES FAIL VAPOR PROCE 09 109 309 209 U U 5
ISD VP STATUS FAIL VEEDER-ROOT POLI 110 5ER17 .1.10
9110.
3 U
ISD HOSE ALARMS 18 212 112 912 3 U 6
ALL:FLOW COLLECT FAIL
LABEL TABLE
1: UNASSIGNED
2 :' BLEND3
3: REGULAR
4: MID GRADE
5: PREMIUM
6: GOLD
7: BRONZE
B: SILVER
9: BLEND2,
10: BLEND4
ALARM HISTORY. REPORT ALARM HISTORY REPORT -
SYSTEM ALARM - - - -- - - -- IN -TANK ALARM - - - --
PAPER OUT ALARM HISTORY REPORT
MAY 18, 2011 2:10 PM T 3:91 - - - -- SENSOR ALARM - - - -- PRINTER ERROR L 3:91 STPMAY18, 2011 2:10 PM STP SUMP
SENSOR OUT ALARM
MAY 18. 2011 12:45 PM
FUEL ALARM
MAY 18, 2011 12:19 .PM
FUEL ALARM
DEC 10. 2010 2:16 P11
SEND * * **
x+ xxEN.D
x * * END
END
ALARM HISTORY REPORT
REPORT
ALARM HISTORY REPORT
1N -TANK ALARM - - ---
SENSOR ALARM - - - --
IN -TANK ALARM. - - - -- L, 1:87 STP
MAY 18, 2011 12:45 PM
STP SUMP
T 1:87 SENSOR OUT ALARM
MAY 18, 2011 12:45 PM
OVERFILL ALARM
MAY iB. 2011 12:19 PM ALARM HISTORY REPORT
MAR 13, 2011 2 :57 PM FUEL ALARM
FUEL ALARM
JAN 6, 2011 4:53 AM
5 : 09 All MAY 18, 2011 12:20 PM ALARM HISTORY REPORTIAN4, 201.1
SENSOR ALARM - - - --
MAY 5, 2011
HIGH PRODUCT ALARM
FUEL ALARM
DEC 10. 2010 11:13 AM SENSOR ALARM - - - --
NOV 8. 2014 9:22 AM L 4:87 ANN
OCT 27., 2010 3:35 AM ANNULAR SPACE
SENSOR OUT ALARM
FUEL ALARM
MAY 18. 2011 1:12 PM
LOW LIQUID ALARM
LOW LIQUID ALARM
MAY 18. 2011 12:45 PH
MAY 18. 2011 12:27 PM
SENSOR OUT ALARM
MAY 1.8, 2011 12:44 PM
END * **
x x x END * .. ...'
x * * END
ALARM HISTORY REPORT
ALARM'H1STORY REPORT SENSOR ALARM - - - -,-
L 2:DIESEL STP
1N -TANK ALARM - - --- STP SUMP
SENSOR OUT ALARM
MAY 18, 2011 12:45 PM
T 2:DIESEL
FUEL.ALARM.
DELIVERY NEEDED
MAY iB. 2011 12:19 PM ALARM HISTORY REPORT
MAY 13, 2011 9:34 AM FUEL ALARM
MAY 6, 2011 8:55 AM DEC 10. 2010 1:1:11 AM SENSOR ALARM - - - --
MAY 5, 2011 6:34 AM L 5:DIESEL ANN
ANNULAR'SPACE
SENSOR OUT ALARM
MAY 18, 2011 12:45,PM
LOW LIQUID ALARM
MAY 18. 2011 12:27 PM
HIGH LIQUID ALARM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 6:91 ANN
E ANNULAR SPACE
SENSOR OUT ALARM ALARM HISTORY REPORT
MAY 18, 2011 12.45 PM SENSOR ALARM - - - --
LOW LIQUID ALARM L 8:NQNE
MAY 18, 2011 12:28 PM OTHER SENSORS
FUEL ALARM
HIGH LIQUID ALARM MAY 18. 2011 12:45 PM
MAY 18, 2011 12:24 PM
x * x x, * END ***xx
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 7:VENT BOX
OTHER SENSORS
FUEL ALARM
MAY 18. 2011 12:53 PM
SENSOR OUT ALARM
MAY 18, 2011 12:45 PM
FUEL ALARM
DEC 21. 2010 12:37 PM
x x x x x END x x x x x
x x x x x END x x x **
ALARM HISTORY REPORT
SENSOR ALARM - ----
e 1
OTHER SENSORS
x x x x x END x x x X x
MONITOR CERT. FAILURE REPORT
SITE NAM: C &M SHELL STATION DATE: 5/18/11
THE FOLLOWING COMPONENTS WERE REPLACED/REPAVED W. COMPLETE
TESTING.
REPAIRS; NONE
LABOR: NONE
PARTS INTALLED : NONE
NAME : TITLE:
SIGNATURE
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN. TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES. OR PENALTIES O.CCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.