MONITORING SYSTEM CERTIFICATION %361
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or reportgtust be prepared for each
monitoring system control panel by the technician who performs the worlc A copy ofthis form must be provided to the tank system owner /operator.
The owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days oftest date.
A. General Information
Facility Name: C&M SHELL STATION Bldg. No.:
Site Address: 3605 ROSEDALE HWY City: BAKERSFIELD Zip: 93308
Facility Contact Person: CHOY Contact Phone No.: (661) 304 -7747
Make/Model of Monitoring System: TLS -350 Date ofTesting/Servicing:
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment insnected/serviced:
Tsnk ID: REG87 Tank ID: PREM91
In -Tank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model: MAG
Annular Space or Vault Sensor. Model: 302 Annular Space or Vault Sensor. Model: 302
Piping Sump / Trench Sensor(s). Model: 206 Piping Sump / Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: FX1V Mechanical Line Leak Detector. Model: FX1V
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank ID: DIESEL Tank ID: VENT BOX
In -Tank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: 302 Annular Space or Vault Sensor. Model:
Piping Sump/ Trench Sensor(s). Model: 352 Piping Sump / Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line leak Detector. Model: FX1 DV Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: 112 Dispenser ID: 314
Dispenser Containment Sensor(s). Model: 406 DispenserContainment Sensor(s). Model: 406
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Floats) and Chain(s).
Dispenser ID: 516 Dispenser ID: 7/8
Dispenser Containment Sensor(s). Model: 351 Dispenser Containment Sensor(s). Model: 351
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 9110 Dispenser 1D: 11/12
Dispenser Containment Sensor(s). Model: 406 Dispenser Containment Sensor(s). Model: 406
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification -1 certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capaery nerating such reports, I have also
attached a copy ofthe report; (check aU that apply): ® System set -up ® Alarnt eport
Technician Name (print): RICH PHILLIPS Signature:
Certification No.: A2908411035169 -UT License. No.: C611 D40 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 392 -8687
Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308 Date of Testing/Servicing: 518/2012
Page 1 of 5
UN -036 1/4 www.unidoes.org Rev. 01/17/08
Monitoring System Certification
A Results of Testing/Servicing
Software Version Installed: 330.01
Comnlete the following checklist:
yG38¢ .
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? %
Yes* E No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* E No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
E Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, ifapplicable
Yes No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments: REPLACED STAND ALONE SENSOR DISP 9/10 (BEAUDREAU 406) AND RE- TESTED
Page 2 of 6
UN -036 — 2/4 www.unidocs.org Rev. 01/17/08
Monitoring System Certification
F. In -Tank Gauging / SIR Equipment:
y 394
Z Check this box if tank gauging is used only for inventory control.
Check this box ifno tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
rmmnlete the fnllnwina ehecklict-
Check this box ifLLDs are not installed.
Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: g 3 g.p.h.; 0.1 g.p.h ; [10.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
g Yes No* Was the testing apparatus properly calibrated?
ER Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut offifthe LLD detects a leak?
g N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
g N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut offif any portion of the monitoring system malfunctions
g N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
L11 Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
UN -036 - 3/4
Page 3 of 5
www.unidoes.org Rev. 01/17/08
Monitoring System Certificaifon
UST Monitoring Site Plan
Site Address: 3605 ROSEDALE HWY. BAKERSFiELD, CA. 93308
l6 3$9 f/
I .. . . . . . . . . . . . . . 1cc3C.0AA.t3b-. ._,... . . . . . . . . ... . . . . . , • f . . . . . . . . . . . . . . . . . t
QA1>; w
4e•.t.d*,r„j c` . . . . . .
fn %7 W!'l1 $t . ....... .
Qr. elizi
E::::....:::
Date map was drawn: 5,'1_3`10.
InAructiOns
If you already have a diagram ihat shows ali requirod information, you may include it, rather than this page. with your Monitoring
Sy tem Certification. On your:site plan, show the general layout of tanks and.piping. Clearly' idcmify locations, of the follmving
equipment; if installed: monitoring system control panels; scissors monitoring tank annular spaces, sumps, dispenser pans. spill
containers. or iother secondary containment areas; mechanical or electronic lute leak detectors; and in -tank liquid level probe~ (if used
for seal: demlion). M the space provided, note the datethis Site Flan was prepared.
Page 3 of ' 5
l :N-M - 4A www.unidoes.org Rev. 0 1if71118
Y 3$1
RICH ENVIRONMENTAL
5643 BROOKS CT. BAKERSFIELD, CA. 93308
OFFICE (661)392 -8687 FAX (661)392 -0621
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
FACILITY NAME: C &M SHELL STATION
FACILITY ADDRESS: 3605 ROSEDALE HWY, BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL87 L/D TYPE: FX1V
NO FAIL
SERIAL # 9838
PREM91 LID TYPE: FX1V
NO FAIL
SERIAL # 0874
LID TYPE: FX1DV
DSL YES 10 PASS
SERIAL # 4746
L/D TYPE:_ YES PASS
SERIAL # _ NO FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICH PHZIPS
SIGNATURE: DATE: 5/8/12
43 f
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and
printouts from tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: C &M SHELL STATION Date ofTesting: 5/8/I2
Facility Address: 3605 ROSEDALE HWY, BAKERSFIELD
Facility Contact: I Phone:
Date Local Agency Was Notified of Testing: 3/28/12
Name ofLocal Agency Inspector (fpresent during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials': CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s): 1035169 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum El Other
Test Equipment Used: VISUAL Equipment Resolution: 0
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
1 REG87 FILL 2 PREM91 FILL 3 DIESEL FILL 4
Bucket Installation Type: X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter. 12" 12" 12"
Bucket Depth: 14" 14" 14"
Wait time between applying
vacuum/water and start oftest: 30 MIN 30 MIN 30 MIN
Test Start Time (Tj): 9:00 9:00 9:00
Initial Reading (RO: 12" 12" 12"
Test End Time (TF): 10 :00 10:00 10:00
Final Reading (RF): 12" 12" 12"
Test Duration (TF — T,): 1 -HOUR i -HOUR 1 -HOUR
Change in Reading (RF- R,): 0 0 0
Pass/Fail Threshold or
Criteria: 0.00 0.00 0.00
Test Result: X Pass Fail X Pass Fail X Pass Fail Pass Fail
Comments — (include information on repairs made prior to testing andrecommendedfollow -upforfailed tests)
CERTIFICATION OF TE NICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the informatio retainedin this report is true, accurate, and infull compliance witlt legal requirements.
Technician's Signature: Date: 5/8/12
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
SOFTWARE REVISION LEVEL TANK CHART SECURITY
DISABLED
VERSION 330.01
PARITY ODD
SOFTWARE0 346330 -100 -B
STOP BIT 1 STOP
DATA LENGTH: 7 DATA
CREATED - 10.07.23.17.25 CUSTOM ALARl -tS
S- MODULE# 330160 -004 -a DISABLED
SYSTEM FEATURES:
PORT SETTINGS:
PERIODIC IN -TANK TESTS
TESTS SERVICE NOTICE
ANNUAL IN -TANK. DISABLED
ISD
RS -232 SECURITY
ISO 3166 COUNTRY
CODE:
MASS /DENSITY
DISABLED
SYSTEM SETUP
MAY 6, 2012 7:05 AM
SYSTEM UNITS
COMM BOARD 3 (FXMOD)
BAUD RATE 2400
U.S.
PARITY ODD
SYSTEM LANGUAGE
STOP BIT 1 STOP
DATA LENGTH: 7 DATA
ENGLISH
SYSTEM DATE /TIME FORMAT COMMUNICATIONS SETUP
MON DD YYYY HH:MM:SS xM
CODE : CODE DISABLED
SHELL PORT SETTINGS:
3605 ROSEDALE HWY
ANSWER ON 1 RING
MODEM SETUP STRING
BAKERSFIELD CA COMM BOARD : 1 (ED IM )
TEMP COMPENSATION
RS -232 SECURITY
SHIFT TIME 1 12:00 AM CODE : DISABLED
SHIFT TIME 2 4:00 AM
SHIFT TIME 3 : DISABLED COMM BOARD 2 (RS -232)
SHIFT TIME 4 DISABLED BAUD RATE 1200
PARITY ODD
TANK PER TST NEEDED WRN STOP BIT l STOP
DATA LENGTH: 7 DATA
DISABLED RS -232 SECURITYTANKANNTSTNEEDEDWRNCODE : DISABLED
DISABLED
DISABLED
LINE RE-ENABLE METHOD COMM BOARD 3 (FXMOD)
BAUD RATE 2400PASSLINETESTPARITYODD
LAVE PER TST NEEDED WRN STOP BIT 1 STOP
DATA LENGTH: 7 DATADISABLEDSECURITYLINEANNTSTNEEDEDWRNCODE : CODE DISABLEDDISABLEDDIALTYPETONE
PRINT TC VOLUMES ANSWER ON 1 RING
MODEM SETUP STRINGENABLED
TEMP COMPENSATION DIAL TONE INTERVAL: 32
VALUE (DEG F ): 60.0
STICK HEIGHT OFFSET AUTO TRANSMIT SETTINGS: DISABLED
ULLAGE: 90% AUTO LEAK ALARM LIMIT
DISABLEDH- PROTOCOL DATA FORMAT AUTO HIGH WATER LIMITHEIGHTDISABLEDDAYLIGHTSAVINGTIMEAUTOOVERFILLLIMITDISABLEDDISABLEDRE- DIRECT LOCAL PRINTOUT AUTO PRODUCTDISABLEDLOW
DISABLED
EURO PROTOCOL PREFIX AUTO THEFT LIMIT
DISABLEDSAUTODELIVERY START
DISABLED
AUTO DELIVERY END
DISABLEDSYSTEMSECURITYAUTOEXTERNAL I tip UT ONCODE : 000000 nTQORT -ED
MAINTENANCE HISTORY
DISABLED
AUTO EXTERNAL INPUT OFF /
DISABLED qb (
il'
AUTO SENSOR FUEL ALARM
DISABLED
AUTO ;SENSOR WATER ALARM
DISABLED
AUTO SENSOR OUT ALARM
DISABLED
RECEIVER SETUP:
NONE
AUTO DIAL TIME SETUP:
NONE
RS -232 END OF MESSAGE
DISABLED
AUTO DIAL ALARM SETUP
46illA tt,lUY
1:97
ODUCT CODE 1
ERMAL COEFF :.000700
NK DIAMETER 92.00
IVK PROFILE 1 PT
FULL VOL 9728
OAT SIZF-:
TER WARNING
GH WATER LIMIT
X OR LABEL VQL
ERFILL LIMIT
GH PRODUCT
LIVERY LIMIT
4.0 IN.
2.0
3.0
9728
909
8755
95i
9241
5%
486
W PRODUCT 500
AK ALARM LIMIT : 3
DDEN LOSS LIMIT: 50
NX TILT 2.20
OBE OFFSET 0.00
PHON MANIFOLDED TANKS
N014E
NE MANIFOLDED TANKS
NONE
AK MIN PERIODIC: 0%
0
AK III N ANNUAL 0yo
0
RIODIC TEST TYPE
STANDARD
NUAL TEST FAIL
ALARM DISABLED
RIODIC TEST FAIL
ALARM DISABLED
OSS TEST FAIL
ALARM DISABLED
N TEST AVERAGING: OFF
R TEST AVERAGING: OFF
NK TEST NOTIFY: OFF
K TST SIPHON BREAK:OFF
LIVERY DELAY 5 MIN
MP THRESHOLD 10.00°
Lr -hlt. 1 ttt 1 1"IJr1• HUU
TEST ON DATE : ALL TANK
JAN 29, 2009
START TIME : DISABLED
TEST RATE :0.20 GAL /HR
DURATIOIV : 2 HOURS
TST EARL`; STOP :DISABLED
LEAK TEST REPORT FORMAT
NORMAL
LIQUID SENSOR SETUP
L 1:87 STP
TRI —STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 2:DIESEL STP
DUAL FLT. HIGH VAPOR
CATEGORY : STP SUMP
L 3:91 STP
TRI —STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 4:87 ANN
NORMALLY CLOSED
CATEGORY : ANNULAR SPACE
L 5 :DIESEL ANN
DUAL POINT HYDROSTATIC
CATEGORY : ANNULAR SPACE
L 6:91 ANN
DUAL POINT HYDROSTATIC
CATEGORY : ANNULAR SPACE
L 7:VENT BOX
TRI —STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 8:NONE
NORMALLY CLOSED
CATEGORY : OTHER SENSORS
OUTPUT RELAY SETUP
R 1:87
TYPE:
STANDARD
NORMALLY CLOSED
TANK 0:
LIQUID SENSOR ALMS
L 1 :FUEL ALARM
L 3:FUEL ALARM
L I:SEI+SOR OUT ALARM
L 3:SENSOR OUT ALARM
L 3:WATER ALARM
L I :HIGH LIQUID ALARM
L 3:LIQUID WARNING
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL :FLOW COLLECT FAIL
R 2:DIESEL
TYPE:
STANDARD
NORMALLY CLOSED
TA14K #: 2
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 2:SENSOR OUT ALARM
L 2:HIGH LIQUID ALARM
R 3:91
TYPE:
STANDARD
NORMALLY CLOSED
TANK 0: 3
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 3 :SENSOR OUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL :FLOW COLLECT FAIL
Y63$9
SMARTSENSOR SETUP
s 1 :VAPOR PRESSURE
CATEGORY VAPOR PRESSURE
s 2:CANISTER
CATEGORY VAPOR VALVE
s S:ATM
CATEGORY ATM P SENSOR
s 9:DISP 1 -2
CATEGORY AIR FLOW METER
510:DISP 3 -4
CATEGORY A.IR FLOW METER
sll:DISP 5 -6
CATEGORY AIR FLOW PIETER
sl2:DISP 7 -8
CATEGORY AIR FLOW METER
sl3:DISP 9 -10
CATEGORY AIR FLOW METER
514:DISP 11 -12
CATEGORY AIR FLOW METER
EVR /ISD SETUP
E %JR TYPE: BALANCE
BALANCE NOZZLE TYPE
VST
VAPOR PROCESSOR TYPE
VEEDER-ROOT POLISHER
ANALYSIS TIMES
TIME: 10:00 All
DELAY MINUTES: 1
ACCEPT HIGH ORVR:
ENABLED
ISD HOSE TABLE
ID FP FL HL AA RR
01 01 01 02 01 03
02 02 02 02 O1 03
03 03 03 02 02 03
04 04 04 02 02 03
05 05 05 02 03 03
06 06 06 02 03 03
07 07 07 02 04' 03
08 08 08 02 04 03
09 09 09 02 05 03
10 16 10 02 05 03
11 17 11 02 06 03
12 18 12 02 06 03
ISD AIRFLOW METER MAR
ID SERIAL NUM LABEL
1 34514 DISP 1 -2
2 39498 DISP 3 -4
3 36972 DISP 5 -6
4 37267 DISP 7 -8
5 36516 DISP 9 -10
6 34444 DISP 11 -12
ISD FUEL GRADE HOSE MAP
1 2 3 4
FP MHH MHH MHH MHH AA
O1 101 301 201 U U 1
02 102 302 202 U U 1
03 103 303 203 U U 2
04 104 304 204 U U 2
05 105 305 205 U U 3
06 106 306 206 U U 3
07 107 307 207 4 U 4
08 108 308 208 4 U 4
09 109 309 209 U U 5
16 110 310 210 U U 5
17 211 111 911 3 U 6
18 212 112 912 3 U 6
LABEL TABLE
1: U14ASSIGNED
2: BLEND3
3: REGULAR
4: MID GRADE
5: PREMIUM
6: GOLD
7: BRONZE
8: SILVER
9: BLEND2
10: BLEND4
PMC SETUP
PMC VERSION: 01.03
VAPOR PROCESSOR TYPE
VEEDER -ROOT POLISHER.
ALARM HISTORY REPORT
SEI4SOR ALARM - - - -- L 1:87 STP
STP SUMP
SEI'ISOR OUT ALARMIlAY8- 2012 10:08 AM
FUEL ALARMMAY8, 2012 9:53 AM
SENSOR OUT ALARMMAY18, 2011 12:45 PM
HLMXI'i H 1;:i- J UK Y Xr-FUX 1
SENSOR ALARM
L 2:DIESEL STP
STP SUMP
SENSOR OUT ALARM
MAY S. 2012 10:09 AM
FUEL ALARM
MAY 8, 2012 9:51 AM
SENSOR OUT ALARM
MAY 18, 2011 12:45 PM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:91 STP
STP SUMP
SENSOR OUT ALARM
MAY 8, 2012 10:09 AM
FUEL ALARr l
MAY 9. 2012 9:50 AM
SENSOR OUT ALARM
MAY 18, 2011 12 :45 PM
ALARM HISTORY REPORT
SENSOR ALARM - - - -- L 4:87 ANN
ANNULAR SPACEFUELALARM
MAY 8, 2012 2:47 PM
FUEL ALARM
MAY 8, 2012 1:17 PM
FUEL ALARM
PIAV 8, 2012 11:13 AM
r
ALARM
HISTUR*f REPORT -
SEflEOR ALARM -
L S:DI SEL ANN
ANNULAR EPAALARM
ENS. O'Z OI,GI2 10:08 Arl
LOW LIQUID ALARMLQ129:52 PJ4
UrF
t'Sg
aQ1flLA"!45 PM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 6:91 ANN
ANNULAR SPACE
SENSOR OUT ALARM
MAY 8. 2012 10:09 All
LOW LIQUID ALARM
MAY 8, 2012 9:50 All
LOW LIQUID ALARM
NOV 28, 2011 12:11 All
y63Xt
A x x x X END X X x x X
ALARM HISTORY REPORT
SENSOR ALARM - -- --
L 7:VENT BOX
OTHER SENSORS
FUEL ALARM
MAY B. 2012 3:34 PM
FUEL ALARM
MAY 8, 2012 11:11 AM
SENSOR OUT ALARM
MAY 8, 2012 10:09 AM
0
zllG3`
4/384
MONITOR CERT. FAILURE REPORT
SITE NAME: C &M SHELL STATION DATE: 5/8/12
ADDRESS: 3605 ROSEDALE HWY TECHNICIAN: RICHIE MILLIPS
CITY: BAKERSFIELD SIGNATURE: 'go/
REPAIRS:
REPLACED TWO RED JACKET LEAK DETECTORS FX1V
REPLACED ONE BEAUDREAU 406 STAND ALONE SENSOR ON DISP 49/10
PARTS INSTALLED:
LEAK DETECTORS - OWNER SUPPLIED
1- BEAUDREAU 406 STAND ALONE SENSOR
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.