HomeMy WebLinkAbout3624 CALIFORNIA AVENUE (4)PL55 Appendix VI Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at.hftl)://www.waterboards.ca.gov.) MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: Stuart Petroleum Mobil Bldg. No.: Site Address: 3624 California Ave. City: Bakersfield Zip: Facility Contact Person: John Stuart Contact Phone No.: ( 661 ) 325 -3620 Make /Model of Monitoring System: Veeder Root TLS 350 Date of Testing /Servicing: 1 / 24 / 2012 B. Inventory of Equipment Tested /Certified Check the appropriate boxes to indicate specific equipment inspected /serviced: TanklD: DSL TanklD: X In -Tank Gauging Probe. Model: Veeder Root 846390XIn -Tank Gauging Probe. Model: Veeder Root 846390 X Annular Space or Vault Sensor. Model: Veeder Root 794390 X Annular Space or Vault Sensor. Model: Veeder Root 794390 X Piping Sump / Trench Sensor(s). Model: Veeder Root 794380 X Piping Sump / Trench Sensor(s). Model: Veeder Root 794380 Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model: X Mechanical Line Leak Detector. Model: Red Jacket FX1 DV X Mechanical Line Leak Detector. Model: Red Jacket FX1 V Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: X Tank Overfill / High -Level Sensor. Model: OPW 61 SO X Tank Overfill / High -Level Sensor. Model: OPW 61 SO Others eci equipment a and model in Section E on Page 2). Other(specify equipment t e and model in Section E on Page 2). TanklD: 87 TanklD: In -Tank Gauging Probe. Model: X In -Tank Gauging Probe. Model: Veeder Root 846390 X Annular Space or Vault Sensor. Model: Veeder Root 794390 E. Annular Space or Vault Sensor. Model: X Piping Sump / Trench Sensor(s). Model: Veeder Root 794380 Piping Sump / Trench Sensor(s). Model: Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model: X Mechanical Line Leak Detector. Model: VMI LD2000 Mechanical Line Leak Detector. Model: Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: X Tank Overfill / High -Level Sensor. Model: OPW 61 SO Tank Overfill / High -Level Sensor. Model: u Other specify a ui ment tyee and model in Section E on Page 2). Other(specify equipment t e and model in Section E on Pa e 2. Dispenser ID: 1 -2 Dispenser ID: 3-4 X Dispenser Containment Sensor(s). Model: BEI -406 X Dispenser Containment Sensor(s). Model: BEI -406 X Shear Valve(s). X Shear Valve(s). Dispenser Containment Floats and Chain(s). Dispenser Containment Floats and Chains . Dispenser ID: 5 -6 Dispenser ID: 7 -8 X Dispenser Containment Sensor(s). Model: BEI -406 X Dispenser Containment Sensor(s). Model: BEI -406 X Shear Valve(s). X Shear Valve(s). Dispenser Containment Floats and Chain(s). Dispenser Containment Floats and Chains . Dispenser ID: 9 -10 Dispenser ID: X Dispenser Containment Sensor(s). Model: BEI -406 Dispenser Containment Sensor(s). Model: X Shear Valve(s). Shear Valve(s). Dispenser Containment Floats and Chains Dispenser Containment Floats and Chain(s). If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment Identified in this document was Inspected /serviced in accordance with the manufacturers' guidelines. Attached to this Certification is Information (e.g. manufacturers' checklists) necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment For any equipment capable of generating such reports, I have also attached a copy of the report; (check all that apply): System set -up Alarm history re Technician Name (print): Stewart Bradlv Signatur Certification No.: 8141938 -UT License. No.: 481053 Testing Company Name: Kern County Construction, Inc Phone No.:( 661 ) 634 -9950 Testing Company Address: PO Box 6096, Bakersfield, CA 93386 Date of Testing /Servicing: 1 / 24 / 2012 Monitoring System Certification Page 1 of 4 12/07 2/21/07 D. Results of Testing/Servicing Software Version Installed: Complete the following checklist: X Yes No' Is the audible alarm operational? X Yes No' Is the visual alarm operational? X Yes No' Were all sensors visually inspected, functionally tested, and confirmed operational? X Yes No' Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No" If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? X N/A X Yes No` For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system N/A detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut -down? (Check all that apply) X Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut -down due to leaks and sensor failure /disconnection? X Yes; No. 7 Yes No' For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill prevention X N/A valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? % Yes' X No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. X Yes' No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; :1 Water. If es, describe causes in Section E, below. X Yes No' Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable X Yes No' Is all monitoring equipment operational per manufacturer's specifications? In Section E below, describe how and when these deficiencies were or will be corrected. Comments: 2/21/07 Monitoring System Certification Page 2 of 4 12/07 2/21/07 F. In -Tank Gauging / SIR Equipment: X Check this box if tank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No* Were all tank gauging probes visually inspected for damage and residue buildup? Yes No* Was accuracy of system product level readings tested? Yes No* Was accuracy of system water level readings tested? Yes No* Were all probes reinstalled properly? Yes No* Were all items on the equipment manufacturer's maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): C Check this box if LLDs are not installed. Complete the following checklist: X Yes No* For equipment start -up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all N/A that apply) Simulated leak rate: X 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h. X Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements? X Yes No* Was the testing apparatus properly calibrated? X Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak? N/A Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? X N/A Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or X N/A disconnected? Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or X N/A fails a test? Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected? X N/A X Yes No* Were all items on the equipment manufacturer's maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: Monitoring System Certification Page 3 of 4 12/07 4 2/21/07 Monitoring System Certification UST Monitoring Site Plan Site Address: '6J b LL' / i' U n i A e - Date map was drawn: / 2 Instructions If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the space provided, note the date this Site Plan was prepared. Monitoring System Certification Page 4 of 4 12/07 5 2/21/07 SWRCB, January 2006 Spill Bucket Testing Report Form Thisform is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and printouts from tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Stuarts Petroleum Mobil Date of Testing: 1 -24 -12 Facility Address: 3624 California Ave. Facility Contact: John Stuart Phone: 661- 325 -6320 Date Local Agency Was Notified of Testing : 1 -17 -12 Name of Local Agency Inspector (ifpresent during testing): Ester Durran 2. TESTING CONTRACTOR INFORMATION Company Name: Kern County Construction, Inc. PO Box 6096, Bakersfield, CA 93386 Technician Conducting Test: Stewart Bradly Credentials': X CSLB Contractor X ]CC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s): 481053 8141938 -UT 3. SPILL BUCKET TESTING INFORMATION Test Method Used: XHydrostatic Vacuum Other Test Equipment Used: Visual Equipment Resolution: 0.0" Identify Spill Bucket (By Tank Number, Stored Product, etc. I 87 2 91 3 DSL 4 Bucket Installation Type: X Direct Bury Contained in Sump X Direct Bury Contained in Sump X Direct Bury Contained in Sump Direct Bury Contained in Sum Bucket Diameter: 12" 12" 12" Bucket Depth: 12" 12" 12" Wait time between applying vacuum /water and start of test: 15 Min. 15 Min. 15 Min. Test Start Time (Ti): 8:20 8:20 8:20 Initial Reading (Rj): 7.5" 8.00" 8.25" Test End Time (TF): 9:20 9:20 9:20 Final Reading (RF): 7.5" 8.00" 98.25" Test Duration (TF — Ti): 1 Hr. I Hr. 1 Hr. Change in Reading (RF - Rj): 0.0" 0.0" 0.0" Pass /Fail Threshold or Criteria: 0.0" 0.0" 0.0" Test Result: X Pass Fail X Pass Fail X Pass Fail Pass Fail Comments — (include information on repairs made prior to testing, and recommendedfollow -up forfailed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature: Date: ` / State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. S',STE11 SETUP SYSTEM UNITS U.S SYSTEI °1 LHfJGL1H =aE ENGLISH SY'21TEM I,HTE.'TII °IE FORMAT I°1O PJ DD `i'1 "i''i' HH :111°1: :5 :;:1^1 DEL TACO 1,T)B I L 36?4 ' 1L I FURI1 I A AVE BHKERSFIELD CA 661-325-47710 SHIFT T I N1E 1 1 1: 59 PI-1 SHIFT T I f1E 2 D I SABLED SHIFT TIME '3 DISABLED SHIFT T I I^'1E 4 D I SABLED TANK PER TST NEEDED WRPJ DISABLED TANI' ANN TST HEEDED WRI'd DISABLED LINE RE— ENABLE I °IETHOD PASS LINE TEST L I NE PER T:T NEEDED WRPJ DISHBLED LINE ANN TST NEEDED WRPJ DISABLED PR I NT TC VC >LUMES ENABLED TEf °IP COMPEIIL "T I i;N VALUE (DEG F ) : 60.0 STICK HEIGHT OFFSET DISHBLED ULLAC= E: y C13 : H— PROTOCOL DHTA F0RIIHT HE I GHT DAYLIGHT SH' r I IV TIME ENABLED START DATE APR WEEK 1 SUN START T I f °lE 00 Hl °1 END DATE OCT WEEK r SUN END TIME 00 AI °1 RE —D I REC'T LoC'HL PR I fd . DISABLED Di - MA I NTENHNCE H I S DISABLED TANK CHHRT SECURITY DISHBLED CUSTOM ALARIIS DISABLED SERV I i'E NOT I C'E DISABLED ISO 3166 C ;U1'JTR'' 1ODE IIASS, DENS I T'i' DISABLED C:OI °lh'IIJIVIC'A'[ 1 I'd5 SETUP PORT SETT I f,G-'S : COMM BOARD : 1 t ED I I "1 i RS —'212 SEC;UR I T`.' CODE : DISABLED C'OMI°I BOARD , e R: BAUD RATE 1'*200 PHRITY ODD STS F' BIT 1 STOP LEIVi;TH : 7 DATA SECURITY DISABLED TRAPJSP'1 I T SETT I Nt 3 LEA}: HL,ARM 1-11111 L•' iHBLED TO HIGH +IATER L 11 °1 I T SABLED JTO OVERFILL LIf1IT ISABLED UTO LOW PRODUCT DISABLED FiUTO THEFT L I II I T D I SABLED AUTO DELIVERY START DISABLED AUTO DELIVER; END DISABLED AUTO EXTERNAL INPUT ON DISABLED AUTO EXTERNAL INPUT OFF DISABLED AUTO SENSOR FUEL HLHRNI DISABLED AUTO SENSOR WATER HL.ARI^1 DISABLED AUTO SENSOR OUT HLAR11 DISABLED RS —':'32 END OF IIESHI_ +E DISHBLED I N_THNI: SETUP — T 1:DIESEL PRODUCT CODE 1 THERMAL =C;EFF :. C100450 TAN}; D I AI IETER 96. 00 TANK PROFILE 1 PT FULL 'JOL 4000 E: 4.0 IN. ER LI11IT: 3.0 LABEL VOL: : 41 ' . L LII °1IT 3 3 1.. LIIIIT DUC:T RP'1 L I I'1 IT: LOSS L 111 IT: I T U FFSE'r 0 IHN I FOLDED THI -.: . E N I FOLDED TANK`: E LEAK 11 I N PERIODIC: MIN HN III UHL : D I C : TEST TYPE STANDARD L TEST FAIL ALARIh1 D I SABLED ODIC TEST FAIL HLARP'I D I SHBLED SS TEST FAIL HLARM DISHBLED 1V TEST HVERHG I NG : OFF I . "EST HVERHC: I IIG : OFF TEST NOTIFY: OFF UST SIPHON BREAK:OFF ER'i' DELAY 1 M I N i q 1 THRESHOLD 10.00% T : PRE11 -91 PRODUCT CODE 3 THER11AL CC'FFF :.000700 TANK D I AI1L I'ER 96.130 TANK PROF I I-L 1 PT FULL (.:,L 8000 T 3:IJNL -87 PRODUCT CODE THER11AL C_OEFF :.0007i TANK DIAMETER 96.00 TANK PROFILE 1 PT FULL VOL I2UDU HNNIJAL TEST FAIL HI_.ARt1 111 ',HBLED PERIODIC 'M- -T FAIL HLHRI1 D I -HBLED GROSS TEST 1=H I L HI_AR11 111 SABLED ANN TEST H' ?E)='A f PJ:_a: OFF PER TEST h', ?EkrG I PJC:: OFF TANY TEST PJOT I FY : OFF TI'411. TST S I PH!i1,J BREAK :OFF DELIVERY DELH'Y I P'1 I N PUMP THRESHOLD 10-00% ANNUAL TEST FAIL ALARI-1 D I SHBLED PER IfOD 11: TEST FHIL ALARfl U I SHBLED GROSS TEST FAIL HLHkhI DISHBLED ANN TEST HVERAG I PJG : OFF PER TEST AVERAG I t--Ii : OFF TANK TEST NOTIFY: OFF TNY; TST SIPHON BPEHK. :O1 , DEL I VERY DELH` ! 1 M . PUMP THRESHOLD : 10 .UU. LEAK TEST METHOD TEST ON DATE : ALL TANK JAN 29. 2009 START TIME : DISABLED TEST RATE :0.20 iAL:'HR DURATION H(.>URS TST EARL`; STOP : D I SABLED LEAK TE S'I REPORT FORMAT NORMAL LIQUID SEdSi_R SETUP L I:PREt'l -91 DUMP TR I —STATE (2--ANGLE FLOAT.) i_HTEGORY . :ATP SU11P L 2:IJIIL -87 TR I —STATE { :- l PJi_,LE FLOAT) C:ATEGOR'Y _TP SU11P L 3:DIESEL ANNULAR TR I — STHTE I PJi LE FLC :HT ) HTEC'- 'k'`;' i= ilVl'IULHR .-- F'HC:E L 4: D I ESEL SU11P TRI —STATE s.SIPlGLE FLOAT} CATEGORY . STP SUMP L 5:87 -91 ANNULAR TRI —STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE FLOAT S I 'E : 4.0 IN. FLOAT SIZ71": 4.0 IN. I ;JHTER WARN I NG 2.0 WATER WAR11 I NG 2.0 H I C:H WATER LIMIT: 3.0 H I i;H WATER L 11°1 I T: 3.0 MAX OR LABEL VOL: 1,2000 MHX OR LABEL VOL: 80130 OVERFILL LIMIT 90.`• OVERFILL LIMIT 90` 10800 7200 HIGH PRODUCI' 95% HIGH PRODU "C 95% 11400 7600 DEL I VERY L I M I T 10` DELIVER',' LIMIT 10% 1200 8130 LOW PRODUCT 80U LOW PRODUCT 500 LEHK ALARM LIMIT: 99 LEHK ALARP I LIMIT: 99 SUDDEN LOSS L 111 I T : 99 SUDDEN LOSS LIf °11T: 99 TANK TILT 5.00 TANK TILT 4.00 PROBE OFFSET 0.00 PROBE OFFSET' 0.00 SIPHON MAN I FOLDED TANKS SIPHON MAP- JIFOLDED TANKS T #: NONE Ttt : NONE LINE MAN I FOLDED THNI< :S LINE MANIFOLDED TANKS T #: NONE Ttt : NONE LEAK MIN PERIODIC: 0% LEHI' MIN PER I tD I': 0' % 0 U LEAK MIN HNNUHL 0% LEAK 11I N ANNUAL 0% 0 U PERIODIC' TEST TYPE PERIODIC TEST T`,''PE STHNDARD STHPJC!HkL, HNNIJAL TEST FAIL HI_.ARt1 111 ',HBLED PERIODIC 'M- -T FAIL HLHRI1 D I -HBLED GROSS TEST 1=H I L HI_AR11 111 SABLED ANN TEST H' ?E)='A f PJ:_a: OFF PER TEST h', ?EkrG I PJC:: OFF TANY TEST PJOT I FY : OFF TI'411. TST S I PH!i1,J BREAK :OFF DELIVERY DELH'Y I P'1 I N PUMP THRESHOLD 10-00% ANNUAL TEST FAIL ALARI-1 D I SHBLED PER If OD 11: TEST FHIL ALARfl U I SHBLED GROSS TEST FAIL HLHkhI DISHBLED ANN TEST HVERAG I PJG : OFF PER TEST AVERAG I t--Ii : OFF TANK TEST NOTIFY: OFF TNY; TST SIPHON BPEHK. :O1 , DEL I VERY DELH` ! 1 M . PUMP THRESHOLD : 10 .UU. LEAK TEST METHOD TEST ON DATE : ALL TANK JAN 29. 2009 START TIME : DISABLED TEST RATE :0.20 iAL:'HR DURATION H(.>URS TST EARL`; STOP : D I SABLED LEAK TE S'I REPORT FORMAT NORMAL LIQUID SEdSi_R SETUP L I:PREt'l -91 DUMP TR I —STATE (2--ANGLE FLOAT.) i_HTEGORY . :ATP SU11P L 2:IJIIL -87 TR I —STATE { :- l PJi_,LE FLOAT) C:ATEGOR'Y _TP SU11P L 3:DIESEL ANNULAR TR I — STHTE I PJi LE FLC :HT ) HTEC'- 'k'`;' i= ilVl'IULHR .-- F'HC:E L 4: D I ESEL SU11P TRI —STATE s.SIPlGLE FLOAT} CATEGORY . STP SUMP L 5:87 -91 ANNULAR TRI —STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE OUTPUT PELA; -1 1:87 T,l;F,F- , STANDARD NORMALLY CLOSED TANK #: 3 IN-THNK ALAR1121 T 3:HIGH WATER T 3:1-OW PRODUCT ALARI-1 LIQUID SENSOR ALf"IS L I :FUEL ALARM L 2:FUEL Al-ARM L 5:FUEL ALARM ISEj SITE HLARMS ANALYSIS TIl-lE;---', ISD GROSS PRES FOIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL isD SETUP FAIL MHH Ar ISD SENSOR OUT FAIL I SE) HOSE HLHRt-'lS FILL :GROSS COLLECT FAIL ALL: DEGRD COLLECT FAIL ALL: FLOW COLLECT FAIL R 91 TYPE: STANDARD NORMALLY CLOSED TANK 0: 2 I N-THNY ' ALARMS T 2H IGH WATER ALARM T 2:LOW PRODUCT ALARI'l LIQUID SENSOR ALl"I'S L 1*.FUEI- ALARM L 2:FUEL ALARI`l L Fj:FUEL ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PREP FA111 UP I L EVR TYPE: R 3:DIESEL TYPE: BHLHIICE NOZ-21-E TYPE STANDARD VST NORI-,IALLY CLOSED v4IOR PROC.E:SOR TYPE TANY 0: 1 \..IEED R-ROOT P"d - -'L I cl-' HER I N-TANb' HLARh9S ANALYSIS TIl-lE;---', T I :HIGH WATER ALHRM T I NE: 8::_-ICI H[°j T I :LOW PRODUCT ALmRm DELAY 1`11 t-41-ITES: 2 3 LIQUID SEfqSOR ALMS L 3: FUEL HLF)Rll HCCEPT HIGH MHH Ar L 4:FUEL ALARM ENABLED ISD HOSE TABLE CATEGORY I D FP FL 111, U u 01 00 ))) 02 cl I 02 u 0121 - 01 0 I 03 02 03 A2 A 2 o FCJ3 903 04 03 04 CI'--' - 0"-, 0 CATEGORY 05 04 05 02 03 O': U U 06 05 06 02 03 C, 07 06 07 02 04 C: SMARTSE1,48OR SETUP 08 07 0b 02 b 506 ';OF, 09 08 09 02 10 09 10 02 OF, i 0 U 4 C7ATEGOR' ll 1.4-F),,)R ',.,,'ALVE 508 908 0 U 4 I RFLOW HETER 1--lA! 2:DISP 1 - 21 IERIAL NUM LABELCATEGORYA [ R Fl-.()L-J tlETER 910 910 0 U 5 3: D I SP 3-4 10755 D I CIP CATEGORY AIR METER 40821 D I SID 5 -r40824DISP7-9 4:DISP 5 -r. 40817 DISF) 9-10 CATEGORY h I R FLO'k.1 IIETER 5:DISP 7-S JEL GPiADE HOSE 11HPCHTEGORYhIRMETER234 lliH MHH f-'IHH MHH Ar 6:DISF, 9-10 CATEGORY AIR FLO1,,3 IIETER 4i, 501 '901 U u I 502 902 U U I7: 1 -22 VAC- PRESS PSE FCJ3 903 U U 2CATEGORYPRE21`,URE 504 904 U U 2 1505 ---0Fi u U 3 8: tMl b 506 ';OF, U U 3 507 --jo? 0 U 4 508 908 0 U 4 509 909 0 U 5 910 910 0 U 5 BLE 31 GINJED IJD3 h D GRADE I 'Al IZE b: SILVER 9: BLEND2 10: BLENN PIC' SETUP R'ICI VERSlor-j: 01 .03 VAPOR F:'R()(_-,ESS0P T'/FE VEEDER-ROOT POLISHER