HomeMy WebLinkAbout3698 MING AVENUE (6)O /[) *d MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State ofCalifornia Authority Cited: Chapter 6 7, Health and Safely Code; Chapter 16, Division 3, Title 23, California Code ofRegulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work A copy ofthis form must be provided to the tank system owner /operator. The owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: SHELL Site Address: 3698 MING AVE Facility Contact Person: KHENG CHAO Make/Model ofMonitoring System: TLS -350 B. Inventory of Equipment Teste&Cerfified Check the appropriate boxes to indicate specific equipment inspected/serviced: City: BAKERSFIELD Contact Phone No.: Bldg. No.: Zip: Date of Testing/Servicing: 1112/2010 Tank ID: UNL87 Tank ID: PLUS89 Z In -Tank Gauging Probe. Model: MAGI Z In -Tank Gauging Probe. Model: MAGI Z Annular Space or Vault Sensor. Model: 302 Annular Space or Vault Sensor. Model: 301 Z Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model: 208 Fill Sump Sensor(s). Model: 208 Fill Sump Sensor(,). Model: 208 Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model: Electronic Line Leak Detector. Model: PLLD Electronic Line Leak Detector. Model: PLLD Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2). Tank ID: PREM91 Tank ID: DIESEL Z In -Tank Gauging Probe. Model: MAGI Z In -Tank Gauging Probe. Model: MAGI Z Annular Space or Vault Sensor. Model: 302 Annular Space or Vault Sensor. Model: 302 Z Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model: 208 Z Fill Sump Sensor(s). Model: 208 Z Fill Sump Sensor(s). Model: 208 Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model: Z Electronic Line Leak Detector. Model: PLLD Z Electronic Line Leak Detector. Model: PLLD Tank Overfill / High -Level Sensor. Model: FLAPPER Z Tank Overfill / High -Level Sensor. Model: FLAPPER Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2). Dispenser ID: 1 -2 Dispenser ID: 3-4 Z Dispenser Containment Sensor(s). Model: 406 Z Dispenser Containment Sensor(s). Model: 406 ShearValve(s). Z Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s). Dispenser ED: 5-6 ID: 7-8 Dispenser Containment Sensor(,). Model: 406 r Containment Sensor(,). Model: 406 Shear Valve(,). EDispenswer lve(,). Dispenser Containment Float(s) and Chain(s). r Containment Float(s) and Chain(s). Dispenser ID: Dispenser ID: Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model: Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s). If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers' guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessa to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capabliv, generating such reports, 1 have alsoattachedacopyofthereport; (check all that apply): System set -up ®Alarm ory report Technician Name (print): RICH PHILLIPS Signature: Certification No.: A29084/1035169-UT License. No.: C611 D40 809850 Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 392 -8687 Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308 Date of Testing/Servicing: 2/2112012 Page 1 of 4 UN- 036 —1/4 www.unidoes.org Rev. 01 /17/08 Monitoring System Certification D. Results of Testing/Servicing Software Version Installed: 329.01 Complete the following checklist: E Yes No* Is the audible alarm operational? E Yes No* Is the visual alarm operational? E Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational? E Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) E N/A operational? E Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut -down? (Check all that apply) ® Sump /Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut -down due to leaks and sensor failure /disconnection? E Yes; No. Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? Ifso, at what percent oftank capacity does the alarm trigger? % Yes* E No Was any monitoring equipment replaced? Ifyes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. Ifyes, describe causes in Section E, below. E Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable E Yes No* 1 Is all monitoring equipment operational per manufacturer's specifications? In Section E below, describe how and when these deficiencies were or will be corrected. E. Comments: Page 2 of 4 UN -036 — 2/4 www.unidocs.org Rev. 01 /17/08 Monitoring System Certification F. In -Tank Gauging / SIR Equipment: Al r Check this box iftank gauging is used only for inventory control. Check this box ifno tank gauging or SIR equipment is installed. This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No* Were all tank gauging probes visually inspected for damage and residue buildup? Yes No* Was accuracy of system product level readings tested? Yes No* Was accuracy of system water level readings tested? Yes No* Were all probes reinstalled properly? Yes No* Were all items on the equipment manufacturer's maintenance checklist completed? In Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): Complete the following checklist: Check this box if LLDs are not installed. Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? N/A Check all that apply) Simulated leak rate: ® 3 g.p.h.; 0.1 g.p.h; 0.2 g.p.h. Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No* Was the testing apparatus properly calibrated? Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak? N/A Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? N/A Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled N/A or disconnected? Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions N/A or fails a test? Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected? N/A Yes No* Were all items on the equipment manufacturer's maintenance checklist completed? In Section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: UN -036 — 3/4 Page 3 of 4 www.unidoes.org Rev. 01 /17/08 Monitoring System Certification UST Monitoring Site Plan Site Address; 3698 MING AVE. BAKERSFIELD, CA. b . . • _ y- - -i. - Date map was drawn: 2/] 1/2012 Ynstructions If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System Certification, On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic lino leak detectors; and in -tank liquid level probes (if used for leak detection). In the space provided, note the date this Site Plan was prepared. UN -036 — W Page 5 of 5 www.unidece.org 110Y. 01117/08 0 RICH ENVIRONMENTAL 5643 BROOKS CT. BAKERSFIELD, CA. 93308 OFFICE (661)392 -8687 FAX (661)392 -0621 PRODUCT LINE LEAK DETECTOR TEST WORK SHEET W /0 #: FACILITY NAME: SHELL FACILITY ADDRESS: 3698 MING AVE, BAKERSFIELD PRODUCT LINE TYPE: PRESSURE PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS BELOW P.S.I. OR SERIAL NUMBER 3 G.P.H. FAIL UNL87 L/D TYPE: ELECTRONIC YES p PASS SERIAL # VEEDER -ROOT PLUS89 L/D TYPE: ELECTRONIC YES p PASS SERIAL # VEEDER -ROOT PREM91 L/D TYPE: ELECTRONIC YES 0 PASS SERIAL # VEEDER -ROOT DIESEL L/D TYPE ELECTRONIC YES p PASS SERIAL # VEEDER -ROOT I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS. THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST OF MY KNOWLEDGE. TECHNICIAN: SIGNATURE: "ov - DATE: 2/21/12 l f. A/ SWRCB, January 2006 Spill Bucket Testing Report Form Thisform is intendedfor use by contractors performing annual testing ofUST spill containment structures. The completedform and printoutsfrom tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: SHELL Date of Testing: 2/21/12 Facility Address: 3698 MING AVE, BAKERSFIELD Facility Contact: KHENG CHAO Phone: Date Local Agency Was Notified ofTesting: Name of Local Agency Inspector (ifpresent during testing): ERNIE MEDINA 2. TESTING CONTRACTOR INFORMATION Company Name: RICH ENVIRONMENTAL Technician Conducting Test: RICH PHILLIPS Credentials. 0 CSLB Contractor X ICC Service Tech. 0 SWRCB Tank Tester 0 Other (Spec) License Number(s): 1035169 -UT 3. SPILL BUCKET TESTING INFORMATION Test Method Used: X Hydrostatic 0 Vacuum 0 Other Test Equipment Used: VISUAL Equipment Resolution: 0.00 Identify Spill Bucket (By Tank Number, Stored Product, etc. 1 87 2 89 3 91 4 DIESEL Bucket Installation Type: 0 Direct Bury X Contained in Sump 0 Direct Bury X Contained in Sump 0 Direct Bury X Contained in Sump 0 Direct Bury X Contained in Sum Bucket Diameter. 12" 12" 12" 12" Bucket Depth: 14" 14" 14" 14" Wait time between applying vacuum/water and start oftest: 30 MIN 30 MIN 30 MIN 30MIN Test Start Time (Tj): 9:15 9:15 9:15 9:15 Initial Reading (Rj): 14" 14" 14" 14" Test End Time (TF): 10:15 10:15 10:15 10:15 Final Reading (RF): 14" 14" 14" 14" Test Duration (TF — Ti): 1 -14OUR 1 -HOUR I -HOUR 1 -HOUR Change in Reading (RF -R,): 0" 0" 0" 0" Pass/Fail Threshold or Criteria: 0.00 0.00 0.00 0.00 Test Result: X Pass 0 Fail X Pass D Fail X Pass 0 Fail X Pass 0 Fail Comments — (include information on repairs made prior to testing•, and recommendedfollow -upforfailed tests) CERTIFICATION OF TEC ICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information ntained in this report is true, accurate, and infull compliance with legal requirements. Technician's Signature: Date: 2/21/12 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. ncv aiwv LtVtLVE3SI(N 330.01 RE— DIRECT LOCAL PRINTOUT DISABLED AUTO TRANSMIT SETTINGS: SOFTWARE# 346330 -100 —BCREATED — 10.07.23.17.25 EURO PROTOCOL PREFIX AUTO LEAK ALARM LIMIT S— MODULEts 330160 -004 —a S DISABLED °$ AUTO HIGH WATER LIMITSYSTEMFEATURES: DISABLEDPERIODICIN —TANK TESTSANNUAL AUTO OVERFILL LIMITIN —TANK TESTSISD SYSTEM SECURITY DISABLED. CODE : 000000 AUTO LOW PRODUCT D I SABL:ED MAINTENANCE HISTORY AUTO THEFT LIMIT DISABLED DISABLED AUTO DELIVERY START DISABLED TANK CHART SECURITY AUTO DELIVERY END DISABLED DISABLED AUTO EXTERNAL INPUT ON DISABLED SYSTEM SETUP CUSTOM ALARMS AUTO EXTERNAL INPUT OFF DISABLED DISABLED FEB 21. 2012 8:58 AUTO SENSOR FUEL ALARM DISABLED SERVICE NOTICE AUTO SENSOR WATER ALARM DISABLED DISABLED SYSTEM UNITS AUTO SENSOR OUT ALARM U.S, DISABLED SYSTEM LANGUAGE ISO 3166 COUNTRY ENGLISH CODE: SYSTEM DATE,ITIME FORMATPIONDDYYYYHH:MM :SS MASS/DENSITY SHELL DISABLED RECEIVER SETUP: 3698 MING AVE NONEBAKERSFIELD. CA SHIFT TIM£ 1 5:00 AMSHIFTTIME2DISABLEDSHIFTTIME3DISABLEDSHIFTTIME4DISABLED TANK PER TST NEEDED WRNDISABLED TANK ANN TST NEEDED WRNISABLED COMMUNICATIONS SETUP AUTO DIAL TIME SETUP: INE RE— ENABLE METHOD NONESASSLINETESTPORTSETTINGS: INE PER TST NEEDED WRNISABLED COMM BOARD : l (ED IM > ANN TST NEEDED WRN RS -232 SECURITY CODE : DISABLEDSINE RI(VT.TC VOLUMES COMM BOARD 2 (RS -232) NABLED BAUD RATE 1200 PARITY ODD EMP COMPENSATION STOP BIT 1 STOP ALUE (DEC F >: 60.0 DATA LENGTH: 7 DATA TICK HEIGHT OFFSET 232 SECURITY ISABLED CODE : DISABLED iLAGE. 90% COMM BOARD 3 (FXMOD) RS -232 END OF MESSAGE PROTOCOL DATA FORMAT BAUD RATE 2400 PARITY ODD DISABLED EIGHT RECIRECISION TEST DURATION STOP BIT 1 STOP AUTO DIAL ALARM— SETUP— — 1N DATA LENGTH: 7 DATA aYLIGHT SAVING TIME SECURITY NABLED CODE : CODE DISABLED FART DATE DIAL TYPE TONE aR WEEK 2 SUN ANSWER ON I RING FART TIME MODEM SETUP STRING 00 AM JD DATE DIAL TONE INTERVAL: 32 1V WEEK 1 SUN0TIME 00 AM IN-- TANK SETUP_ T I:REGULAR 87 PRODUCT CODE I THERMAL COEFF :.000700 TANK DIAMETER 89.75 TANK PROFILE 1 PT FULL VOL 11527 FLOAT SIZE: 4.0 IN. WATER WARNING 2.0 HIGH WATER LIMIT: 3.0 MAX OR LABEL VOL: 11527 OVERFILL LIMIT 90% 89.75 10374 HIGH PRODUCT 95% I PT 11527 10950 DELIVERY LIMIT 150 1729 LOW PRODUCT 500 LEAK ALARM LIMIT: 3 SUDDEN LOSS LIMIT: 50 TANK TILT 4.00 PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS TO: NONE LINE MANIFOLDED TANKS TO' NONE LEAK MIN PERIODIC: 0% 0 LEAK MIN ANNUAL ON - 0 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY 1 MIN PUMP THRESHOLD 10.000 1 G . Y1..U7 ulj PRODUCT CODE 2 T 3:PREMIUM 91 3 THERMAL COEFF :.000700 PRODUCT CODE COEFF :.0007000000700 TANK DIAMETER 89.75 THERMAL TANK DIAMETER 89TANKPROFILE FULL VOL I PT 11527 TANK PROFIEVOL 1 PT 11527L FLOAT SIZE: 4.0 IN. FLOAT SIZE, 4.0 IN. WATER WARNING HIGH WATER LIMIT: 2.0 3.0 WATER WARNING 2,0 3.0HIGHWATERLIMIT: OVERFILL ALIMITOL. 119m MAX OR LABEL VOL: 11527 10374 OVERFILL LIMIT 9010 10374 HIGH PRODULT 95% 10950 HIGH PRODUCT 95% 10950DELIVERYLIMIT15% 1729 DELIVERY LIMIT 150 115% LOW PRODUCT 500 500LEAKALARMLIMIT: 3 LOW PRODUCT 3SUDDENLOSSLIMIT: 50 LEAK ALARM LIMIT: LIMIT: 50TANKTILT4.03 SUDDEN LOSS 2.61PROBEOFFSET0.00 TANK TILT 0.00PROBEOFFSET SIPHON 1.1AN I FOLDED TANKS TO: NONE LINE MANIFOLDED TANKS TO: NONE LEAK MIN PERIODIC: 0% 0 LEAK MIN ANNUAL 0% p PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY 1 MIN PUMP THRESHOLD 10.00% SIPHON MANIFOLDED TANKS T#: NONE LINE MANIFOLDED TANKS TO: NONE LEAK MIN PERIODIC: O LEAK MIN ANNUAL : 0'/ 0 PERIODIC TEST TY TANDARD ANNUAL TEST ALAARMLDISABLED PERIODIC TEST GROSS TEST ALA M DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHO14 BREAK :OFF DELIVERY PUMP THRESHOLD : 10.00% 0 3:PREMIUM 91 TVP:2.0/3.QIN%FI9ERGLASS 2.0IN DIA LEN: 200 FEET 3.0IN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 3:PREMIUM 91 DISPENSE MODE: STANDARD SENSOR: NON - VENTED' PRESSURE OFFSET: O.OPSI MECHANICAL BLENDER: NO Q 5:DIESEL TYP:2.0/3.QIN FIBERGLASS 2.0IN DIA LEN: 200 FEET 3.0IN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 4:DIESEL DISPENSE MODE: STANDARD SENSOR: N014- VENTED PRESSURE OFFSET: O.OPSI MECHANICAL BLENDER: NO LINE LEAK LOCKOUT SETUP LOCKOUT SCHEDULE DAILY START TIME: DISABLED STOP TIME : DISABLED LEAK TEST METHOD - T 4:DIESEL TEST ON DATE ALL TANK PRODUCT CODE 4 JAN 29, 2009 THER•lAL COEFF :.000450 START TIME : DISABLED TANK DIAMETER : 89.75 TEST RATE :0.20 GAL /HR TANK PROFILE I PT DURATION 2 HOURS FULL VOL 9684 TST EARLY STOP:DISABLED FLOAT SIZE: 4.0 IN. LEAK TEST REPORT FORMAT NORMAL WATER WARNING : 2.0 HIGH WATER LIMIT: 3.0 MAX OR LABEL VOL: 9684 OVERFILL LIMIT r 6705 HIGH PR6UCT 95% 9199 DELIVERY LIMIT 1152 LOW pRODUCT 500 PRESSURE LINE LEAK SETUP LEAK ALARM LIMIT: 3 SUDDEN LOSS LIMIT: TANK TILT 2.79 PROBE OFFSET 0.00 G I:REGULAR 87 TYP•2.0 3,OIN FIBERGLASS SIPHON IlA1VJFOLDED TANKS 2.0IN DIA LEN: 200 FEET Tit: NONE LINE MANIFOLDED TANKS 3.0JN DIA LEN: 0 FEET TO: NONE SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LEAK MIN PERIODIC: 0'O LOW PRESSURE 0 PSI 010 T 1:REGULAR 87 LEAK MIN ANNUAL DISPENSE MODE: STANDARD SENSOR: NON- VENTED RESSURE OFFSET: O.OPSI PERIODIC TEST TYPESTANDARD MECHANICAL BLENDER: NO ANNUAL TEST ALARM DISABLED PERIODIC TARADISABLED GROSS TESTALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF Q 2:PLUS 89 TANK TEST NOTIFY: OFF TYP:2.0i3.0IN FIBERGLASS TNK TST SIPHON BREAK:OFF 2.0IN DIA LEN: 200 FEET 3.OIN DIA LEN: 0 FEET DELIVERY DELAY : 1 MIN PUMP THRESHOLD : 10.D0 °. SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:110 LOW PRESSURE 0 PSI T 2:PLUS 89 DISPENSE MODE: STANDARD SENSOR: NON- VENTED PRESSURE OFFSET: O.OPSI MECHANICAL BLENDER: NO 0 3:PREMIUM 91 TVP:2.0/3.QIN%FI9ERGLASS 2.0IN DIA LEN: 200 FEET 3.0IN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 3:PREMIUM 91 DISPENSE MODE: STANDARD SENSOR: NON - VENTED' PRESSURE OFFSET: O.OPSI MECHANICAL BLENDER: NO Q 5:DIESEL TYP:2.0/3.QIN FIBERGLASS 2.0IN DIA LEN: 200 FEET 3.0IN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 4:DIESEL DISPENSE MODE: STANDARD SENSOR: N014- VENTED PRESSURE OFFSET: O.OPSI MECHANICAL BLENDER: NO LINE LEAK LOCKOUT SETUP LOCKOUT SCHEDULE DAILY START TIME: DISABLED STOP TIME : DISABLED SMARTSENSOR SETUP- LIQUID SENSOR SETUP PLLD LINE DISABLE SETUP s 1:CARBON CANIST4R CATEGORY VAPOR VALVE L 1:87 ANNULAR TRI -STATE (SINGLE FLOAT) Q 1:REGULAR 87 s 2:VAPOR PRESSURE CATEGORY : ANNULAR SPACE CATEGORY VAPOR PRESSURE LIQUID SENSOR ALMS L 3:FUEL ALARM s 3:_DISP 3 -4 L 3'SENSOR OUT ALARM CATEGORY AIR FLOW METER L 2:87 FILL SUMP TRI -STATE (SINGLE FLOAT) ISD SITE ALARMS s 4:DISP 1 -2 CATEGORY : PIPING SUMP ISD GROSS PRES FAIL CATEGORY AIR FLOW METER ISD DEGRD PRES FAIL ISD R 5AIRL3:87 STP SUMP ISD VPPPRESEFAILAIL CATEGORY FLOW METER TRI -STATE (SINGLE FLOAT) ISD VP STATUS FAILCATEGORY : STP SUMP s 6:DISP 7 -8 ISD HOSE ALARMS CATEGORY AIR FLOW METER 89 ANNULARL4:89 AN ALL:GROSS COLLECT FAILALL:FLOW COLLECT FAIL s 8:ATMSINGLEFLOAT) CATEGORY ATM P SENSORCATEGORY : ANNULAR SPACE G 2:PLUS 89 LIQUID SENSOR ALMS L 6:FUEL ALAR'lL5:69 FILL SUMP L 6:SENSOR OUT ALARMTRI -STATE (SINGLE FLOAT) CATEGORY : PIPING SUMP ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAILL6:89 STP ISD VAPOR LEAK FAILTRI - STATE (SINGLE FLOAT) 1 SD VP PRES FAILCATEGORYSTPSUMPISDVPSTATUSFAIL ISD HOSE ALARMS7:91 ANNULAR ALL :GROSS COLLECT FAIL EVR /ISD SETUPTRI -STATE (SINGLE FLOAT) ALL:FLOW COLLECT FAILATEGORY : ANNULAR SPACE Q 3:PREMIUM 91 EVR TYPE: BALANCE LIQUID SENSOR ALMS8:91 FILL SUMP L 9:FUEL ALARM BALANCE NOZZLE TYPECRI -STATE (SINGLE FLOAT) L 9:SENSOR OUT ALARM VSTATEGORY : PIPING SUMP ISD SITE ALARMS VAPOR PROCESSOR TYPE ISD GROSS PRES FAIL VEEDER -ROOT POLISHER9:91 STP RI -STATE (TINGLE FLOAT) ISD DEGRD PRES FAIL ISD VAPOR LEAK FAILATEGORY : STP SUMP ISD VP PRES FAIL ANALYSIS TIMES ISD VP STATUS FAIL TIME: 10:00 AM IO:DIESEL ANIVULAR ISD HOSE ALARMS DELAY MINUTES: 1 RI -STATE (SINGLE FLOAT) ALL:GROSS COLLECT FAILATEGORYANNULARSPACEALL:FLOW COLLECT FAIL ACCEPT HIGH ORVR: DISABLED Q 5:DIESEL 11:DIESEL PILL SUMP LIQUID SENSOR ALMS ISD HOSE TABLE ID FP FL HL AA RR RI -STATE (SINGLE FLOAT) L12:FUEL ALARMATEGORY : PIPING SUMP L12:SENSOR OUT ALARM OI Ol 01 02 02 00 02 02 02 02 02 00 12:DIESEL STP 03 03 03 02 01 00 04 04 04 02 01 00 RI-STATE (SINGLE FLOAT) 05 05 05 02 03 00ATEGORYSTPSUMP060606020300 07 07 07 02 04 00 OB 08 08 02 04 00 ISD AIRFLOW METER MAP ID SERIAL NUM LABEL 1 38958 DISP 3 -4 2 38933 DISP 1 -2 3 38919 DISP 5 -6 4 37771 DISP 7 -8 ISD FUEL GRADE HOSE MAP 1 2 3 4 FPMHH MHH MHHMHH AA 01 101 201 301 U U 2 02 102 202 302 U U 2 03 103 203 303 4 U 1 04 104 204 304 4 U 1 05 105 205 305 U U 3 06 106 206 306 U U 3 07 107 207 307 4 U 4 08 108 208 308 4 U 4 LABEL TABLE 4-------------- 1 : UNASSIGNED 2: BLEND3 3: REGULAR 4: MID GRADE 5: PREMIUM 6: GOLD 7: BRONZE 8: SILVER 9: BLEND2 10: BLEND4 PMC SETUP PMC VERSION: 01.03 VAPOR PROCESSOR TYPE VEEDER -ROOT POLISHER ALARM HISTORY REPORT L 1:87ANNULARLARM - - - -- ANNULAR SPACESENSOROUTALARMFEB21, 2012 10:34 FUEL ALARM FEB 21, 2012 9:38 FUEL ALARM JAN 14, 2011 10:25 ALARM HISTORY REPORT SENSOR ALARM - - - -- L 2:67 FILL SUMP PIPING SUMP SENSOR OUT ALARM FEB 21, 2012 10:34 FUEL ALARM FEB 21, 2012 9 :37 SENSOR OUT ALARM JAN 14. 2011 10:24 SENSOR ALARM - - - -- L. 3:87 STP SUMP STP SUMP SENSOR OUT ALARM FEB 21, 2012 10:34 FUEL ALARM FEB 21, 2012 9:59 FUEL ALARM FEB 21, 2012 9:36 ALARM HISTORY REPORT SENSOR ALARM L 4:69 ANNULAR ANNULAR SPACE SENSOR OUT ALARM FEB 21, 2012 tO:34 FUEL ALARM FEB 21, 2012 9:39 SENSOR OUT ALARM JAN 14, 2011 10:24 ALARM HISTORY REPORT SENSOR ALARM - - - -- L 5:89 FILL SUMP PIPING SUMP SENSOR OUT ALARM FEB 21, 2012 10:34 FUEL ALARM FEB 21, 2012 9:40 SENSOR OUT ALARM JAN 14, 2011 10 :24 ALARM HISTORY REPORT SENSOR ALARM - - - -- L 6:89 STP STP SUMP SENSOR OUT ALARM FEB 21, 2012 10:34 FUEL ALARM FEB 21, 2012 10:00 FUEL ALARM FEB 21, 2012 9:51 ALARM HISTORY REPORT SENSOR ALARM L 7:91 ANNULAR ANNULAR SPACE SENSOR OUT ALARM FEB 21, 2012 10 :34 FUEL ALARM FEB 21, 2012 9:41 FUEL ALARM SEP 15, 2011 8:47 ALARM HISTORY REPORT SENSOR ALARM - - - -- L 8:91 FILL SUMP, PIPING SUMP SENSOR OUT ALARM FEB 21. 2012 10:34 FUEL ALARM FEB 21. 2012 9:41 SENSOR OUT ALARM JAN 14. 2011 10:24 ALARM HISTORY REPORT' SENSOR ALARM - - -- L 9:91 STP - STP SUMP SENSOR OUT ALARMFEB21. 2012 10:34 FUEL ALARMFEB21, 2012 10:00 FUEL ALARMFEB21. 2012 9:47 ALARM HISTORY REPORT SENSOR ALARM 1-10:DIESEL ANNULAR ANNULAR SPACE SENSOR OUT ALAR11 FEB 21, 2012 10:34 FUEL ALARM I2 9:42FEB21, SENSOR OUT ALARM JAN 14, 2011 10:24 ALARM HISTORY REPORT FILL ALARM PIPING SUMP SENSOR OUT ALARMFEB21, 2012 10:34 FUEL ALARMFEB21. 2012 9:42 SENSOR OUT ALARMJAN14. 2011 10:24 ALARM HISTORY REPORT L12:DIESrELOSTpLARh1 -- STP SUMP SENSOR OUT ALARMFEB21, 2012 10:34 FUEL ALARMFEB21. 2012 10 :00 FUEL ALARMFEB21, 2012 9:48 MONITOR CERT. FAILURE REPORT SITE NAME: MING SHELL DATE:. -)--j 2- ADDRESS: 3698 MING AVE CITY: BAKERSFIELD REPAIRS: PARTS INSTALLED:I+ TECHNICLA2 SIGNATURE: L b" /'-"I THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE. A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SrrE FOR YOUR CONVIENENCE.