HomeMy WebLinkAbout3699 WILSON ROAD (8)MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: HP Go Go
Site Address: 3699 Wilson Road City: Bakersfield
Facility Contact Person: Alondra Hernandez
Make /Model of Monitoring System: Veeder -Root TLS -350
B. Inventory of Equipment Tested /CertifiedChecktheappropriateboxestoindicatespecincequipmenti®pectediterviced:
Bldg. No.:
Zip: 93309
Contact Phone No.: 661 - 835 -8044
Date of Testing/Servicing: 5/4/2011
Tank ID: 12000 gal. Regular Tank ID: 12000 gal. Regular 2
X] In -Tank Gauging Probe. Model: 847390-109 x] In -Tank Gauging Probe. Model: 847390 -109
x] Annular Space or Vault Probe. Model: 794390-303 x] Annular Space or Vault Sensor. Model: 794390 -303
x] Piping Sump / Trench Sensor(s). Model: 794380-208 Piping Sump / Trench Sensor(s). Model: Veeder -Root
X] Fill Sump Sensor(s) Model: Veeder -Root X] Fill Sump Sensor(s). Model: Veeder -Root
J Mechanical Line Leak Detector. Model:FX1V X] Mechanical Line Leak Detector. Model: FX1V
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
LxJ Tank Overfill / High Level Sensor. ModeI:OPW -6I -SO Tank Overfill / High Leval Sensor. Model: OPW -61-SO
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2)
Tank ID: 12000 gal. Super Tank ID: Waste Oil
x] In -Tank Gauging Probe. Model: 847390-109 In -Tank Gauging Probe. Model:
x] Annular Space or Vault Sensor. Model:794390 -303 X Annular Space or Vault Sensor. Model: 794390 -420
X] Piping Sump / Trench Sensor(s). Model:Veeder -Root Piping Sump / Trench Sensor(s). Model:
X] Fill Sump Sensors(s). Model: Veeder -Root X] Fill Sump Sensor(s). Model: Veeder -Root
C1 Mechanical Line Leak Decector. Model:FX1V Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
rxl Tank Overfill / High Level Sensor. Model:OPW -6I-SO Tank Overfill / High Level Sensor. Model:
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2)
Dispenser ID: .1 & 2 Dispenser ID: 3 & 4
n Dispenser Containment Sensor(s). Model: Veeder -Root x] Dispenser Containment Sensor(s). Model: Veeder -Root
X] Shear Valve(s). x] Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s)
Dispenser ID: 5 & 6 Dispenser ID: 7 & 8
x] Dispenser Containment Sensor(s). Model: Veeder -Root x] Dispenser Containment Sensor(s). Model: Veeder -Root
x] Shear Valve(s). x] Shear Valve(s).
Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /services in accordance with the
manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating
such reports, I have attached a copy of the report; (check all that apply) Q S Set -up AI rm h!175 r ort
Technician Name (print): Bryan A Self Signature:
Certification No: B37501 License No: 804904
Testing Company Name: Confidence UST Services, Inc.
Site Address: 3699 Wilson Road, Bakersfield, CA 93309
Phone No: 800 - 339 -9930
Date of Testing/Servicing: 514/2011
D. Results of Testing/Servicing
Software Version Installed:
Complete the following checklist:
x] Yes No* Is the audible alarm operational?
x Yes No* T-s—tFe-Visual alarm operational?
x I Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
x Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Lxj Yes No* Ifalarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) HN/A operational?
x Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? Ifyes:
which sensors initate positive shut - down? Lx] Sumplfrench Sensors [x] Dispenser Containment Sensors
Did you confirm positive shut -down due to leaks and sensor failure /disconnected? [X] Yes; No;
X] Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
L] N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at
the tank fill point(s) and operating properly? If so, at what percent oftank capasity does the alarm
trigger? 90 %
Yes* No Was any monitoring equipment rep ac ? IfYes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
x] Yes* No Was liquid found inside any secondary containment systems designed as dry systems?
Product; U Water. If yes, describe causes in Section E, below.
N * Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if app icable. Mes No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, discribe how and when these deficiencies were or will be corrected.
E. Comments: I replaced the Veeder -Root Sensor in the regular Fill Sump with a 794380 -208 sensor.
I also pulled out about 35 gallons of water from the super fill sump.
F. In -Tank Guaging / SIR Equipment: [X] Check this box if tank guaging is used only for inventory control.
Check this box if tank guaging -or SIR equipment is installed.
This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Lx] Yes No* Has all input wiring been inspected for proper enter and term ination,including testing for ground faults?
Yes No* Were all tank guaging probes visually inspected for damage and residue buildup?
Yes F71 No* Was accuracy of system product level readings tested?
x Yes No* Was accuracy of system water level readings tested?
For machamca LLD's, does the LLD restrict product ow i it detects a leak?
Yes No* Were all probes reinstalled properly? xj
U Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLD's are not installed.
Complete the following checklist:
x] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance?
Check all that apply) Simulated leak rate: E3 g.p.h.: 0.1 g.p.h.; 0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes 7 No Was the testing apparatus properly calibrated?
Yes For machamca LLD's, does the LLD restrict product ow i it detects a leak? LN/A
Yes No* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak?
x] N/A
Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is
x] N/A disabled or disconnected?
Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system
Cx] N/A malfunction or fails a test?
Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected?
U N/A
Lxj Yes No I Were all items on the equipment manufacturer's maintenance checklist completed?
In the section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments: There is a problem with the way the LLD's are wired. To insure that the LLD are working correctly, and
catching the we had to disconnect the regular 2 tank. At this time we are trying to figure out a way to fix the wireing problem.
HP GO GO
3369 WILSON RD
6AKERSFIE ,-D CA 93309
MAY 4. 2311 9:05 AM
SYSTEM :3TATUS REPORT
T I:DELIV3RY- NEEDED
T 3; DEL IV, -R1' NEEDED
INVENTORY REPORT
T I: SUPREME
VOLUME 706 GALS
ULLAGE. 11143 GALS
90% ULLAG3m 9958 GALS
TC VOLUME = 698 GALS
HEIGHT 13.19 INCHES
WATER VOL 9 GALS
WATER 0.75 INCHES
TEMP 75.7 DEG F
T 2: UNLEADED 2
VOLUME = 1788 GALS
ULLAGE a 10061 GALS
90% ULLAG'. =- 8876 GALS
TC VOLUME a 1765 GALS
HEIGHT = 25.03 INCHES
WATER. VOL - 0 GALS
WATER a 0.00 INCHES
TEMP = 77.4 DEG F
T 3: UNLEADED 1
VOLUME v 1713 GALS
ULLAGE a 10136 GALS
90% ULLAG E!- 8951 GALS
TC VOLLIME = 1694 GALS
HEIGHT a 24.29 INCHES
WATER VOL m 0 GALS
WATER = 0.00 INCHES
TEMP = 75.7 DEG F
x x x* x END x x x w w
SYSTEM SETUP - - - - -
MAY 4.__,2 D.14 -,_9:05 AM
SYSTEM UNITS
U.S.
SYSTEM LAVGUAGE
ENGLISH
HP GO GO
3369 WILSON PEI
BAKERSFIE:J? CA 93309
SH 1 FT '1.1 M? i : D I.SABLED
SHIFT TNT 2 : DISABLED
SHIFT TIM= 3 : DISABLED
PER (OD 1 +.: 'fEST WARN 1 NGS
DISABLED
ANNUAL TEST WARNINGS
DISABLED
SYST131 SE,_ UR I T' '
CODE : 001000
UUMMUN I CAT I ONS Sh:.i'IJP ^ l
PORT SET"I' I NGS :
NONE FOUND
RS -232 SEl,URITY
CODE : 003000
1149-232 EN') OF MESSAGE
DISABLED `
IN-TANK S:jfUP
T I : SUPREME
PRODUCT CODE I
THERMAL COEFF :.000700
000700
TANK DIAM3TER 120.00
TANK PROFILE 4 PTS
FUEL VOL 11849
90;. 0 104'.H. VOL 9894
6,Q:10' 1'0,'H VOL 6143
30..01 ljN'3H VOL : 2313
FL'OAT' S Z-2: 4.0 INCHES
WATER - WAR- g-I,NG -:.: 1:,0
3.0HIGHWATVLIMIT:
MAX OR LA'3EL VOL: 11849
OVERFILL '_IM[T 90%
10664
HIGH PRODJCT 95%
11256
DELIVERY 15%
1777
LOW PRODUCT 600
LEAK ALARM LIMIT: 8
SUDDEN LOSS LIMIT: 25
TANK TILT - 0.50
MANIFOLDED TANKS
Tit: NONE
LEAK MIN ANNUAL 0
PERIODIC TEST TYPE
STANDARD
ANNUAL TE3T FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
CROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 3 MIN
T 2:UNLEA)ED 2
PRODUCT CODE 2
THERMAL CoEFF 000700
TANK DIAM :rTER 120.00
TANK PROFILE 4 PTS
FULL VOL 11849
90.0 I Nt'H VOL 9894
60.0 1 ro`H VOL 61.43
30.0 IN,,H VOL 2313
FLOAT SIZ3: 4.0 INCHES
WATER WARVING 1.0
HIGH WATER LIMIT: 3.0
MAX OR LA:3EL'VOL: 11849
OVERFILL LIMIT 9011
10664
HIGH PRODUCT 951.1
11256
DELIVERY LIMIT 15%4
1777
LOW PRODUCT 600
LEAK, ALARM LIMIT: 8
SUDDEN LOSS LIMIT: 25
TANK TILT 0.75
MAN I FO1.DE:) TANKS
Tit: NONE
LEAK. MIN ANNUAL 0
PERIODIC TEST TYPE
QUICK
ANNUAL TENT FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY ,)ELAY 3 M 1 N
T 3: UNLEA;)ED l
PRODUCT CODE 3
THERMAL COEFF :.000700
TANK D I AM:ETER 120.00
TANK PROFILE 4 F' CS
FULL VOL 11849
50.0 INCH VOL 9894
E0.0 IN13H VOL 6143
30.0 IN,;H VOL 2313
FLOAT SIZE: 4.0 INCHES
WAT9R WARNING 1.0
HIGH WATER LIMIT: 3.0
MAX OR LA3EL VOL k 11849
OVERFILL -IM1T 9on
10664
HIGH PRODJCT 95:
11256
DELIVERY :.IM1T 15yo
1777
LOW PRODL4:T 600
LEAK ALARIh LIMIT: 8
SUDDEN LOSS LIMIT: 25
TANK TILT 0.00
MANIEOLDED TANKS- " - -t,
TO: NONE
LEAK MIN ANNUAL 0
PERIODIC TEST TYPE
QUICK
ANNUAL TE:3-T FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TES'C FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY :BELAY . 3 MIN
LEAK TEST ME'T'HOD
TEST ON DENTE : ALL TANK
NOV 24, 2308
START TIMT : 12:01 AM
TEST RATE :0.20 GAL /HR
DURATION : 2 HOURS
LINE LEAK DETECTOR SETUP
l' ry,E_LEAK TEST SETUP - -
TES'f ON A TE ALL, L1 NE.S
JAN 1. 2107
START 'TI Mz : DISABLED
TEST PATE :0.20 GAL /HR
LINE LEAK LOCKOUT SETUP
LOCKOUT S, :HEDULE
DAILY
START TIM' =: DISABLED
STOP TIME : DISABLED
LIQUID SENSOR SETUP
L 1:
DUAL FLOAT HYDROSTATIC
CATEGORY : DISPENSER PAN
L 2:WASTE OIL ANNULAR
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 3:WASTE OIL SUMP
TRI -STATE ( SINGLE FLOAT)
CATEGORY : PIPING SUMP
L 4:WASTE OIL HI LEVEL
TRI -STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 5:DISP 1 -2
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 6:DISP 3 -4
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 7:DISP 3 -6
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 8:DISP 7 -8
TRI -STATE (SINGLE FLOAT)
CATJEGORY : DISPENSER PAN
L 9:91 ANNULAR
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
1-10:91 Fl-
TRI -STATE (SINGLE FLOAT)
CATEGORY : PIPING SUMP
Ll1:91 ST?
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L12:67 2 ANNULAR
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L13:87 2 . :ILL
TRI -STATE (SINGLE FLOAT)
CATEGORY : PIPING SUMP
L14:07 2 2TP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L15:87 ANNULAR
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L16:87 Fl.: L
TRI -STATE (SINGLE FLOAT)
CATEGORY : PIPING SUMP
OUTPUT RE`_AY SETUP SENSOR'ALARIM
1.11:91 ST_ SENSOR ALARM - ----
3369 WILSON RD
TYPE:
L 9:91 ANNULAR
BAKERSFIE, --D CA 93309
STP SUMP
FUEL ALARM
ANNULAR VACE
NORMALLY CLOSED
FUEL ALARM FUEL ALARMMAY4, 2311 9:29 Ah! MAY 4. 2311 9:46 AM
R.I:SUPREME
T 3:HICH WATER ALARM
TYPE:
SYSTEI °I;'FATUS REPORT
STANDAR')
I• 1 : DEL I V. -RY NEEDED
LIQUID SENSOR ALMS
NORMALLY j "LOSED
ALL:FUEL ALARM BEN30R ALARM - - - -- T 3:11ELIV3RY NEEDED
IN-TANK N -ARMS
L16-:87 F l " L L 10 : F UEL P3LARM
T.I:HIGH WATER ALARM
LINE DISA3LE SETUP FUEL ALARIN °
MAY 4, 2 )1 1 9:41 AM
T I:LOW '?RODUCT ALARM 5-- SENSOR ALARM ----- SENSOR ALARM - -- --
1'4 : 87 2 :STP L 10:91 F 1: L
LIQUID SENSOR ALMS STP SUMP '
FUEL ALARM.
PIPING SUMP
ALL:FUEL ALARM
ALL:SENS•)R OUT ALARM MAY '4, 2311 9:30 AM FUEL ALARM
MAY 4, 2311 9:48 AM
ALL:SHOR'P ALARM
R 2:87 2
TYPE:
STANDARD
NORMALLY CLOSED SE0 OR ALARh1 SENSOR ALARM - - - -- L 1: 1.10:91 Fl"L
IN-TANK "RMS DISPENSER PAN PIPING SUMP
T.2 :HIGH WATER ALARM LOW LIQUID ALARM FUEL ALARM
T 2:LOW ?RODUCT ALARM MAY 4. 2311 9:32 AM MAY 4. 2311 9:49 AM
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHOR'C ALARM
SENSOR ALARM - - - -- HP GO GO
1.12:87 2 ANNULAR 3369 WIL9)N RD
ANNULAR S?ACE BA}.ERSF I E':D CA 93309
FUEL ALARM
MAY 4, 2111 9:43 AM MAY 4, 2311 9:50 AM
SYSTEM :STATUS REPORT
T 1:DELIV:z-RY NEEDED
T 3 :DEL1vz_RY NEEDED
SENSOR ALARM - - --- L10:FUEL XARML13:87 2 !ILL
PIPING SUI'IP
FUEL ALARM
MAY 4. 2311 9:45 AM
SENSOR ALARM -- --- HP GO GO
R 3:87 1 L15:87 ANVULAR 3369 WILSON RD
TYPE: ANNULAR S?ACE BAKERSFIE, --D CA 93309
STANDARD FUEL ALARM
NORMALLY CLOSED MAY 4, 2311 9:38 AM
MAY 4 .. 23 1 1 9: 50 All
I N -TANK 'A'.'ARMS
T 3:HICH WATER ALARM
T 3:LOW ?RODUCT ALARM SYSTEI °I;'FATUS REPORT
I• 1 : DEL I V. -RY NEEDED
LIQUID SENSOR ALMS
ALL:FUEL ALARM BEN30R ALARM - - - -- T 3:11ELIV3RY NEEDED
ALL:SENS-)R OUT ALARM
AL.L : SHORT ALARM L16-:87 F l " L L 10 : F UEL P3LARMPIPINGSUMP
LINE DISA3LE SETUP FUEL ALARIN °
MAY 4, 2 )1 1 9:41 AM
SENSOR ALARM - - - -- HP GO GO
1.12:87 2 ANNULAR 3369 WIL9)N RD
ANNULAR S?ACE BA}.ERSF I E':D CA 93309
FUEL ALARM
MAY 4, 2111 9:43 AM MAY 4, 2311 9:50 AM
SYSTEM :STATUS REPORT
T 1:DELIV:z-RY NEEDED
T 3 :DEL1vz_RY NEEDED
SENSOR ALARM - - --- L10:FUEL XARML13:87 2 !ILL
PIPING SUI'IP
FUEL ALARM
MAY 4. 2311 9:45 AM
SENSOR ALARM - -- --
L 5:D1SP 1 -2
DISPENSER PAN
FUEL ALARM
MAY 4. 2711 9:54 AM
ui
SEN:30R ALAP41:= --
I- 6:DISP 3 -4
PISPENSER PAN
FUEL- ALARM
MAY 4, 2711 9:55 AM
SEN30R ALARM
L 8 :DISP 7 -8
DISPENSER PAN
FUEL ALARM
MAY 4, 2711 0:57 AM
SENSOR ALARM - -- --
L 1:
DISPENSER PAN
SENSOR OUT ALARM
MAY 4. 2311 9:57 AM
SENSOP ALARM
L 7 DISP 5 -6
DISPENSER PAN
FUEL ALARM
MAY 4. 2311 10:01 AM
SEN:30R ALARM -- - --
i_ 1
DISPENSER PAN
LOW LIQU1 :) ALARM
MAY 4. 2711 10:03 AM
HP 00 GO
3369 WILSON RD
EAKENSFIE --D CA 93309
MAY 4, 2711 10:04 AP1
SYSTEM :STATUS REPORT
T 1 : DEL I V.RY NEEDED
T 3:DELIV -RY NEEDED
L I:LOW LIQUID ALARM
HP GO GO
3369 WILSON RD
BAKERSF i E:.D CA 93119
MAY 4. 2)11 10:06 AM
SYSTEM I.,,IATUS REPORT
T I : DEL I V; RY NEEDED
T 3:DELIV =RY NEEDED
L I:LOIJ LIQUID ALARM
4
HP GO GO
3369 WILSON RD
BAI:FRSF I E:_D CA 93309
MAY 4. 2311 10:14 AM
S-M. CM :STATUS REPORT
T I:DELIVL -RY NEEDED
T 3:DELIV2RY NEEDED
SEN:sOR ALARM - -_
L 9 :91 ANNULAR
ANNULAR S?ACE
SENSOR OUT ALARM
MAY 4. 2311 10:'14 All
SEN:30R ALARM - - - --
L 10:9.1 F.i :..I.
PIPING SUMP
SENSOR OUT ALARM
MAY 4. 2711 10:14 AM
ui?
SER30R ALAI ---
LI 1 :91 ST:?
STP SUMP
SEit"OR OUT ALARM
MAY 4. 2311 10:14 AM
SENSOR ALARM - - ---
L12:07 2 ANNULAR
ANNULAR WACE
SENSOR OUT ALARM
MAY 4. 2311 10:14 AM
SENSOR ALARM - - - --
L13:87 2 =ILL
PIPING,, SUMP
SENSOR OUT ALARM
MAY 4. 2311 10:14 AM
SEN30R ALARM - - --
L14:87 2 :3TP
STP SUMP
SENSOR OUT ALARM
MAY 4. 2)11 10:15 AM
HP GO GO
3369 W I LS-)N RD
BAKERSFIE: -D CA 93309
MAY 4, 2311 10:15 AM
3!STEM :STATUS REPORT
T I:DELIV---RY NEEDED
T 3:1)ELIVERY NEEDED
1.1 1 : SEWR OUT ALARM
SENSOR ALARM - - - --
L 4:WASTE OIL HI LEVEL
OTHER SENSORS
FUEL ALARM
MAY 4. 2311 10:22 AM
SENSOR ALARM - ----
L 2:WASTE OIL ANNULAR
ANNULAR &-ACE
FUEL ALARM
MAY 4, 2311 10:24 AM
I
SENSOR ALARM - - - --
1-10:91 Fill.
PIPING SUMP
FUEL ALARM
MAY 4. 2 31 1 12:21 PI-1
HP CO GO
3369 WILSON RD
BAKERSFIEA CA 93309
MAY 4, 2311 12:51 PM
SYSTEM STATUS REPORT
T I:DELIV3RY NEEDED
T 3:DEL1V'7-RY NEEDED
L10:FUEL ALARM
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing of UST spill containment .structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: HP Go Go I Date of Testing: 5/4/2011
Facility Address: 3699 Wilson Road, Bakersfield, CA 93309
Facility Contact: Alondra Hernandez I Phone: 661 -835 -8044
Date Local Agency Was Notified of Testing : 4/28/2011
Name of Local Agency Inspector (ifpresent during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Bryan A Self
Credentials: Z CSLB Contractor 0 ICC Service Tech. SWRCB Tank Tester Other (Spec)
License Number(s): CSLB# 804904 ICC# 8022804 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic Vacuum Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
1 Regular 1 2 Regular 2 3 Super 4 Waste oil
Bucket Installation Type: Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00" 12.00"
Bucket Depth: 14.00" 14.00" 14.00" 16.00"
Wait time between applying
vacuum /water and start oftest: 5 min. 5 min. 5 min. 5 min.
Test Start Time (Ti): 9:25am 9:25am 9:25am 10:30am
Initial Reading (Rj): 10.00" 10.25" 10.00" 12.00"
Test End Time (TF): 10:25am 10:25am 10:25am 11:30am
Final Reading (RF): 10.00" 10.25" 10.00" 12.00"
Test Duration (TF — Ti): 1 hour 1 hour 1 hour 1 hour
Change in Reading (RF - Ri): 0.00" 0.00" 0.00" 0.00"
Pass /Fail Threshold or
Criteria: 0.0625" 0.0625" 0.0625" 0.0625"
Test Result: X Pass Fail X Pass Fail X Pass Fail X Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature: Date: 5/4/2011
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.