HomeMy WebLinkAbout2700 OSWELL CUPA REPORT 6.8.15Underground Storage Tank Program DW Inspection Report , Permission to Inspect: / BAKERSFIELD FIRE DEPARTMENT Prevention Services Division 2101 H Street Bakersfield, CA 93301 Phone: 661-326-3979 Fax: 661-852-2171 Business Name: OSWELL CHEVRON-15-021-003013 Date:06/08/2015 Address Name: 2700 OSWELL ST-Rahmi Fahil Inspector Name: Shane Gardner #8248557 Inspection Type: Routine Report : Final NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined COS = Corrected On Site RPT = Repeat Violation Violation Program Requirement 46 C 0 SOC Comments No in 0 z 0 z M 0 W > File Review Facility Tank Information 2030021 Facility has a valid Permit Tank 1-10000-PRM-DW to Operate from the Tank 2-1 0000-DSL-DW CUPA - 23 CCR 16 2712(1); EJ El ❑ ❑ ❑ None Tank 3-1 0000-REG-DW HSC 6.7 25284 Tank 4- 2010010 UST Operating Permit owner has failed to notify cupa of Application for Facility changes within 30 days, tank information and Tank information is missing information None submitted/maintained - 23 CCR 16 2711; HSC 6.7 25286(a) 2010001 Current BOE number submitted to the CUPA E ❑ F-1 r-1 ❑ ❑ None and/or CERS - HSC 6.7 25286(c) 2030011 UST compliance statement and/or Designated Operator None current certification submitted - 23 CCR 16 2715(a), 2715(b) 2030046 A complete and accurate response plan has been submitted, approved and ❑ ❑ ❑ ❑ ❑ None maintained - 23 CCR 16 2632, 2634(e), 2641(h), 2712(i) 2030041 A complete and accurate plot plan has been submitted, approved and ❑ ❑ ❑ ❑ None maintained - 23 CCR 16 2632(d)(1)(C), 2711(a)(8) 2010006 Owner/Operator has not made false statements or representation on any None required document - HSC 6.725299 2010003 Owner/Operator has a DO and/or informed the CUPA of any change (s) None within 30 days - 23 CCR 16 2715(a) Violation Program Requirement %I- 00 .0 SOC Comments No ® (1) 0 (L 12 010 Z 0 z D Testing 2030002 Owner/Operator has tested and certified leak Z ❑ ❑ ❑ ❑ ❑ None detection equipment annually - 23 CCR 16 2638 2030048 Secondary containment testing conducted every 36 months in accordance None with requirements - 23 CCR 16 2637 2030055 Spill buckets have been tested annually as Z r_1 ❑ ❑ ❑ ❑ None required - HSC 6.7 25284.2 2010009 Secondary containment test results submitted to the CUPA within 30 days Z ❑ ❑ ❑ ❑ ❑ None after the test - 23 CCR 16 2637(e) 2030064 CUPA was poperly notified within the prescribed number of Z ❑ ❑ F-1 ❑ ❑ None hours prior to testing - 23 CCR 16 2637(1), 2638(e), 2643(g), 2644.1(a)(4) Install/Repair 2060009 Permits obtained to install, replace, repair, or Z El El El El ❑ None modify part of the UST system - 23 CCR 16 2712 UST System Observation General Monitoring 2030003 Leak detection system maintains continuous RD monitoring that activates 0 F1 ❑ ❑ ❑ F-1 None ❑ an audible and visual Yes alarm - 23 CCR 16 2632, 2634, 2636, 2666 2030016 The annular space of the tank, piping and sumps are continuously RD monitored and activates Z 1:1 1:1 1:1 ❑ ❑ None ❑ the alarm - 23 CCR 16 Yes 2631(8), 2632(c)(2)(A)&(8), 2633(c), 2636(o 2030017 Product piping outside the UDC is fail-safe and shuts down the pump or Z r_1 ❑ ❑ ❑ ❑ None restricts flow - 23 CCR 16 2636(0 (5 2030018 Turbine sump monitor activates an audible and RD visual alarm or stops the Z None ❑ flow of at the dispenser - Yes 23 CCR 16 2636(0(1) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement o SOC Comments No a o p a �o z O z U W �j 2030019 Monitoring system in the UDCs activates an audible and visual alarm ® ❑ ❑ ❑ ❑ ❑ None or stops the flow at the UDC - 23 CCR 16 2636( (1 2030043 Leak detection equipment properly programmed or RD properly operated - 23 ® ❑ ❑ ❑ ❑ ❑ None ❑ CCR 16 2632, 2634, 2636, Yes 2666 2060005 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25291 b) 2060014 Correct leak detection equipment installed for RD the type of system ® ❑ ❑ ❑ ❑ None ❑ present - 23 CCR 16 2638; Yes HSC 6.7 25290.1, 25290.2, 25291 2060015 Sensor located in the RD proper position /location - ® ❑ ❑ ❑ ❑ ❑ None ❑ 23 CCR 16 2630(d), 2641(a) Yes 2030062 Facility is in compliance with not tampering with or RD disabling leak detection ® ❑ ❑ ❑ ❑ ❑ None ❑ devices or alarms -- HSC Yes 6.7 25299 a 9) 2060022 System constructed with a monitoring system capable of detecting entry ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25290.2(d) 2030034 Tag /sticker on affixed monitoring equipment being certified, repaired, ® ❑ ❑ ❑ ❑ ❑ None or replaced - 23 CCR 16 2638( VPH Monitoring VPH 2030065 Interstitial monitoring of the annular spaces of the RD UST is properly ❑ ❑ ® ❑ ❑ ❑ None ❑ maintained - HSC 6.7 Yes 25290.1(e) 2060023 System constructed with a monitoring system capable of detecting entry into secondary ❑ ❑ ® ❑ ❑ ❑ None containment - HSC 6.7 25290.1(d) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0.0 SOC Comments No D < 0 0 0 . CO 0 Z 0 Z :D 0 W Line Leak Detector 2060012 Line leak detector installed on pressurized RD piping system - HSC 6.7 0 ❑ ❑ 1:1 1:1 F-1 None [:1 25290.1(h), 25290.2(8), Yes 252910, 25292(e), 2636(0(2) 2030026 Line leak detectors detect a 3 gph leak and/or RD audible and visual alarm F-1 ❑ F-I None F-1 function properly - 23 Yes CCR 16 2636(0(6), 2666(c) 2030027 Turbine shuts down when a leak is detected or RD when line leak detector is None F-1 disconnected - 23 CCR 16 Yes 2666(c) 2030025 Pressurized piping able to detect a 3.0 gph leak RD within an hour, and 0 1:1 ❑ ❑ None ❑ restricts the flow or Yes alarms - 23 CCR 16 2636(0(2) Secondary Containment 2060010 UST storing a hazardous RD substance has secondary Z ❑ ❑ E] None ❑ containment - HSC 6.7 Yes 25292 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 46 a 0 0 SOC Comments No D 0 = 110- M Z Z 0 Z > 2030008 UDC, sumps, and/or other secondary containment in good E ❑ ❑ ❑ ❑ F-1 None condition and/or are free of debris/liquid - HSC 6.7 25290.1, 25290.2, 25291 2030040 Secondarily contained RD piping maintained to allow E E:] E] E:] ❑ E] None 1:1 liquid to drain into sump - Yes 23 CCR 16 2630(d), 2641(a) 2060006 Secondary containment piping slopes back to the E ❑ ❑ ❑ 1:1 ❑ None collection sump - 23 CCR 16 263(c) 2030047 Secondary containment maintained tight and has been confirmed by testing E ❑ ❑ ❑ ❑ ❑ None - 23 CCR 16 2662, HSC 6.7 25290.1(c)(2), 25290.2(c)(2), 25291(a), 25292(e) 2030060 Entry fittings in secondary containment for UST system maintained F-1 ❑ ❑ 1:1 ❑ None tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666 2060020 Spill bucket is installed and has a functional drain RP valve or other means to 1:1 ❑ r-1 None ❑ remove liquid - 23 CCR 16 Yes 2635(b), 2665 2030054 Spill bucket maintained in RP good condition and free of ❑ ❑ F-1 ❑ ❑ None ❑ debris and/or liquid - 23 Yes CCR 16 2635(b), 2715(c)(2) 2060019 Spill bucket to has a minimum capacity of five r-] ❑ ❑ F-1 ❑ None gallons - 23 CCR 16 2635(b), 2665 Overfill 2030035 UST system is operated to prevent unauthorized RP release, including spills ❑ ❑ F-I ❑ None ❑ and overfills - HSC 6.7 Yes 25292.1 (a) 2030036 Overfill prevention system has not been overridden RP and meets overfill E ❑ F-1 ❑ F-1 ❑ None ❑ requirements - 23 CCR 16 Yes 2635(b)(2), 2665 1 1 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0.0 SOC Comments No >0 D < a 0 a . 120 030 z 1 0 1 2 :3 0 1 w On Site Records Certifications 2030023 Required designated operators or contractors maintain a proper and F-1 ❑ ❑ ❑ ❑ None current ICC certification - 23 CCR 16 2715 2030024 Service technician, installer, and/ or employee maintain a None proper license - 23 CCR 162715 2030031 Employee or contractor obtained and maintained proper manufacturer None certification - 23 CCR 16 2715 2010007 Submit/maintain current Certificate of Financial Responsibility /mechanism of financial assurance - ❑ ❑ None 23 CCR 16 2711; 23 CCR 18 2808.1, 2809-2809.2; HSC 6.7 25292.2; HSC 6.75 25299.30-25299.34 Designated Operator 2010004 Copies of DO inspections for last 12 months and list of trained employees None maintained - 23 CCR 16 2715 2030013 Designated operator properly conducted the monthly inspection and None the reports are complete - 23 CCR 16 2715 2030010 DO notified operator of any condition observed during the monthly None inspection that may require action - 23 CCR 16 2715(d) 2030012 DO employee training performed, current for at least one employee on None site, and a log kept - 23 CCR 16 2715(c) (6), 27150 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 0 0.0 SOC Comments No 0 > 0) 0 W 120 C 0 a CD Z 0 Z 0 W Logs 2030001 Leak detection alarm logs, maintenance and RD records of appropriate 0 ❑ ❑ 1:1 ❑ ❑ None ❑ follow-up actions Yes maintained - 23 CCR 16 2632, 2634, 2712(b) Maintenance/Tests 2010008 Monitoring, maintenance, repairs, linings, and RD upgrade records ❑ ❑ ❑ ❑ ❑ None ❑ maintained for the proper Yes time period - 23 CCR 16 2712(b) Documentation 2030033 Failure to maintain on site an approved monitoring None plan - 23 CCR 16 2632, 2634, 2711, 2712(1) 2030037 Written agreement between the tank owner and tank operator to monitor the tank system ❑ ❑ None is maintained - 23 CCR 16 2620(b); HSC 6.7 25284(a)(3) 2030061 Suspected or actual unauthorized release RD reported in appropriate ❑ ❑ ❑ 1:1 ❑ ❑ None ❑ time frame - HSC 6.7 Yes 29294,29295 General Operating Requirements Permit Condition/Approval 2030039 Compliance with all operating permit None conditions - 23 CCR 16 2712; HSC 6.7 25299 2030059 UST system maintained in accordance with exclusion/exemption None status - HSC 6.7 25281.6, 25283.5 2030014 Owner/Operator received approval and has implemented a training ❑ ❑ 0 ❑ ❑ ❑ None program at an unstaffed facility - 23 CCR 16 2715 0(2) 2030015 Facility exhibited that the method used to monitor the tank meets the monitoring methods in None 2643(f - 23 CCR 16 2643 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 .2 w SOC Comments No 0 co 0 0. 0 z 0 z D J 0 W Red Tag 2030045 Red Tag information is legible and has not been None tampered with - 23 CCR 16 2717.1 2030044 Facility did not allow for deposit of petroleum into a UST that has a red tag None affixed to the fill - 23 CCR 162717.1(0 Install/Repair 2060024 UST system is made of or lined with materials that are compatible with the None substance stored - 23 CCR 16 2631.1 2060021 Striker plate installed and positioned correctly - 23 2 ❑ 1:1 ❑ 1:1 ❑ None CCR 16 2631(c), 2662(d) I I I I I I I I E There were no violations noted for this inspection. ❑This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) Inspectors Signature: Date: Inspector: Enter # of Violations: RD: <:Z� RP:Q Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA: ETSOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations) ❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations) ❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention violations) ❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection violations) Underground Storage Tank Program - DW Inspection Report v 2.0