Loading...
HomeMy WebLinkAboutCUPA REPORT 4.11.19Underground Storage Tank Pr ram DW Inspection Repo Permission to Inspect BAKERSFIELD FIRE DEPARTMENT Prevention Services Division 2101 H Street Bakersfield, CA 93301 Phone: 661 - 326 -3979 Fax: 661 -852 -2171 aA;Jfflj1rRriffN Business Name: Dale: 4/11Y2019 (EPA ID# Address Name: Inspector Name: Kris Kams ICC# 8292402 Inspection Type: Routine Report : Final NVO = No Violation Observed OUT = Out of Compliance COS = Corrected On Site RPT = Repeat Violation NA = Not Applicable UD = Undetermined Violation Program Requirement 8 `o SOC Comments No in a. m 00 i O 0 its Review Facility Tank Information 2030021 Facility has a valid Permit Tank 1 - 12000- Reg - DW to Operate from the Tank 2 - 8000 - E85 - DW CUPA - 23 CCR 162712(i); ® ❑ El ❑ El ❑ None Tank 3- 12000 - Sup -DW HSC 6.725284 Tank 4 -8000 - Dies - DW 2010010 UST Opemting Permit Application for Facility information and Tank information ® ❑ ❑ ❑ ❑ ❑ None submitted /maintained - 23 CCR 16 2711; HSC 6.7 25286(a) 2010001 Current BOE number submitted to the CUPA ® ❑ ❑ ❑ ❑ ❑ None and /or CERS - HSC 6.7 25286 c 2030011 UST compliance statement and /or Designated Operator ® ❑ ❑ ❑ ❑ ❑ None current certification submitted - 23 CCR 16 2715(a), 27156 2030046 A complete and accurate response plan has been submitted, approved and ® ❑ ❑ ❑ ❑ ❑ None maintained - 23 CCR 16 2632, 2634(e), 2641(h), 2712 i 2030041 A complete and accurate plot plan has been submitted, approved and ® ❑ ❑ ❑ ❑ ❑ Minor maintained - 23 CCR 16 2632 d 1 C, 2711(a)L82 2010006 Owner /Operator has not made false statements or representation on any ® ❑ ❑ ❑ ❑ ❑ None required document - HSC 6.725299 2010003 Owner / Operetor has a DO and /or informed the CUPA of any change (s) ® ❑ ❑ ❑ ❑ ❑ None within 30 days - 23 CCR 16 2715(a) Violation Program Requirement v o SOC Comments No OV a m o z O z K p Testing 2030002 Owner /Operator has tested and certified leak ® ❑ ❑ ❑ ❑ ❑ None detection equipment annual) - 23 CCR 16 2638 2030048 Secondary containment testing conducted every 36 months in accordance ® ❑ ❑ ❑ ❑ ❑ None with requirements - 23 CCR 16 2637 2030055 Spill buckets have been tested annually as ® ❑ ❑ ❑ ❑ ❑ None required - HSC 6.7 25284.2 2010009 Secondary containment test results submitted to the CUPA within 30 days ® ❑ ❑ ❑ ❑ ❑ None after the test - 23. CCR 16 2637(e) 2030064 CUPA was poperly notified within the prescribed number of ® ❑ ❑ ❑ ❑ ❑ None hours prior to testing - 23 OCR 16 2637(0, 2636(e), 2643 q), 2644.1(0)(4 Install /Repair 2060009 Permits obtained to install, replace, repair, or ® ❑ ❑ ❑ ❑ ❑ None modify part df the UST s Stem - 23 CCR 16 2712 UST System Observation General Monitoring 2030003 Leak detection system maintains continuous RD monitoring that activates ® El El El ❑ None 1-1 an audible and visual Yes alarm - 23 CCR 16 2632, 2634, 2636, 2666 2030016 The annular space of the tank, piping and sumps RD are continuously ® ❑ ❑ ❑ ❑ ❑ None ❑ monitored and activates the alarm - 23 CCR 16 Yes 2631(9), 2632(c)(2)(A) &(8), 2633(c), 2636 2030017 Product piping outside the UDC is fail -safe and shuts down the pump or 0 ❑ ❑ ❑ ❑ ❑ None restricts flow - 23 CCR 16 2636(f)(5) 2030018 Turbine sump monitor RD activates an audible and ® ❑ ❑ ❑ ❑ ❑ None ❑ visual alarm or stops the flow of at the dispenser - Yes 23 CCR 16 2636(0(1) Underground Storage Tank program - DW Inspection Report v 2.0 Violation Program Requirement o SOG Comments HO 0U m z O z M K O 2030019 Monitoring system in the UDCs activates an audible and visual alarm ® ❑ ❑ ❑ ❑ ❑ None or stops the flow at the UDC - 23 CCR 16 2636 d i 2030043 Leak detection equipment RD properly programmed or properly operated - 23 ® ❑ ❑ ❑ ❑ ❑ None ❑ CCR 16 2632, 2634, 2636, Yes 2666 2060005 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25291(6 2060014 Correct leak detection equipment installed for RD the type of system ® ❑ ❑ ❑ ❑ ❑ None ❑ present - 23 CCR 16 2638, Yes HSC 6.725290.1, 25290.2, 25291 2060015 Sensor located in the RD proper position /location - ® ❑ ❑ ❑ ❑ ❑ None ❑ 23 CCR 16 2630(d), 2641(a) Yes 2030062 Facility is in compliance RD with not tampering with or disabling leak detection ® ❑ ❑ ❑ ❑ ❑ None ❑ devices or alarms - HSC Yes 6.7 25299 a 9 2060022 System constructed with a monitoring system capable of detecting entry ® ❑ TOE] L1 E] None into secondary containment - HSC 6.7 25290.2 tl 2030034 Tag /sticker on affixed monitoring equipment being certified, repaired, ® ❑ ❑ ❑ ❑ ❑ None or replaced - 23 CCR 16 263B LO VPH Monitoring VPH 2030065 Interstitial monitoring of RD the annular spaces of the UST is properly ® ❑ ❑ ❑ ❑ ❑ None ❑ maintained - HSC 6.7 Yes 25290.11e) 2060023 System constructed with a monitoring system capable of detecting entry into secondary ® ❑ ❑ ❑ ❑ ❑ None containment - HSC 6.7 25290.1(d) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program. Requirement SOC Comments No o' TL.6 z l ca Line Leak Detector 2060012 Line leak detector installed on pressurized RD piping system - HSC 6.7 ® ❑ ❑ ❑ ❑ ❑ None El 25290, 1(h), 25290.2(9), Yes 252910, 25292(e), 2636 2) 2030026 Line leak detectors detect a 3 gph leak and/or RD audible and visual alarm ® ❑ ❑ ❑ ❑ ❑ None ❑ function properly - 23 Yes CCR 16 26360(6), 2666(c) 2030027 Turbine shuts down when RD a leak is detected or when line leak detector is ® ❑ ❑ ❑ ❑ ❑ None ❑ disconnected - 23 CCR 16 Yes 2666 c 2030025 Pressurized piping able to detect a 3.0 gph leak RD within an hour, and ® ❑ ❑ ❑ ❑ ❑ None ❑ restricts the flow or Yes alarms - 23 CCR 16 2636(9(2 Secondary Containment hazardous RD rn295292? secondary ® ❑ ❑ ❑ ❑ ❑ None ❑ HSC 6.7 Yes Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement SOC Comments No to T A i o z o 2030008 UDC, sumps, and /or other secondary containment in good ® ❑ ❑ ❑ ❑ ❑ None condition and /or are free of debris /liquid - HSC 6.7 25290.1, 25290.2, 25291 2030040 Secondarily contained RD piping maintained to allow ® ❑ ❑ ❑ ❑ ❑ None ❑ liquid to drain into sump- Yes 23 CCR 16 2630(c), 2641 a 2060006 Secondary containment piping slopes back to the ® ❑ ❑ ❑ ❑ ❑ None collection sump - 23 CCR 16 263(c) 2030047 Secondary containment maintained tight and has been confirmed by testing ® ❑ ❑ ❑ ❑ ❑ None - 23 CCR 16 2662, HSC 6.7 25290.1(c)(2), 25290.2(c)(2), 25291(a), 25292 e 2030060 Entry fittings in secondary containment for UST System maintained ® ❑ ❑ ❑ ❑ ❑ None tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666 2060020 Spill bucket is installed RP and has a functional drain ® ❑ ❑ ❑ ❑ ❑ None ❑ valve or other means to remove liquid - 23 CCR 16 Yes 2635(b), 2665 2030054 Spill bucket maintained in RP good condition and free of ® ❑ ❑ ❑ ❑ ❑ None ❑ debris and /or liquid - 23 Yes CCR 16 2635(b), 2715(c)(2) 2060019 Spill bucket to has a minimum capacity of five ® ❑ ❑ ❑ ❑ T[N.ne gallons - 23 CCR 16 2635(b), 2665 Overfill 2030035 UST system is operated RP to prevent unauthorized release, including spills ® ❑ ❑ ❑ ❑ ❑ None ❑ and overfills - HSC 6.7 Yes 25292.1(a) 2030036 Overfill prevention system RP has not been overridden ® ❑ ❑ ❑ ❑ ❑ None ❑ and meets overfill requirements - 23 CCR 16 Yes 2635(b)(2),2665 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement m o SOC Comments No 0U m z O z K j On Site Records Certifications 2030023 Required designated operators or contractors maintain a proper and. ® ❑ ❑ ❑ ❑ ❑ None current ICC certification - 23 CCR 16 2715 2030024 Service technician, installer, and/ or employee maintain a ® ❑ ❑ ❑ ❑ ❑ None proper license - 23 CCR 162715 2030031 Employee or contractor obtained and maintained proper manufacturer ® ❑ ❑ ❑ ❑ ❑ None certification - 23 CCR 16 2715 2010007 Submit/maintain current Certificate of Financial Responsibility /mechanism of financial assurance - ® ❑ ❑ ❑ ❑ ❑ None 23 CCR 16 2711; 23 CCR 18 2808.1, 2809- 2809.2, HSC 6.725292.2; HSC 6.75 25299.30- 25299.34 Designated Operator 2010004 Copies of DO inspections for last 12 months and list of trained employees ® ❑ ❑ ❑ ❑ ❑ None maintained - 23 CCR 16 2715 2030013 Designated operator properly conducted the monthly inspection and ® ❑ ❑ ❑ ❑ ❑ None the reports are complete - 23 CCR 16 2715 2030010 DO notified operator of any condition observed during the monthly ® ❑ ❑ ❑ ❑ ❑ None inspection that may require action - 23 CCR 16 2715(d) 2030012 DO employee training performed, current for at least one employee on ® ❑ ❑ ❑ ❑ ❑ None site, and a log kept - 23 CCR 16 2715(c)(6), 2715 LO Underground Storage Tank Program - DW Inspection Report ° 2.0 Violation Program Requirement v o SOC Comments NO m z O 2 D 0U K 0> Logs 2030001 Leak detection alarm logs, maintenance and RD records of appropriate 11AE] ❑ ❑ ❑ ❑ None ❑ follow -up actions Yes maintained - 23 CCR 16 2632, 2634, 2712(6) Maintenance/Tests 2010008 Monitoring, maintenance, repairs, linings, and upgrade records ® E-1 ❑ ❑ ❑ ❑ None kRD maintained for theproper time period - 23 CCR 16 2712(b) Documentation 2030033 Failure to maintain on site an approved monitoring ® ❑ ❑ ❑ ❑ ❑ None plan - 23 CCR 16 2632, 2634, 2711, 2712(i) 2030037 Written agreement between the tank owner and tank operator to monitor the tank system ® ❑ ❑ ❑ ❑ ❑ None is maintained - 23 CCR 16 2620(6); HSC 6.7 25284 a 3 2030061 Suspected or actual RD unauthorized release reported in appropriate ❑ ❑ ® ❑ ❑ ❑ None ❑ time frame - HSC 6.7 Yes 29294, 29295 General Operating Requirements Permit Condition /Approval 2030039 Compliance with all operating permit ® ❑ ❑ ❑ ❑ ❑ None conditions- 23 CCR 16 2712, HSC 6.725299 2030059 UST system maintained in accordance with exclusion /exemption ❑ ❑ ❑ ❑ ❑ ❑ None status - HSC 6.7 25281.6, 25283.5 2030014 Owner /Operator received approval and has implemented a training ❑ ❑ ® ❑ ❑ ❑ None program at an unstaffed facility - 23 CCR 16 2715 2 .2030015 Facility exhibited that the method used to monitor the tank meets the monitoring methods in ® ❑ ❑ ❑ ❑ ❑ None 2643(f) - 23 CCR 16 2543 Underground Storage Tank Program - DW Inspection Report ° 2.0 Violation Program Requirement ,°, ,`o_ SOC Comments No m z o az D pj Red Tag 2030045 Red Tag information is legible and has not been ❑ ❑ ® ❑ ❑ ❑ None tampered with - 23 CCR 162717.1(9) 2030044 Facility did not allow for deposit of petroleum into a UST that has a red tag ❑ ❑ ® ❑ ❑ ❑ None affixed to the fill - 23 CCR 16 2717.1 Install /Repair 2060024 UST system is made of or lined with materials that are compatible with the ® ❑ ❑ ❑ ❑ ❑ None substance stored - 23 CCR 16 2631.1 2060021 Striker plate installed and positioned correctly - 23 ❑ ❑ ❑ ® ❑ ❑ None CCR 16 2631(c), 2662 tl Z There were no violations noted for this inspection. ❑This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION' for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) Inspectors Signature: Date. .....r Check ,.... one .... box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA: ❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations) ❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations) ❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection Underground Storage Tank Program - D W Inspection Report ° 2.0