Business Name: Wholesale Fuels, Inc 1001 (15 -021- 03393)
Date: 11/22/2019 (CAL000147010)
Address Name: 2200 East Brundage Lane, Bakersfield, CA 93307
(661) 3274900
Inspector Name: Kris Kams ICCH 6292402
Inspection Type: Routine
Report: Final
NVO =No Violation Observed OUT= Out of Compliance NA =Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation
Program Requirement
d `c
SOC
Comments
No
OO
0
m
0'6
i
O
z
,
rc
os
File Review
Facility Tank Information
2030021
Facility has a valid Permit
Tank 1 - 10000 - Clear Diesel - SW
to Operate from the
Tank 2- 10000 - Dyed Diesel - SW
CUPA - 23 CCR 16 2712(1);
Tank 3 - 20000 - Clear Diesel - SW
HSC 6.725284
❑
❑
❑
❑
❑
None
Tank 4 - 20000 - Regular - SW
Tank 5 - 20000 - Dyed Diesel - SW
Tank 6 - 20000 - Dyed Diesel - SW
2010010
UST Operating Permit
Application for Facility
information and Tank
information
®
❑
❑
❑
❑
❑
None
submitted /maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001
Current BOE number
submitted to the CUPA
0
❑
❑
❑
❑
❑
None
and /or CERS - HSC 6.7
25286(c)
2030011
UST compliance
statement and /or
Designated Operator
®
❑
❑
❑
❑
❑
None
current oertifcetion
submitted - 23 CCR 16
2715(a), 27156
2030046
A complete and accurate
response plan has been
submitted, approved and
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
27121
2030041
A complete and accurate
plot plan has been
submitted, approved and
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2632 d 1 C, 2711 a 8
2010006
Owner /Operator has not
made false statements or
representation on any
®
❑
❑
❑
❑
❑
None
required document - HSC
6.725299
Bakersfield Fire Department Prevention
Program Requirement
2101HSt
fA )rXY
Bakersfield CA. 93301
661- 326 -3911
SOC
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY /NOTICE OF VIOLATION
Violation
Program Requirement
v o
SOC
Comments
No
°
:
i
O
z
0
U
rc
5.
0
Owner /Operator has a
DO and /or informed the
CUPA of any change (s)
®
❑
❑
❑
❑
❑
None
within 30 days - 23 CCR
16 2715(a)
Testing
2030002
Owner /Operator has
tested and certified leak
®
❑
❑
❑
❑
❑
None
detection equipment
annual) - 23 CCR 16 2638
2030048
Secondary containment
testing conducted every
36 months in accordance
®
❑
❑
❑
❑
❑
None
with requirements - 23
CCR 16 2637
2030055
Spill buckets have been
tested annually as
®
❑
❑
❑
❑
❑
None
required - HSC 6.725284.2
2010009
Secondary containment
test results submitted to
the CUPA within 30 days
®
❑
❑
❑
❑
❑
None
after the test - 23 CCR 16
2637(e)
2030042
0.1 gph annual line test
performed and passed for
RD
pressurized piping without
❑
❑
®
❑
❑
❑
None
❑
fail safe or shut down - 23
Yes
CCR 16 2636( 0(4)
2030050
0.1 gallon per hour piping
integrity test conducted
RD
every three years (pre-
❑
❑
0
❑
❑
❑
None
❑
January 1984) - 23 CCR
Yes
16 2643(d)
2030051
Piping integrity test or
overfill integrity test
conducted every two
❑
❑
®
❑
❑
❑
None
years (pre - January 1,
1984 ) - 23 CCR 16 2643(e)
2030029
Lined or repaired steel
tank was inspected within
RP
10 years of lining and
®
❑
❑
❑
❑
❑
None
❑
every 5 years after - 23
Yes
CCR 16 2663
2030028
Tank lining certification
submitted to the CUPA
within 30 days, proper
®
❑
❑
❑
❑
❑
None
tests and inspector used -
23 CCR 16 2663
2030067
ELD testing conducted
every 36 months on USTs
located within 1,000 feet
❑
❑
❑
❑
❑
None
of a public drinking well -
23 CCR 16 2644.1(s)(3)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661- 326 -3911
Underground Storage Tank Program
SW Inspection Report
•tRt NOTICE TO COMPLY /NOTICE OF VIOLATION
I�
Violation
Program Requirement
'15 `o
SOC
Comments
No
m
i
O
i
M
U
X
g j
2010005
ELD testing results sent
to the board and the
CUPA within 60 days of
❑
❑
❑
❑
❑
❑
None
completion of the test - 23
CCR 16 2644. 1 a 5
2030056
SIR Report submitted
annually to the CUPA - 23
❑
❑
®
❑
❑
❑
None
CCR 16 2646.1
2030064
CUPA was properly
notified within the
prescribed number of
®
❑
❑
❑
❑
❑
None
hours prior to testing - 23
CCR 162637(o, 2638(e),
2643(a). 2644.1(a)(4)
InstaII /Repair
2060009
Permits obtained to
install, replace, repair, or
®
❑
❑ ❑
Ej
❑
None
modify part of the UST
system - 23 CCR 16 2712
UST
System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
®
❑
❑
❑
❑
❑
None
❑
an audible and visual
Yes
alarm - 23 CCR 16 2632,
2634, 2636, 2666
2030017
Product piping outside the
UDC is fail -safe and shuts
down the pump or
®
❑
❑
❑
❑
❑
None
restricts flow - 23 CCR 16
2636
2030018
Turbine sump monitor
RD
activates an audible and
visual alarm or stops the
®
11
[:1
E:]
E]
❑
flow of at the dispenser-
Yes
23 CCR 16 2636(f)(1)
2030019
Monitoring system in the
UDCs activates an
audible and visual alarm
®
❑
❑
❑
❑
❑
None
or stops the flow at the
UDC -23 CCR 16
2636 1
2030043
Leak detection equipment
Failure of the T -5 (Dyed Diesel UDC
properly programmed or
RD
Stand Alone Sensor). Failure of the
properly operated - 23
❑
®
❑
❑
❑
❑
None
❑
T -2 (Dyed Diesel Stand Alone Sensor).
CCR 16 2632, 2634, 2636,
Both sensors were replaced, re- tested
2666
Yes
and confirmed operational. Violations
were corrected on site.
2060005
System constructed with
a monitoring system
capable of detecting entry
®
❑
❑
❑
❑
❑
None
into secondary
containment - HSC 6.7
25291(b)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661 - 326 -3911
Violation
Underground Storage Tank Program
SW Inspection Report
•err
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
o co
SOC
Comments
No
0
0
m
00
i
O
z
K
05
2060014
Correct leak detection
equipment installed for
RD
the type of system
®
1:1
El
El
E]
❑
None
❑
present -23 CCR 162638;
Yes
HSC 6.7 25290.1, 25290.2,
25291
2060015
Sensor located in the
RD
proper position /location -
®
❑
❑
❑
❑
❑
None
❑
23 CCR 16 2630(d), 2641(a)
Yes
2030062
Facility is in compliance
with not tampering with or
RD
disabling leak detection
®
❑
❑
❑
❑
❑
None
❑
devices or alarms - HSC
Yes
6.7 25299 a 9
2030034
Tag/sticker on affixed
monitoring equipment
being certified, repaired,
0
❑
❑
❑
❑
❑
None
or replaced - 23 CCR 16
2638
Cathodic Protection
2030009
Impressed- current system
is turned on and
RP
functioning properly and
0
El
❑
E]
E]
❑
None
❑
inspected as required - 23
Yes
CCR 16 2635 a 2
Single Walled
Tank Monitoring
2030004
Automatic tank gauge
tests the tank at least
RD
once per month at 0.1
❑
❑
®
❑
❑
❑
None
❑
gallons per hour - 23 CCR
Yes
16 2643 b 2
2030005
The 0.2 gallons per hour
continuous in tank leak
RD
detection test is being
®
❑
❑
❑
❑
❑
None
❑
conducted - 23 CCR 16
Yes
2643 6 5
2030006
Monthly 0.2 gallons per
hour automatic tank
RD
gauging test on a single
®
❑
❑
❑
❑
❑
None
❑
wall tank is being
Yes
conducted - 23 CCR 16
1
2643 MI)
2060002
Automatic tank
gauging /continuous in
RD
tank leak detection
®
El
E]
❑
❑
❑
None
❑
system installed /properly
Yes
functioning - 23 CCR 16
2643; HSC 6.7 25292(a)
2030030
Weekly manual tank
gauging performed in
RD
accordance to the
❑
❑
®
❑
❑
❑
None
❑
required specifications -
Yes
23 CCR 16 2645
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661 - 326 -3911
Violation
Underground Storage Tank Program
• "' "
SW Inspection Report
Ifrl r
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
'15 ,`o
SOC
Comments
No
m
z
O
z
M
U
W
0 j
2030022
Groundwater and /or
vadose zone monitoring
❑
❑
®
❑
❑
❑
None
conducted as required -
23 CCR 16 2647, 2648
Single Walled
Piping Monitoring
2030052
Piping monitored hourly
and a 0.2 gph monthly or
RD
0.1 gph annual line
®
El
[:1
❑
❑
El
Non.
[:1
integrity test is performed
Yes
- 23 CCR 162641(a),
2643(c)
Line Leak
Detector
2060012
Line leak detector
installed on pressurized
RD
piping system - HSC 6.7
®
El
❑
El
El
❑
None
El
25290, f (h), 25290.2(9),
Yes
25291(1), 25292(e),
2636 (0(2)
2030026
Line leak detectors detect
a 3 gph leak and /or
RD
audible and visual alarm
Z
El
E]
❑
E]
E]
None
El
function properly - 23
Yes
CCR 16 2636(f)(6),
2666 c
2030027
Turbine shuts down when
a leak is detected or
RD
when line leak detector is
®
❑
❑
❑
❑
❑
None
❑
disconnected - 23 CCR 16
Yes
2666 c
2030025
Pressurized piping able to
detect a 3.0 gph leak
RD
within an hour, and
®
❑
❑
❑
❑
❑
None
❑
restricts the flow or
Yes
alarms - 23 CCR 16
2636(f)(2)
Suction Piping
2030053
Suction piping sloped to
drain back into storage
RD
tank, one check valve and
❑
❑
®
❑
❑
❑
None
❑
inspections conducted -
Yes
23 CCR 162636(a)(3),
2641(b)
Secondary Containment
2030008
UDC, sumps, and /or
other secondary
containment in good
®
❑
❑
❑
❑
❑
None
condition and /or are free
of debristliquid - HSC 6.7
25290.1, 25290.2, 25291
2030047
Secondary containment
maintained tight and has
been confirmed by testing
®
❑
❑
❑
❑
❑
None
- 23 CCR 16 2662, HSC 6.7
25290.1(c)(2), 25290.2(c)(2),
25291(a), 25292(e)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661- 326 -3911
Underground Storage Tank Program
SW Inspection Report
I/ff
T NOTICE TO COMPLY/NOTICE OF VIOLATION
AR►/
Violation
Program Requirement
m ,`o_
SOC
Comments
No
O
0
1-
2%
Z
O
Z
U
ao
D
W
�>
2030060
Entry fittings in secondary
containment for UST
system maintained
M
❑
❑
❑
❑
❑
None
tight/sealed - 23 CCR 16
2630, 2635(d), 2636(c),
2666
2060020
Spill bucket is installed
Failure of the T -4 (87 Spill Bucket),
and has a functional drain
RP
Bucket was replaced, re- tested and
valve or other means to
❑
M
❑
❑
❑
❑
None
❑
confirmed to be tight after replacement.
remove liquid - 23 CCR 16
Yes
Violation was corrected on site.
2635(b), 2665
2030054
Spill bucket maintained in
RP
good condition and free of
M
❑
❑
❑
❑
❑
None
❑
debris and /or liquid - 23
Yes
CCR 16 2635(b). 2715 c 2
2060019
Spill bucket to has
minimum rapacity oa f five
®
❑
❑
❑
❑
❑
None
gallons - 23 CCR 16
2635(b), 2665
Overfill
2030035
UST system is operated
to prevent unauthorized
RP
release, including spills
M
11
El
❑
❑
❑
None
❑
and overfills - HSC 6.7
Yes
25292.1 ii
2030036
Overfill prevention system
RP
has not been overridden
and meets overfill
M
❑
❑
❑
❑
❑
None
❑
requirements - 23 CCR 16
Yes
2635(b)(2), 2665
On Site Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
M
❑
❑
❑
❑
❑
None
current [CC certification -
23 CCR 16 2715
2030024
Service technician,
installer, and/ or
employee maintain a
M
❑
❑
❑
❑
❑
None
proper license - 23 CCR
162715
2030031
Employee or contractor
obtained and maintained
proper manufacturer
M
❑
❑
❑
❑
❑
None
certification - 23 CCR 16
2715
2010007
Submittmaintain current
Certificate of Financial
Responsibility/mechanism
of financial assurance -
M
❑
❑
❑
❑
❑
None
23 CCR 16 2711; 23 CCR
IS 2808.1, 2809 - 2809.2,
HSC 6.7 25292.2; HSC
6.75 25299.30 - 25299.34
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661- 326 -3911
Violation
Underground Storage Tank Program
1.4711NIJIrt,
SW Inspection Report
NOTICE TO COMPLY /NOTICE OF VIOLATION
Violation
Program Requirement
m o
SOC
Comments
No
a
z
O
z
v
rc
o>
2030007
Positive statement of
compatibility for UST
system components
®
❑
❑
❑
❑
❑
submitted and maintained on
site - 23 CCR 16 263 10)
Designated
Operator
2010004
Copies of DO inspections
for last 12 months and list of
trained employees
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2715
2030013
Designated operator
properly conducted the
monthly inspection and the
®
❑
❑
❑
❑
❑
None
reports are complete - 23
CCR 16 2715
2030010
DO notified operator of any
condition observed during
the monthly inspection that
®
❑
❑
❑
❑
❑
None
may require action - 23 CCR
16 2715(d)
2030012
DO employee training
performed, current for at
least one employee on site,
®
❑
❑
❑
❑
❑
None
and a log kept - 23 CCR 16
2715(c)(6),2715 (f)
Logs
2030001
Leak detection alarm logs,
maintenance and records of
appropriate follow -up
TMEI
❑
❑
❑
❑
None
actions maintained - 23
CCR 162632, 2634,
2712(b)
2030020
Unburied fuel piping
RD
visually inspected at least
❑
El
®
1-1
❑
El
None
El
monthly and log kept - HSC
Yes
6.725281.5 3)
2030049
Suction pipe monitored
daily and results logged - 23
❑
❑
Z
❑
❑
❑
None
CCR 16 2643(d)
2030057
When SIR results indicate
failure: The facility met all
RD
corrective action
❑
❑
®
❑
❑
❑
None
❑
requirements - 23 CCR 16
Yes
2646.1 d
2030058
All Statistical Inventory
RD
Reconciliation (SIR)
❑
El
[O
❑
❑
E]
None
El
requirements met - 23 CCR
Yes
16 2646.1
Maintenance
rests
2010008
Monitoring, maintenance,
repairs, linings, and upgrade
RD
records maintained for the
®
❑
❑
❑
❑
❑
None
❑
proper time period - 23 CCR
Yes
16 2712(b
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA 93301
661 - 326,3911
Underground Storage Tank Program
' ° R' "' SW Inspection Report
/Iff
Afr/ r NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
`o
SOC
Comments
No
114
i
O
i
m > o
�
2010002
Records of cathodic
protection systems testing
®
❑
❑
❑
❑
❑
None
maintained -23 CCR 16
2635, 2712(b)
Documentation
2030033
Failure to maintain on site
an approved monitoring plan
®
❑
❑
❑
❑
❑
None
- 23 CCR 16 2632, 2634,
2711,2712(i)
2030037
Written agreement between
the tank owner and tank
operator to monitor the tank
❑
❑
®
❑
❑
❑
None
system is maintained - 23
CCR 16 2620(b); HSC 6.7
25284(a)(3)
2030061
Suspected or actual
unauthorized release
RD
reported in appropriate time
El
El
®
El
E:]
E]
None
El
frame - HSC 6.7 29294,
Yes
29295
General Operating
Requirements
Permit Condition/Approval
2030039
Compliance with all
operating permit conditions
®
❑
❑
❑
❑
❑
None
- 23 CCR 16 2712; HSC 6.7
25299
2030059
UST system maintained in
accordance with
❑
❑
®
❑
❑
❑
None
exclusion/exemption status -
HSC 6.7 25281.6, 25283.5
2030014
Owner /Operator received
approval and has
implemented a training
❑
❑
®
❑
❑
❑
None
program at an unstaffed
facility - 23 CCR 16
z715(f)(2)
2030015
Facility exhibited that the
method used to monitor the
tank meets the monitoring
®
❑
❑
❑
❑
❑
None
methods in 2643(f) - 23
CCR 16 2643
Red Tap
2030045
Red Tag information is
legible and has not been
T[:]E]
®
El
E]
El
None
tampered with -23 CCR 16
2717.1 )
2030044
Facility did not allow for
deposit of petroleum into a
UST that has a red tag
❑
❑
®
❑
❑
❑
None
affixed to the fill - 23 CCR
16 2717.1(f)
Install/Repair
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661- 326 -3911
Underground Storage Tank Program
SW Inspection Report
its
,roar NOTICE TO COMPLYINOTICE OF VIOLATION
Violation
Program Requirement
d ,`a_
SOC
Comments
No
2
O
Z
M
U
K
ac
OS
2030066
Repaired and retested the
system due to a failed ELD
test when located within
❑
❑
❑
❑
❑
None
1000' of public well - HSC
6.7 25292.4(d), 25292.5(c)
2060018
Existing SW piping is
constructed of FRP,
cathodically protected steel,
®
El
❑
El
El
El
None
RP
El
or steel clad with FRP - 23
Yes
CCR 16 2666(b); HSC 6.7
25292 e 2
2060021
Striker plate installed and
positioned correctly - 23
❑
❑
❑
®
❑
❑
Now
CCR 16 2631(c), 2662(d)
2060004
Corrosion protection
installed for USTs and
RP
cathodic protection system
®
❑
❑
❑
❑
❑
None
❑
meets the consensus
Yes
standards - 23 CCR 16
2635(a)(2)(A)
❑ There were no violations noted for this inspection.
®This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Fonnal enforcement and/or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature: / A • .7- i Date: //— 27- /�
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention
violations)
❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection