Business Name: UPS - Bakersfield (15021- 003310)
Date: 10129/2019 (EPA ID# CAD982403065)
Address Name: 3800 N Sillect Ave, Bakersfield, CA 93308
209 736 -0878
Inspector Name: Kris Karns ICC# 8292402
Inspection Type: Routine
Report : Final
NVO =No Violation Observed OUT= Out of Compliance NA =Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation
Program Requirement
6 `o
SOC
Comments
No
m
z
O
i
n
U
K
g j
Violation
Program Requirement
v o
SOC
Comments
No
O0
m
z
O
i
n
,o >
Testing
2030002
Owner /Operator has
tested and certified leak
®
❑
❑
❑
❑
❑
None
detection equipment
annuall - 23CCR162638
2030048
Secondary containment
testing conducted every
36 months in accordance
®
❑
❑
❑
❑
❑
None
with requirements - 23
CCR 16 2637
2030055
Spill buckets hav -been
tested annually as
®
❑
❑
❑
❑
❑
None
required - HSC 6.7 25264.2
2010009
Secondary containment
test results submitted to
the CU PA within 30 days
®
❑
❑
❑
❑
❑
None
after the test - 23 CCR 16
2637(e)
2030064
CUPA was poperly
notified within the
prescribed number of
®
❑
❑
❑
❑
❑
None
hours prior to testing- 23
CCR.. 16 26370, 2638(e),
2643(g), 2644.1(a)(4)
Install /Repair
2060009
Permits obtained to
install, replace, repair, or
®
❑
❑
❑
❑
❑
None
modify part of the UST
system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
®
❑
❑
❑
❑
❑
None
❑
an audible and visual
Yes
alarm - 23 CCR 16 2632,
2634, 2636, 2666
2030016
The annular space of the
tank, piping and sumps
RD
are continuously
monitored and activates
®
❑
❑
❑
❑
❑
None
❑
the alarm - 23 CCR 16
Yes
2631(9), 2632(c)(2)(A) &(B),
2633(c), 2636
2030017
Product piping outside the
UDC is fail -safe and shuts
down the pump or
®
❑
❑
❑
❑
❑
None
restricts flow - 23 CCR 16
2636(0(5)
2030018
Turbine sump monitor
activates an audible and
RD
visual alarm or stops the
®
❑
❑
❑
❑
❑
None
❑
flow of at the dispenser -
Yes
23 CCR 16 26360(1)
Underground Storage Tank Program - D W Inspection Report v 2.0
Violation
Program Requirement
m o
S OC
Comments
No`
o0
..
.
,
z
o
z M
rc
f
2030019
Monitoring system in the
UDCs activates an
audible and visual alarm
®
❑
❑
❑
❑
❑
None
or stops the flow at the
UDC - 23 CCR 16
2636 (0(1)
2030043
Leak detection equipment
properly programmed or
RD
properly operated - 23
®
❑
❑
❑
❑
❑
None
❑
CCR 16 2632, 2634, 2636,
Yes
2666
2060005
System constructed with
a monitoring system
capable . of detecting entry
®
❑
❑
❑
❑
❑
None
into secondary
containment - HSC 6.7
25291 6
2060014
Correct leak detection
equipment installed for
RD
the type of system
®
❑
❑
❑
❑
❑
None
❑
present - 23 CCR 16 2638,
Yes
HSC 6.7 25290. 1, 25290.2,
25291
2060015
Sensor located in the
RD
proper position /location -
®
❑
El
❑
❑
El
None
El
23 CCR 16 2630(d), 2641(a)
Yes
2030062
Facility is in compliance
with not tampering with or
RD
disabling leak detection
®
❑
❑
❑
❑
❑
None
❑
devices or alarms - HSC
Yes
6.7 25299 a 9
2060022
System constructed with
a monitoring system
capable of detecting entry
®
❑
❑
❑
❑
❑
None
into secondary
containment - HSC 6.7
25290.2(d)
2030034
Tag /sticker on affixed
monitoring equipment
being certified, repaired,
®
❑
❑
❑
❑
E]
None
or replaced - 23 CCR 16
2638 (0
VPH Monitoring VPH
2030065
Interstitial monitoring of
the annular spaces of the
RD
UST is properly
1:1
El
®
❑
❑
❑
None
❑
maintained -HSC 6.7
Yes
25290.1 e)
2060023
System constructed with
a monitoring system
capable of detecting entry
into secondary
❑
❑
®
❑
❑
❑
None
containment - HSC 6.7
25290A(d)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
°y ; o
SOC
Comments
No
t
z
o
z
U
x
o °'>
Line Leak Detector
2060012
Line leak detector
installed on pressurized
RD
piping system - HSC 6.7
®
El
El
❑
❑
L1
None
❑
25290.1(h), 25290.2(g),
Yes
252910, 25292(e),
26360(2)
2030026
Line leak detectors detect
a 3 gph leak and /or
RD
audible and visual alarm
®
❑
❑
❑
❑
❑
None
❑
function properly - 23
Yes
CCR 1626360(6),
2666(c)
2030027
Turbine shuts down when
a leak is detected or
RD
when line leak detector is
❑
❑
®
❑
❑
❑
None
❑
disconnected - 23 CCR 16
Yes
2666(c)
2030025
Pressurized piping able to
detect a 3.0 gph leak
RD
within an hour, and
®
❑
❑
❑
❑
❑
None
❑
restricts the flow or
Yes
alarms - 23 CCR 96
2636p)(2)
Secondary Containment
2060010
UST storing a hazardous
substance has secondary
El
❑
1:1
None
7RD
containment - HSC 6.7
25292
Underground Storage Tank Program- DW Inspection Report v 2.0
Violation
Program Requirement
v o
SOC
Comments
No
a
°
M
❑
o
a
P
Z
O
Z
J
U
K
o
2030008
UDC, sumps, and/or
other secondary
containment in good
E
❑
❑
❑
❑
❑
None
'..
condition and /or are free
of debris /liquid - HSC 6.7
'..
25290.1, 25290.2 25291
2030040
Secondarily contained
RD
'..
piping maintained to allow
E
❑
❑
❑
❑
❑
None
❑
'..
liquid to drain into sump -
Yes
23 CCR 16 2630(d), 2641(a)
2060006
Secondary containment
piping slopes back to the
E
❑
❑
❑
❑
❑
None
collection sump - 23 CCR
16 263(c)
2030047
Secondary containment
T -1 (87) STP and T -2 (Diesel) STP
maintained tight and has
failed SB -989 testing on
been confirmed by testing
6/26/19. Failed to correct by
- 23 CCR 16 2662; HSC 6.7
❑
E
❑
❑
❑
❑
None
7126/19, violations have now been
25290.1(c)(2), 25290.2(c)(2),
elevated to Class 1 and given until
25291(a), 25292(e)
11 -29 -19 to correct or bath UST's
will be red tagged.
2030060
Entry fittings in secondary
containment for UST
system maintained
E
❑
❑
❑
❑
❑
None
tight/sealed - 23 CCR 16
2630, 2635(d), 2636(c),
2666
2060020
Spill bucket is installed
RP
and has a functional drain
valve or other means to
E
❑
❑
❑
❑
❑
None
❑
remove liquid - 23 CCR 16
Yes
2635(b), 2665
2030054
Spill bucket maintained in
RP
cod condition and free of
®
❑
❑
El
❑
E]
None
E]
debris and /or liquid - 23
Yes
CCR 16 2636(b), 2715 c 2
2060019
Spill bucket to has a
minimum capacity of five
E
❑
❑
❑
❑
❑
None
gallons - 23 CCR 16
2635(b), 2665
Overfill
2030035
UST system is operated
RP
to prevent unauthorized
release, including spills
E
❑
❑
❑
❑
❑
None
❑
and overfills - HSC 6.7
Yes
25292.1(a
2030036
Overfill prevention system
RP
has not been overridden
and meets overfill
E
❑
❑
❑
❑
❑
None
❑
requirements -. 23 CCR 16
Yes
2635(b) 2 , 2665
Underground Storage 'lank Program - DW Inspection Report v2.0
Violation
Program Requirement
d o
SOC
Comments
No
>
o
o
0
n
i
Q;o
On Site
Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
®
❑
❑
❑
❑
❑
None
current ICC certification -
23 CCR 16.2715
2030024
Service technician,
installer, and/or
employee maintain a
®
❑
❑
❑
❑
❑
None
proper license - 23 CCR
162715
2030031
Employee or contractor
obtained and maintained
proper manufacturer
®
❑
❑
❑
❑
❑
None
certification - 23 CCR 16
2715
2010007
Submit/maintain current
Certificate of Financial
Responsibility/mechanism
of financial assurance -
®
❑
11
El
❑
F]
None
23 CCR 16 2711; 23 CCR
18 2808.1, 2809 - 2809.2;
HSC 6.7 25292.2; HSC
6.75 25299,39- 25299.34
Designated Operator
2010004
Copies of DO inspections
for last 12 months and list
of trained employees
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2715
2030013
Designated operator
properly conducted the
monthly inspection and
®
❑
❑
❑
❑
❑
None
the reports are complete -
23 CCR 16 2715
2030010
DO notified . operator of
any condition observed
during the monthly
®
❑
❑
❑
❑
❑
None
inspection that may
require action - 23 CCR 16
2715(d)
2030012
DO employee training
performed, current for at
least one employee on
®
❑
❑
❑
❑
❑
None
site, and a log kept - 23
CCR 16 2715(c)(6), 2715
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
a o
SOC
Comments
No
z
o
z
n
O
K
p j
Logs
2030001
Leak detection alarm
lags, maintenance and
RD
records of appropriate
®
❑
❑
❑
❑
❑
None
❑
follow -up actions
Yes
maintained - 23 CCR 16
2632, 2634, 2712(b)
MaintenancelTests
2010008
.Monitoring, maintenance,
repairs, linings, and
RD
upgrade records
®
El
❑
El
11
❑
None
[_1
maintained for the proper
Yes
time period - 23 CCR 16
2712(b)
Documentation
2030033
Failure to maintain on site
an approved monitoring
®
❑
❑
❑
❑
❑
None
plan - 23 CCR 16 2632,
2634, 2711, 2712(1)
2030037
Written agreement
between the tank owner
and tank operator to
monitor the tank system
®
❑
❑
❑
❑
❑
None
is maintained - 23 CCR 16
2620(b); HSC 6.7
25284 (a) (3)
2030061
Suspected or actual
unauthorized release
RD
reported in appropriate
❑
❑
®
❑
❑
❑
None
❑
time frame - HSC 6.7
Yes
29294, 29295
General Operating Requirements
Permit Condition /Approval
2030039
Compliance with all
operating permit
®
❑
❑
❑
❑
❑
None
conditions - 23 CCR 16
2712; HSC 6.7 25299
2030059
UST system maintained
in accordance with
exclusion /exemption
®
❑
❑
❑
❑
❑
None
status - HSC 6.7 25281.6,
25283.5
2030014
Owner /Operator received
approval and has
implemented a training
❑
❑
®
❑
❑
❑
None
program at an unstaffed
facility - 23 CCR 16
2715 2
2030015
Facility exhibited that the
method used to monitor
the tank meets the
monitoring methods in
®
❑
❑
❑
❑
❑
None
2643(f) - 23 CCR 16 2643
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
v o
SOC
Comments
No
u
z
O
i
M
U
M
�y-
Red Tag
2030045
Red Tag information is
legible and has not been
❑
❑
N
❑
❑
❑
None
tampered with -23. CCR
162717.1(g)
2030044
Facility did not allow for
deposit of petroleum into
a UST that has a red tag
❑
❑
N
❑
❑
❑
None
affixed to the fill - 23 CCR
162717. IM
Install /Repair
2060024
UST system is made of or
lined with materials that
are compatible with the
®
❑
❑
❑
❑
❑
None
substance stored - 23
CCR 16 2631.1
2060021
Striker plate installed and
positioned correctly - 23
❑
❑
❑
❑
❑
None
CCR 16 2631 c , 2662 d)
❑ There were no violations noted for this inspection.
NThis report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and /or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature:
Date:
...- I..ew....... r v. ................. ... .
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCS and US EPA:
❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention
violations)
❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection
Underground Storage Tank Program - D W Inspection Report v 2.0