HomeMy WebLinkAboutCUPA 1-21-2020Underground Storage Tank Program
DW Inspection Report
Permission to Inspect: -1 '( 'L
'j
BAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
2101 H Street
Bakersfield, CA 93301
Phone: 661-326-3979
Fax! 661-852-21.71.
Business Name: OLIVE REFRESH
Date: 1/21/2020
Address Name: 11206 Olive Dr Unit 101 Bakersfield, CA 93312
Inspector Name: Peter Armagost #8856813
Inspection Type: Routine
Report: Final
NVO =.No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT =Repeat Violation
Violation
Program Fit quiremento
SCIC
Comments
No
N
a.
B A
z
o
zT
a
p5
File Review
Facility Tank Information
2030021
Facility has a valid Permit
Tank 1 -15000 -REG -DW
to Operate from the
Tank 2 -10000 -PRM -DW
CUPA-23CCR162712(i);
®
❑
❑
❑
❑
❑
None
Tank 3 -10000 -DSL -DW
HSC 6.7 25284
2010010
UST Operating Permit
Application for Facility
information and Tank
information
®
❑
❑
❑
❑
❑
None
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001
Current BOE number
submitted to the CUPA
®
❑
❑
❑
❑
❑
None
and/or CERS - HSC 6.7
25286(c
2030011
UST compliance
statement and/or
Designated Operator
®
❑
❑
❑
❑
❑
None
current certification
submitted - 23 CCR 16
2715(a), 2715(b)
2030046
A complete and accurate
response plan has been
submitted, approved and
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2712 i
2030041
A complete and accurate
plot plan has been
submitted, approved and
0
❑
❑
❑
❑
❑
Minor
maintained - 23 CCR 16
2632 d 1 C, 2711 a 8
2010006
Owner/Operator has not
made false statements or
representation on any
®
❑
❑
❑
❑
❑
None
required document - HSC
6.7 25299
Violation
Program Requirement
u: o.
SOC
Comments
NO
O]
aU
E
z
O
z
K
p.
2010003
Owner/Operator has a
DO and/or informed the
CUPA of any change (s)
®
❑
❑
❑
❑
❑
None
within 30 days - 23 COR
16 2715(x)
Testing
2030002
Owner/Operator has
tested and certified leak
®
❑
❑
❑
❑
❑
None
detection equipment
annual) - 23 CCR 16 2638
2030048
Secondary containment
testing conducted every
36 months in accordance
®
❑
❑
❑
❑
❑
None
with requirements -.23
CCR 16 2637
2030055
Spill buckets have been
tested annually as
®
❑
❑
❑
❑
❑
None
required - HSC 6.7 25284.2
2010009
Secondary containment
-
test results submitted to
the CUPA within 30 days
®
❑
❑
❑
❑
❑
None
after the test.- 23 CCR 16
2637 e
2030064
CUPA was poperly
notified within the
prescribed number of
0
❑
❑
❑
❑
❑
None
hours prior to testing - 23
CCR 16 2637(0, 2638(e),
2643(g), 2644.1 a 4
Install/Repair
2060009
Permits obtained to
install, replace, repair, or
HZEI
❑
❑
❑
None
FT
modify part of the UST
system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
®
❑
❑
❑
❑
❑
None
❑
an audible and visual
Yes
alarm - 23 CCR 16 2632,
2534, 2636, 2666
2030016
The annular space of the
tank, piping and sumps
RD
are continuously
®
❑
❑
❑
❑
❑
None.
❑
monitored and activates
the alarm - 23 CCR 16
Yes
2631(8), 2632(c)(2)(A)&(e),
2633(c), 2636
2030017
Product piping outside the
UDC is fail-safe and shuts
down the pump or®
TI[
❑Tol
None
restricts flow - 23 CCR 16
2636(0(5)
Underground Storage Tank Program - DW Inspection Report v 2'0
Violation
Program Requirement
v ,Y
SOC
Comments
No
x
z
O
z
rc
of
2030018
Turbine sump monitor
RD
activates an audible and
visual alarm or stops the
®
❑
❑
❑
❑
❑
None
❑
flow of at the dispenser -
Yes
23 CCR 16 2636 0(1)
2030019
Monitoring system in the
UDCs activates an
audible and visual alarm
®
❑
❑
❑
❑
❑
None
or stops the flow at the
UDC - 23 CCR 16
2636 (0(1)
2030043
Leak detection equipment
RD
properly programmed or
®
❑
❑
❑
❑
❑
None
❑
properly operated - 23
CCR 16 2632, 2634, 2636,
Yes
2666
2060005
System constructed with
a monitoring system
capable of detecting entry
®
❑
❑
❑
❑
❑
None
into secondary
containment -HSC 6.7
25291 6
2060014
Correct leak detection
equipment installed for
RD
the type of system
®
❑
❑
❑
❑
❑
None
❑
present - 23 CCR 16 2638;
Yes
HSC 6.7 25290.1, 252902,
25297
2060015
Sensor located in the
RD
proper position/location -
®
❑
❑
❑
❑
❑
None
❑
23 CCR 16 2630(d), 2641(a)
Yes
2030062
Facility is in compliance
RD
with not tampering with or
❑
disabling leak detection
®
❑
❑
❑
❑
❑
None
devices or alarms - HSC
Yes
6.7 25299(a)(9
2060022
System constructed with
amonitoring system
capable of detecting entry
®
❑
❑
❑
❑
❑
None
into secondary
containment - HSC. 6.7
-
25290.2(d)
2030034
Tag/sticker on affixed
monitoring equipment
being certified, repaired,
®
❑
❑
❑
❑
❑
None
or replaced - 23 CCR 16
2638
VPH Monitoring VPH
2030065
Interstitial monitoring ofRD
the annular spaces of. the
❑
UST is properly
❑
❑
®
❑
❑
❑
None
maintained -HSC 6.7
Yes
25290A(e)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
v.;o
SOC
Comments
No
o
v n
z
o
z
D
W
0
p
2060023
System constructed with
a monitoring system
capable of detecting entry
into secondary
❑
❑
®
❑
❑
❑
None
containment - HSC 6.7
25290.1(d)
Line Leak Detector
2060012
Line leak detector
installed on pressurized
RD
piping system - HSC 6.7
❑
❑
®
❑
❑
❑
None
❑
25290.1(h),. 25290.2(g),
Yes
25291(0,. 25292(e),
2636 (0(2)
2030026
Line leak detectors detect
a 3 gph leak and/or
RD
audible and visual alarm
❑
❑
®
❑
❑
❑
None
❑
function properly - 23
Yes
CCR 16 26360(6),
2666(g)
2030027
Turbine shuts down when
RD
a leak is detected or
is
❑
❑
®
❑
❑
❑
None
❑
when line leak detector
disconnected - 23 CCR 16
Yes
2666(c)
2030025
Pressurized piping able to
detect a 3.0 gph leak
RD
within an hour, and
❑
❑
®
❑
❑
❑
None
❑
restricts the flow or
Yes
alarms - 23 CCR 16
2636 2
Secondary Containment
2060010
UST storing a hazardous
RD
substance has secondary
®
❑
❑
❑
❑
❑
None
❑
containment -HSC 6.7
Yes
25292
Underground Storage Tank Program - DW inspection Report v 2.0
Violation
Program Requirement
w ,o
SOC
Comments
No
vz
o
z
M
0
W
o>
2030008
UDC, sumps, and/or
other secondary
containment in good
®
❑
❑
❑
❑
❑
None
condition and/or are free
of debris/liquid - HSC 6.7
25290.1, 25290.2, 25291
2030040
Secondarily contained
RD
piping maintained to allow
®
❑
❑
❑
❑
❑
None
❑
liquid to drain into sump -
Yes
23 CCR 16 2630(d), 2641La)
2060006
Secondary containment
piping slopes back to the
®
❑
❑
❑
❑
❑
None
collection sump - 23 CCR
16 263(c)
2030047
Secondary containment
maintained tight and has
been confirmed by testing
®
❑
❑
❑
❑
❑
None
- 23 CCR 16 2662: HSC 6.7
25290.1(c)(2), 25290.2(c)(2),
25291(a), 25292 e
2030060
Entry fittings in secondary
containment for UST
system maintained
®
❑
❑
❑
❑
❑
None
tight/seated - 23 CCR 16
2630,2635(d), 2636(c),
2666
2060020
Spill bucket is installed
RP
and has a functional drain
❑
valve or other means to
®
❑
❑
❑
❑
❑
None
remove liquid - 23 CCR 16
Yes
2635 6 , 2665
2030054
Spill bucket maintained in
RP
good condition and free of
®
❑
❑
❑
❑
❑
None
❑
debris and/or liquid - 23
Yes
CCR 16 2635(b), 2715 c (2)
2060019 Spill bucket to has a.
minimum capacity of five ® ❑
❑ ❑ ❑ ❑
None
gallons - 23 CCR 16
2635(b), 2665
Overfill
2030035
UST system is operated
RP
to prevent unauthorized
®
❑
❑
❑
❑
❑
None
❑
release, including spills
and overfills - HSC 6.7
Yes
25292.1(a)
2030036
Overfill prevention system
RP
has not been overridden
®
❑
❑
❑
❑
❑
None
❑
and meets. overfill
requirements - 23 CCR 16
Yes
2635(b)(2),2665
Underground Storage Tank Program- DW Inspection Report v 2.0
Violation
Program Requirement
m;`o_
SOC
Comments
O
N
O
H
e;N
M O
p
On Site
Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
®
❑[EEI
❑
❑
❑
None
current ICC certification -
23 CCR 16 2715
2030024
Service technician,
installer, and/ or
employee maintain a
®
❑
❑
❑
❑
None
proper license - 23 CCR
162715
2030031
Employee o ccontractor
obtained and maintained
proper manufacturer
®
❑
❑
❑
❑
None
certification - 23 CCR 16
2715
2010007
Submit/maintain current
Certificate of Financial
Responsibility/mechanism
of financial assurance -
®
❑
❑
❑
❑
❑
None
23 CCR 16 2711; 23 CCR
18 2808.1, 2809-2609.2;
HSC 6.7 25292.2; HSC
6.75 25299.30-25299.34
Designated Operator
2010004
Copies of DO inspections
for last 12 months and list
of trained employees
®
❑
❑
❑
❑
❑
None
maintained -23 CCR 16
2715
2030018
Designated operator
properly conducted the
monthly inspection and
®
❑
❑
❑
❑
❑
None
the reports are complete -
23 CCR 16 2715
2030010
DO notified operator of
any condition observed
during the monthly
®
❑
❑
❑
❑
❑
None
inspection that may
require action - 23 CCR 16
2715 d)
2030012
DO employee training
performed, current for at
®
El
1-10
El
El
None
least one employee on
site, and a log kept - 23
CCR 16 2715(c)(6), 2715
Underground Storage Tank Program - DW inspection Report v 2.0
Violation
Program Requirement
v o
SOCComments
No
z
o
z
0
0
os
Logs
2030001
Leak detection alarm
logs, maintenance and
RD
records of appropriate
®
❑
❑
❑
❑
❑
None
❑
follow-up actions
Yes
maintained - 23 CCR 16
2632, 2634, 2712(6)
Maintenance)Tests
2010008
Monitoring, maintenance,
repairs, linings, and
RD
upgrade records
010
❑
❑
❑
❑
None
❑
maintained for the proper
Yes
time period - 23 CCR 16
2712 6
Documentation
2030033
Failure to. maintain on site
an approved monitoring
®
❑
❑
❑
❑
❑
None
plan - 23 CCR 16 2632,
2634, 2711, 2712(i
2030037
Written agreement
between the tank owner
and tank operator to
®
El
11
❑
❑
None
monitor the tank system
is maintained - 23 CCR 16
2620(6); HSC 6.7
25264(a)f3)
2030061
Suspected or actual
RD
unauthorized release
❑
❑
®
❑
❑
❑
None
❑
reported in appropriate
time frame - HSC 6.7
Yes
29294, 29295
General operating Requirements
Permit Condition/Approval
2030039
Compliance with all
operating permit
®
❑
❑
❑
❑
❑
None
conditions - 23 CCR 16
2712; HSC 6.7 25299
2030059
UST system maintained
in accordance with
®
❑
❑
❑
❑
❑
None
exclusion/exemption
status - HSC 6.725281.6,
25283.5
2030014
Owner/Operator received
approval and has
implemented a training
❑
❑
®
❑
❑
❑
None
program at an unstaffed
facility - 23 CCR 16
2715 2
2030015
Facility exhibited that the
method used to monitor
the tank meets the
®
❑
❑
❑
❑
❑
None
monitoring methods in
2643(f) - 23 CCR 16 2643
Underground Storage Tank Program - DW Inspection Report
Violation
Program Requirement
'c2
'SOC
Comments
NO
0
m_z
O
z
M
0U
K
O
Red Tag
2030045
Red Tag information is
legible and has not been❑
❑
®
❑
❑
❑
No
tampered with - 23 CCR
16 2717.1
2030044
Facility did not allow for
deposit of petroleum into
a UST that has a red tag
❑
❑
®
❑
❑
❑
None
affixed to the fill - 23 CCR
16 2717.1
Install/Repair
2060024
UST system is made of or
lined with materials that
are compatible with the
❑
❑
❑
❑
❑
❑
None
substance stored - 23
CCR 16 2631.1
2060021
Striker plate installed and
positioned correctly - 23
®
❑
❑
❑
❑
❑
None
CCR 16 2631(c), 2662 d
® There were no violations noted for this inspection.
❑This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any
violations noted, and for those not coy ected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.) /?
Inspectors Signature: G/ Date:
uispecw,.....o, m �. __..
Check one box forfacility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release
Prevention violations)
❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release
Underground Storage Tank Program - DW inspection Report v 2.0