HomeMy WebLinkAboutCUPA 2-24-20BAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
Underground Storage To r ram 2101 H Street rA
DW Inspection Re Bakersfield, CA 93301Permission to Inspect' Phone: 661-326-3979
Fax: 661-852-2171
Business Name: Lucky 7 #3 15-021-020875 CAL000364693 Date:2124/2020
I Address Name: 726 S. Union BAKERSFIELD, CA 93307 (661) 324-8516 1 Inspector Name: Peter Armagost 1/8856813 9
Inspection Type: Routine N Report : Final
NVO COS = Corrected On Site RPT O Repeat Violation bserved UT= Out of pliance NA =Not Applicable UD = Undetermined I
Violation
Program Requirement
cSOC
Comments
No
N
i
O
i
U
K
p'>
File Review
Facility Tank Information
2030021
Facility has a valid Permit
Tank 1 -15000 -REG -DW
to Operate from the
Tank 2 -5000 -PRM -DW
CUPA-23CCR162712(i);
M
❑
❑
❑
❑
❑
None'
Tank 3 -5000 -DSL -DW
HSC 6.7 25284
2010010
UST Operating Permit
Application for Facility
information and Tank
information
M
❑
❑
❑
❑
❑
None
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001
Current BOE number
submitted to the CUPA
M
❑
❑
❑
❑
❑
None
and/or CERS - HSC 6.7
25286 c
2030011
UST compliance
statement and/or
Designated Operator
M
❑
❑
❑
❑
❑
None
current certification
submitted - 23 CCR 16
2715(a), 2715(b)
2030046
A complete and accurate
response plan has been
submitted, approved and
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
27121
2030041
A complete and accurate
plot plan has been
submitted, approved and
M
❑
❑
❑
❑
❑
Minor
maintained - 23 CCR 16
2632 d 1 C, 2711 a 8
2010006
Owner/Operator has not
made false statements or
representation on any
M
❑
❑
❑
❑
❑
None
required document - HSC
6.725299
Violation
Program Requirement
m. 2
SOC
Comments
O
z
O
O
b
O
F
215
00
Z
K
.>
2010003
Owner/Operator has a
CUPA was not informed of change
DO and/or informed the
in ownership of the facility.
CU PA of any change (s)
within 30 days - 23 CCR
❑
®
❑
❑
❑
❑
None
16 2715(a)
Testing
2030002
Owner/Operator has
tested and certified leak
®
❑
❑
❑
❑
❑
None
detection equipment
annual) - 23 CCR 16 2638
2030048
Secondary containment
testing conducted every
36 months in accordance
®
❑
❑.
❑
❑
❑
None
with requirements - 23
CCR 16 2637
2030055
Spill buckets have been
tested annually as
®
❑
❑
❑
❑
❑
None
required - HSC 6.7 25264.2
2010009
Secondary containment
test results submitted to
the CUPA within 30 days
®
❑
❑
❑
❑
❑
None
after the test- 23 CCR 16
2637 e
2030064
CUPA was poperly
notified within the
prescribed number of
®
❑
❑
❑
❑
❑
None
hours prior to testing - 23
CCR 16 2637p), 2638(e),
2643(g), 2644.1(8)(4)
Install/Repair
2060009
Permits obtained to
install, replace, repair, or
®
❑
❑
❑
❑
❑
None
modify part of the UST
s Stem - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
®
❑
❑
❑
❑
❑
None
❑
an audible and visual
Yes
alarm - 23 CCR 162632,
2634, 2636, 2666
2030016
The annular space of the
tank, piping and sumps
RD
are continuously
®
❑
❑
❑
❑
❑
None
❑
monitored and activates
the alarm - 23 CCR 16
Yes
2631(g), 2632(c)(2)(A)&(8),
2633(c), 2636
Underground Storage Tank Program -DW Inspection Report v 2.0
Violation
Program Requirement
v a
SOC
Comments
No
O
a
o
o.
0.
m
Z
0
Z
U
K
o';o
2030017
Product piping outside the
UDC is fail-safe and shuts
down the pump or
®
❑
❑
❑
❑
❑
None
restricts flow - 23 CCR 16
2636(0 (5)
2030018
Turbine sump monitor
RD
activates an audible and
visual alarm or stops the
®
❑
❑
❑
❑
❑
None
❑
flow of at the dispenser -
Yes
23 CCR 16 2636 (0(1)
2030019
Monitoring system in the
UDCs activates an
audible and visual alarm
®
❑
❑
❑
❑
❑
None
or stops the flow at the
UDC - 23 CCR 16
2636 1
2030043
Leak detection equipment
RD
properly. programmed or
properly operated - 23
®
❑
❑
❑
❑
❑
None
❑
CCR 16 2632, 2634, 2636,
Yes
2666
2060005
System constructed with
a monitoring system
capable of detecting entry
®
❑
❑
❑
❑
❑
None
into secondary
containment - HSC 6.7
25291(b)
2060014
Correct leak detection
equipment installed for
RD
the type of system
®
❑
❑
❑
❑
❑
None
❑
present- 23 CCR 16 2638;
Yes
HSC 6.7 25290.1, 25290.2,
25291
2060015
Sensor located in the
RD
proper position/location -
®
❑
❑
❑
❑
❑
None
❑
23 CCR 16 2630(d), 2641(a)
Yes
2030062
Facility is in compliance
RD
with not tampering with or
disabling leak detection
®
❑
❑
❑
❑
❑
None
❑
devices or alarms - HSC
Yes
6.7 25299 a 9
2060022
System constructed with
a monitoring system
capable of detecting entry
®
❑
❑
❑
❑
❑
None
into secondary
containment - HSC 6.7
25290.2(d)
2030034
Tag/ ticker on affixed
monitoring equipment
being certified, repaired,
®
❑
❑
❑
❑
❑
None
or replaced - 23 CCR 16
2638
VPH Monitoring VPH
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
v o.
SOC
Comments
No
o.
K
v
z
o
z
p'j
2030065
Interstitial monitoring of
RD
the annular spaces of the
UST is properly
❑
❑
®
❑
❑
❑
None
❑
maintained - HSC 6.7
Yes
25290.1(e)
2060023
System constructed with
a monitoring system
capable of detecting entry
into secondary
❑
❑
®
❑
❑
❑
None
containment - HSC 6.7
25290.1(d)
Line Leak Detector
2060012
Line leak detector
installed on pressurized
RD
piping system - HSC 6.7
❑
❑
®
❑
❑
❑
None
❑
25290.1(h), 25290.2(8),
Yes
25291(0, 25292(e),
2636(f)(2)
2030026
Line leak detectors detect
87 Line Leak Detector failed
a 3 gph leak and/or
RD
during the annual FMC
audible and visual alarm
❑
®
❑
❑
❑
❑
None
❑
function properly - 23
Yes
CCR 16 2636(0(6),
2666(c)
2030027
Turbine shuts down when
RD
a leak is detected or
when line leak detector is
❑
❑
®
❑
❑
❑
None
❑
disconnected - 23 CCR 16
Yes
2666(c)
2030025
Pressurized piping able to
detect a 3.0.gph leak
RD
within an hour, and
❑
❑
®
❑
❑
❑
None
❑
restricts the flow or
Yes
alarms - 23 CCR 16
2636 2
Secondary Containment
2060010
UST storing a hazardous
RD
substance has secondary
®
❑7FF-11❑
❑
❑
None
❑
E_
containment - HSC 6.7
Yes
25292
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirementn;
o
SOC
Comments
No
S
i
o
z
o
o
0
W
m—
2030008
UDC, sumps, and/or
other secondary
containment in good
®
❑
❑
❑
❑
❑
None
condition and/or are free
of debris/liquid - HSC 67
25290.1, 25290.2, 25291
2030040
Secondarily contained
RD
piping maintained to allow
®
❑
❑
❑
❑
❑
None
❑
liquid to drain into sump -
Yes
23 CCR 16 2630(d), 2641 a
2060006
Secondary containment
piping slopes back to the
®
❑
❑
❑
❑
❑
None
collection sump - 23 CCR
6 263 c
2030047
Secondary containment
maintained tight and has
been confirmed by testing
®
❑
❑
❑
❑
❑
None
- 23 CCR 16 2662, HSC 6.7
25290. 1 (c)(2), 25290.2(c)(2),
25291(a), 25292(e)
2030060
Entry fittings in secondary
containment for UST
system maintained
®
❑
❑
❑
❑
❑
None
tightfsealed - 23 CCR 16
2630, 2635(d), 2636(c),
2666
2060020
Spill bucket is installed
RP
and has a functional drain
valve or other means to
®
❑
❑
❑
❑
❑
None
❑
remove liquid - 23 CCR 16
Yes
2635(b), 2665
2030054
Spill bucket maintained in
RP
good condition and free of
®
❑
❑
❑
❑
❑
None
❑
debris and/or liquid - 23
Yes
CCR 16 2635(b), 2715(c)(2)
2060019
Spill bucket to has a
minimum capacity of five
®
❑
❑
❑
❑
❑
None
gallons - 23 CCR 16
2635(b), 2665
Overfill
2030035
UST system is operated
RP
to prevent unauthorized
release, including spills
®
❑
❑
❑
❑
❑
None
❑
and overfills - HSC 6.7
Yes
25292J(a)
2030036
Overfill prevention system
RP
has not been overridden
and meets ovefll
®
❑
❑
❑
❑
❑
None
❑
requirements - 23 CCR 16
Yes
2635(b)(2),2665
Underground Storage'Pank Program - DW Inspection Report v 2.0
Violation
Program Req!no
v o
SOC
Comments
No
O
o_
D
O
Q
Z
D
U
Y
On Site
Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
®
❑
❑
❑
❑
❑
None
current ICC certification -
23 CCR 162715
2030024
Service technician,
installer, and/ or
employee maintain a
®
❑
❑
❑
❑
❑
None
proper license - 23 CCR
152715
2030031
Employee orcontractor
obtained and maintained
proper manufacturer
®
❑
❑
❑
❑
❑
None
certification - 23 CCR 16
2715
2010007
Submit/maintain current
Certificate of Financial
Responsibility/mechanism
of financial assurance -
®
❑
❑
❑
❑
❑
None
23 CCR 16 2711; 23 CCR
18 2808.1, 2809-2809.2;
HSC 6.7 25292.2; HSC
6.75 25299.30-25299.34
Designated Operator
2010004
Copies of DO inspections
Over 6 months DO inspection are
for last 12 months and list
missing from the UST binder.Last
of trained employees
❑
H
❑
❑
❑
❑
None
DO inspection found was 6/19
maintained - 23 CCR 16
2715
2030013
Designated operator
properly conducted the
monthly inspection and
®
❑
❑
❑
❑
❑
None
the reports are complete -
23 CCR 16 2715
2030010
DO notified operator of
any condition observed
during the monthly
®
❑
❑
❑
❑
❑
None
inspection that may
require action - 23 CCR 16
2715(d)
2030012
DO employee training
performed, current for at
least one employee on
®
❑
❑
❑
❑
❑
None
site, and a log kept - 23
CCR 162715c 6,2715(
Underground Storage Tank. Program - DW Inspection Report v 2.0
Violation
Program Requirement
m ;o
SOC
Comments
No
O0
a 8
z
o
z
n
¢
.5.
Logs
2030001
Leak detection alarm
Alarm logs for the site are not
logs, maintenance andRD
current. On duty employee was
records of appropriate
❑
®
1-1
El❑
❑
None
❑
not trained on how to monitor and
follow-up actions
Yes
log events.
maintained - 23 CCR 16
2632, 2634, 2712(b)
Maintenance/Tests
2010008
Monitoring, maintenance,
repairs, linings, and
RD
upgrade records
®
❑
❑
❑
❑
❑
None
❑
maintained for the proper
Yes
time period - 23 CCR 16
2712(b)
Documentation
2030033
Failure to maintain on site
an approved monitoring
®
❑
❑
❑
❑
❑
None
plan - 23 CCR 16 2632,
2634, 2711, 2712(1
2030037
Written agreement
between the tank owner
and tank operator to
monitor the tank system
®
❑
❑
❑
❑
❑
None
is maintained - 23 CCR 16
2620(b); HSC 6,7
25284 a 3
2030061
Suspected or actual
RD
unauthorized release
reported in appropriate
❑
❑
®
❑
❑
❑
None
❑
time frame - HSC 6.7
Yes
29294, 29295
General Operating Requirements
Permit Condition/Approval.
2030039
Compliance with all
operating permit
®
❑
❑
❑
❑
❑
None
conditions - 23 CCR 16
2712; HSC 6.7 25299
2030059
UST system maintained
in accordance with
exclusion/exemption
®
❑
❑
❑
❑
❑
None
status - HSC 6.7 25281.6,
25263.5
2030014
Owner/Operator received
approval and has
Implemented a training
❑
❑
®
❑
❑
❑
None
program at an unstaffed
facility - 23 CCR 16
2716 (0(2)
2030015
Facility exhibited that the.
method used to monitor
the tank meets the
monitoring methods in
JEEI
❑
❑
❑
❑
None
2643(f) - 23 CCR 16 2643
Underground Storage Tank Program - DW Inspection Report v 2,0
Violation
Program Requirementd
o
SOC
Comments
No
m
i
O
z
v
rc
o�
Red Tag
2030045
Red Tag information is
legible and has not been
❑
❑
®
❑
❑
tampered with - 23 CCR
16271716o)
2030044
Facility did not allow for
tE]None
deposit of petroleum into
a UST that has a red tag
ElEl®
E]
E]
affixed to the fill - 23 CCR
16 2717.1
Install/Repair
2060024
UST system is made of or
lined with materials that
are compatible with the
E
❑
❑
❑
❑
❑
None
substance stored - 23
CCR 162631.1
2060021
Striker plate installed and
positioned correctly - 23
Z
❑
❑
❑
❑
❑
None
CCR 16 2631(c), 2662 d
❑ There were no violations noted for this inspection.
ZThis report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION' for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature: /' i Date: 2�Y 5��7dZ0
Inspector: Enter # of Violations: RD: _ RP:
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release
Prevention violations)
❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release
Underground Storage Tank Program - DW Inspection Report v 2.0