Loading...
HomeMy WebLinkAboutMinit Stop 1-16-2020 91 LLDAdvanced Compliance 3704 Littlefalls Ct. Bakersfield, Ca. 93308 661-706-4321 Fax# 661-589-9329 VAPORLESS MANUFACTURING, INC. LDT-890 Leak Detector Test Record Contractor: Advanced Compliance Customer: Minit Stop Date: 1/16/2020 Location: 2900 Union AveBakersfield, Ca. Product:91 Technician: Bradley W. Hinsley Submersible Pump Identification Manufacturer: Red Jacket Model No.: Serial No.: Notes: Leak Detector Identification Manufacturer: Red Jacket Description: FX-1V Diaphragm-type: Piston-type: Tamper-proof seal installed: Other Style Leak Detector: Notes: Leak Detector in Submersible Pump Test at Dispenser Operating Pump Pressure (psi): 28 (para. 15) Gallons per hour rate: 3.0 (para. 22) Line pressure with pump shut off (psi): 16 (para. 23) Bleed-back Test with pump off (ml): 105 (para. 26) Step-through time to full flow (secs): 3 (para. 30) Leak detector stays in leak search position (Yes/No): Yes (para. 42) Leak Detector Test Pass / Fail Notes: Pass *Complete thermal expansion test before failing leak detector