Loading...
HomeMy WebLinkAboutFINAL ELD 4-14-2020Exclusive Providers for MDleak® MSleak® DPleak® and PHDleak® Testing Technologies Page 1 of 3 Test Type: Facility Name: Job #: 4197 Prepared For: PO #: NA Site Address: City: Primary Test Leak Rate: 0.005 gph State and Zip: CA 93313 Secondary Test Leak Rate: 0.1 gph Start Date:End Date: SYSTEM TK-1-87 TK-2-87 TK-3-91 TK-4-Dsl Product Primary MDleak:PASS PASS PASS PASS Product Secondary:PASS PASS PASS PASS Vent Primary MDleak:PASS PASS PASS PASS Vent Secondary:PASS PASS PASS PASS VR Primary MDleak:PASS PASS PASS NA VR Secondary:PASS PASS PASS NA MCleak ELD Tank:NA NA NA NA 72 Hr. Out of Service:NA NA NA NA MDleak ELD Tank:PASS PASS PASS PASS Turbine Sump MDleak:PASS PASS PASS PASS Turbine Head MDleak:PASS PASS PASS PASS F/Vapor Sump MDleak:PASS PASS PASS PASS UDC's MDleak:PASS PASS PASS PASS Fill Bucket MDleak:PASS PASS PASS PASS Vapor Bucket MDleak:PASS PASS PASS NA Vent Box MDleak:PASS PASS PASS PASS Fill Spill Bucket Hydo:PASS PASS PASS PASS Vapor Bucket Hydro:PASS PASS PASS NA STP Sump Elect DPleak:PASS PASS PASS PASS Certifying Field Technician: Ricardo Gonzalez State Lic. # : Certification Leak Rate: 0.005 gph Certifying Technician Signature: Date: Statement Confirmed by: Date: Jaco Oil Company Facility Certification CONFIDENTIAL California ELD New Construction Test MDleak Howard's Mini Mart 3200 Panama Lane Bakersfield This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak sensitivity listed above by using one or more of the following DPleak®,MDleak®and PHDleak®EPA aproved Methods. The DPleak®,MDleak®and PHDleak®Methods are the most versatile and comprehensive testing procedures offered to the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®and PHDleak®Method can be assured that their facility has passed the Nation's highest standard in preventative leak detection. 4/14/2020 4/14/20204/13/2020 4/14/2020 Office use only I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is true and correct to the best of my knowledge. If you have any questions on the testing please do not hesitate to call. @ 855-255-5325. 04-1695 Exclusive Providers for MDleak® MSleak® DPleak® and PHDleak® Testing Technologies Page 2 of 3 3200 Panama Lane Log of Repaired Leak/s CONFIDENTIAL TK-1-87 TK-2-87 TK-3-91 TK-4-Dsl Tank Volume:12000 12000 12000 12000 Manufacture:Modern Modern Modern Modern Interstice:Dry Dry Dry Dry Depth To Tank:56"56"55"55" Tank Dia:8 ft 8 ft 8 ft 8 ft Depth of Liquid:No Fuel No Fuel No Fuel No Fuel Tank Sump Boots Turbine Bravo Bravo FE Petro 4 Gilbarco Emco-Wheaton Bravo OmegaFlex Smith Fire-Flex Emco-Wheaton EVR: Healy Reference #Date Time Status System Component Manufacture 137 4/13/20 12:52 Leak Final TK-1-87 STP Sump ATG to riser leaking. 139 4/13/20 12:54 Leak Final TK-2-87 STP Sump ATG to riser leaking. 141 4/13/20 12:56 Leak Final TK-3-91 STP Sump ATG to riser leaking. 146 4/13/20 13:04 Leak Final UDC 3 Clamp on 87-1 & 87-2 Leaking. 147 4/13/20 13:05 Leak Final UDC 4 91 Shear valve cracked. 164 4/13/20 15:52 Leak Final UDC 4 Shear valve cracked on DSL. Reference #Date Time Status System Component Manufacture None Vapor Return / Vent: UDC/Dispensers Information Depth to Ground Water: Manufacture: NA Log of Repaired Leaks Log of Unrepaired Leaks Tank Information Containment Boots: Piping Information Manufacture Spill Buckets: Number of Dispensers: Manufacture: Shear Valve Manufacture: Flex: Product Lines: Exclusive Providers for MDleak® MSleak® DPleak® and PHDleak® Testing Technologies Page 3 of 3 3200 Panama Lane Reference Addendum CONFIDENTIAL Site Photo