HomeMy WebLinkAboutFINAL ELD 4-14-2020Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 1 of 3
Test Type:
Facility Name: Job #: 4197
Prepared For: PO #: NA
Site Address:
City: Primary Test Leak Rate: 0.005 gph
State and Zip: CA 93313 Secondary Test Leak Rate: 0.1 gph
Start Date:End Date:
SYSTEM TK-1-87 TK-2-87 TK-3-91 TK-4-Dsl
Product Primary MDleak:PASS PASS PASS PASS
Product Secondary:PASS PASS PASS PASS
Vent Primary MDleak:PASS PASS PASS PASS
Vent Secondary:PASS PASS PASS PASS
VR Primary MDleak:PASS PASS PASS NA
VR Secondary:PASS PASS PASS NA
MCleak ELD Tank:NA NA NA NA
72 Hr. Out of Service:NA NA NA NA
MDleak ELD Tank:PASS PASS PASS PASS
Turbine Sump MDleak:PASS PASS PASS PASS
Turbine Head MDleak:PASS PASS PASS PASS
F/Vapor Sump MDleak:PASS PASS PASS PASS
UDC's MDleak:PASS PASS PASS PASS
Fill Bucket MDleak:PASS PASS PASS PASS
Vapor Bucket MDleak:PASS PASS PASS NA
Vent Box MDleak:PASS PASS PASS PASS
Fill Spill Bucket Hydo:PASS PASS PASS PASS
Vapor Bucket Hydro:PASS PASS PASS NA
STP Sump Elect DPleak:PASS PASS PASS PASS
Certifying Field Technician: Ricardo Gonzalez State Lic. # :
Certification Leak Rate: 0.005 gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date:
Jaco Oil Company
Facility Certification CONFIDENTIAL
California ELD New Construction Test MDleak
Howard's Mini Mart
3200 Panama Lane
Bakersfield
This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak
sensitivity listed above by using one or more of the following DPleak®,MDleak®and PHDleak®EPA aproved Methods.
The DPleak®,MDleak®and PHDleak®Methods are the most versatile and comprehensive testing procedures offered to
the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®and PHDleak®Method
can be assured that their facility has passed the Nation's highest standard in preventative leak detection.
4/14/2020
4/14/20204/13/2020
4/14/2020
Office use only
I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National
Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is
true and correct to the best of my knowledge.
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
04-1695
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 2 of 3
3200 Panama Lane Log of Repaired Leak/s
CONFIDENTIAL
TK-1-87 TK-2-87 TK-3-91 TK-4-Dsl
Tank Volume:12000 12000 12000 12000
Manufacture:Modern Modern Modern Modern
Interstice:Dry Dry Dry Dry
Depth To Tank:56"56"55"55"
Tank Dia:8 ft 8 ft 8 ft 8 ft
Depth of Liquid:No Fuel No Fuel No Fuel No Fuel
Tank Sump Boots Turbine
Bravo Bravo FE Petro
4
Gilbarco
Emco-Wheaton
Bravo
OmegaFlex
Smith
Fire-Flex
Emco-Wheaton
EVR: Healy
Reference #Date Time Status System Component Manufacture
137 4/13/20 12:52 Leak Final TK-1-87 STP Sump ATG to riser leaking.
139 4/13/20 12:54 Leak Final TK-2-87 STP Sump ATG to riser leaking.
141 4/13/20 12:56 Leak Final TK-3-91 STP Sump ATG to riser leaking.
146 4/13/20 13:04 Leak Final UDC 3 Clamp on 87-1 & 87-2 Leaking.
147 4/13/20 13:05 Leak Final UDC 4 91 Shear valve cracked.
164 4/13/20 15:52 Leak Final UDC 4 Shear valve cracked on DSL.
Reference #Date Time Status System Component Manufacture
None
Vapor Return / Vent:
UDC/Dispensers Information
Depth to Ground Water:
Manufacture:
NA
Log of Repaired Leaks
Log of Unrepaired Leaks
Tank Information
Containment Boots:
Piping Information
Manufacture
Spill Buckets:
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Flex:
Product Lines:
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 3 of 3
3200 Panama Lane Reference Addendum CONFIDENTIAL
Site Photo