HomeMy WebLinkAboutFMC - 4012 WHITE LN 11-23-2020MONITOR CERTIFICATION
11000 N. MoPac Expressway, Suite 500
Austin, Texas 78759
Phone: (512) 451-6334
Fax: (512) 459-1459 Date Printed and Mailed: 12/7/2020
BAKERSFIELD FIRE DEPARTMENT
OFFICE OF ENVIRONMENTAL SERVICES
INSPECTOR KRIS KARNS
1501 TRUXTUN AVE.
BAKERSFIELD, CA 93301
Test Date: 11/23/2020
Order Number: 3453427
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7-ELEVEN #22150
4012 WHITE LN
BAKERSFIELD, CA 93309
In an effort to keep all our record keeping and reporting requirements as current as possible,
Tanknology kindly requests you notify Dawn Kohlmeyer in writing at dkohlmeyer@tanknology.com
when your CUPA requires all records to be submitted electronically via the CERS database. Your
assistance in this endeavor is greatly appreciated.
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
Tanknology, Inc.800-964-1250
11000 N Mopac Expy #500 Austin, Tx 78759
Luis Navarro
10461655 11/23/2020
7-ELEVEN #22150
4012 WHITE LN BAKERSFIELD 93309
Class A General Engineering 743160
8171123 01/05/2021
05/28/2022
11/23/2020 6
Veeder Root:VR TLS-3XX
Veeder Root TLS-350 335.00
S11 87 Product857280-100
T2 91 T2 91 Unleaded
On site tested the S11 87 Product for "No Vacuum" alarm and the T2 probe for high water warning. On the original certification on 10-19-20 we found the S11 in no
Vacuum alarm on arrival. The T2 probe went in high water warning but would not clear on veeder root, installed new 4" float kit and waning cleared. The veeder root returned to "ALL FUNCTIONS NORMAL".
847390-110
11/23/2020
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:3453427
Site ID / Name:22150 / 7-ELEVEN #22150
Address:4012 WHITE LN
City:BAKERSFIELD State:CA Zip:93309
W.O.# SC1-3453427
ALarm history