HomeMy WebLinkAboutFMC RESULTS 2020Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ☐☐☐☐Installation ☐☐☐☐Repair XXXX12 Month
1. FACILITY INFORMATION
CERS ID
10022869
Certification Date
12/16/2020
Facility Name
Cirkle K
Facility Address
5634 Stine Rd.
City
Bakersfield
ZIP Code
93313
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification
B&T Service Station Contractors
Phone
805-929-8944
Mailing Address
630 S. Frontage Rd. Nipomo, CA 93444
Service Technician Performing Test
Michael A. Molacek
Contractor/Tank Tester License Number
902034
ICC Number
9175943
ICC Expiration Date
11/15/2021
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
Veeder Root TLS 350 technician C27091 10/29/2022
Catastrophic Testing Technician VMI #4640 04/06/2022
4.CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is
attached; and all information contained herein is accurate.
Service Technician Signature Date
12/16/2020
Total # of Pages
5.MONITORING SYSTEM AND PROGRAMMING
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Veeder Root
Model of Monitoring System
Control Panel
TLS 350
Software Version Installed
335.00
Attach the post-certification reports if the monitoring system is capable of generating
either;XXXXMonitoring System Set-up XXXXAlarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? XXXX ☐☐☐☐
Secondary containment systems arefree of damage, debris, or liquid? XXXX ☐☐☐☐
Are the audible and visual alarms operational? XXXX ☐☐☐☐
All sensors have been: 1) visually inspected for wiring kinks, breaks andresidual buildup on
floats; and 2) tested for functionality and confirmed operational? XXXX ☐☐☐☐ ☐☐☐☐
Are all sensors installed to detect a release at the earliest opportunity in the secondary
containment? XXXX ☐☐☐☐ ☐☐☐☐
The monitoring system set-up was reviewed,and proper settings confirmed? XXXX ☐☐☐☐ ☐☐☐☐
Was the monitoring control panel’s backup battery visually inspected, functionally tested,
and confirmed operational? XXXX ☐☐☐☐ ☐☐☐☐
Does the flow of fuel stop at the dispenser if a release is detected in the under-dispenser
containment? XXXX ☐☐☐☐ ☐☐☐☐
Does the turbine automatically shut down if the piping secondary containment monitoring
system fails to operate or is electrically disconnected? XXXX ☐☐☐☐ ☐☐☐☐
Does the turbine automatically shut down if the piping secondary containment monitoring
system detects a release?Which sensors initiate positive shut down? (Check all that
apply)XSump ☐UDC
XXXX ☐☐☐☐ ☐☐☐☐
If monitoring system alarms are relayed to a remote monitoring center, is all communication
equipment operational? XXXX ☐☐☐☐ ☐☐☐☐
Describe all answers marked “No” or “Fail”and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming.
Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
L1 409 87 Annular Space XXXX ☐☐☐☐
L2 208 87 STP XXXX ☐☐☐☐
L3 409 91 Annular Space XXXX ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L4 208 91 STP X
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
☐☐☐☐Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
XXXX3 GPH ☐☐☐☐0.1 GPH☐☐☐☐0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? XXXX ☐☐☐☐ ☐☐☐☐
For emergency generator tank systems, does the LLD create an audible and visual alarm
when a leak is detected? ☐☐☐☐ ☐☐☐☐ XXXX
For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is
detected? XXXX ☐☐☐☐ ☐☐☐☐
For electronic LLDs, does the turbine automatically shut off when a release is detected? ☐☐☐☐ ☐☐☐☐ XXXX
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring
system is disabled or disconnected? ☐☐☐☐ ☐☐☐☐ XXXX
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring
system malfunctions or fails a tightness test? ☐☐☐☐ ☐☐☐☐ XXXX
For electronic LLDs, have all accessible wiring connections been visually inspected for
kinks and breaks? ☐☐☐☐ ☐☐☐☐ XXXX
Were all items on the equipment manufacturer’s maintenance checklist completed? XXXX ☐☐☐☐ ☐☐☐☐
Were all LLDs confirmed operational within regulatory requirements? XXXX ☐☐☐☐ ☐☐☐☐
LLD ID LLD Model Lines Monitored Pass Fail
T1 LD2200 87 XXXX ☐☐☐☐
T2 LD2200 91 XXXX ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
XXXXCheck this box if tank gauging is used only for inventory control.
☐☐☐☐Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination;
and 2) tested for ground faults? ☐☐☐☐ ☐☐☐☐ ☐☐☐☐
Were all in-tank gauging probes visually inspected for damage and residue buildup to
ensure that floats move freely, functionally tested, and confirmed operational? ☐☐☐☐ ☐☐☐☐ ☐☐☐☐
Was accuracy of system’s product level readings tested? ☐☐☐☐ ☐☐☐☐ ☐☐☐☐
Was accuracy of system’s water level readings tested? ☐☐☐☐ ☐☐☐☐ ☐☐☐☐
Were all probes reinstalled properly? ☐☐☐☐ ☐☐☐☐ ☐☐☐☐
Were all items on the equipment manufacturer’s maintenance checklist completed? ☐☐☐☐ ☐☐☐☐ ☐☐☐☐
Probe ID Probe Model Tanks Monitored Pass Fail
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
☐☐☐☐ ☐☐☐☐
9. COMMENTS
10. MONITORING SITE PLAN
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
<
I10100
DEC 16, 2020 11:53 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
SYSTEM STATUS REPORT
PAPER OUT
PRINTER ERROR
ISD GROSS PRES WARN
>
<
I51700
DEC 16, 2020 11:53 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
>
<
I50F00
DEC 16, 2020 11:53 AM
MON DD YYYY HH:MM:SS xM
>
<
I60100
DEC 16, 2020 11:53 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNL-REG(005) ON
2 UNL-PREM ON
3 OFF
4 OFF
>
<
I60200
DEC 16, 2020 11:53 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNL-REG(005)
2 UNL-PREM
3
4
>
<
I60300
DEC 16, 2020 11:53 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNL-REG(005) A
2 UNL-PREM B
3 3
4 4
>
<
I60400
DEC 16, 2020 11:53 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL-REG(005) 14425
2 UNL-PREM 11849
3 0
4 0
>
<
I60700
DEC 16, 2020 11:53 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNL-REG(005) 117.75
2 UNL-PREM 117.75
3 0.00
4 0.00
>
<
I60900
DEC 16, 2020 11:53 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNL-REG(005) 0.000700
2 UNL-PREM 0.000700
3 0.000000
4 0.000000
>
<
I61200
DEC 16, 2020 11:53 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNL-REG(005) NONE NONE
2 UNL-PREM NONE NONE
3 NONE NONE
4 NONE NONE
>
<
I62100
DEC 16, 2020 11:54 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL-REG(005) 1084
2 UNL-PREM 900
3 0
4 0
>
<
I62200
DEC 16, 2020 11:54 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL-REG(005) 12825
2 UNL-PREM 11257
3 0
4 0
>
<
I62300
DEC 16, 2020 11:54 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL-REG(005) 12983
2 UNL-PREM 10664
3 0
4 0
>
<
I62400
DEC 16, 2020 11:54 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNL-REG(005) 2.5
2 UNL-PREM 2.5
>
<
I62800
DEC 16, 2020 11:54 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL-REG(005) 14425
2 UNL-PREM 11849
3 0
4 0
>
<
I62900
DEC 16, 2020 11:54 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL-REG(005) 749
2 UNL-PREM 948
3 0
4 0
>
<
I70300
DEC 16, 2020 11:54 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87 ANNULAR TRI-STATE (SINGLE FLOAT)
2 87 TURBINE TRI-STATE (SINGLE FLOAT)
3 91 ANNULAR TRI-STATE (SINGLE FLOAT)
4 91 TURBINE TRI-STATE (SINGLE FLOAT)
5 TRI-STATE (SINGLE FLOAT)
6 TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
>
<
I20600
DEC 16, 2020 11:54 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
TANK ALARM HISTORY
TANK 1 UNL-REG(005)
SETUP DATA WARNING OCT 8, 2020 11:23 PM
SEP 22, 2020 5:39 AM
LOW PRODUCT ALARM SEP 20, 2019 7:37 PM
TANK 2 UNL-PREM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
>
<
I30200
DEC 16, 2020 11:54 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 ANNULAR
DEC 16, 2020 10:37 AM SENSOR OUT ALARM
DEC 16, 2020 10:22 AM FUEL ALARM
DEC 16, 2020 10:22 AM FUEL ALARM
2 87 TURBINE
DEC 16, 2020 10:37 AM SENSOR OUT ALARM
DEC 16, 2020 10:20 AM FUEL ALARM
DEC 19, 2019 9:30 AM FUEL ALARM
3 91 ANNULAR
DEC 16, 2020 10:37 AM SENSOR OUT ALARM
DEC 16, 2020 10:16 AM FUEL ALARM
DEC 19, 2019 9:40 AM FUEL ALARM
4 91 TURBINE
DEC 16, 2020 10:37 AM SENSOR OUT ALARM
DEC 16, 2020 10:13 AM FUEL ALARM
DEC 19, 2019 9:29 AM FUEL ALARM
>
<
I38200
DEC 16, 2020 11:55 AM
>
<
I90200
DEC 16, 2020 11:55 AM
SOFTWARE REVISION LEVEL
VERSION 335.00
SOFTWARE# 346335-100-A
CREATED - 18.08.27.10.22
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
>
<
I31600
DEC 16, 2020 11:55 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2 AFM
2 DISP 3-4 AFM
MAY 9, 2019 11:52 AM COMMUNICATION ALARM
3 DISP 5-6 AFM
4 DISP 7-8 AFM
5 DISP 1-2 VPS
>
<
I32300
DEC 16, 2020 11:55 AM
>
<
I34200
DEC 16, 2020 11:55 AM
>
<
I34700
DEC 16, 2020 11:55 AM
>
<
I20700
DEC 16, 2020 11:55 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
TANK LEAK TEST HISTORY
T 1:UNL-REG(005)
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST
PASSED EACH MONTH:
TEST START TIME HOURS VOLUME % VOLUME TEST TYPE
TANK LEAK TEST HISTORY
T 2:UNL-PREM
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST
PASSED EACH MONTH:
TEST START TIME HOURS VOLUME % VOLUME TEST TYPE
>
<
I31200
DEC 16, 2020 11:55 AM
>
<
I38700
DEC 16, 2020 11:56 AM
>
<
I20300
DEC 16, 2020 11:56 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
TANK 1 UNL-REG(005)
TEST STATUS: OFF
LEAK DATA NOT AVAILABLE ON THIS TANK
TANK 2 UNL-PREM
TEST STATUS: OFF
LEAK DATA NOT AVAILABLE ON THIS TANK
>
<
I25100
DEC 16, 2020 11:56 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
CSLD TEST RESULTS
TANK PRODUCT RESULT
>
<
I21300
DEC 16, 2020 11:56 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
DELIVERY REPORT
T 1:UNL-REG(005)
INCREASE DATE / TIME GALLONS TC GALLONS WATER TEMP DEG F HEIGHT
T 2:UNL-PREM
INCREASE DATE / TIME GALLONS TC GALLONS WATER TEMP DEG F HEIGHT
>
<
I31800
DEC 16, 2020 11:56 AM
>
<
I37400
DEC 16, 2020 11:56 AM
>
<
I38900
DEC 16, 2020 11:56 AM
>
<
I11100
DEC 16, 2020 11:56 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 4 STP SUMP 91 TURBINE SENSOR OUT ALARM CLEAR 12-16-20 10:38AM
L 3 ANNULAR 91 ANNULAR SENSOR OUT ALARM CLEAR 12-16-20 10:38AM
L 2 STP SUMP 87 TURBINE SENSOR OUT ALARM CLEAR 12-16-20 10:38AM
L 1 ANNULAR 87 ANNULAR SENSOR OUT ALARM CLEAR 12-16-20 10:38AM
L 4 STP SUMP 91 TURBINE SENSOR OUT ALARM ALARM 12-16-20 10:37AM
L 3 ANNULAR 91 ANNULAR SENSOR OUT ALARM ALARM 12-16-20 10:37AM
L 2 STP SUMP 87 TURBINE SENSOR OUT ALARM ALARM 12-16-20 10:37AM
L 1 ANNULAR 87 ANNULAR SENSOR OUT ALARM ALARM 12-16-20 10:37AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-16-20 10:22AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM ALARM 12-16-20 10:22AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-16-20 10:22AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM ALARM 12-16-20 10:22AM
L 2 STP SUMP 87 TURBINE FUEL ALARM CLEAR 12-16-20 10:21AM
L 2 STP SUMP 87 TURBINE FUEL ALARM ALARM 12-16-20 10:20AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-16-20 10:17AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM ALARM 12-16-20 10:16AM
L 4 STP SUMP 91 TURBINE FUEL ALARM CLEAR 12-16-20 10:13AM
L 4 STP SUMP 91 TURBINE FUEL ALARM ALARM 12-16-20 10:13AM
f 1 OTHER DISP 1-2 AFM CHK VAPOR FLOW MTR CLEAR 10-12-20 9:40AM
f 1 OTHER DISP 1-2 AFM CHK VAPOR FLOW MTR ALARM 10-12-20 9:05AM
f 1 OTHER DISP 1-2 AFM CHK VAPOR FLOW MTR CLEAR 10-12-20 8:36AM
f 1 OTHER DISP 1-2 AFM CHK VAPOR FLOW MTR ALARM 10-07-20 9:05AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:40AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM ALARM 12-19-19 9:40AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:40AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM ALARM 12-19-19 9:39AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:38AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM ALARM 12-19-19 9:38AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:38AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM ALARM 12-19-19 9:38AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:37AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM ALARM 12-19-19 9:37AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:37AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM ALARM 12-19-19 9:36AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:33AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM ALARM 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM ALARM 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM ALARM 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM ALARM 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM ALARM 12-19-19 9:31AM
L 2 STP SUMP 87 TURBINE FUEL ALARM CLEAR 12-19-19 9:30AM
L 2 STP SUMP 87 TURBINE FUEL ALARM ALARM 12-19-19 9:30AM
L 4 STP SUMP 91 TURBINE FUEL ALARM CLEAR 12-19-19 9:29AM
L 4 STP SUMP 91 TURBINE FUEL ALARM ALARM 12-19-19 9:29AM
OTHER ISD GROSS PRES FAIL CLEAR 12-02-19 10:01AM
OTHER ISD GROSS PRES FAIL ALARM 12-02-19 9:02AM
>
<
I11200
DEC 16, 2020 11:56 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR ALARM 12-16-20 11:48AM
SYSTEM PAPER OUT ALARM 12-16-20 11:48AM
OTHER ISD GROSS PRES WARN ALARM 12-10-20 9:02AM
OTHER ISD GROSS PRES WARN CLEAR 12-03-20 9:35AM
SYSTEM PRINTER ERROR CLEAR 11-29-20 5:00AM
SYSTEM PAPER OUT CLEAR 11-29-20 5:00AM
SYSTEM PRINTER ERROR ALARM 11-29-20 5:00AM
SYSTEM PAPER OUT ALARM 11-29-20 5:00AM
OTHER ISD GROSS PRES WARN ALARM 11-28-20 9:02AM
OTHER ISD GROSS PRES WARN CLEAR 11-21-20 11:11AM
OTHER ISD GROSS PRES WARN ALARM 11-16-20 9:04AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 11-13-20 9:00AM
SYSTEM PRINTER ERROR CLEAR 11-12-20 9:12AM
SYSTEM PRINTER ERROR ALARM 11-12-20 9:12AM
SYSTEM PRINTER ERROR CLEAR 11-12-20 9:12AM
SYSTEM PAPER OUT CLEAR 11-12-20 9:12AM
SYSTEM PRINTER ERROR ALARM 11-12-20 9:07AM
SYSTEM PAPER OUT ALARM 11-12-20 9:07AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 11-12-20 9:03AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 11-11-20 9:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 11-10-20 9:05AM
OTHER ISD GROSS PRES WARN CLEAR 11-09-20 1:11PM
OTHER ISD GROSS PRES WARN ALARM 11-07-20 9:04AM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 10-12-20 9:39AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 10-12-20 9:39AM
OTHER ISD SENSOR OUT WARN CLEAR 10-12-20 9:39AM
OTHER ISD SENSOR OUT WARN ALARM 10-12-20 9:05AM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN ALARM 10-12-20 9:05AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN ALARM 10-12-20 9:05AM
OTHER ISD SENSOR OUT WARN CLEAR 10-12-20 8:34AM
T 1 TANK UNL-REG(005) SETUP DATA WARNING CLEAR 10-08-20 11:24PM
T 1 TANK UNL-REG(005) SETUP DATA WARNING ALARM 10-08-20 11:23PM
OTHER ISD SENSOR OUT WARN ALARM 10-07-20 9:05AM
T 1 TANK UNL-REG(005) SETUP DATA WARNING CLEAR 9-22-20 5:40AM
T 1 TANK UNL-REG(005) SETUP DATA WARNING ALARM 9-22-20 5:39AM
SYSTEM PRINTER ERROR CLEAR 9-21-20 11:53PM
SYSTEM PAPER OUT CLEAR 9-21-20 11:53PM
SYSTEM PRINTER ERROR ALARM 9-21-20 11:53PM
SYSTEM PAPER OUT ALARM 9-21-20 11:53PM
SYSTEM PRINTER ERROR CLEAR 9-21-20 5:06AM
SYSTEM PAPER OUT CLEAR 9-21-20 5:06AM
SYSTEM PRINTER ERROR ALARM 9-21-20 5:06AM
SYSTEM PAPER OUT ALARM 9-21-20 5:06AM
SYSTEM PRINTER ERROR CLEAR 9-21-20 5:06AM
SYSTEM PAPER OUT CLEAR 9-21-20 5:06AM
SYSTEM PRINTER ERROR ALARM 9-21-20 5:00AM
SYSTEM PAPER OUT ALARM 9-21-20 5:00AM
OTHER ISD GROSS PRES WARN CLEAR 8-14-20 8:34AM
OTHER ISD GROSS PRES WARN ALARM 8-13-20 9:04AM
SYSTEM PRINTER ERROR CLEAR 7-17-20 9:21AM
>
<
I11400
DEC 16, 2020 11:57 AM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
80749873405001
CLEARED ALARMS REPORT
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 4 STP SUMP 91 TURBINE SENSOR OUT ALARM CLEAR 12-16-20 10:38AM
L 3 ANNULAR 91 ANNULAR SENSOR OUT ALARM CLEAR 12-16-20 10:38AM
L 2 STP SUMP 87 TURBINE SENSOR OUT ALARM CLEAR 12-16-20 10:38AM
L 1 ANNULAR 87 ANNULAR SENSOR OUT ALARM CLEAR 12-16-20 10:38AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-16-20 10:22AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-16-20 10:22AM
L 2 STP SUMP 87 TURBINE FUEL ALARM CLEAR 12-16-20 10:21AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-16-20 10:17AM
L 4 STP SUMP 91 TURBINE FUEL ALARM CLEAR 12-16-20 10:13AM
f 1 OTHER DISP 1-2 AFM CHK VAPOR FLOW MTR CLEAR 10-12-20 9:40AM
f 1 OTHER DISP 1-2 AFM CHK VAPOR FLOW MTR CLEAR 10-12-20 8:36AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:40AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:40AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:38AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:38AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:37AM
L 3 ANNULAR 91 ANNULAR FUEL ALARM CLEAR 12-19-19 9:37AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:33AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:32AM
L 1 ANNULAR 87 ANNULAR FUEL ALARM CLEAR 12-19-19 9:32AM
L 2 STP SUMP 87 TURBINE FUEL ALARM CLEAR 12-19-19 9:30AM
L 4 STP SUMP 91 TURBINE FUEL ALARM CLEAR 12-19-19 9:29AM
OTHER ISD GROSS PRES FAIL CLEAR 12-02-19 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 12-03-20 9:35AM
SYSTEM PRINTER ERROR CLEAR 11-29-20 5:00AM
SYSTEM PAPER OUT CLEAR 11-29-20 5:00AM
OTHER ISD GROSS PRES WARN CLEAR 11-21-20 11:11AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 11-13-20 9:00AM
SYSTEM PRINTER ERROR CLEAR 11-12-20 9:12AM
SYSTEM PRINTER ERROR CLEAR 11-12-20 9:12AM
SYSTEM PAPER OUT CLEAR 11-12-20 9:12AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 11-11-20 9:00AM
OTHER ISD GROSS PRES WARN CLEAR 11-09-20 1:11PM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 10-12-20 9:39AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 10-12-20 9:39AM
OTHER ISD SENSOR OUT WARN CLEAR 10-12-20 9:39AM
OTHER ISD SENSOR OUT WARN CLEAR 10-12-20 8:34AM
T 1 TANK UNL-REG(005) SETUP DATA WARNING CLEAR 10-08-20 11:24PM
T 1 TANK UNL-REG(005) SETUP DATA WARNING CLEAR 9-22-20 5:40AM
SYSTEM PRINTER ERROR CLEAR 9-21-20 11:53PM
SYSTEM PAPER OUT CLEAR 9-21-20 11:53PM
SYSTEM PRINTER ERROR CLEAR 9-21-20 5:06AM
SYSTEM PAPER OUT CLEAR 9-21-20 5:06AM
SYSTEM PRINTER ERROR CLEAR 9-21-20 5:06AM
SYSTEM PAPER OUT CLEAR 9-21-20 5:06AM
OTHER ISD GROSS PRES WARN CLEAR 8-14-20 8:34AM
SYSTEM PRINTER ERROR CLEAR 7-17-20 9:21AM
>
<
I40200
DEC 16, 2020 11:57 AM
>