HomeMy WebLinkAbout631 Baker Street Final ELD 3-4-2019Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 1 of 3
Test Type:
Facility Name: Job #: 3968
Prepared For: PO #: NA
Site Address:
City: Primary Test Leak Rate: 0.005 gph
State and Zip: CA 93305 Secondary Test Leak Rate: 0.1 gph
Start Date:End Date:
SYSTEM TK-1 87 TK-2 91
Product Primary:PASS PASS
Product Secondary:PASS PASS
Vent Primary:PASS PASS
Vent Secondary:PASS PASS
VR Primary:PASS PASS
VR Secondary:PASS PASS
Tank:PASS PASS
Turbine Sump:PASS PASS
Turbine Sump Elect:PASS PASS
Turbine Head:PASS PASS
Fill/Vapor Sump:PASS PASS
UDC's:PASS PASS
Fill Bucket Primary:PASS PASS
Vapor Bucket Primary:PASS PASS
Fill Spill Bucket Hydo:PASS PASS
Vapor Bucket Hydro:PASS PASS
Vent Box:PASS PASS
Certifying Field Technician: Ricardo Gonzalez State Lic. # :
Certification Leak Rate: 0.005 gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date: 3/6/2019
Office use only
I declare under penalty of perjury that I am a licensed tank tester in the DPleak®,MDleak®and PHDleak®method,a
method listed by the NWGLDE organization and that the information contained in this report is true and correct to the best
of my knowledge.
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
04-1695
This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak
sensitivity listed above by using one or more of the following DPleak®,MDleak®and PHDleak®EPA aproved Methods.
The DPleak®,MDleak®and PHDleak®Methods are the most versatile and comprehensive testing procedures offered to
the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®and PHDleak®Method
can be assured that their facility has passed the Nation's highest standard in preventative leak detection.
3/5/2019
3/5/20193/4/2019
631 Baker Street
Bakersfield
Falcon Services
Facility Certification CONFIDENTIAL
California ELD New Construction Test MSleak
Roy's Market
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 2 of 3
631 Baker Street Log of Repaired Leak/s
CONFIDENTIAL
TK-1 87 TK-2 91
Tank Volume: 10000 5000
Manufacture: Modern Modern
Interstice: Dry Dry
Depth To Tank: 60"66"
Tank Dia: 10 ft 10 ft
Depth to Fuel:
Tank Sump Boots Turbine
Bravo Smith FE Petro
4
Gilbarco
OPW
Smith
Smith
Smith
Fire-Flex
OPW
EVR: Healy
Reference #Date Time Status System Component Manufacture
128 3/4/19 13:23 Leak Final TK-2 91 Sump Turbine leak on riser to turbine.
129 3/4/19 13:45 Leak Final TK-1 87 Sump Turbine leak on riser to turbine.
Reference #Date Time Status System Component Manufacture
None
Log of Repaired Leaks
Log of Unrepaired Leaks
Tank Information
Containment Boots:
Piping Information
Manufacture
Spill Buckets:
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Flex:
Product Lines:
Vapor Return / Vent:
UDC/Dispensers Information
Depth to Ground Water:
Manufacture:
NA
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 3 of 3
631 Baker Street Reference Addendum CONFIDENTIAL
Site Photo