HomeMy WebLinkAboutFMC 2021Appendix VI Underground Storage Tank  Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION Installation Repair 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3.TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4.CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages Underground Storage Tank  Monitoring System Certification Form Page 2 of 6 5.MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; Monitoring System Set-up Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? Secondary containment systems are free of damage, debris, or liquid? Are the audible and visual alarms operational? All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? The monitoring system set-up was reviewed, and proper settings confirmed? Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) Sump UDC If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Underground Storage Tank  Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Underground Storage Tank  Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) 3 GPH 0.1 GPH 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? For electronic LLDs, does the turbine automatically shut off when a release is detected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? Were all items on the equipment manufacturer’s maintenance checklist completed? Were all LLDs confirmed operational within regulatory requirements? LLD ID LLD Model Lines Monitored Pass Fail Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Underground Storage Tank  Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING Check this box if tank gauging is used only for inventory control. Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? Was accuracy of system’s product level readings tested? Was accuracy of system’s water level readings tested? Were all probes reinstalled properly? Were all items on the equipment manufacturer’s maintenance checklist completed? Probe ID Probe Model Tanks Monitored Pass Fail 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ☐ Installation ☐ Repair ☐ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ☐ Manufacturer ☐ Industry Standard ☐ Professional Engineer Test Type ☐ Pressure ☐ Vacuum ☐ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other Is the spill container minimum capacity five gallons excluding riser volume? ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* Method to keep spill container empty ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other Spill Container Test Results ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other Is the spill container minimum capacity five gallons excluding riser volume? ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* Method to keep spill container empty ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other Spill Container Test Results ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. SPILL BUCKET TESTING INFORMATION Test Method Used: Test Equipment Used: Equipment Resolution: Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1 2 3 4 Bucket Installation Type: Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test: Test Start Time (TI): Initial Reading (RI): Test End Time (TF): Final Reading (RF): Test Duration (TF – TI): Change in Reading (RF - RI): Pass/Fail Threshold or Criteria: Test Result: CVE Cal- Valley Equipment 3500 Gilmore Ave. Bakersfield CA 93308 661 -327-9341 FAX# 661 -325-2529 VAPORLESS MANUFACTURING, INC. LDT-890 Leak Detector Test Record Technician Date Pass / Fail Product Manufacturer Leak rate Operating pressure Line pressure (pump off) Facility Address Bleed back (pump off) Step through time to full flow Stays in leak search position file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] < I20100FEB 5, 2021 9:30 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 IN-TANK INVENTORY TANK PRODUCT VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP 1 UNLEADED 13948 13928 6134 83.55 0.83 62.01 2 PREMIUM 6768 6747 5273 69.98 0.00 64.28 3 DIESEL 6308 6292 1719 93.49 0.00 65.49 > <I90500 FEB 5, 2021 9:31 AMSOFTWARE REVISION LEVEL VERSION 327.04SOFTWARE# 346327-100-E CREATED - 07.02.06.10.28 S-MODULE# 330160-004-aSYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD PMC > <I50201 FEB 5, 2021 9:31 AM SHIFT TIME 1 : 11:00 PM >< I50202FEB 5, 2021 9:31 AM SHIFT TIME 2 : DISABLED > <I50203 FEB 5, 2021 9:31 AM SHIFT TIME 3 : DISABLED file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] > <I50204 FEB 5, 2021 9:31 AM SHIFT TIME 4 : DISABLED >< I54600FEB 5, 2021 9:31 AM TANK PER TST NEEDED WRN: DISABLED > <I54900 FEB 5, 2021 9:31 AM TANK ANN TST NEEDED WRN: DISABLED >< I55300FEB 5, 2021 9:31 AM LINE RE-ENABLE METHOD PASS LINE TEST >< I55600FEB 5, 2021 9:31 AM LINE PER TST NEEDED WRN: DISABLED > <I55900 FEB 5, 2021 9:31 AM LINE ANN TST NEEDED WRN: DISABLED >< I51400FEB 5, 2021 9:31 AM H-PROTOCOL DATA FORMAT HEIGHT >< I51A01 file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] FEB 5, 2021 9:31 AM DAYLIGHT SAVING TIME ENABLED OFF >< I51B00FEB 5, 2021 9:31 AM DAYLIGHT SAVING TIME START DATE APR WEEK 1 SUN 2:00 AM END DATE OCT WEEK 6 SUN 2:00 AM > <I51600 FEB 5, 2021 9:31 AM RE-DIRECT LOCAL PRINTOUTDISABLED > <I50400 FEB 5, 2021 9:31 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED > <I21900 FEB 5, 2021 9:31 AM TANK CHART SECURITYENABLED > <I5BD00 FEB 5, 2021 9:32 AM file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] CUSTOM ALARM LABELS DISABLED > <I56000 FEB 5, 2021 9:32 AM MASS/DENSITY DISABLED >< I88101FEB 5, 2021 9:32 AM PORT SETTINGS: COMM BOARD : 1 (EDIM )RS-232 SECURITY CODE : ****** >< I88102FEB 5, 2021 9:32 AM PORT SETTINGS: COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATARS-232 SECURITY CODE : ****** DTR NORMAL STATE: HIGH > <I88103 FEB 5, 2021 9:32 AMPORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITYCODE : ****** > file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] < I60100FEB 5, 2021 9:32 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED ON 2 PREMIUM ON 3 DIESEL ON 4 HACKED OFF > <I60200 FEB 5, 2021 9:32 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 2 PREMIUM 3 DIESEL 4 HACKED > <I60300 FEB 5, 2021 9:32 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 2 3 DIESEL 3 4 HACKED 4> <I60900 FEB 5, 2021 9:32 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 0.000700 2 PREMIUM 0.000700 3 DIESEL 0.000450 4 HACKED 0.000000> <I60700 FEB 5, 2021 9:32 AM TANK DIAMETER file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] TANK PRODUCT LABEL INCHES 1 UNLEADED 127.50 2 PREMIUM 127.50 3 DIESEL 127.50 4 HACKED 0.00> <I60A00 FEB 5, 2021 9:32 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 PT 20082 2 PREMIUM 1 PT 12041 3 DIESEL 1 PT 8027 4 HACKED 1 PT 111111 > <I60400 FEB 5, 2021 9:32 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 20082 2 PREMIUM 12041 3 DIESEL 8027 4 HACKED 111111> <I60500 FEB 5, 2021 9:32 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 20082 0 0 0 2 PREMIUM 12041 0 0 0 3 DIESEL 8027 0 0 0 4 HACKED 111111 0 0 0 >< I60600FEB 5, 2021 9:32 AM file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 20082 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PREMIUM 12041 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 8027 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 HACKED 111111 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 > <I61500 FEB 5, 2021 9:33 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED NO 2 PREMIUM NO 3 DIESEL NO 4 HACKED NO >< I62F00FEB 5, 2021 9:33 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 4.0 INCHES 2 PREMIUM 4.0 INCHES 3 DIESEL 4.0 INCHES >< I62700FEB 5, 2021 9:33 AM TANK HIGH WATER WARNING LIMIT file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] TANK PRODUCT LABEL INCHES 1 UNLEADED 2.0 2 PREMIUM 2.0 3 DIESEL 2.0> <9999FF1B>< I62400FEB 5, 2021 9:33 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 3.0 2 PREMIUM 3.0 3 DIESEL 3.0> <I62800 FEB 5, 2021 9:33 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 20082 2 PREMIUM 12041 3 DIESEL 8027 4 HACKED 111111> <I62300 FEB 5, 2021 9:33 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 18073 2 PREMIUM 10837 3 DIESEL 7224 4 HACKED 0> <I62200 FEB 5, 2021 9:33 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 19078 2 PREMIUM 11439 3 DIESEL 7625 4 HACKED 0> < file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] I62900 FEB 5, 2021 9:33 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 2008 2 PREMIUM 1204 3 DIESEL 802 4 HACKED 0> <I62100 FEB 5, 2021 9:33 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 500 2 PREMIUM 500 3 DIESEL 500 4 HACKED 0> <I62600 FEB 5, 2021 9:33 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 HACKED 99> <I62500 FEB 5, 2021 9:33 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 50 2 PREMIUM 50 3 DIESEL 50 4 HACKED 99> <I60800 FEB 5, 2021 9:34 AM TANK TILT TANK PRODUCT LABEL INCHES file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] 1 UNLEADED 0.00 2 PREMIUM 0.00 3 DIESEL 0.00 4 HACKED 0.00> <I60B00 FEB 5, 2021 9:34 AM STICK HEIGHT OFFSET ENABLE STATUSDISABLED > <I60C00 FEB 5, 2021 9:34 AM TANK STICK HEIGHT OFFSETTANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 PREMIUM 0.00 3 DIESEL 0.00 4 HACKED 0.00 >< I61200FEB 5, 2021 9:34 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NONE NONE 2 PREMIUM NONE NONE 3 DIESEL NONE NONE 4 HACKED NONE NONE >< I63600FEB 5, 2021 9:34 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 2008 2 PREMIUM 1204 3 DIESEL 802 4 HACKED 0 >< I62A00FEB 5, 2021 9:34 AM ANNUAL LEAK TEST MIN VOLUME file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] TANK PRODUCT LABEL GALLONS 1 UNLEADED 2008 2 PREMIUM 1204 3 DIESEL 802 4 HACKED 0 >< I62C00FEB 5, 2021 9:34 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED STANDARD 2 PREMIUM STANDARD 3 DIESEL STANDARD 4 HACKED STANDARD > <I62D00 FEB 5, 2021 9:34 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 HACKED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED >< I63100FEB 5, 2021 9:34 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED OFF OFF 2 PREMIUM OFF OFF 3 DIESEL OFF OFF file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] 4 HACKED OFF OFF > <I63000 FEB 5, 2021 9:34 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 HACKED OFF >< I63200FEB 5, 2021 9:34 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 HACKED OFF > <I61000 FEB 5, 2021 9:34 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 15 2 PREMIUM 15 3 DIESEL 15 4 HACKED 1> <I63A00 FEB 5, 2021 9:35 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 10.00% 2 PREMIUM 10.00% 3 DIESEL 10.00% 4 HACKED 10.00% > file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] < I61100FEB 5, 2021 9:35 AM LEAK TEST METHOD - - - - - - - - - - - -TEST ANNUALLY: ALL TANK DEC WEEK 2 WEDSTART TIME : 2:30 AM TEST RATE :0.20 GAL/HRDURATION : 2 HOURS TST EARLY STOP:DISABLED > <I61300 FEB 5, 2021 9:35 AMCSLD PROBABLITY OF DETECTION >< I61400FEB 5, 2021 9:35 AM CSLD CLIMATE FACTOR > <I61600 FEB 5, 2021 9:35 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED IMMEDIATE 2 PREMIUM IMMEDIATE 3 DIESEL IMMEDIATE 4 HACKED IMMEDIATE >< I61A00FEB 5, 2021 9:35 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED DISABLED 2 PREMIUM DISABLED 3 DIESEL DISABLED 4 HACKED DISABLED >< I61B00 file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] FEB 5, 2021 9:35 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM >< I61C00FEB 5, 2021 9:35 AM CSLD REPORT ONLY >< I63400FEB 5, 2021 9:35 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 0 2 PREMIUM 0 3 DIESEL 0 4 HACKED 0 >< I63500FEB 5, 2021 9:35 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 HACKED 1 >< I78700FEB 5, 2021 9:35 AM > <I70200 FEB 5, 2021 9:35 AM LIQUID LABEL DEVICE LABEL 1 87 ANNULAR 2 87 STP 3 87 FILL 4 91-DIESEL ANNULAR file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] 5 91 STP 6 91 FILL 7 DIESEL STP 8 DIESEL FILL 9 DISP 1-2 10 DISP 3-4 11 DISP 5-6 12 DISP 7-8 13 14 15 16 >< I70300FEB 5, 2021 9:35 AM LIQUID TYPE SENSOR LOCATION TYPE 1 87 ANNULAR TRI-STATE (SINGLE FLOAT) 2 87 STP TRI-STATE (SINGLE FLOAT) 3 87 FILL TRI-STATE (SINGLE FLOAT) 4 91-DIESEL ANNULAR TRI-STATE (SINGLE FLOAT) 5 91 STP TRI-STATE (SINGLE FLOAT) 6 91 FILL TRI-STATE (SINGLE FLOAT) 7 DIESEL STP TRI-STATE (SINGLE FLOAT) 8 DIESEL FILL TRI-STATE (SINGLE FLOAT) 9 DISP 1-2 TRI-STATE (SINGLE FLOAT) 10 DISP 3-4 TRI-STATE (SINGLE FLOAT) 11 DISP 5-6 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) > <I70400 FEB 5, 2021 9:35 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 87 ANNULAR ANNULAR SPACE 2 87 STP STP SUMP 3 87 FILL OTHER SENSORS 4 91-DIESEL ANNULAR ANNULAR SPACE 5 91 STP STP SUMP 6 91 FILL OTHER SENSORS 7 DIESEL STP STP SUMP 8 DIESEL FILL OTHER SENSORS file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] 9 DISP 1-2 DISPENSER PAN 10 DISP 3-4 DISPENSER PAN 11 DISP 5-6 DISPENSER PAN 12 DISP 7-8 DISPENSER PAN 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS >< I80700FEB 5, 2021 9:35 AM RELAY LABEL DEVICE LABEL 1 87 STP 2 91 STP 3 DIESEL STP 4 > <I80900 FEB 5, 2021 9:36 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 87 STP NORMALLY CLOSED 2 91 STP NORMALLY CLOSED 3 DIESEL STP NORMALLY CLOSED 4 NORMALLY OPEN >< I80B00FEB 5, 2021 9:36 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 87 STP 1 2 91 STP 2 3 DIESEL STP 3 4 NONE > <I80A00 FEB 5, 2021 9:36 AM RELAY TYPE file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] RELAY DESIGNATION TYPE 1 87 STP STANDARD 2 91 STP STANDARD 3 DIESEL STP STANDARD 4 STANDARD > <I80800 FEB 5, 2021 9:36 AM RELAY SETUP REPORT R 1:87 STP TYPE: STANDARDNORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:FLOW COLLECT FAIL R 2:91 STP TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] L 4:FUEL ALARM L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:FLOW COLLECT FAIL R 3:DIESEL STP TYPE: STANDARD NORMALLY CLOSED TANK #: 3 LIQUID SENSOR ALMS L 4:FUEL ALARM L 7:FUEL ALARM L12:FUEL ALARM L 4:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L12:SENSOR OUT ALARM R 4: TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - >< I79000FEB 5, 2021 9:36 AM file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] EDIM:1 VR:349643-001-B TD:97.10.27.11.25 > <I72300 FEB 5, 2021 9:36 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY01 DISP 1-2 FM AIR FLOW METER 02 DISP 3-4 FM AIR FLOW METER03 DISP 5-6 FM AIR FLOW METER 04 DISP 7-8 FM AIR FLOW METER05 PRESS SENSOR VAPOR PRESSURE 06 UNKNOWN07 UNKNOWN 08 UNKNOWN09 UNKNOWN 10 UNKNOWN11 UNKNOWN 12 UNKNOWN13 UNKNOWN 14 UNKNOWN15 UNKNOWN 16 UNKNOWN17 UNKNOWN 18 UNKNOWN19 UNKNOWN 20 UNKNOWN21 UNKNOWN 22 UNKNOWN23 UNKNOWN 24 UNKNOWN25 UNKNOWN 26 UNKNOWN27 UNKNOWN 28 UNKNOWN29 UNKNOWN 30 UNKNOWN31 UNKNOWN 32 UNKNOWN33 UNKNOWN 34 UNKNOWN35 UNKNOWN 36 UNKNOWN37 UNKNOWN 38 UNKNOWN file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] 39 UNKNOWN 40 UNKNOWN >< IV4700 FEB 5, 2021 9:37 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 ASSESSMENT TIME START TIME: 10:00 AMTIME DELAY MINUTES: 1 > <IV5200 FEB 5, 2021 9:37 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 ACCEPT HIGH ORVR: NO >< IV4A00FEB 5, 2021 9:37 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 ISD HOSE TABLE HOSE FP FP AFM HOSE ID ID LABEL ID LABEL 01 01 01 01 BLEND3 02 02 02 01 BLEND3 03 03 03 02 BLEND3 04 04 04 02 BLEND3 05 05 05 03 BLEND3 06 06 06 03 BLEND3 07 07 07 04 BLEND3 08 08 08 04 BLEND3 > < file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] IV4B00 FEB 5, 2021 9:37 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 09/01 01/01 xx/xx02 01 02/02 09/02 01/02 xx/xx 03 02 02/03 09/03 01/03 xx/xx04 02 02/04 09/04 01/04 xx/xx 05 03 02/05 09/05 01/05 xx/xx06 03 02/06 09/06 01/06 xx/xx 07 04 02/07 09/07 01/07 xx/xx08 04 02/08 09/08 01/08 xx/xx > <IV4900 FEB 5, 2021 9:37 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 LABEL TABLE ID LABEL01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 >< IV1000FEB 5, 2021 9:37 AM ISD VERSION: 01.01 > <I90200 FEB 5, 2021 9:37 AM file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] SOFTWARE REVISION LEVEL VERSION 327.04SOFTWARE# 346327-100-E CREATED - 07.02.06.10.28 S-MODULE# 330160-004-aSYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD PMC > <I11100 FEB 5, 2021 9:37 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIMEE 1 OTHER COMMUNICATION ALARM CLEAR 2-01-21 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 2-01-21 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 1-25-21 2:08AM E 1 OTHER COMMUNICATION ALARM ALARM 1-25-21 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 1-18-21 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 1-18-21 2:07AME 1 OTHER COMMUNICATION ALARM CLEAR 1-11-21 2:10AM E 1 OTHER COMMUNICATION ALARM ALARM 1-11-21 2:07AME 1 OTHER COMMUNICATION ALARM CLEAR 1-04-21 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 1-04-21 2:07AME 1 OTHER COMMUNICATION ALARM CLEAR 12-28-20 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 12-28-20 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 12-21-20 2:08AM E 1 OTHER COMMUNICATION ALARM ALARM 12-21-20 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 12-14-20 2:10AM E 1 OTHER COMMUNICATION ALARM ALARM 12-14-20 2:08AME 1 OTHER COMMUNICATION ALARM CLEAR 12-07-20 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 12-07-20 2:07AME 1 OTHER COMMUNICATION ALARM CLEAR 11-30-20 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 11-30-20 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 11-27-20 8:03AM E 1 OTHER COMMUNICATION ALARM ALARM 11-27-20 7:59AME 1 OTHER COMMUNICATION ALARM CLEAR 11-23-20 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 11-23-20 2:07AME 1 OTHER COMMUNICATION ALARM CLEAR 11-16-20 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 11-16-20 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 11-09-20 2:08AM E 1 OTHER COMMUNICATION ALARM ALARM 11-09-20 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 11-02-20 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 11-02-20 2:07AM file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] E 1 OTHER COMMUNICATION ALARM CLEAR 10-26-20 1:09AM E 1 OTHER COMMUNICATION ALARM ALARM 10-26-20 1:06AMT 1 TANK UNLEADED OVERFILL ALARM CLEAR 10-23-20 9:53AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 10-23-20 9:36AME 1 OTHER COMMUNICATION ALARM CLEAR 10-19-20 2:08AM E 1 OTHER COMMUNICATION ALARM ALARM 10-19-20 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 10-12-20 2:08AM E 1 OTHER COMMUNICATION ALARM ALARM 10-12-20 2:05AME 1 OTHER COMMUNICATION ALARM CLEAR 10-08-20 9:16AM E 1 OTHER COMMUNICATION ALARM ALARM 10-08-20 9:11AME 1 OTHER COMMUNICATION ALARM CLEAR 10-05-20 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 10-05-20 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 9-28-20 2:10AM E 1 OTHER COMMUNICATION ALARM ALARM 9-28-20 2:07AMT 1 TANK UNLEADED OVERFILL ALARM CLEAR 9-24-20 7:02AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 9-24-20 6:43AME 1 OTHER COMMUNICATION ALARM CLEAR 9-21-20 2:09AM E 1 OTHER COMMUNICATION ALARM ALARM 9-21-20 2:07AME 1 OTHER COMMUNICATION ALARM CLEAR 9-14-20 2:08AM E 1 OTHER COMMUNICATION ALARM ALARM 9-14-20 2:06AM >< I11200FEB 5, 2021 9:37 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 NON-PRIORITY ALARM HISTORYID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 1-22-21 4:15PM SYSTEM PAPER OUT CLEAR 1-22-21 4:15PM SYSTEM PRINTER ERROR ALARM 1-22-21 4:15PM SYSTEM PAPER OUT ALARM 1-22-21 4:15PM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN CLEAR 10-09-20 12:21PMh 2 OTHER FP2: BLEND3 FLOW COLLECT WARN ALARM 10-09-20 10:05AM OTHER ISD VAPOR LEAK WARN CLEAR 8-24-20 3:39PM OTHER ISD VAPOR LEAK WARN ALARM 8-24-20 10:04AM SYSTEM PRINTER ERROR CLEAR 8-24-20 8:53AM SYSTEM PAPER OUT CLEAR 8-24-20 8:53AM SYSTEM PRINTER ERROR ALARM 8-24-20 8:53AM SYSTEM PAPER OUT ALARM 8-24-20 8:53AM h 7 OTHER FP7: BLEND3 FLOW COLLECT WARN CLEAR 8-10-20 8:27AMh 7 OTHER FP7: BLEND3 FLOW COLLECT WARN ALARM 8-09-20 10:04AM SYSTEM PRINTER ERROR CLEAR 7-27-20 9:52AM SYSTEM PRINTER ERROR ALARM 7-27-20 9:52AM SYSTEM PRINTER ERROR CLEAR 7-06-20 9:24AM SYSTEM PRINTER ERROR ALARM 7-06-20 9:24AM SYSTEM PRINTER ERROR CLEAR 6-26-20 10:11AM SYSTEM PRINTER ERROR ALARM 6-26-20 10:11AM SYSTEM PRINTER ERROR CLEAR 6-25-20 11:51PM file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] SYSTEM PAPER OUT CLEAR 6-25-20 11:51PM SYSTEM PRINTER ERROR ALARM 6-25-20 11:50PM SYSTEM PAPER OUT ALARM 6-25-20 11:50PM SYSTEM PRINTER ERROR CLEAR 6-12-20 12:05AM SYSTEM PAPER OUT CLEAR 6-12-20 12:05AM SYSTEM PRINTER ERROR ALARM 6-12-20 12:04AM SYSTEM PAPER OUT ALARM 6-12-20 12:04AM SYSTEM PRINTER ERROR CLEAR 5-28-20 11:59PM SYSTEM PAPER OUT CLEAR 5-28-20 11:59PM SYSTEM PRINTER ERROR ALARM 5-28-20 11:59PM SYSTEM PAPER OUT ALARM 5-28-20 11:59PM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 5-26-20 3:50PMh 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 5-26-20 10:05AM SYSTEM PRINTER ERROR CLEAR 5-15-20 12:00AM SYSTEM PAPER OUT CLEAR 5-15-20 12:00AM SYSTEM PRINTER ERROR ALARM 5-15-20 12:00AM SYSTEM PAPER OUT ALARM 5-15-20 12:00AM SYSTEM PRINTER ERROR CLEAR 5-15-20 12:00AM SYSTEM PAPER OUT CLEAR 5-15-20 12:00AM SYSTEM PRINTER ERROR ALARM 5-15-20 12:00AM SYSTEM PAPER OUT ALARM 5-15-20 12:00AM SYSTEM PRINTER ERROR CLEAR 4-17-20 10:53AM SYSTEM PRINTER ERROR ALARM 4-17-20 10:53AM SYSTEM PRINTER ERROR CLEAR 4-16-20 11:57PM SYSTEM PAPER OUT CLEAR 4-16-20 11:57PM SYSTEM PRINTER ERROR ALARM 4-16-20 11:57PM SYSTEM PAPER OUT ALARM 4-16-20 11:57PM SYSTEM PRINTER ERROR CLEAR 4-03-20 9:29AM SYSTEM PAPER OUT CLEAR 4-03-20 9:29AM > <I20600 FEB 5, 2021 9:37 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM OCT 23, 2020 9:36 AM SEP 24, 2020 6:43 AM MAY 22, 2020 2:24 PM HIGH PRODUCT ALARM DEC 9, 2019 7:24 AM OCT 25, 2019 3:47 AM TANK 2 PREMIUM file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] TANK 3 DIESEL >< I38200FEB 5, 2021 9:38 AM > <I30200 FEB 5, 2021 9:38 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 ANNULAR FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 9:51 AM FUEL ALARM FEB 12, 2020 9:51 AM FUEL ALARM 2 87 STP FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 9:56 AM FUEL ALARM 3 87 FILL FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 10:09 AM FUEL ALARM 4 91-DIESEL ANNULAR FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 9:57 AM FUEL ALARM 5 91 STP FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 9:58 AM FUEL ALARM 6 91 FILL FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 10:07 AM FUEL ALARM 7 DIESEL STP FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 10:00 AM FUEL ALARM 8 DIESEL FILL APR 8, 2020 5:48 PM FUEL ALARM FEB 12, 2020 12:50 PM FUEL ALARM FEB 12, 2020 10:11 AM SENSOR OUT ALARM 9 DISP 1-2 FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 10:05 AM FUEL ALARM 10 DISP 3-4 FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 10:06 AM FUEL ALARM 11 DISP 5-6 file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 10:04 AM FUEL ALARM 12 DISP 7-8 FEB 12, 2020 10:11 AM SENSOR OUT ALARM FEB 12, 2020 10:03 AM FUEL ALARM FEB 12, 2020 10:01 AM FUEL ALARM >< I31600FEB 5, 2021 9:38 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 DISP 1-2 FM 2 DISP 3-4 FM 3 DISP 5-6 FM 4 DISP 7-8 FM 5 PRESS SENSOR > <I10200 FEB 5, 2021 9:38 AM BROOKSIDE MARKET 8803 CAMINO MEDIA BAKERSFIELD CA 93311 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9962839 10287769 2 UNUSED 9940357 10184894 3 UNUSED 9943437 10167121 4 UNUSED 9937717 10166505 5 4 PROBE / G.T. 163824 164332 6 INTERSTITIAL BD 202188 202927 7 INTERSTITIAL BD 203453 203910 8 8SMARTSENSOR BD 39564 39616 9 UNUSED 9944648 10186285 10 RELAY BOARD 14965 14980 11 UNUSED 9947895 10169314 12 UNUSED 9939053 10160705 13 UNUSED 9943558 10155856 14 UNUSED 9941568 10159205 15 UNUSED 9943810 10159822 file:///C/Users/jerryr/Desktop/02-05-21%20Oaks%20Monitor/Oaks%20setup.txt[2/5/2021 12:51:49 PM] 16 UNUSED 9937649 10157294 COMM 1 ELEC DISP INT. 101498 101726 COMM 2 SERIAL SAT BD 485684 487208 COMM 3 RS232 SERIAL BD 15049 15063 COMM 4 UNUSED 9949928 10173444 COMM 5 UNUSED 9937587 10155527 COMM 6 UNUSED 9944899 10156596 > <I90200 FEB 5, 2021 9:38 AMSOFTWARE REVISION LEVEL VERSION 327.04SOFTWARE# 346327-100-E CREATED - 07.02.06.10.28 S-MODULE# 330160-004-aSYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD PMC >