HomeMy WebLinkAboutCUPA REPORT 2-18-21Underground Storage Tank Program
DW Inspection Report
Permission to Inspect:
BAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
2101 H Street
Bakersfield, CA 93301
Phone: 661-326-3979
Fax: 661-852-2171
Business Name: Arco 83894 15-021-100533 / CAL000440588
Date:2/18/2021
Address Name: 1701 Brundage Lane Bakersfield, CA 93304
Inspector Name:, Peter Armagost #8856813
Inspection Type: Routine
Report: Final
NVO = No Violation Observed OUT - Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation,
ProgramRequirement
0 0
SOC
Comments
No
0
>
D
in
0
F-
0.
0) 0
Z
0
z
n
0
W
>
File Review
Facility Tank Information
2030021
Facility has a valid Permit
Tank 1 -10000 -DW -REG
to Operate from the
Tank 2- 10000 -DW -REG
CUPA - 23 CCR 16 2712(1);
F]
F1
F
None
Tank 3- 10000 -DW -REG
HSC 6.7 25284
Tank 4- 10000 -DW -REG
2010010
UST Operating Permit
Application for Facility
information and Tank
information
F
❑
F
F-1
F
None
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001
Current BOE number
submitted to the CUPA
H
F]
F
F
F
F
None
and/or CERS -HSC 6.7
25286(c)
2030011
UST compliance
statement and/or
Designated Operator
None
current certification
submitted - 23 CCR 16
2715(a)y 2715(b)
2030046
A complete and accurate
response plan has been
submitted, approved and
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2 712 (i)
2030041
A complete and accurate
plot plan has been
submitted, approved and
Minor
maintained - 23 CCR 16
,2632(d)(1)(C), 2711(a)(8)
2010006
Owner/Operator has not
made false statements or
representation on any
M
F-1
El
E]❑
F❑
None
required document -HSC
6.725299
2010003
Owner/Operator has a
DO and/or informed the
CUPA of any change (s)
F
F
F]
None
within 30 days - 23 CCR
76 2715(a)
Violation
Program Requirement
� o
SOC
Comments.
No
Z
o
=
o
CL
r
Z
Testing
2030002
Owner/Operator has
tested and certified leak
M
F-1
F]
F-1
F-1
None
detection equipment
annual) - 23 CCR 16 2638
2030048
Secondary containment
testing conducted every
36 months in accordance
❑
❑
❑
❑
❑
None
with requirements - 23
CCR 76 2637
2030055
Spill buckets have been
tested annually as
Z
❑
❑
❑
❑
❑
None
re uired -HSC 6.7 25284.2
2010009
Secondary containment
test results submitted to
the CUPA within 30 days
Z
❑
❑
❑
❑
❑
None
after the test - 23 CCR 16
2637(e)
2030064
CUPA was poperly
notified within the
prescribed number of
Z
F-1
M
F1
F]
None
hours prior to testing - 23
CCR 16 26370, 2638(e),
2643(8), 2644.1(a)(4)
Install/Repair
2060009
Permits obtained to
install, replace, repair, or
Z
F1
F-1
F-1
F-1
[_1
None
modify part of the UST
system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
Z
F1
F
F-1
F-1
F]
None
❑
an audible and visual
Yes
alarm - 23 CCR 16 26321
2634, 2636, 2666
2030016
The annular space of the
tank, piping and sumps
are continuously
RD
monitored and activates
Z
❑
❑
❑
1:1
❑
None
❑
the alarm - 23 CCR 76
Yes
2631(8), 2632(c)(2)(A)&(8),
2633(c), 2636(o
2030017
Product piping outside the
UDC is fail-safe and shuts
down the pump or
Z
F]❑
F]
F-1❑
None
restricts flow - 23 CCR 16
2636 (0(5)
2030018
Turbine sump monitor
activates an audible and
RD
visual alarm or stops the
Z
❑
❑
❑
❑
❑
.None
❑
flow of at the dispenser -
Yes
23 CCR 16 2636 (0(1)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program ': Requirement
0
:�'thents
S'Oc
COrn
No
D,
0
CL
0
0,
Z
M
0
11W
>
2030019
Monitoring system in the
UDCs activates an
audible and visual alarm
0
�
R
R
R
R
None
or stops the flow at the
UDC -23 CCR 16
2636 (0(1)
2030043
Leak detection equipment
properly programmed or
RD
properly operated - 23
F1
R
R
R
None
❑
CCR 16 2632, 2634, 2636,
Yes
2666
2060005
System constructed with
a monitoring system
capable of detecting entry
None
into secondary
containment -HSC 6.7
25291(b)
2060014
Correct leak detection
equipment installed for
RD
the type of system
None
R
present - 23 CCR 16 2638;
Yes
HSC 6.7 25290. 1, 25290.21
25291
2060015
Sensor located in the
RD
proper position/location -
R
F]
None
R
23 CCR 16 2630(d), 2641(a)
Yes
2030062
Facility is in compliance
with not tampering with or
RD
disabling leak detection
None
❑
devices or alarms -HSC
Yes
6.7 25299(a)(9)
2060022
System constructed with
a monitoring system
capable of detecting entry
None
into secondary
containment -HSC 6.7
25290.2(d)
2030034
Tag/sticker on affixed
monitoring equipment
being certified, repaired,
None
or replaced - 23 CCR 16
2638(o
VPH Monitoring VPH
2030065
Interstitial monitoring of
the annular spaces of the
RD
UST is properly
None
❑
maintained -HSC 6.7
Yes
25290.7 (e)
2060023
System constructed with
a monitoring system
capable of detecting entry
into secondary
1-1
El
M
F-1
F-1
F-1
None
containment -HSC 6.7
25290.1 (d)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation ,
l0l.::�:
Program '..Requirement ''
0
SOC
comments
No
10
0:
z'
O
z �
Line Leak
Detector
2060012
Line leak detector
installed on pressurized
RD
piping system -HSC 6.7
None
R
25290. 1(h), 25290.2(8),
25291(o, 25292(e),
Yes
2636( 0(2)
2030026
Line leak detectors detect
a 3 gph leak and/or
RD
audible and visual alarm
R
R
R
None
R
function properly - 23
CCR 16 2636(f)(6),
Yes
2666(c)
2030027
Turbine shuts down when
a leak is detected or
RD
when line leak detector is
R
R
F-1
None
R
disconnected - 23 CCR 16
Yes
2666(c
2030025
Pressurized piping able to
37 LL -0 jrrj!La�i) N07-2rA
detect a 3.0 gph leak
within an hour, and
RD
D ILje�D -50Z)FN
g7 I-LFA
restricts the flow or
None
R
alarms - 23 CCR 16
Yes
2636(0(2)
Secondary Containment
2060010
UST storing a hazardous
RD
substance has secondary
None
R
containment - HSC 6.7
25292
Yes
Underground Storage Tank Program - DW Inspection Report v 2.0
Underground Storage Tank Program - DW Inspection Report v 2.0
Z:) 4:)
Program ogramk6:
Requirement
0
SOC
Comments
No
D
0
Z
0
Z
�
o'>'
2030008
UDC, sumps, and/or
other secondary
containment in good
0
F-1
F-1
F-1
F-1
F]
None
condition and/or are free
of debris/liquid -HSC 6.7
25290.1) 25290.2) 25291
2030040
Secondarily contained
RD
piping maintained to allow
Z
F-]
F-]
�
F-1
�
None
F-1
liquid to drain into sump -
23 CCR 16 2630(c(), 2641 (a)
Yes
2060006
Secondary containment
piping slopes back to the
1-1
F-1
El
F]
None
collection sump - 23 CCR
16 263(c)
2030047
Secondary containment
maintained tight and has
been confirmed by testing
Z
E]
�
F-]
F-]
F-]
None
- 23 CCR 16 2662; HSC 6.7
25290.1(c)(2), 25290.2(c)(2),
25291(a), 25292(e)
2030060
Entry fittings in secondary
containment for UST
system maintained
Z
F-1
1-1
F-1
F-1
F]
None
tight/sealed - 23 CCR 16
2630, 2635(d), 2636(c),
2666
2060020
Spill bucket is installed
and has a functional drain
RP
valve or other means to
Z
1-1
F�
F-1
M
F
None
F-1
remove liquid - 23 CCR 16
Yes
2635(b), 2665
2030054
Spill bucket maintained in
RP
good condition and free of
R
R
R
R
None
R
debris and/or liquid - 23
Yes
CCR 16 2635(b), 2715(c)(2)
2060019
Spill bucket to has a
minimum capacity of five
R
F]
R
None
gallons - 23 CCR 16
2635(b)) 2665
Overfill
2030035
UST system is operated
to prevent unauthorized
RIP
release, including spills
R
F1
R
R
R
None
R
and overfills -HSC 6.7
Yes
25292.1 (a)
2030036
Overfill prevention system
has not been overridden
RID
and meets overfill
None
❑
requirements - 23 CCR 16
Yes
2635(b)(2), 266- -5
Underground Storage Tank Program - DW Inspection Report v 2.0
Z:) 4:)
Violation.
Program Requirement0"0
SOC
'Comments
No
0
>
o,
�
� o.:
Z
0
Z L
>
On Site Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
F-1
F-1
R
R
None
current ICC certification -
23 CCR 16 2715
2030024
Service technician,
installer, and/ or
employee maintain a
0
F]
F-1
R
R
F]
None
proper license - 23 CCR
162715
2030031
Employee or contractor
obtained and maintained
proper manufacturer
None
certification - 23 CCR 16
2715
2010007
Submit/maintain current
Certificate of Financial
Responsibility/mechanism
of financial assurance -
�
�
�
�
�
❑
None
23 CCR 16 2711; 23 CCR
18 2808.1) 2809 -2809.2) -
HSC 6.7 25292.2; HSC
6.75 25299.30-25299.34__
Designated Operator
2010004
Copies of DO inspections
for last 12 months and list
of trained employees
None
maintained - 23 CCR 16
2715
2030013
Designated operator
properly conducted the
monthly inspection and
None
the reports are complete -
23 CCR 16 2715
2030010
DO notified operator of
any condition observed
during the monthly
None
inspection that may
require action - 23 CCR 16
2715(d)
2030012
DO employee training
performed, current for at
least one employee on
R
F-1
❑
R
None
site, and a log kept - 23
CCR 16 2715(c)(6), 27150
Underground Storage Tank Program - DW Inspection Report v 2.0
violation.
Peograrn.Requirem ent
0SO
.0
C
Comments
No
.0
>
a
U)
0
CL
Z
0
Z
D
X
o >
Logs
2030001
Leak detection alarm
logs, maintenance and
RD
records of appropriate
0
F]
F1
F-1
F-1
[_1
None
M
follow-up actions
maintained - 23 CCR 16
Yes
2632) 2634) 2712(b)
Maintenance/Tests
2010008
Monitoring, maintenance,
repairs, linings, and
RD
upgrade records
M
F-1
F-1
1-1
None
F-1
maintained for the proper
time period - 23 CCR 16
Yes
2712 b)
Documentation
2030033
Failure to maintain on site
an approved monitoring
M
F-1
F-1
F1
[_1
None
plan - 23 CCR 16 2632,
2634, 2711, 2712(1)
2030037
Written agreement
between the tank owner
and tank operator to
monitor the tank system
[_1
F1
[_1
F]
None
is maintained - 23 CCR 16
2620(b); HSC 6.7
25284(a)(3)
2030061
Suspected or actual
unauthorized release
RD
reported in appropriate
El
M
N
M
M
F-1
None
F-1
time frame -HSC 6.7
Yes
29294,29295
General Operating Requirements
Permit Condition/Approval
2030039
Compliance with all
operating permit
M
M
F1
El
El
F]
None
conditions - 23 CCR 16
2712; HSC 6.7 25299
2030059
UST system maintained
in accordance with
exclusion/exemption
M
F]
F-1
F1
None
status -HSC 6.7 25281.6)
25283.5
2030014
Owner/Operator received
approval and has
implemented a training
F1
F-1
N
F-1
F-1
F]
None
program at an unstaffed
facility - 23 CCR 16
2715 2)
2030015
Facility exhibited that the
method used to monitor
the tank meets the
monitoring methods in
1-1
F-1
F-1
[_1
❑
None
2643(f) - 23 CCR 16 2643
Program Underground Storage Program- DW Inspection Report v 2.0
4n Z:�
2030045 Red Tag information is
legible and has not been
tampered with - 23 CCR
16 271 7.1(g)
2030044 Facility did not allow for
deposit of petroleum into
a UST that has a red tag
affixed to the fill - 23 CCR
16 2717.1(
Install/Repair
2060024 UST system is made of or
lined with materials that
are compatible with the
substance stored - 23
CCR 16 2631.1
2060021 Striker plate installed and
positioned correctly - 23
CCR 16 2631(c), 2662(4)
F]
1-1
0
F-1
F]
[-1
None
F-1
FIN
R
R
R
None
❑
❑
❑
❑
❑
None
R
F]
None
—'here were no violations noted for this inspection.
XThis report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature: Date: Z -115,12v
Inspector: Enter # of Violations: RD: RP:
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
❑SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release
Prevention violations)
M SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release
Detection violations)
Underground Storage Tank Program - DW Inspection Report v 2.0