Monitor Cert/Annual lnsp
Foods Co# 384
2501 Haley St.
Bakersfield, CA 93305
TRANSMITTAL
The following test report(s) are included:
Monitor Certification
Comments:
Please do not hesitate to call me at (949) 460-5200 if you have any questions or concerns regarding this work.
Zac Kavanaugh
Project Coordinator
2126152
Appendix VI
UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM /Pam~ 1 of6l
This form must be used to document testing and servicing of underground storage tank {UST) monitoring eguigment. A COQll: of this form
must be Qrovided to the UST owner or 012erator. The owner or OQerator must submit a COQll: of this form to the local agencll: regulating the
USTs within 30 dall:S of the date of the monitoring SJl:stem certification.
I. FACILITY INFORMATION
CERSID I pate of Monitorinq Svstem Certification
10123132 11/19/2019
Business Name (Same as Facilil'L. Name or OBA -Doing Business As.! I Building#
Foods Co# 384
Business Site Address I Qi1y I ZIP Code
2501 Haley St. Bakersfield 93305
II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION
Name of Comganll: Performing the Certification I Phone#
Belshire Environmental Services, Inc. (949) 460-5200
Mailing Address
25971 Towne Centre Dr., Foothill Ranch, CA 92610
Name of UST Service Technician Performing the Certification {.Print as shown on the ICC Cettification.)
David Walker
Contractorrrank Tester License# I ICC Certification# I ICC Certification ExQiration Date
808313 8854235 12/10/2020
Monitorina Svstem Trainina and Certifications /List all a11nficab/e cerlifications. l Exoiration Date
See Attached
m. RESULTS OF TESTING/SERVICING
Indicate and attach the following_ ree.orts if the monitoring_ eg_uie.ment is cae.able of generating_ either. y M NA 0 Monitoring Sll:slem Set-uQ IV] Alarm Histoty ReQorl
Was anll: monitoring eguiQment reQlaced? 0 D D (Jf "Yes," identifi. the sg_ecific devices reQ.laced and list the manufacturer and model for all re12Jacement 12.arts in section IV below.)
Was damage. debris, or liguid found inside anll: seconda[Y containment Sll:Stems? • 0 D (If "Yes," cfescribe what was found in section IV below.)
Is all monitoring eguiQment ogerational Qer manufacturer's sgecifications? 0 D D (If "No,'' describe Whl:'.'. in section IV below.)
IV. COMMENTS
If directed to use this section, describe how and when the issues were or will be corrected,
Replaced 91 drain valve
V. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING
I hereby certify that the egui~ment identified in this document was insf;!ected/serviced in accordance with California Code of
Regulations, title 23, division 3, cha12ter 16, section 2638 and all information contained herein is true and accurate. Attached to
this certification is information (e.g., manufacturers' checklists, monitoring system set•UQ, alarm history re1;1ort, etc.} necessary
to verifv that this information and the site olan showina the lavout of UST svstem is complete and accurate.
UST Service Technician Signature
~r_\) "'--J ,,J}\__ ____
UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM 1Paae2of6\
VI. INVENTORY OF EQUIPMENT CERTIFIED
A se12arate Monitoring_ S)lstem Certification Form must be e.ree.ared for each monitoring sj!stem control eanel.
Make of Monitoring S~stem Control Panel I Model of Monitoring Sl£stem Control Panel II Software Version Installed
Veeder-Root TLS-350 330.01
------•,tt --··:--..
Monitorina Device Used Device Model # Monitorina Device Used Device Model #
Tank ID: T1-87 Tank ID: T2-91
{Bv tank number stored vroduct etc. J /Bv tank number stored oroduct etc.)
M ln-tank Gauging (SW Tank) Mag Plus ~ In-tank Gauging (SW Tank) Mag Plus
~ Annular SQace or Vault Sensor 794380-303 M Annular SQace or Vault Sensor 794380-303
0VPH Sensor nvPH Sensor
Product Pioina Product Pioina
D Mechanical LLD D Mechanical LLD
@ Electronic LLD PLLD -Veeder-Ro @ Electronic LLD PLLD -Veeder-Ro
M VPH Sensor (PiQing} VR001 M VPH Sensor (Piging) VR001
M SumQ Sensor 794380-323 M Sum12 Sensor 794380-323
M VPH Sensor (SumQ) 794380-304 M VPH Sensor (Sum12) 794380-304
Fill Pinina Fill Piolno
n VPH Sensor (PiQing) n VPH Sensor (PiQing)
~ SumQ Sensor 794380-323 ~ SumQ Sensor 794380-323
M VPH Sensor (SumQ) 794380-304 M VPH Sensor (SumQ) 794380-304
Vent PiQing Vent PiQing
M VPH Sensor (PiQing} VR001 M VPH Sensor (Piging) VR001
n SumQ Sensor n SumQ Sensor
n VPH Sensor (SumQ) n VPH Sensor (Sum12)
Vai;ior Recoverl£ Pi12ing Va12or Recove(Y PiQing
MVPH Sensor (Piging) VR001 n VPH Sensor (PiQing)
n SumQ Sensor D SumQ Sensor
D VPH Sensor (Sum12} D VPH Sensor (SumQ)
lc::B d 1 .... r1,,, #. J~
Tank ID: T3-DSL Tank ID:
fBv tank number stored oroduct etc.l (Bv tank number stored oroduct etc.)
M In-tank Gauging (SW Tank) Mag Plus n In-tank Gauging (SW Tank)
~ Annular SQace or Vault Sensor 794380-303 D Annular S12ace or Vault Sensor
OVPH Sensor nvPH Sensor
Product Ph:iina Product Pioino
D Mechanical LLD D Mechanical LLD
~ Electronic LLD PLLD • Veeder-Ro D Electronic LLD
~ VPH Sensor (PiQing) VR001 D VPH Sensor (PiQing)
~ Sumr2 Sensor 794380-323 n Sum12 Sensor
M VPH Sensor (Sum12l 794380-304 n VPH Sensor (SumQ)
Fill PiPina Fill PiPina
n VPH Sensor (Piill!l9J n VPH Sensor (PiQing)
~ SumQ Sensor 794380-323 n SumQ Sensor
~ VPH Sensor (Sum12} 794380-304 n VPH Sensor (SumQ)
Vent Pioina Vent Pinina
M VPH Sensor (PiQing) VR001 n VPH Sensor (PiQing)
n SumQ Sensor n SumQ Sensor
n VPH Sensor (SumQ) n VPH Sensor (Sumr2l
Vaoor Recoverv Ph:iina Vaoor Recoverv Pioina
n VPH Sensor (PiQing) n VPH Sensor (PiQing)
n SumQ Sensor n Sumg Sensor
n VPH Sensor (Sum12} n VPH Sensor (SumQ)
Monitoring Device Used
UDC ID;
~ Electronic Sensor
~ Mechanical Device
~ VPH Sensor
Ironic Sensor
hanical Device
Sensor
~ Electronic Sensor
~ Mechanical Device
~VPH Sensor
UOCID:
D Electronic Sensor
D Mechanical Device
UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM (Page 3of6)
Device Model #
1/2
794380-323
Shear Valve
-794380-304
5/6
794380-323
Shear Valve
794380-304
9/10
794380-323
Shear Valve
794380-304
13/14
794380-323
Shear Valve
794380-304
Vent Box
Monitoring Device Used
UDC 10: 3/4
~ Electronic Sensor 794380-323
~ Mechanical Device Shear Valve
~VPH Sensor 794380-304
UDCID: 7/8
~ Electronic Sensor 794380-323
@ Mechanical Device Shear Valve
@VPH Sensor 794380-304
UDC ID: 11/12
~ Electronic Sensor 794380-323
~ Mechanical Device Shear Valve
~VPH Sensor 794380-304
UDCIO:
D Electronic Sensor
Sump Sensor
D VPH Sensor
Device Model #
Include information for every underground storage tank component monitored by this monitoring system control panel. If the monitoring
system control panel monitors more components than this form accommodates, additional copies of these pages may be attached.
VII. COMMENTS
Use this section to provide any additional comments abou/ the inventory of /he equipment certified.
UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM /Paae 4 of 6l
vm. MONITORING SYSTEM AND PROGRAMMING
This section must be comgJeted if a monitoring l}_anel is used to ll_erlorm teak detection monitoring, y N NA
Are the visual and audible alarms 012erational? 0 • •
Were all sensors visually insi:1ected for kinks and breaks in the cables and for residual builduQ to ensure that floats move freely, 0 • D functionallv tested and confirmed ooerational?
Were all sensors installed at lowest i:1oint of secondary containment and 12ositioned so that other eguiQment will not interfere with their 0 • • orooer ooeration?
Was monitoring system sel-uQ reviewed to ensure QroQer settings? 0 • D
Was the monitoring i:1anel's backuQ battery visually ins1:1ected, functionally tested, and confirmed oQerational? 0 • •
Does the flow of fuel stoQ at the disi:1enser if a leak is detected in the under-disi:1enser containment? 0 D D
Does the turbine automatically shut down if the QiQing secondary containment monitoring system fails to OQerate or is electrically 0 • • disconnected?
Does the turbine automatically shut down if the QiQing secondai:y containment monitoring system detects a leak? 0 D D Which sensors initiate Qositive shut down? (Check all that a12Ql'i_.) MSumi:1 M Under-disQenser containment
If alarms are relayed to a remote monitoring station, is all communications eguiQment (e.g. modem) oQerational? • • 0
For anv answer of "N" above describe in section IX how and when these deficiencies were or will be corrected.
IX. COMMENTS
X. IN-TANK GAUGING TESTING
IV'I Check this box if tank oauoino is used onlv for inventorv control. fDo not comnlete this section.) n Check this box if NO tank gauging eguiQment is installed. (Do not com9/ete this section.) X M NA
This section must be comoleted if in-tank aauaina is used to oerform leak detection monitorina,
Has all in12ut wiring been ins12ected for kinks and breaks in the cables and for i:1roi:1er enti:y and termination, including testing for ground D D D faults?
Were all in-tank gauging Qrobes visually ins12ected for damage and residue builduQ to ensure that floats move freel~, functional!~ tested, • • • and confirmed ooerational?
Was accurac~ of s~stem's Qroduct level readings tested? • D •
Was accuracy of s~stem's water level readings tested? • D •
Were all Qrobes reinstalled QrOQerly? • D D
Were all items on the eguiQment manufacturer's maintenance checklist comi:1leted? D D D
For anv answer of "N" above describe in section XI how and when these deficiencies were or will be corrected.
XI. COMMENTS
UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM rPaae s of 6l
XII. LINE LEAK DETECTOR TESTING
n Check this box if line leak detectors (LLD) are NOT installed. (Po not comQlete this section.) X M NA This section must be comvleted if LLDs are installed.
Was a leak simulated to verify LLD Qerformance? 0 • • (Check all that ann/v.) Simulated leak rate verified: ~ 3GPH n 0.1 GPH no.2 GPH
Was the testing aQQaratus QroQerly calibrated? 0 • •
For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? • • ~
For mechanical LLDs, does the LLD restrict the flow through the QiQe when a leak is detected? • • ~
For electronic LLDs, does the turbine automatically shut off when a leak is detected? 0 • •
For electronic LLDs, does the turbine automatically shut off if any Qortion of the monitoring system is disabled or disconnected? 0 • •
For electronic LLDs, does the turbine automatically shut off if any QOrtion of the monitoring system malfunctions or fails a test? 0 • •
For electronic LLDs, have all accessible wiring connections been visually ins12ected for kinks and breaks? 0 • •
Were all items on the eguiQment manufacturer's maintenance checklist comQleted? ~ • •
Were all LLDs confirmed OQerational within regulalO!Y reguirements? ~ • • For anv answer of "N" above describe in section XIII how and when these issues were or will be corrected.
XIII. COMMENTS
XIV. VACUUM/ PRESSURE/ HYDROSTATIC MONITORING EQUIPMENT TESTING
• Check this box if VPH monitoring is NOT used. (Do not comQlete this section.)
This section must be come.feted if VPH monitoring_ is used to £2,erform leak detection monitoring_.
System TyQe (Mark all that aQQI~.) M Vacuum n Pressure D Hydrostatic
Sensor Functionality Interstitial Communication
Sensor ID ComQonent(s) Monitored by this Sensor Test Test
S-9 87 Prod ~Pass •.Bill MPass D..Eill1
S-10 87-91 Vapor MPass D£ill! MPass D..Eill1
S-11 87 Vent Chase MPass [IDjJ M Pass D..Eill1
S-12 91 Prod MPass [IDjJ M Pass D..Eill1
S-13 91 Vent ~Pass •.Bill ~Pass D..Eill1
S-14 Diesel Prod MPass •.Bill MPass D..Eill1
S-17 Diesel Vent Chase MPass •.Bill MPass D..Eill1 •Pass [IDjJ •Pass D..Eill1 •Pass [IDjJ •Pass •Fail
~ •Fail ~ Ohl! •Pass D£ill! ~ Ohl!
~ [IDjJ •Pass D..Eill1
How was interstitial communication verified? M Simulated leak at far ends of the interstitial SQace. n Visual lnsQection
n Other (Desctibe the method in section XV below.) nGauge
Was the vacuum or Qressure restored to OQerating levels in all interstitial sQaces? ~Yes n No (Describe the reason in sec/ion XV below.)
For anv answer of "FAIL" above describe in section XV how and when these issues were or will be corrected. xv. COMMENTS
UNDERGROUND STORAGE TANK
SPILL CONTAINER TESTING REPORT FORM (Page 1 of 1)
Type of Action D Installation Test D Repair Test ~ 12 Month Test
I. FACILITY INFORMATION
CERSID Date of Spill Container Test
10123132 11/19/2019
Business Name (Same as Facility Name or OBA-Doing Business As)
Foods Co # 384
Business Site Address I City I ZIP Code
2501 Haley St. Bakersfield CA
II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION
Name of UST Service Technician Performing the Test (Print as shown on t/Je ICC Cer/ifica/ion.) I Phone#
David Walker
Contractor I Tank Tester License# 11cc Certification # ICC Certification Expiration Date
808313 8854235 12/10/2020
Spill Container Testing Training and CerlificalioM (List applicable certifications.)
See Attached
Ill. SPILL CONTAINER TESTING INFORMATION
Test Method Used: D Manufacturer Guidelines (Specify):
Visual
~ Industry Code or Engineering Standard (Specify): PEIRP1200
D Engineered Method (Specify):
Attach the testing procedures and all documentation required to determine the results. I # of Attached Pages
TANK ID: (By lank number. stored product, etc.) 87 S Fill 87 N Fill 91 Fill Diesel Fill
Spill Container Manufacturer: PhilTite PhilTite PhilTite PhilTite
Method of Cathodic Protection: !ill Non-Metallic ~ Non-Metallic ~ Non-Metallic ~ Non-Metallic
0 Isolation 0 Isolation 0 Isolation 0 Isolation
D Other (Specify in V.) D Other (Specify in V.) D Other (Specify in V.) D Other (Specify in V.)
Inside Diameter of Spill Container: (Inches) 12" 12" 12" 12"
Depth of Spill Container: (Inches) 14" 14" 14" 14"
Does the spill container have a 5 gallon capacity? @Yes ONo @Yes ONo @Yes ONo ~Yes ONo
Method to Keep Spill Container Empty: ~ Drain Valve !ill Drain Valve ~ Drain Valve ~ Drain Valve
Onsite Pump D 0nslte Pump D Onsite Pump D 0nsite Pump
D Other (Specify 111 V.J D Other (Specify in V.J D Other /Specify in V.) D Other (Specify In V.)
IV. SUMMARY OF TESTING RESULTS
Spill Container Test Results: ~Pass • v. COMMENTS
Any items marked "Fail" above must be explained in this section. Any additional comments may also be provided here.
Replaced and re-tested 91 drain valve assembly.
VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING
I hereby certify that the spill containers were tested in accordance with California Code of Regulations, Title 23, Division 3,
Chapter 16, Section 2637.1 and all the information contained herein is accurate.
UST Service Technician Signature D_:_V ~ ...,V\__ ___
If the facility has more components than this form accommodates, additional copies of this page may be attached.
GERS " California Environments.I Reporting System, ID " Identification, UST= Underground Storage Tank, ICC = International Code Council
UNDERGROUND STORAGE TANK
SPILL CONTAINER TESTING REPORT FORM (Page1 of1)
Type of Action D Installation Test D Repair Test ~ 12 Month Test
I. FACILITY INFORMATION
CERSID
10123132
Date of Spill Container Test
11/19/2019
Business Name (Same as Facility Name or DBA-Doing Business As)
Foods Co # 384
Business Site Address
2501 Haley St.
City
Bakersfield
ZIP Code
CA
II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION
Name of UST Service Technician Performing the Test (Print as shown 011 tile ICC CMification,)
David Walker
Phone#
Contractor I Tank Tester License#
808313
ICC Certification #
8854235
ICC Certification Expiration Dale
12/10/2020
Spill Container Testing Training and Certifications (List applicable certifications.)
See Attached
111. SPILL CONTAINER TESTING INFORMATION
Test Method Used: D Manufacturer Guidelines (Specify):
Visual ~ Industry Code or Engineering Standard (Specify): PEI RPl200
O Engineered Method (Specify):
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
TANK ID: (By lank number, s/ored product, etc.)
Spill Container Manufacturer:
Method of Cathodic Protection:
Inside Diameter of Spill Container: (Inches)
Depth of Spill Container: (Inches)
87 S Vapor
PhilTite
~ Non-Metallic
D Isolation
D Other (Specify in V.)
12"
87 N Vapor
PhilTite
~ Non-Metallic
D Isolation
0 Other (Specify in V.)
12"
14" 14"
91 Vapor
PhilTite
~ Non-Metallic
D Isolation
D Other (Specify in V.)
12"
14"
0 Non-Metallic
D Isolation
D Other (Specify in V,)
t:>oes the spill container have a 5 gallon capacity?
Method to Keep Spill Container Empty:
~ Yes D No 1r~c=v"v_e_s--,•=,-N-o""'ih=-v-e-s--.=•,,-N-o-11,=;,Y-e-s ----;,•=.-N-0--1
~ Drain Valve ~ Drain Valve ~ Drain Valve
D Onsite Pump Onsite Pump D Onsite Pump
0 Other (Specify in V.) Other (Specify in V,) 0 Other (Specify in V.)
IV. SUMMARY OF TESTING RESULTS
Spill Container Test Results:
V. COMMENTS
D Drain Valve
D Onsite Pump
0 Other (Specify In V.J
Any items marked "Fail" above must be explained in this section. Any additional comments may also be provided here.
VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING
I hereby certify that the spill containers were tested in accordance with California Code of Regulations, Title 23, Division 3,
Chapter 16, Section 2637.1 and all the information contained herein is accurate.
UST Service Technician Signature
If the fac/1/ty has more components than this form accommodates, additional copies of this page may be attached.
CERS = California Environmental Reportlng System, ID= Identification, UST= Underground Storage Tank, ICC= International Code Council
Name
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Walker, David
Manufacturer Training
Training
NOV FiberGlass Systems Piping (Formerly AO S
ICC California UST Service Technician
ICC Vapor Recovery System Installation and Rep
INCON Level 2 -FMS Programming
INCON Level 1 -FMS Installation (EVO)
Xerxes UST Installation Training Seminar
Veeder Root Level 2/3/4
INCON Level 4 -Franklin Sump Test System
PEI RP1200 Testing/Verification of UST Equipme
Vaporless LDT-890 Leak Detector Tester
Vaporless Mechanical LLD Installer
Modern Welding Tank Installation
ICC Vapor Recovery System Testing and Repair
OPW EVR Phase I -UST
Franklin Fueling Phase I -VR-101 (Formerly Phil
OPW Fueling Containment Systems -FlexWorks
Completed
6/22/2017
12/8/2017
1/11/2018
1/4/2018
5/2/2018
9/14/2018
10/25/2018
11/5/2018
11/3/2018
11/1/2018
11/1/2018
12/6/2018
3/3/2019
5/2/2019
7/19/2019
8/2/2019
Expires
6/22/2020
12/8/2019
1/11/2020
1/4/2020
5/2/2020
9/14/2021
10/25/2020
11/5/2020
11/3/2021
11/1/2020
11/1/2020
12/6/2021
3/3/2021
5/2/2021
7/19/2021
8/2/2021
BUSINESS NAME: FOODSCO FUEL CENTER #384
SITE ADDRESS: 2501 HALEY STREET I CITY: BAKERSFIELD I ZIP: 93305
MAP DATE: 2/22/19 I SURVEYED BY: FB I DRAWN BY: CT I FACILITY ID#:
10,000
DIESEL
8,000
PREMIU
Driveway
7/8
L4:Disp 7-8 Dual
54:Disp 7-8 VFM
5/6
L3:Disp 5-6 Dual
53:Disp 5-6 VFM
3/4
L2:Disp 3-4 Dual
52:Disp 3-4 VFM
1/2
Ll:Disp 1-2 Dual
51:Disp 1-2 VFM
Vent
L22:Vent Sump
515:PMC Canister
L23:Vent Sump Brine_ ~
..-, ,,,o..._ I ~ DSL Reg_ular 20k
f '?. I • • l ..1 I L18:Diesel Turbine L8:87 Turb~ne .
.-----..,..;.:-•, 11 ?"O~-I L19:Diesel Turbine Brir~f 87 Tu_rbme Brine '• ,' I I ,99, I L20:Diesel Fill 0:87 F~II . I -~-, I ::0 I L21:Diesel Fill Brine Lll:87 Fill Brine •'o :+ 'is~ 514:Diesel Product L1 2:87 Annular \ '-.. ,' j 11 co I 517:Diesel Vent 59:87 Product -;-./ • g 91 510:87 91 Vapor
1,,-'.-tll ::0 I L13:91 Turbine 511:87 Vent
I'~.'?,• 111,,··, I L14:91 T_urbine Brine
.-. , • L15:91 Fill .-----•--. ~ I I '-.. ,,'I L16:91 Fill Brine
~--• --. / L17:91DieseIAnnular
"11 0 0
0 "' I 512:91 Product
""' ... 513:91 Vent PARKING LOT ~
• ""'I ---MI
'
.__ 13/14
~L7:Disp 13-14 Dual
57:Disp 13-14 VFM
58:Disp 13-14 PS
~ 11/12
~L6:Disp 11-12 Dual
'"'56:Disp 11-12 VFM
o 9/10
:::'._ L5:Disp 9-10 Dual
en 55:Disp 9-10 VFM
0
!!I 0 ::0 m
**NOTE: All PIPING LOCATIONS ARE ESTIMATED & SCALING IS APPROXIMATE**
N
CARBON
CANNISTER
-
U DISPENSER VENT RISER
v[;;] VENT BOX
PRODUCT
PIPING
VAPOR
RETURN/
VENT LINE
• MONITORING
PANEL
ANNULAR A SENSOR
FILL SUMP F SENSOR
TURBINE
T SUMP
SENSOR
HEIGHT STREET
VEEDER ROOT L LINE LEAK VEEDER ROOT
TLS-350R DETECTOR PLLD (8484)
VEEDER ROOT VEEDER ROOT
794380-303 u UDC SENSOR 794380-323 (SUMP)
794380-304 (INTERSTITIAL)
VEEDER ROOT VENT BOX VEEDER ROOT
794380-323 (SUMP) V SENSOR 794380-323 (SUMP)
794380-304 (INTERSTITIAL) 794380-304 (INTERSTITIAL)
VEEDER ROOT ALL LINES MONITORED UNDER VACUUM 794380-323 (SUMP) SENSOR 330020-463. 794380-304 (INTERSTITIAL)
Bel shire TLS Poll er SYSTEM SETUP Command Set ver 5 .12 Started at 11/19/2019 11: 19: 09 AM
110200 NOV 19, 2019 11: 18 AM
FOODS CO, 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
SYSTEM CONFIGURATION
SLOT 1 2 1 5 6 7 ~ 10 11 12 13 14 15 16
BOARD TYPE 4 PROBE / G.T. PLLD SENSOR BD INTERSTITIAL BD INTERSTITIAL BO INTERSTITIAL BO 8SMARTSENSOR BO 7SMARTSENSOR BO 8SMARTSENSOR BO COMBO I/0 BOARD PLLD POWER BO UNUSED UNUSED UNUSED UNUSED UNUSED UNUSED COMM 1 ELEC DISP INT, COMM 2 SERIAL SAT BO COMM 3 UNUSED COMM 4 UNUSED COMM 5 RS485 SERIAL BO COMM 6 RS232 SERIAL BO
110100 NOV 19, 2019 11:18 AM
FOODS CO, 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
SYSTEM STATUS REPORT
T 3: SUDDEN LOSS ALARM T 3: PROBE OUT
I50100 NOV 19, 2019 11: 18 AM
SYSTEM DATE AND TIME
150200 NOV 19, 2019 11:18 AM
150300 NOV 19, 2019 11: 18 AM
I50400 NOV 19, 2019 11:18 AM
232 SECURITY CODE
PORT SECURITY CODE
1 000000 2 000000 3 000000 4 000000 5 000000 6 000000
150500 NOV 19, 2019 11: 18 AM
STATUS
DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH ~6~T5~ ~◊W~~~~l~~M~i
I50600 NOV 19, 2019 11: 18 AM
PERIODIC TEST WARNINGS: DISABLED
150700 NOV 19, 2019 11:18 AM
PERIODIC TEST WARNING: DAYS 2 5
I50800 NOV 19, 2019 11:18 AM
PERIODIC TEST ALARM: DAYS 30
I50900 NOV 19, 2019 11: 18 AM
ANNUAL TEST WARNINGS: DISABLED
I50A00 NOV 19, 2019 11: 18 AM
ANNUAL TEST WARNING: DAYS 355
I50B00 NOV 19, 2019 11:18 AM
ANNUAL TEST ALARM: DAYS 365
I50c00 NOV 19, 2019 11:18 AM
POWER ON RESET 164807 3919 202970 203082 203127 39544 514845 9949365 9928 102072 9852763 9870287 9798228 9823814
9765830 9798012 101521 9786178 9767641 9753587 68839 15029
CURRENT 163215 3922 201176 201686 201431 39392 509850 39481 9942 101796 8413409 8398860 8399103 ~mg~i 8403783 101095 485954 8402525 84mbl 15013
Page 1
REMOTE PRINTER DISABLED
I50D00 NOV 19, 2019 11:18 AM
PRINT TC VOLUMES ENABLED
I50EOO NOV 19, 2019 11: 18 AM
TEMP COMPENSATION VALUE (DEG F ) : 60.0
I50F00 NOV 19, 2019 11:18 AM
MON DD YYYY HH:MM:SS XM
I51100 NOV 19, 2019 11:18 AM
SHIFT BIR PRINTOUTS DISABLED
151200 NOV 19, 2019 11: 18 AM
DAILY BIR PRINTOUTS DISABLED
151300 NOV 19, 2019 11: 18 AM
I51400 NOV 19, 2019 11: 18 AM
H-PROTOCOL DATA FORMAT HEIGHT
I51500 NOV 19, 2019 11: 18 AM
I51600 NOV 19, 2019 11: 18 AM
RE-DIRECT LOCAL PRINTOUT DISABLED
I51700 NOV 19, 2019 11: 18 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS XM
I51800
~E¥E~~AT~0t?NMJ..~~ ~~DE PAGE
CODE PAGE SELECTED: WINDOWS
I51900 NOV 19, 2019 11: 18 AM
PRECISION TEST DURATION HOURS: 12
I51A00 NOV 19, 2019 11:18 AM
DAYLIGHT SAVING TIME ENABLED OFF
I51B00 NOV 19, 2019 11: 18 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK
END DATE NOV WEEK
I51c00 NOV 19, 2019 11: 18 AM
TICKETED DELIVERY DISABLED
I51D00 NOV 19, 2019 11: 18 AM
I51E00 NOV 19, 2019 11: 18 AM
I52000 NOV 19, 2019 11: 18 AM
1
SUN 2:00
SUN 2:00
RECEIVER AUTO DIAL TYPE & START TIME
LOCATION LABEL
system setup
DIAL TYPE ON DATE ON DATE ON DATE ON DATE ON DATE
AM
AM
START TIME JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011
DISABLED DISABLED DISABLED DISABLED DISABLED
I52100 NOV 19, 2019 11: 18 AM
RECEIVER CONFIGURATION
ON DATE ON DATE ON DATE
JAN 5, 2011 JAN 5, 2011 JAN 5, 2011
DEVICE LABEL 1 CONFIGURED OFF 2 3 1 7 8
I52200
NOV 19, 2019 11: 18 AM
RECEIVER LABEL
LABEL
152300 NOV 19, 2019 11:18 AM
RECEIVER TELEPHONE NUMBER
RCVR LOCATION LABEL 1 2 l 6 7 8
152400 NOV 19, 2019 11:18 AM
OFF OFF OFF OFF OFF OFF OFF
PHONE NUMBER
RECEIVER DIALING DESTINATION TYPE
RCVR LOCATION LABEL 1 l 7 8
152500 NOV 19, 2019 11: 18 AM
FAX TYPE COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER
RECEIVER MODEM NUMBER TO DIAL
RCVR LOCATION LABEL 1
I 5 6 7 8
152600
NOV 19, 2019 11: 18 AM
RECEIVER RETRY NUMBER
RCVR LOCATION LABEL 1 2
¾ 5
6 7 8
152700 NOV 19, 2019 11: 18 AM
RECEIVER RETRY DELAY TIME
RCVR LOCATION LABEL 1 2 3 4 5 6 7 8
152800 NOV 19, 2019 11: 18 AM
PORT fUMBER
1 1 1 1 1
RETRY NUMBER 3 3 3 3 3 3 3 3
RETRY DELAY 3 3 ~ 3 3 3 3
RECEIVER CONFIRMATION REPORT FLAG
RCVR LOCATION LABEL
½
¾ 5 6 7
8
I52900 NOV 19, 2019 11: 18 AM
ALL PHONES
I52A00 NOV 19, 2019 11: 18 AM
RECEIVER REPORT LIST
RCVR LOCATION LABEL
CONFIRMATION OFF OFF OFF OFF OFF OFF OFF OFF
REPORT LIST
REPORT
DISABLED DISABLED DISABLED
Page 2
I52B00 NOV 19, 2019 11: 18 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL 1 2 I
I52C00 NOV 19, 2019 11: 18 AM
RECEIVER SETUP REPORT
D 1: -NO ALARM ASSIGNMENTS -
D 2: NO ALARM ASSIGNMENTS -
D 3: -NO ALARM ASSIGNMENTS -
D 4: -NO ALARM ASSIGNMENTS -
D 5: -NO ALARM ASSIGNMENTS -
D 6: -NO ALARM ASSIGNMENTS
D 7: -NO ALARM ASSIGNMENTS -
D 8: -NO ALARM ASSIGNMENTS -
I52D00 NOV 19, 2019 11: 18 AM
DIAL TYPE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE
RECEIVER AUTODIAL ALARM STATUS RCVR STATUS 1 CLEAR 2 CLEAR 3 CLEAR 4 CLEAR 5 CLEAR 6 CLEAR 7 CLEAR 8 CLEAR
I52EOO NOV 19, 2019 11: 18 AM
FOODS CO. 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
START TIME JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011
RECEIVER CLEARED ALARMS REPORT DELAY PERIOD
RCVR LOCATION LABEL 1 2 l ~ 8
I52F00 NOV 19, 2019 11: 18 AM
RECEIVER ALARM STATUS
D 1: SERVICE REPORT WARN: CLEAR ALARM CLEAR WARNING: CLEAR
DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 2: SERVICE REPORT WARN: CLEAR ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 3: SERVICE REPORT WARN: CLEAR
ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 4: SERVICE REPORT WARN: CLEAR
ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 5: SERVICE REPORT WARN: CLEAR
ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 6: SERVICE REPORT WARN: CLEAR
ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 7: SERVICE REPORT WARN: CLEAR
ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 8: SERVICE REPORT WARN: CLEAR
ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
system setup
DELAY PERIOD
48
48 48 48 48 48 48 48
DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED
I53000 NOV 19, 2019 11:18 AM
I53100 NOV 19, 2019 11: 18 AM
RS-232 END OF MESSAGE DISABLED
I53200 NOV 19, 2019 11: 18 AM
I53300 NOV 19, 2019 11: 18 AM
I53400 NOV 19, 2019 11: 18 AM
I53600 NOV 19, 2019 11:18 AM
I53700 NOV 19, 2019 11: 18 AM
I53800 NOV 19, 2019 11: 18 AM
I54600 NOV 19, 2019 11: 18 AM
TANK PER TST NEEDED WRN:
I54700 NOV 19, 2019 11: 18 AM
TANK PER TST NEEDED WRN:
I54800 NOV 19, 2019 11:18 AM
DISABLED
DAYS
TANK PER TST NEEDED ALM: DAYS
I54900 NOV 19, 2019 11: 18 AM
TANK ANN TST NEEDED WRN: DISABLED
I54A00 NOV 19, 2019 11:18 AM
25
30
TANK ANN TST NEEDED WRN: DAYS 355
I54B00 NOV 19, 2019 11:18 AM
TANK ANN TST NEEDED ALM:
I54C00 NOV 19, 2019 11: 18 AM
9999FF1B
I55300 NOV 19, 2019 11:19 AM
LINE RE-ENABLE METHOD PASS LINE TEST
I55400 NOV 19, 2019 11:19 AM
I55500 NOV 19, 2019 11: 19 AM
I55600 NOV 19, 2019 11: 19 AM
DAYS 365
LINE PER TST NEEDED WRN: DISABLED
I55700 NOV 19, 2019 11: 19 AM
LINE PER TST NEEDED WRN: DAYS 25
I55800 NOV 19, 2019 11: 19 AM
LINE PER TST NEEDED ALM: DAYS 30
I55900 NOV 19, 2019 11:19 AM
LINE ANN TST NEEDED WRN: DISABLED
I55A00 NOV 19, 2019 11:19 AM
LINE ANN TST NEEDED WRN: DAYS 355
Page 3
I55B00 NOV 19, 2019 11:19 AM
LINE ANN TST NEEDED ALM: DAYS 365
9999FF1B
I56000 NOV 19, 2019 11: 19 AM
MASS/DENSITY
DISABLED
I56400 NOV 19, 2019 11:19 AM
ULLAGE: 90%
I56500 NOV 19, 2019 11: 19 AM
MAINTENANCE HISTORY
DISABLED
I56600 NOV 19, 2019 11:19 AM
SERVICE NOTICE: DISABLED
I56700 NOV 19, 2019 11: 19 AM
I56800 NOV 19, 2019 11: 19 AM
I56900 NOV 19, 2019 11: 19 AM
I56AOO NOV 19, 2019 11:19 AM
I5BC00 NOV 19, 2019 11: 19 AM
RECEIVER SETUP REPORT
D 1: -NO ALARM ASSIGNMENTS -
D 2: -NO ALARM ASSIGNMENTS -
D 3: -NO ALARM ASSIGNMENTS -
D 4: -NO ALARM ASSIGNMENTS -
D 5: -NO ALARM ASSIGNMENTS -
D 6: -NO ALARM ASSIGNMENTS -
D 7: -NO ALARM ASSIGNMENTS -
D 8: -NO ALARM ASSIGNMENTS -
I5BD00 NOV 19, 2019 11: 19 AM
CUSTOM ALARM LABELS
DISABLED
I5BE00 NOV 19, 2019 11:19 AM
I5BF00 NOV 19, 2019 11: 19 AM
I5E200 NOV 19, 2019 11: 19 AM
I60100 NOV 19, 2019 11: 19 AM
TANK CONFIGURATION
DEVICE 1 2 3 4
I60200
LABEL unleaded Premuim Diesel
NOV 19, 2019 11:19 AM
TANK PRODUCT LABEL
I60300
PRODUc;T LABEL Unl eaQed Premu1m Diesel
NOV 19, 2019 11: 19 AM
TANK PRODUCT CODE
system setup
CONFIGURED ON ON ON OFF
TrK e~9~~a~/ABEL
2 Premu,m 3 Diesel 4
160400 NOV 19, 2019 11: 19 AM
TANK FULL VOLUME
TANK 1 2 J
160500
NOV 19, 2019 11:19 AM
TANK 4 POINT VOLUMES
TA1NK PRODU<;T LABEL Unl ea\led 2 Premu,m 1 Diesel
160600 NOV 19, 2019 11: 19 AM
TANK 20 POINT VOLUMES
TfNK e~9~~~~/ABEL
Premuim
Diesel
I60700 NOV 19, 2019 11: 19 AM
TANK DIAMETER
TANK 1 2 J
I60800
PRODU<;T LABEL Unl ea11ed Premu,m Diesel
NOV 19, 2019 11: 19 AM
TANK TILT
TANK 1 2 1
160900
NOV 19, 2019 11:19 AM
TANK THERMAL COEFFICIENT
TANK 1 2 3 4
I60A00
PRODUc;T LABEL unl ea\led bi:~~1m
NOV 19, 2019 11: 19 AM
TANK FULL VOLUME
A B
C 4
GALLONS 19782 7901 10420 0
19782 7901 10428
19782 0 0 0 0 7901 0 0
0 0 10420
INCHES 118. 35 118. 35 118. 38 o.oo
INCHES 0.00 o.oo o.oo o.oo
0 0
0 0 0 0 0
0 0
0. 000700 0. 000700 0. 000450 0. 000000
GALLONS 16033 6356
8506
GALLONS 0 16033 0 0 0 0 6356 0
0 0 0 8505 0
0 0 0 0 0
0 0
9897 3964 5192 0
0 0 9897 0 0 0 0 3964
0 0 0 0 5192
0 0 0 0 0
0 0
TANK 4.PTS D1 esel 1 PT
PRODUCT LABEL 19782 2 Premui!ANK PROFILE GALLONS 1
4 PTS 10420 4 4 PTS
0
I60B00 NOV 19, 2019 11:19 AM
STICK HEIGHT OFFSET ENABLE STATUS DISABLED
I60C00 NOV 19, 2019 11: 19 AM
TANK TANK 1 2 J
I60EOO NOV 19, 2019 11: 19 AM
CUSTOM FLOAT PARAMETERS
INCHES o.oo o.oo o.oo o.oo
TANK WATER OFFSET FUEL OFFSET 3 99.000 99.000
I60F00 NOV 19, 2019 11: 19 AM
PROBE OFFSET
TANK PR!)DU<;T LABEL 1 Un I ea\led 2 Premu,m
INCHES 0.00 o.oo
INVALID FUEL 99. 000
3741 1560 1898
0 0 0 3741 0 0 0 0
1560 0 0 0 0
1890 0 0 0 0
0 0
WATER MINIMUM 99 .000
Page 4
3 Diesel 4
161000 NOV 19, 2019 11:19 AM
TANK DELIVERY DELAY
TANK 1 2 1
161100
PR!)DUc;T LABEL Un lea11ed Premu,m Diesel
NOV 19, 2019 11: 19 AM
LEAK TEST METHOD
TEST ON DATE : ALL TANK
mR.Pfr~~l? DISABLED TEST RATE : 0. 20 GAL/HR DURATION : 2 HOURS
TST EARLY STOP: DISABLED
161200 NOV 19, 2019 11:19 AM
TANK MANIFOLDED PARTNERS
TANK TANKS 1 2 3 4
161300
PRODUCT LABEL
unlea<jed bi~~~101
NOV 19, 2019 11: 19 AM CSLD PROBABLITY OF DETECTION
161400 NOV 19, 2019 11: 19 AM CSLD CLIMATE FACTOR
161500 NOV 19, 2019 11:19 AM
TANK 1 2 1
161600
e~9~~~~/ABEL
Premu,m Diesel
NOV 19, 2019 11: 19 AM
TANK PRODUc;T LABEL 1 unl ea11ed ~ bf:;~1m
4
161800 NOV 19, 2019 11: 19 AM
161900 NOV 19, 2019 11: 19 AM
I61A00 NOV 19, 2019 11: 19 AM
IN-TANK LEAK TEST EARLY STOP
I61B00
PRODUCT LABEL Unl ea<;led Premu,m Diesel
NOV 19, 2019 11: 19 AM
0.00 0.00
SIPHON MANIFOLDED TANKS
NONE NONE NONE NONE
METER DATA NO NO NO NO
CAL UPDATE IMMEDIATE IMMEDIATE IMMEDIATE IMMEDIATE
TST EARLY STOP: DISABLED DISABLED DISABLED DISABLED
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00 NOV 19, 2019 11: 19 AM
CSLD REPORT ONLY
I61D00 NOV 19, 2019 11:19 AM
TANK MANIFOLDED PARTNERS
I61E00
PRODUCT LABEL
Unl ea<;led Premu,m Diesel
NOV 19, 2019 11: 19 AM
162100 NOV 19, 2019 11: 19 AM
TANK LOW PRODUCT LIMIT
TANK 1 2 3 4
162200
system setup
SIPHON MANIFOLDED TANKS
NONE NONE NONE NONE
GALLONS ~38
25/i
LINE MANIFOLDED
NONE NONE NONE NONE
LINE MANIFOLDED
NONE NONE NONE NONE
NOV 19, 2019 11:19 AM
TANK HIGH PRODUCT LIMIT
TANK PR!)DUc;T LABEL 1 Un I eaQed 2 Premu,m 3 oiesel 4
162300 NOV 19, 2019 11:19 AM
TANK OVERFILL LEVEL LIMIT
PRODUCT LABEL ~~!~~1~d Diesel
162400 NOV 19, 2019 11:19 AM
TANK HIGH WATER LEVEL LIMIT
162500
(;~9~~~!/ABEL Premu,m Diesel
NOV 19, 2019 11:19 AM
TANK SUDDEN LOSS LIMIT
TANK 1 2 l
162600
PRODUc;T LABEL Unl eaQed Premu1m Diesel
NOV 19, 2019 11: 19 AM
TANK LEAK ALARM LIMIT
162700
PRODUc;T LABEL Unl eaQed Premu,m Diesel
NOV 19, 2019 11: 19 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL 1 unlea~ed ~ bi:~~~m
162800 NOV 19, 2019 11: 19 AM
TANK MAXIMUM VOLUME LIMIT
TANK 1 2 l
PRODUc;T LABEL Unl eaQed Premu1m Diesel
162900 NOV 19, 2019 11: 19 AM
TANK
TANK 1 2 3 4
DELIVERY REQUIRED
PR!)DUc;T LABEL Unl eaQed Premu,m
Diesel
I62A00 NOV 19, 2019 11: 19 AM
LIMIT
ANNUAL LEAK TEST MIN VOLUME
162800
PRODUc;T LABEL Unl eaQed Premu1m Diesel
NOV 19, 2019 11:19 AM
TANK LAST ANNUAL TEST
TANK 1 2 l
I62c00
PRODUCT LABEL Unl ea~ed Premu1m Diesel
NOV 19, 2019 11: 19 AM
TANK PERIODIC TEST TYPE
TANK 1 2 l
I62D00
NOV 19, 2019 11: 19 AM
TANK LEAK TEST FAIL ALARMS
TtNK 0~9~~auABEL
Premuim
Diesel
GALLONS
18793 7506 9899 0
GALLONS 17803 7110 9378 0
INCHES 3.0 3.0 3.0
GALLONS I~
GALLONS 15 15 15 99
INCHES 1.0 1.0 1.0
GALLONS 19782 7901 10420 0
GALLONS 2967 1185 1042 0
GALLONS 989
395 494 0
DATE ~~~ 0,
??? 8: ??? 0, 8 0
PERIODIC TEST TYPE
STANDARD STANDARD STANDARD STANDARD
GROSS TEST FAIL
PERIODIC TEST FAIL
ANNUAL TEST FAIL
GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL
GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL
ALARM DISABLED ALARM DISABLED ALARM DISABLED
ALARM DISABLED ALARM DISABLED ALARM DISABLED
ALARM DISABLED ALARM DISABLED ALARM DISABLED
Page 5
I62EOO NOV 19, 2019 11:19 AM
GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL
CAPO PROBE CONDUCTIVE BOOT FLAG
TANK PRODUCT LABEL
I62F00 NOV 19, 2019 11: 19 AM
MAG PROBE FLOAT SIZE
TANK PRODUaT LABEL 1 unl ea ed 2 Premu,m 3 Diesel
163000 NOV 19, 2019 11:19 AM
IN-TANK LEAK TEST NOTIFY
TANK /;~9~~~!d LABEL 1 2 bi~~~lm 3 4
163100 NOV 19, 2019 11:19 AM
TANK LEAK TEST AVERAGING
TANK 1 2 3 4
163200
(;~9~~~!/ABEL
Premu1m Diesel
NOV 19, 2019 11: 19 AM
TANK TEST SIPHON BREAK
163300 NOV 19, 2019 11:19 AM
CAPO CONDUCTIVE BOOT:
FLOAT SIZE: 3.0 IN.
3.0 IN. 3.0 IN.
TANK TEST NOTIFY:
ANNUAL OFF OFF OFF OFF
OFF OFF OFF OFF
PERIODIC OFF OFF OFF OFF
SIPHON BREAK OFF OFF
OFF OFF
LEAK TEST REPORT FORMAT: NORMAL
163400 NOV 19, 2019 11: 19 AM
RECONCILIATION WARNING LIMIT
TANK 1 2 3 4
163500 NOV 19, 2019 11: 19 AM
RECONCILIATION ALARM LIMIT
163600 NOV 19, 2019 11: 19 AM
PERIODIC LEAK TEST MIN VOLUME
TANK 1 2 l
163900
PRODUc;T LABEL unl eaQed bi~~~lm
NOV 19, 2019 11: 19 AM
ACCU CHART END SHAPE FACTOR
TtNK e~9~~a!/ABEL
END FACTOR: NONE
2 Premuim END FACTOR: NONE
3 Diesel END FACTOR: NONE
4 END FACTOR: NONE
I63A00 NOV 19, 2019 11:19 AM
GALLONS 8 0 0
GALLONS 1 1 1 1
GALLONS 989 395 496
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
system Setup
PUMP THRESHOLD 10.00% 10.00% 10.00%
10.00%
ALARM DISABLED ALARM DISABLED ALARM DISABLED
163800
~2~/~6 ~gJc~lMJcM~ AND VOLUMES
I63C00 NOV 19, 2019 11: 19 AM
TANK 50 POINT FULL VOLUME
163000
NOV 19, 2019 11: 19 AM
9999FF18
168000
NOV 19, 2019 11: 19 AM
FOODS CO. 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
FUEL MANAGEMENT SETUP
DELIVERY WARN DAYS: 0. 0 AUTO PRINT: DISABLED
GALLONS ~
FUEL MANAGEMENT AVERAGE SALES (GALLONS)
Unleaded ~ TANK 1 ) SUN MON TUE ED THR FRI SAT 0 0 0 0 0 0 0
Premuim ( TANK 2 )
SUN MON TUE WED THR FRI SAT 0 0 0 0 0 0 0
Diesel ( TANK 3 ) SUN MON TUE WED THR FRI SAT 0 0 0 0 0 0 0
168100 NOV 19, 2019 11: 19 AM
168200 NOV 19, 2019 11:19 AM
168300 NOV 19, 2019 11:19 AM
170100 NOV 19, 2019 11:19 AM
LIQUID CONFIGURATION
DEVICE LABEL CONFIGURED 1 DISP 1-2 DUAL ON 2 DISP 3-4 DUAL ON 3 DISP 5-6 DUAL ON 4 DISP 7-8 DUAL ON 5 DISP 9-10 DUAL ON 6 DISP 11-12 DUAL ON 7 DISP 13-14 DUAL ON 8 87 TURBINE ON 9 87 TURBINE BRINE ON 10 87 FILL ON 11 87 FILL BRINE ON 12 87 ANNULAR ON 13 91 TURBINE ON 14 91 TURBINE BRINE ON 15 91 FILL ON 16 91 FILL BRINE ON 17 91 DIESEL ANNULAR ON 18 DIESEL TURBINE ON 19 DIESEL TURBINE BRINE ON
20 DIESEL FILL ON 21 DIESEL FILL BRINE ON 22 VENT SUMP ON 23 VENT SUMP BRINE ON 24 OFF
170200 NOV 19, 2019 11: 19 AM
LIQUID LABEL
DEVICE LABEL 1 DISP 1-2 DUAL 2 DISP 3-4 DUAL 3 DISP 5-6 DUAL 4 DISP 7-8 DUAL 5 DISP 9-10 DUAL 6 DISP 11-12 DUAL 7 DISP 13-14 DUAL 8 87 TURBINE
9 87 TURBINE BRINE
10 87 FILL
11 87 FILL BRINE
12 87 ANNULAR 13 91 TURBINE
14 91 TURBINE BRINE
15 91 FILL
16 91 FILL BRINE
17 91 DIESEL ANNULAR
18 DIESEL TURBINE
19 DIESEL TURBINE BRINE
20 DIESEL FILL
21 DIESEL FILL BRINE
22 VENT SUMP
23 VENT SUMP BRINE 24
170300 NOV 19, 2019 11:19 AM
LIQUID TYPE
SENSOR LOCATION TYPE 1 DISP 1-2 DUAL OW SUMP 2-1 2 DISP 3-4 DUAL OW SUMP 2-1 3 DISP 5-6 DUAL OW SUMP 2-1 4 DISP 7-8 DUAL DW SUMP 2-1 5 DISP 9-10 DUAL OW SUMP 2-1
6 DISP 11-12 DUAL OW SUMP 2-1 7 DISP 13-14 DUAL OW SUMP 2-1 8 87 TURBINE TRI-STATE (SINGLE FLOAT)
9 87 TURBINE BRINE TRI-STATE (SINGLE FLOAT)
10 87 FILL TRI-STATE (SINGLE FLOAT)
11 87 FILL BRINE TRI-STATE (SINGLE FLOAT)
12 87 ANNULAR DUAL POINT HYDROSTATIC 13 91 TURBINE TRI-STATE (SINGLE FLOAT)
14 91 TURBINE BRINE TRI-STATE (SINGLE FLOAT)
15 91 FILL TRI-STATE (SINGLE FLOAT)
16 91 FILL BRINE TRI-STATE (SINGLE FLOAT)
17 91 DIESEL ANNULAR DUAL POINT HYDROSTATIC 18 DIESEL TURBINE TRI-STATE (SINGLE FLOAT)
19 DIESEL TURBINE BRINE TRI-STATE (SINGLE FLOAT)
20 DIESEL FILL TRI-STATE (SINGLE FLOAT)
21 DIESEL FILL BRINE TRI-STATE (SINGLE FLOAT)
22 VENT SUMP TRI-STATE (SINGLE FLOAT)
23 VENT SUMP BRINE TRI-STATE (SINGLE FLOAT)
24 TRI-STATE (SINGLE FLOAT)
170400 NOV 19, 2019 11:19 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY 1 DISP 1-2 DUAL DISPENSER PAN 2 DISP 3-4 DUAL DISPENSER PAN 3 DISP 5-6 DUAL DISPENSER PAN 4 DISP 7-8 DUAL DISPENSER PAN 5 DISP 9-10 DUAL DISPENSER PAN 6 DISP 11-12 DUAL DISPENSER PAN 7 DISP 13-14 DUAL DISPENSER PAN 8 87 TURBINE STP SUMP
9 87 TURBINE BRINE STP SUMP
10 87 FILL PIPING SUMP 11 87 FILL BRINE PIPING SUMP 12 87 ANNULAR ANNULAR SPACE 13 91 TURBINE STP SUMP
14 91 TURBINE BRINE STP SUMP
15 91 FILL PIPING SUMP 16 91 FILL BRINE PIPING SUMP 17 91 DIESEL ANNULAR ANNULAR SPACE 18 DIESEL TURBINE STP SUMP
19 DIESEL TURBINE BRINE STP SUMP
20 DIESEL FILL PIPING SUMP 21 DIESEL FILL BRINE PIPING SUMP 22 VENT SUMP PIPING SUMP 23 VENT SUMP BRINE PIPING SUMP 24 OTHER SENSORS
170600 NOV 19, 2019 11: 19 AM
170700 NOV 19, 2019 11:19 AM
170800 NOV 19, 2019 11: 19 AM
170900 NOV 19, 2019 11:19 AM
171100 NOV 19, 2019 11:20 AM
171200 NOV 19, 2019 11: 20 AM
171300 NOV 19, 2019 11:20 AM
172100 NOV 19, 2019 11: 20 AM
SMART SENSOR CONFIGURATION
DEVICE LABEL CONFIGURED 1 DISP 1-2 VFM ON 2 DISP 3-4 VFM ON 3 DISP 5-6 VFM ON 4 DISP 7-8 VFM ON 5 DISP 9-10 VFM ON 6 DISP 11-12 VFM ON 7 gm H=U ~~M ON 8 ON 9 87 PRODUCT ON 10 87 91 VAPOR ON 11 87 VENT-CHASE ON 12 91 PRODUCT ON 13 91 VENT-CHASE ON 14 DIESEL PRODUCT ON 15 PMC CANISTER ON 16 ATM P ON 17 DIESEL VENT-CHASE ON
Page 6 system setup
18 19 20 21 22 23 24
I72200 NOV 19, 2019 11: 20 AM
SMART SENSOR LABEL
DEVICE LABEL 1 DISP 1-2 VFM 2 DISP 3-4 VFM 3 DISP 5-6 VFM 4 DISP 7-8 VFM 5 DISP 9-10 VFM 6 DISP 11-12 VFM 7 DISP 13-14 VFM
8 DISP 13-14 PS
9 87 PRODUCT
10 87 91 VAPOR 11 87 VENT-CHASE
12 91 PRODUCT
13 91 VENT-CHASE
14 DIESEL PRODUCT
15 PMC CANISTER
16 ATM P
17 DIESEL VENT-CHASE
18
19
20
21 22
23
24
I72300 NOV 19, 2019 11:20 AM
FOODS CO, 384 2501 HALEY
BAKERSFIELD CA, 661-873-9343
SMARTSENSOR ASSIGNMENT DEVICE LABEL 01 DISP 1-2 VFM 02 DISP 3-4 VFM 03 DISP 5-6 VFM 04 DISP 7-8 VFM 05 DISP 9-10 VFM 06 DISP 11-12 VFM 07 DISP 13-14 VFM 08 DISP 13-14 PS
09 87 PRODUCT 10 87 91 VAPOR 11 87 VENT-CHASE 12 91 PRODUCT 13 91 VENT-CHASE 14 DIESEL PRODUCT 15 PMC CANISTER 16 ATM P 17 DIESEL VENT-CHASE 18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
172700 NOV 19, 2019 11: 20 AM
I72800 NOV 19, 2019 11: 20 AM
172900 NOV 19, 2019 11: 20 AM
OFF OFF OFF
OFF OFF OFF OFF
CATEGORY AIR FLOW METER AIR FLOW METER AIR FLOW METER
AIR FLOW METER AIR FLOW METER AIR FLOW METER AIR FLOW METER VAPOR PRESSURE
VAC SENSOR VAC SENSOR VAC SENSOR VAC SENSOR VAC SENSOR
VAC SENSOR VAPOR VALVE ATM P SENSOR VAC SENSOR UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
Page 7
VACUUM SENSOR PUMP NUMBER
DEVIC§
10 11 12 13 14
17
I72A00
LABEL
87 PRODUCT
87 91 VAPOR 87 VENT-CHASE 91 PRODUCT 91 VENT-CHASE
DIESEL PRODUCT DIESEL VENT-CHASE
NOV 19, 2019 11:20 AM
VACUUM SENSOR VOLUME
DEVICE 9 10 11 12
13 14 17
I72B00 NOV 19,
VACUUM
DEVICE 9 10 11
12
13
14
17
I72COO
LABEL 87 PRODUCT 87 91 VAPOR 87 VENT-CHASE 91 PRODUCT
91 VENT-CHASE DIESEL PRODUCT DIESEL VENT-CHASE
2019 11: 20 AM
SENSOR RELIEF VALVE
LABEL 87 PRODUCT 87 91 VAPOR 87 VENT-CHASE
91 PRODUCT
91 VENT-CHASE
DIESEL PRODUCT
DIESEL VENT-CHASE
NOV 19, 2019 11: 20 AM
PUMP NUMBER Q 1: 87 UNLEADED
Q 1: 87 UNLEADED Q 1: 87 UNLEADED Q 2: 91 UNLEADED Q 2: 91 UNLEADED
Q 3 :DIESEL
Q 3 :DIESEL
VOLUME 57, 5 GALLONS 69, 0 GALLONS 29, 4 GALLONS 57, 5 GALLONS
25, 9 GALLONS 46.0 GALLONS 25. 9 GALLONS
PRESENT
RELIEF VALVE NO NO NO
NO
NO
NO
NO
VACUUM SENSOR RELIEF VALVE PRESSURE
DEVICE LABEL RELIEF VALVE PRESSURE 9 87 PRODUCT -9,0 PSI 10 87 91 VAPOR -9.0 PSI 11 87 VENT-CHASE -9.0 PSI
12 91 PRODUCT -9.0 PSI 13 91 VENT-CHASE -9.0 PSI 14 DIESEL PRODUCT -9.0 PSI 17 DIESEL VENT-CHASE -9.0 PSI
174100 NOV 19, 2019 11: 20 AM
I74200 NOV 19, 2019 11:20 AM
174300 NOV 19, 2019 11: 20 AM
I74400 NOV 19, 2019 11:20 AM
174600 NOV 19, 2019 11: 20 AM
I74700 2019 11: 20 AM NOV 19,
174800 NOV 19, 2019 11: 20 AM
I74900 NOV 19, 2019 11: 20 AM
174800 NOV 19, 2019 11: 20 AM
I74cOO NOV 19, 2019 11: 20 AM
174D00 NOV 19, 2019 11: 20 AM
I74EOO NOV 19, 2019 11: 20 AM
I75100 NOV 19, 2019 11:20 AM
175200 NOV 19, 2019 11: 20 AM
I75300 NOV 19, 2019 11: 20 AM
175400 NOV 19, 2019 11: 20 AM
175500 NOV 19, 2019 11: 20 AM
system setup
I75600
NOV 19, 2019 11:20 AM
I75700
NOV 19, 2019 11: 20 AM
I75800 NOV 19, 2019 11: 20 AM
I75900
NOV 19, 2019 11: 20 AM
I75A00
NOV 19, 2019 11:20 AM
LINE LEAK LOCKOUT SETUP
LOCKOUT SCHEDULE
DAILY
START TIME: DISABLED STOP TIME : DISABLED
I75B00 NOV 19, 2019 11: 20 AM
I75COO NOV 19, 2019 11:20 AM
I75D00 NOV 19, 2019 11: 20 AM
I75EOO NOV 19, 2019 11:20 AM
I75FOO NOV 19, 2019 11: 20 AM
176000 NOV 19, 2019 11: 20 AM
176100 NOV 19, 2019 11: 20 AM
I77100 NOV 19, 2019 11: 20 AM
I77200 NOV 19, 2019 11:20 AM
I77300 NOV 19, 2019 11:20 AM
I77400 NOV 19, 2019 11:20 AM
PLLD CONTINUOUS HANDLE TIMEOUT
LINE Q 1: 87 UNLEADED Q 2: 91 UNLEADED Q 3:DIESEL
I77500
NOV 19, 2019 11: 20 AM
TIMEOUT 16 HOURS
3:g ~88~~
PRESSURE LINE LEAK PROFILE LINE TEST LEAK RATE
LINE Q 1:87 UNLEADED Q 2: 91 UNLEADED Q 3 :DIESEL
I77600 NOV 19, 2019 11: 20 AM
TEST LEAK RATE 3.00 GPH 3.00 GPH 3.00 GPH
PRESSURE LINE LEAK PROFILE LINE TEST REFERENCE PRESSURE
LINE Q 1: 87 UNLEADED Q 2: 91 UNLEADED
Q 3 :DIESEL
I77700
NOV 19, 2019 11: 20 AM
177800
NOV 19, 2019 11: 20 AM
177900
NOV 19, 2019 11: 20 AM
I77AOO
NOV 19, 2019 11: 20 AM
I77B00
NOV 19, 2019 11:20 AM
I77COO NOV 19, 2019 11: 20 AM
TESil!li ~~iSSURE
10.00 PSI 10.00 PSI
Page 8
PRESSURE LINE LEAK LOW PRESSURE SHUTOFF
LINE Q l: 87 UNLEADED Q 2: 91 UNLEADED Q 3 :DIESEL
I77D00 NOV 19, 2019 11:20 AM
LOW PRESSURE SHUTOFF
NO NO NO
ALTITUDE PRESSURE OFFSET ADJUSTMENT
LINE Q 1: 87 UNLEADED Q 2: 91 UNLEADED
Q 3 :DIESEL
I77E00 NOV 19, 2019 11: 20 AM
I77FOO NOV 19, 2019 11: 20 AM
PRESSURE OFFSET 0. 0 PSI 0. 0 PSI 0.0 PSI
PRESSURE LINE LEAK LINE LENGTH LARGE
LINE Q 1: 87 UNLEADED
Q 2: 91 UNLEADED Q 3 :DIESEL
178000 NOV 19, 2019 11: 20 AM
PRESSURE LINE LEAK SETUP
Q 1: 87 UNLEADED 1:m · g{l ·~I~: FmR~~N-s
3. OIN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LO,/ PRESSURE SHUTOFF: NO LO,i PRESSURE : 0 PSI
T 1: Unleaded DISPENSE MODE: STANDARD SENSOR: HIGH PRESSURE PRESSURE OFFSET: 0. OPSI
MECHANICAL BLENDER: NO
Q 2: 91 UNLEADED
TYP: 2. 0/3. OIN FIBERGLASS
2. QIN DIA LEN: 250 FEET 3. QIN DIA LEN: 0 FEET SHUTDO,iN RATE: 3.0 GPH LO,i PRESSURE SHUTOFF: NO
LO,/ PRESSURE :
T 2:Premuim DISPENSE MODE: STANDARD
0 PSI
SENSOR: HIGH PRESSURE PRESSURE OFFSET: 0. OPSI
MECHANICAL BLENDER: NO
Q 3 :DIESEL
TYP: 2. 0/3. OIN FIBERGLASS 2 • OIN DIA LEN: 200 FEET 3 • OIN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LO,/ PRESSURE SHUTOFF: NO
LOW PRESSURE :
T 3:Diesel DISPENSE MODE: STANDARD
0 PSI
SENSOR: HIGH PRESSURE PRESSURE OFFSET: 0. OPSI
MECHANICAL BLENDER: NO
I78100 NOV 19, 2019 11: 20 AM
PRESSURE LLD CONFIGURATION
DEVICE LABEL 1 87 UNLEADED 2 91 UNLEADED 3 DIESEL
178200 NOV 19, 2019 11: 20 AM
PRESSURE LLD LABEL
DEVICE LABEL 1 87 UNLEADED 2 91 UNLEADED 3 DIESEL
178300 NOV 19, 2019 11: 20 AM
178400 NOV 19, 2019 11:20 AM
LINE LENGTH 0 FEET
0 FEET 0 FEET
CONFIGURED ON ON ON
PRESSURE LINE LEAK SHUTDOWN RATE
LINE Q 1: 87 UNLEADED Q 2: 91 UNLEADED
Q 3: DIESEL
178500 NOV 19, 2019 11:20 AM
SHUTDOWN RATE 3. 0 GPH 3 .0 GPH 3 .0 GPH
PRESSURE LINE LEAK TANK NUMBER
system Setup
LINE Q 1: 87 UNLEADED Q 2: 91 UNLEADED
Q 3 :DIESEL
I78600
NOV 19, 2019 11: 20 AM
TANK NUMBER
½
3
PRESSURE LINE LEAK DISPENSE MODE
LINE Q l: 87 UNLEADED Q 2: 91 UNLEADED Q 3: DIESEL
178700 NOV 19, 2019 11: 20 AM
PRESSURE LLD SETUP REPORT
Q 1:87 UNLEADED
IN-TANK ALARMS T 1: HIGH WATER ALARM T 1: LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L l: FUEL ALARM
L 2: FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM
L 5: FUEL ALARM L 6: FUEL ALARM L 7: FUEL ALARM L 8: FUEL ALARM L 9: FUEL ALARM
LlO: FUEL ALARM Lll: FUEL ALARM L22: FUEL ALARM
L23: FUEL ALARM
L l: SENSOR OUT ALARM L 2 ; SENSOR OUT ALARM L 3: SENSOR OUT ALARM L 4: SENSOR OUT ALARM L 5 : SENSOR OUT ALARM
L 6: SENSOR OUT ALARM L 7: SENSOR OUT ALARM
L 8: SENSOR OUT ALARM L 9: SENSOR OUT ALARM
LlO: SENSOR OUT ALARM Lll: SENSOR OUT ALARM L22: SENSOR OUT ALARM L23: SENSOR OUT ALARM L 1: SHORT ALARM
L 2 : SHORT ALARM L 3: SHORT ALARM L 4: SHORT ALARM L 5:SHORT ALARM
L 6: SHORT ALARM L 7: SHORT ALARM L 8: SHORT ALARM L 9: SHORT ALARM LlO: SHORT ALARM
Lll: SHORT ALARM Ll2 : SHORT ALARM L22: SHORT ALARM L23: SHORT ALARM t11: rli~H Li/i8~ti0 At~~:M L 2 : LOW LIQUID ALARM L 3: LOW LIQUID ALARM L 4: LOW LIQUID ALARM L 5 : LOW LIQUID ALARM L 6: LOW LIQUID ALARM
L 7: LOW LIQUID ALARM
Lll: LOW LIQUID ALARM Ll2 : LOW LIQUID ALARM
PRESSURE LINE LEAK Q 1: PLLD OPEN ALARM
SMARTSENSOR ALARMS
slO: FUEL ALARM
s 9: HIGH LIQUID ALARM slO: HIGH LIQUID ALARM
~1§: ~/iGMli8~I~L!~~RM
slO: NO VACUUM ALARM sll:No VACUUM ALARM
ISO SITE ALARMS
ISD GROSS PRES FAIL ISO DEGRO PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISO VP STATUS FAIL
ISO HOSE ALARMS ALL: FLO\v COLLECT FAIL
Q 2: 91 UNLEADED
IN-TANK ALARMS T 2: HIGH WATER ALARM T 2 : LOW PRODUCT ALARM
L[ Q~7~u~[N~2:R~LMS
L 2 FUEL ALARM L 3 FUEL ALARM L 4 FUEL ALARM L 5 FUEL ALARM L 6 FUEL ALARM L 7 FUEL ALARM Ll3 FUEL ALARM
Ll4 FUEL ALARM L15 FUEL ALARM L16 FUEL ALARM Ll7 FUEL ALARM
L22 FUEL ALARM L23 FUEL ALARM L 1 SENSOR OUT ALARM L 2 SENSOR OUT ALARM L 3 SENSOR OUT ALARM L 4 SENSOR OUT ALARM L 5 SENSOR OUT ALARM L 6 SENSOR OUT ALARM L 7 SENSOR OUT ALARM
Ll3 SENSOR OUT ALARM Ll4 SENSOR OUT ALARM Ll5 SENSOR OUT ALARM Ll6 SENSOR OUT ALARM
DISPENSE MODE
STANDARD STANDARD STANDARD
Page 9
Ll7 SENSOR OUT ALARM L22 SENSOR OUT ALARM L23 SENSOR OUT ALARM L l SHORT ALARM L 2 SHORT ALARM L 3 SHORT ALARM L 4 SHORT ALARM L 5 SHORT ALARM L 6 SHORT ALARM L 7 SHORT ALARM Ll3 SHORT ALARM Ll4 SHORT ALARM Ll5 SHORT ALARM Ll6 SHORT ALARM Ll7 SHORT ALARM L22 SHORT ALARM L23 SHORT ALARM t1i r5~\i@~5D At~~:M
L 2 LOW LIQUID ALARM L 3 LOW LIQUID ALARM L 4 LOW LIQUID ALARM L 5 LOW LIQUID ALARM L 6 LOW LIQUID ALARM L 7 LOW LIQUID ALARM
Ll7: LO\v LIQUID ALARM
PRESSURE LINE LEAK Q 2: PLLD OPEN ALARM
SMARTSENSOR ALARMS slO: FUEL ALARM
sl2 : FUEL ALARM sl3: FUEL ALARM slO: HIGH LIQUID ALARM sl2: HIGH LIQUID ALARM sl3: HIGH LIQUID ALARM sl2 :NO VACUUM ALARM sl3: NO VACUUM ALARM
ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRO PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL
ISD HOSE ALARMS ALL: FLOW COLLECT FAIL
Q 3 :DIESEL
IN-TANK ALARMS T 3: HIGH WATER ALARM T 3: LOW PRODUCT ALARM
LIQUID SENSOR ALMS L 1: FUEL ALARM
L 2: FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM Ll7: FUEL ALARM
Ll8: FUEL ALARM Ll9: FUEL ALARM L20: FUEL ALARM L21: FUEL ALARM L22: FUEL ALARM L23: FUEL ALARM L 1: SENSOR OUT ALARM L 2: SENSOR OUT ALARM L 3: SENSOR OUT ALARM L 4; SENSOR OUT ALARM Ll7: SENSOR OUT ALARM Ll8: SENSOR OUT ALARM Ll9: SENSOR OUT ALARM L20: SENSOR OUT ALARM
L21:SENSOR OUT ALARM L22: SENSOR OUT ALARM L23: SENSOR OUT ALARM
L 1: SHORT ALARM L 2 : SHORT ALARM L 3: SHORT ALARM L 4: SHORT ALARM Ll7: SHORT ALARM Ll8: SHORT ALARM Ll9: SHORT ALARM L20: SHORT ALARM L21: SHORT ALARM L22: SHORT ALARM L23: SHORT ALARM Ll7: HIGH LIQUID ALARM L 1: LOW LIQUID ALARM L 2: LOW LIQUID ALARM L 3: LOW LIQUID ALARM L 4: LOW LIQUID ALARM Ll7: LOW LIQUID ALARM
PRESSURE LINE LEAK
Q 3: PLLD OPEN ALARM
SMARTSENSOR ALARMS sl4: FUEL ALARM
sl7: FUEL ALARM
sl4: HIGH LIQUID ALARM sl7: HIGH LIQUID ALARM sl4:No VACUUM ALARM
sl7:NO VACUUM ALARM
I78800 NOV 19, 2019 11: 21 AM
PRESSURE LINE LEAK PIPE TYPE
LINE Q 1: 87 UNLEADED Q 2: 91 UNLEADED Q 3 :DIESEL
I78900 NOV 19, 2019 11: 21 AM
PRESSURE LINE LEAK LINE LENGTH
LINE Q 1: 87 UNLEADED
Q 2 : 91 UNLEADED Q 3 :DIESEL
I78A00 NOV 19, 2019 11:21 AM
PRESSURE LINE LEAK
system setup
LINE LENGTH 250 FEET 250 FEET 200 FEET
LINE Q 1: 87 UNLEADED Q 2: 91 UNLEADED Q 3:DIESEL
9999FF1B
I78C00 NOV 19, 2019 11:21 AM
I78E00 NOV 19, 2019 11:21 AM
I78F00 NOV 19, 2019 11: 21 AM
PUMP HIGH PRESSURE HIGH PRESSURE HIGH PRESSURE
PRESSURE LINE LEAK DISPENSE THRESHOLD
LINE Q 1:87 UNLEADED Q 2 :91 UNLEADED Q 3:DIESEL
I79000 NOV 19, 2019 11: 21 AM
LOW PRESSURE 0 PSI 0 PSI 0 PSI
EDIM:l VR:330273-002-C TD:97.11,13.15.52
I79100 NOV 19, 2019 11:21 AM
I79200 NOV 19, 2019 11: 21 AM
DISP, MODULE DATA STRING EDIM 1: B9DNHG
I79300 NOV 19, 2019 11: 21 AM
AUTOMATIC DAILY CLOSING TIME: 2:00 AM
I79400 NOV 19, 2019 11:21 AM
I79500 NOV 19, 2019 11: 21 AM
PERIODIC RECONCILIATION MODE: MONTHLY
I79600 NOV 19, 2019 11: 21 AM
PERIODIC RECONCILIATION LENGTH: 31 DAYS
I79700 NOV 19, 2019 11: 21 AM
PERIODIC RECONCILIATION ALARM: DISABLED
I79800 NOV 19, 2019 11:21 AM
PERIODIC RECONCILIATION
ALARM THRESHOLD: 1. 00%
I79900 NOV 19, 2019 11:21 AM
PERIODIC RECONCILIATION ALARM OFFSET: 130
I79A00 NOV 19, 2019 11: 21 AM
REMOTE REPORT FORMAT SELECT: ROW
I79D00 NOV 19, 2019 11: 21 AM
MANUAL SHIFT CLOSE
I79EOO NOV 19, 2019 11:21 AM
RECONCILIATION CLEAR MAP
I79F00 NOV 19, 2019 11: 21 AM
TEMP COMPENSATION STANDARD
I7AOOO NOV 19, 2019 11:21 AM
I7Al00 NOV 19, 2019 11: 21 AM
I7A200 NOV 19, 2019 11: 21 AM
Page 10
I7A300 NOV 19, 2019 11:21 AM
I7A400 NOV 19, 2019 11: 21 AM
I7A500 NOV 19, 2019 11:21 AM
I7A600 NOV 19, 2019 11: 21 AM
I7A700 NOV 19, 2019 11:21 AM
I7A800 NOV 19, 2019 11:21 AM
I7A900 NOV 19, 2019 11:21 AM
9999FF1B
I7AC00 NOV 19, 2019 11:21 AM
I7AD00 NOV 19, 2019 11: 21 AM
I7AE00 NOV 19, 2019 11: 21 AM
I7AF00 NOV 19, 2019 11: 21 AM
I7B100
~8¥Li~/; 2019 11: 21 AM POSITION -METER -TANK
BUS SLOT FUEL_P METER TANK -------------------------------
TANK MAP EMPTY
I7B200 NOV 19, 2019 11: 21 AM
METER CALIBRATION OFFSET: 0, 000%
I7B400 NOV 19, 2019 11: 21 AM
I7BC00 NOV 19, 2019 11: 21 AM
I7BD00 NOV 19, 2019 11:21 AM
PRESSURE LLD SETUP REPORT
Q 1: 87 UNLEADED
IN-TANK ALARMS T l:HIGH WATER ALARM T 1: LOW PRODUCT ALARM
LtQ~f ~u~[N~eMLMS
L 2 : FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM L 5: FUEL ALARM L 6: FUEL ALARM L 7: FUEL ALARM L 8; FUEL ALARM L 9: FUEL ALARM
LlO: FUEL ALARM Lll: FUEL ALARM L22: FUEL ALARM
L23; FUEL ALARM L 1: SENSOR OUT ALARM L 2: SENSOR OUT ALARM L 3: SENSOR OUT ALARM L 4: SENSOR OUT ALARM L 5 : SENSOR OUT ALARM L 6: SENSOR OUT ALARM L 7; SENSOR OUT ALARM
L 8; SENSOR OUT ALARM L 9: SENSOR OUT ALARM LlO: SENSOR OUT ALARM Lll: SENSOR OUT ALARM L22: SENSOR OUT ALARM L23: SENSOR OUT ALARM L 1: SHORT ALARM L 2 : SHORT ALARM L 3: SHORT ALARM L 4: SHORT ALARM L 5: SHORT ALARM L 6: SHORT ALARM L 7: SHORT ALARM L 8: SHORT ALARM L 9: SHORT ALARM LlO: SHORT ALARM Lll: SHORT ALARM Ll2: SHORT ALARM L22: SHORT ALARM L23: SHORT ALARM t1i \ t6~H Li~8~5D At~~~M
L 2 : LOW LIQUID ALARM L 3: LOW LIQUID ALARM L 4: LOW LIQUID ALARM L 5: LOW LIQUID ALARM
system Setup
MAP
L 6: LOW LIQUID ALARM L 7: LOW LIQUID ALARM
Lll: LOW LIQUID ALARM Ll2 : LOW LIQUID ALARM
PRESSURE LINE LEAK Q 1: PLLD OPEN ALARM
SMARTSENSOR ALARMS slO: FUEL ALARM
s 9: HIGH LIQUID ALARM slO: HIGH LIQUID ALARM
~1§: ~/iGM/i8~I~L!~tiRM
slO:NO VACUUM ALARM sll: NO VACUUM ALARM
ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPDR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL
ISD HOSE ALARMS ALL: FLOW COLLECT FAIL
Q 2:91 UNLEADED
IN-TANK ALARMS T 2: HIGH WATER ALARM T 2 : LOW PRODUCT ALARM
LIQUID SENSOR ALMS L 1: FUEL ALARM
L 2: FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM L 5 : FUEL ALARM L 6: FUEL ALARM L 7: FUEL ALARM L13: FUEL ALARM
Ll4: FUEL ALARM LlS: FUEL ALARM Ll6: FUEL ALARM Ll7: FUEL ALARM
L22: FUEL ALARM L23: FUEL ALARM L 1: SENSOR OUT ALARM L 2: SENSOR OUT ALARM L 3: SENSOR OUT ALARM L 4: SENSOR OUT ALARM L 5: SENSOR OUT ALARM L 6: SENSOR OUT ALARM L 7: SENSOR OUT ALARM
L13: SENSOR OUT ALARM Ll4: SENSOR OUT ALARM LlS : SENSOR OUT ALARM Ll6: SENSOR OUT ALARM L17: SENSOR OUT ALARM L22: SENSOR OUT ALARM L23: SENSOR OUT ALARM L l: SHORT ALARM
L 2: SHORT ALARM L 3: SHORT ALARM L 4: SHORT ALARM L 5 : SHORT ALARM L 6: SHORT ALARM L 7: SHORT ALARM L13: SHORT ALARM Ll4: SHORT ALARM LlS: SHORT ALARM Ll6: SHORT ALARM Ll7: SHORT ALARM L22: SHORT ALARM L23: SHORT ALARM t1n6~HLi/;8~6D At~~~M
L 2: LOW LIQUID ALARM L 3: LOW LIQUID ALARM L 4: LOW LIQUID ALARM L 5 : LOW LIQUID ALARM L 6: LOW LIQUID ALARM L 7: LOW LIQUID ALARM
Ll7: LOW LIQUID ALARM
PRESSURE LINE LEAK Q 2 : PLLD OPEN ALARM
SMARTSENSOR ALARMS slO: FUEL ALARM
sl2: FUEL ALARM s13: FUEL ALARM slO: HIGH LIQUID ALARM sl2: HIGH LIQUID ALARM m: ~liGMlia~1~L!~tiRM
s13 :NO VACUUM ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL
ISD VP STATUS FAIL
ISO HOSE ALARMS ALL: FLOW COLLECT FAIL
Q 3 :DIESEL
IN-TANK ALARMS T 3: HIGH WATER ALARM T 3: LOW PRODUCT ALARM
LIQUID SENSOR ALMS L 1: FUEL ALARM
L 2 FUEL ALARM L 3 FUEL ALARM L 4 FUEL ALARM Ll7 FUEL ALARM
Ll8 FUEL ALARM Ll9 FUEL ALARM L20 FUEL ALARM L21 FUEL ALARM
L22 FUEL ALARM L23 FUEL ALARM L 1 SENSOR OUT ALARM L 2 SENSOR OUT ALARM L 3 SENSOR OUT ALARM
L 4 SENSOR OUT ALARM Ll7 SENSOR OUT ALARM Ll8 SENSOR OUT ALARM Ll9 SENSOR OUT ALARM L20 SENSOR OUT ALARM
L21 SENSOR OUT ALARM L22 SENSOR OUT ALARM
Page 11
L23: SENSOR OUT ALARM
L 1: SHORT ALARM
L 2 : SHORT ALARM L 3: SHORT ALARM L 4: SHORT ALARM Ll7: SHORT ALARM Ll8: SHORT ALARM L19: SHORT ALARM L20: SHORT ALARM L21: SHORT ALARM L22: SHORT ALARM L23: SHORT ALARM Ll7: HIGH LIQUID ALARM L 1: LOW LIQUID ALARM L 2: LOW LIQUID ALARM L 3: LOW LIQUID ALARM L 4: LOW LIQUID ALARM Ll7: LOW LIQUID ALARM
PRESSURE LINE LEAK
Q 3: PLLD OPEN ALARM
SMARTSENSOR ALARMS sl4: FUEL ALARM
sl7: FUEL ALARM
sl4: HIGH LIQUID ALARM sl7: HIGH LIQUID ALARM sl4: NO VACUUM ALARM sl7: NO VACUUM ALARM
I7BE00 NOV 19, 2019 11:22 AM
I7C400 NOV 19, 2019 11: 22 AM
I7C500 NOV 19, 2019 11: 22 AM
I7C600 NOV 19, 2019 11:22 AM
I7c700 NOV 19, 2019 11: 22 AM
I7C800 NOV 19, 2019 11:22 AM
I7C900 NOV 19, 2019 11: 22 AM
180100 NOV 19, 2019 11:22 AM
EXTERNAL INPUT CONFIGURATION
DEVICE LABEL
1 EMERGENCY SHUT OFF 2
!80200 NOV 19, 2019 11:22 AM
EXTERNAL INPUT LABEL
DEVICE LABEL 1 EMERGENCY SHUT OFF 2
180300 NOV 19, 2019 11: 22 AM
EXTERNAL INPUT TYPE
INPUT NAME 1 EMERGENCY SHUT OFF 2
180400 NOV 19, 2019 11:22 AM
180600 NOV 19, 2019 11:22 AM
RELAY CONFIGURATION
DEVICE LABEL 1 OVERFILL 2
180700 NOV 19, 2019 11:22 AM
RELAY LABEL
DEVICE LABEL 1 OVERFILL 2
180800 NOV 19, 2019 11: 22 AM
RELAY SETUP REPORT
R l:OVERFILL TYPE:
STANDARD NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS ALL: OVERFILL ALARM ALL: HIGH PRODUCT ALARM
system Setup
CONFIGURED
ON OFF
TYPE STANDARD STANDARD
CONFIGURED ON OFF
ORIENTATION NORMALLY OPEN NORMALLY OPEN
TANK#
R 2: TYPE:
STANDARD NORMALLY OPEN
TANK #: NONE
-NO ALARM ASSIGNMENTS -
!80900 NOV 19, 2019 11:22 AM
RELAY ORIENTATION
RELAi g~mmION
2
I80A00 NOV 19, 2019 11: 22 AM
RELAY TYPE
RELAY DESIGNATION ½ OVERFILL
I80B00 NOV 19, 2019 11: 22 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION ½ OVERFILL
I80C00 NOV 19, 2019 11: 22 AM
EXTERNAL INPUT TYPE
INPUT NAME 1 EMERGENCY SHUT OFF 2
!85100 NOV 19, 2019 11:22 AM
RESTORE SETUP DATA: DISABLED
!85200 NOV 19, 2019 11: 22 AM
SAVE SETUP DATA: DISABLED
!85300 NOV 19, 2019 11:22 AM
CLEAR SETUP DATA: DISABLED
!88100 NOV 19, 2019 11: 22 AM
!88200 NOV 19, 2019 11:22 AM
!88500 NOV 19, 2019 11: 22 AM
188600 NOV 19, 2019 11:22 AM
!88700 NOV 19, 2019 11: 22 AM
!88800
~~l~6A~gl9 ,in~D~~: )
CONNECTION : NONE
c~Mg~rnN ~o~~-SAT )
cg~Mg~~gN ~o~~s-485)
cg~Mg~~gN ~o~~s-232)
!88900 NOV 19, 2019 11:22 AM
I88D00 NOV 19, 2019 11:22 AM
!89100
NOV 19, 2019 11: 22 AM
I8A200
NOV 19, 2019 11:22 AM
FOODS CO, 384 2501 HALEY
BAKERSFIELD CA, 661-873-9343
SERVICE CODE LIST
STANDARD LABEL REPROGRAMMED TLS CODE
0101
ORIENTATION NORMALLY OPEN NORMALLY OPEN
TYPE STANDARD STANDARD
TANK NONE NONE
TYPE STANDARD STANDARD
ORIENTATION NORMALLY OPEN NORMALLY OPEN
TANK#
Page 12
COLD BOOT SYSTEM 0102 REPLACED PC BOARD 0103 NO PROBLEM FOUND 0104
~~H~~L~6c8M~UND 818~
REPLACED KEYBOARD 0107 REPLACED DISPLAY 0108 SYSTEM UPGRADE 0109 CONDUCTED TRAINING 0110 OPERATOR ERROR 0111 INSTALLED PAPER 0201 REPLACED PRINTER 0202 NEW LINE SHARE DEV 0203 CLEARED PAPER JAM 0204 ~~~m~o~A~~N~AH~T gm RECONNECTED PROBE 0303
mL~~og/~egh mi
CLEANED PROBE 0306 CORRECT TANK CHART 0307 RESET ACCUCHART 0308 REPLACED SENSOR 0401 REWIRED SENSOR 0402 REMOVED FUEL 0403 REMOVED WATER 0404 ADJUSTED BRINE LVL 0405 REPAIRED PRIMARY LK 0406 REPAIRED SEC LK 0407 RECHARGED VACUUM 0408 REPLACED VAC TUBING 0409 ADDED COMM BOARD 0501 RESET MODEM 0502 RECONNECT PHONE LN 0503 NEW PHONE NUMBER 0504 NEW IP ADDRESS 0505 REPLACED COMM CABLE 0506 REPLACED DIM MODULE 0601 REPLACED DIM CABLE 0602 DIM MISAPPLICATION 0603 CAB RUN MODE 0604 REPAIRED LEAK 0701 REPAIRED STP CAP 0702 RESTORE STP POWER 0703 CLEAN FUNC ELEMENT 0704 DISBLE FUNC ELEMENT 0705 OUT OF FUEL 0706 REPL LLD TRANSDUCER 0707 REWIRED LLD 0708 REPLACED LLD MODULE 0709 REPLACED CHECK VLV 0710 REPLACE PRODUCT RL Y 0711 REPLACE DISP VALVE 0712 ELIM WPLLD NOISE 0713 INSTALL MECH LLD 0714 PERFORM LINE TEST 0715 REPLACED MLLD 0716 INSTALL NEW STP 0801 REPLACED UMP 0802 REPL FUNC ELEMENT 0803 REPL CHECK VALVE 0804 PMP NEW IP ADDRESS 0805 REPL CONTROL BOX 0806 REPLACED CAPACITOR 0807 REPLACED SEALS 0808 REPL VAR SPD CNTRL 0809 REWIRED PUMP 0810 REPL VLLD CONTROL 0901 REPL VLLD CHECK VLV 0902 VLLD SELF CHECK 0903 VLLD PUMP SELF TST 0904 VLLD OTHER ACTION 0905 CAL VAC ASSIST PUMP 1001 ~~~~u~mse,~ HH rm 2 IN DECAY TEST 1004 10 IN DECAY TEST 1005 REPAIRED CONT LEAK 1006 RPR VAC ASSIST PUMP 1007 REPL VAC ASSIST PMP 1008
~elu~;lJ8lt~oCESSOR 18~6 RPR SPILL BUCKET 1101 RPR DELIVERY CAP 1102 RPR VPR EXTR CAP 1103 RPR PROBE RISER CAP 1104 REPLACED FILTER 1201 REPL DISPENSER SW 1202 COLD BOOT SYSTEM 1203 REPAIRED DISPENSER 1204 RESET SHEAR VALVE 1205 REPL SHEAR VALVE 1206 REPAIRED PIPING 1207 REPAIRED BOOT 1208 CALIB LIQUID MTR 1209 REPL DISPENSER PRTR 1210 INSTALLED PAPER 1211 CLEARED PAPER JAM 1212 REPAIRED DOOR LOCK 1213 REPAIRED DOOR SW 1214 REPL HANGING HW 1301 REPLACED NOZZLE 1302 REPLACED BOOT 1303 REPLACED SPOUT 1304 REPL PRIMARY HOSE 1305 REPLACED BREAKAWAY 1306 REPAIRED BREAKAWAY 1307 REPLACED WHIP HOSE 1308 REPL HOSE EXTRACTOR 1309 REPL FLOW LIMITER 1310 REPL NOZZLE COVER 1311 BAGGED OFF NOZZLE 1312 RETURNED NOZZLE 1313 REPROGRAMMED POS 1401 REPL POS SOFTWARE 1402 COLD BOOT SYSTEM 1403 REPLACED POS 1404 REWIRED POS 1405 RPR OUTSIDE LIGHTS 1501 REPAIRED SIGNAGE 1502 CLEANED STORM DRAIN 1503 SVC OIL VfTR SEPRATR 1504 ANN OPERABILITY TST 1601 WEIGHT MEASURES TST 1602 SUMP INTEGRITY TST 1603 OPERATOR VISIT 1604 ELD TEST 1605 SPILL BUCKET TEST 1606
USER DEFINED LABEL CODE NONE
I8A300 NOV 19, 2019 11:23 AM
I8A400 NOV 19, 2019 11: 23 AM
I8BC00 NOV 19, 2019 11:23 AM
RELAY SETUP REPORT
R !:OVERFILL
system setup
TYPE:
STANDARD NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS ALL:OVERFILL ALARM ALL: HIGH PRODUCT ALARM
R 2: TYPE:
STANDARD NORMALLY OPEN
TANK #: NONE
NO ALARM ASSIGNMENTS -
I8Cl00 NOV 19, 2019 11:23 AM
I8C200 NOV 19, 2019 11: 23 AM
9999FF1B 9999FF1B
190100 NOV 19, 2019 11:23 AM
SYSTEM BOARD
190200
I/0 PASS
NOV 19, 2019 11:23 AM SOFfWARE REVISION LEVEL VERSION 330. 01 SOFTivARE# 346330-100-B CREATED -10.07,23.17.25
S-MODULE# 330160-104-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR ISD
190300 NOV 19, 2019 11:23 AM PC DIAGNOSTIC DATA PERIPHERAL CONTROLLER
PC SWARE# 330269-002-B CREATED -94.12.16.13.26 PC ROM CHECKSUM PASSED
PC RESET COUNTS = 154 PC COMM ERRORS = 167 MC CKSUM ERRS = 23 MC->PC COMMS =3476133314 MC<-PC COMMS =3476148795
190500 NOV 19, 2019 11:23 AM SOFTWARE REVISION LEVEL VERSION 330. 01 SOFTWARE# 346330-100-B CREATED -10.07.23.17.25
S-MODULE# 330160-104-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR ISD
IAOlOO NOV 19, 2019 11: 23 AM
TANK 1 Un 1 eaded m~ ~ m~~~m
RAM PASS
TYPE MAG MAG MAG
PROM PASS
CODE D004 D004 D004
LENGTH 126.00 126.00 126.00
sEmh~o.
551174 551172
Page 13 System Setup
Bel shire TLS PO ll er DO ALARM HISTORY Command set ver 5 .12 Started at 11/19/2019 11:50:01 AM
!10200 NOV 19, 2019 11:49 AM
FOODS CO, 384 2501 HALEY BAKERSFIELD CA, 661-873-9343
SYSTEM CONFIGURATION
SLOT 1 2 I 6 7 8 9 10 11 12 13 14 15 16
BOARD TYPE 4 PROBE / G.T. PLLD SENSOR BO INTERSTITIAL BO INTERSTITIAL BO INTERSTITIAL BO 8SMARTSENSOR BO 7SMARTSENSOR BO 8SMARTSiNSOR BO COMBO I O BOARD PLLD PO ER BO UNUSED UNUSED UNUSED UNUSED UNUSED UNUSED COMM 1 ELEC DISP INT, COMM 2 SERIAL SAT BO COMM 3 UNUSED COMM 4 UNUSED COMM 5 RS485 SERIAL BO COMM 6 RS232 SERIAL BO
120600 NOV 19, 2019 11: 49 AM
FOODS CO, 384 2501 HALEY BAKERSFIELD CA, 661-873-9343
TANK ALARM HISTORY
TANK 1 Unleaded
OVERFILL ALARM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
HIGH WATER WARNING
DELIVERY NEEDED
LOW TEMP WARNING
TANK Premuim
OVERFILL ALARM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
HIGH WATER WARNING
DELIVERY NEEDED
LOW TEMP WARNING
TANK 3 Diesel
OVERFILL ALARM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM
POWER ON RESET 164807
NOV 19, AUG 9, JUL 28,
SEP ~j: DEC DEC
NOV 19, NOV 27, NOV 28,
NOV 19, DEC 3' DEC 4,
DEC 15,
NOV 19, NOV 1~: JUL
NOV 27,
NOV 27, SEP 21, AUG 20,
NOV 19, NOV 28, DEC 5.
NOV H: NOV SEP 21,
DEC it DEC DEC
NOV 27, NOV 27, DEC 4,
DEC §: DEC DEC 6,
DEC ~: DEC DEC 6,
NOV 19, NOV 27, NOV 27,
NOV H: DEC
H: DEC MAR SEP 29,
NOV 19, SEP 21, NOV 28,
NOV H: NOV SEP 21,
SEP 21, DEC ~: DEC
NOV 19, NOV 27,
3919 202970 203082 203127 39544 514845 9949365 9928 102072 9852763 9870287 9798228 9823814 9765830 9798012 101521 9786178 9767641 9753587 68839 15029
2019 11:21 AM 2019 12:43 AM 2019 3: 10 PM
2015 5: 51 PM 2014 7: 57 AM 2010 3: 26 PM
2019 11:12 AM 2018 10:29 AM 2017 10:22 AM
2019 11: 20 AM 2015 9:23 AM 2014 8:16 AM
2010 2: 55 PM
2019 11:21 AM 2019 11:12 AM 2019 8: 25 PM
2018 3: 36 PM
2018 10: 30 AM 2018 8:03 AM 2018 11:43 AM
2019 11: 22 AM 2017 10: 30 AM 2016 9:05 AM
2019 11:23 AM 2018 10:25 AM 2018 8:15 AM
2015 9: 41 AM 2012 2: 35 PM 2010 3: 26 PM
2018 3 :40 PM 2018 10:22 AM 2014 7: 55 AM
2016 9:20 AM 2015 9:42 AM 2011 11:29 AM
2015 9: 46 AM 2013 10: 35 AM 2011 11: 31 AM
2019 11: 23 AM 2018 3:40 PM 2018 10: 26 AM
2017 10: 24 AM 2010 1:01 PM
2018 10:02 PM 2018 11: 30 AM 2017 7: 17 PM
2019 11:24 AM 2018 8: 23 AM 2017 10: 33 AM
2019 11:25 AM 2018 10:13 AM 2018 8:24 AM
2018 7: 59 AM 2015 9: 59 AM 2015 9:55 AM
2019 11:16 AM 2018 10:11 AM
CURRENT 163215 3922 201176 201686 201431 39392 509850 39481 9942 101796 8413409 8398860 8399103 8404004 8406896 8403783 101095 485954 8402525 8408574 68704 15013
Page 1 Alarm
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
HIGH WATER WARNING
DELIVERY NEEDED
MAX PRODUCT ALARM
LOW TEMP WARNING
130200 NOV 19, 2019 11:49 AM
FOODS CO. 384 2501 HALEY BAKERSFIELD CA, 661-873-9343
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION 1 DISP 1-2 DUAL NOV 19, 2019 10: 29 AM NOV 19, 2019 9: 5 8 AM NOV 19, 2019 9:58 AM DISP 3-4 DUAL
NOV 19, 2019 10: 30 AM NOV 19, 2019 10: 04 AM NOV 19, 2019 10: 04 AM DISP 5-6 DUAL NOV 19, 2019 10: 30 AM NOV 19, 2019 10: 08 AM NOV 19, 2019 10: 07 AM 4 DISP 7-8 DUAL NOV 19, 2019 10: 30 AM NOV 19, 2019 10: 18 AM NOV 19, 2019 10: 17 AM DISP 9-10 DUAL NOV 19, 2019 10: 29 AM NOV 19, 2019 10: 01 AM NOV 19, 2019 9:59 AM
6 DISP 11-12 DUAL NOV 19, 2019 10: 29 AM NOV 19, 2019 10: 11 AM ~~¥r1h-r211lule: 11 AM 7 NOV 19, 2019 10:30 AM NOV 19, 2019 10: 14 AM
~9\G~BI~~19 10: 13 AM 8 NOV 19, 2019 10: 29 AM NOV 19, 2019 9:38 AM NOV 19, 2019 9:38 AM
9 87 TURBINE BRINE NOV 19, 2019 10:29 AM NOV 19, 2019 9: 36 AM
NOV 27, 2018 1:48 PM
10 87 FILL NOV 19, 2019 10:30 AM NOV 19, 2019 9:36 AM NOV 19, 2019 9: 35 AM
11 87 FILL BRINE NOV 19, 2019 10: 29 AM NOV 19, 2019 9:34 AM
NOV 27, 2018 1:48 PM
12 87 ANNULAR NOV 19, 2019 10: 30 AM NOV 19, 2019 9:33 AM
~~\G~liI~~19 9: 33 AM 13 NOV 19, 2019 10:29 AM NOV 19, 2019 9:46 AM NOV 19, 2019 9:45 AM
14 91 TURBINE BRINE NOV 19, 2019 10: 29 AM NOV 19, 2019 9 :44 AM
NOV 27, 2018 1:48 PM
15 91 FILL NOV 19, 2019 10: 30 AM NOV 19, 2019 9:43 AM NOV 19, 2019 9:43 AM
16 91 FILL BRINE NOV 19, 2019 10: 30 AM NOV 19, 2019 9:42 AM
NOV 27, 2018 1:48 PM
17 91 DIESEL ANNULAR NOV 19, 2019 10: 30 AM NOV 19, 2019 9:41 AM
18 NOV 19, 2019 9:41 AM DIESEL TURBINE NOV 19, 2019 10: 30 AM NOV 19, 2019 9:51 AM NOV 19, 2019 9:51 AM
19 DIESEL TURBINE BRINE NOV 19, 2019 10: 30 AM NOV 19, 2019 9:50 AM
JUN 21, 2019 8:42 AM
20 DIESEL FILL NOV 19, 2019 10:30 AM ~gt l:§: ~m 9:49 AM 9:49 AM
21 DIESEL FILL BRINE NOV 19, 2019 10: 30 AM NOV 19, 2019 9:48 AM
NOV 27, 2018 1:48 PM
22 VENT SUMP NOV 19, 2019 10: 30 AM
Hi story
SEP 21, 2018 7: 59 AM
DEC 2~: 2011 11: 58 AM DEC 2010 1: 31 PM
NOV 28, 2017 10: 36 AM DEC 5' 2016 9: 36 AM DEC 3' 2015 9: 59 AM
NOV H: 2019 11:25 AM NOV 2019 11:18 AM NOV 19, 2019 11:17 AM
DEC 4, 2014 8:04 AM
NOV 27, 2018 10:11 AM
SEP 21, 2018 7: 59 AM NOV 28, 2017 10: 37 AM
DEC 27, 2010 1:31 PM
NOV 19, 2019 11:26 AM NOV 27, 2018 10:14 AM SEP 21, 2018 8: 28 AM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM LOW LIQUID ALARM SENSOR OUT ALARM
SENSOR OUT ALARM
LOW LIQUID ALARM SENSOR OUT ALARM
SENSOR OUT ALARM LOW LIQUID ALARM SENSOR OUT ALARM
SENSOR OUT ALARM LOW LIQUID ALARM FUEL ALARM
SENSOR OUT ALARM LOW LIQUID ALARM SENSOR OUT ALARM
SENSOR OUT ALARM LOW LIQUID ALARM SENSOR OUT ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM
~6~\~i8~5D At~;~M
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM LOW LIQUID ALARM HIGH LIQUID ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM
~g~ H: mi m~ ~
2 3 VENT SUMP BRINE ~g~ l:§: mi 1~: ~~ ~
JUN 21, 2019 8:42 AM
I30700 NOV 19, 2019 11: 49 AM
I31600 NOV 19, 2019 11:49 AM
FOODS CO. 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION 1 DISP 1-2 VFM DEC 15, 2010 3:59 PM DISP 3-4 VFM DISP 5-6 VFM DEC 15, 2010 3: 59 PM 4 DISP 7-8 VFM DEC 15, 2010 3: 26 PM DISP 9-10 VFM
6 mr11d~1eFM3
=
25 PM
mp lh-I~1eFM 3 = 2 6 PM 7
mlh-i~1~s 3 '26 PM
8 DEC 6, 2011 10: 34 AM DEC 15, 2010 3: 26 PM 9 87 PRODUCT ~g~ l:§: mi im ~ NOV 11, 2019 10: 21 PM 10 87 91 VAPOR ~g~ i:i• mi u~ ~
~9vv~~Um?o:29 AM 11 ~g~ H· mi u~ ~ NOV 27: 2018 10: 29 AM 12 91 PRODUCT NOV 19, 2019 9:46 AM NOV 27, 2018 10:22 AM
13
NOV 28, 2017 9:02 AM 91 VENT-CHASE ~g~ H· ~m u~ AM
AM NOV 27: 2018 10:22 AM 14 DIESEL PRODUCT ~g~ H· ~81§ u~ AM AM NOV 27: 2018 10:07 AM 15 PMC CANISTER :~~ H: ~m nr ~ ~~~ ~4, 2018 9:01 PM 16 17 DIESEL VENT-CHASE NOV 19, 2019 9:52 AM NOV 19, 2019 9:51 AM
NOV 27, 2018 10: 07 AM
I32300 NOV 19, 2019 11:49 AM
!34200 NOV 19, 2019 11:49 AM
I34700 NOV 19, 2019 11:49 AM
I34C00 NOV 19, 2019 11:49 AM
120700 NOV 19, 2019 11:49 AM
FOODS CO. 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
TANK LEAK TEST HISTORY
T l:Unleaded
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST PASSED EACH MONTH:
TEST START TIME
TANK LEAK TEST HISTORY
T 2:Premuim
LAST GROSS TEST PASSED:
NO TEST PASSED
HOURS
SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM COMMUNICATION ALARM
~6G~A~58W2L!kt,RM
VACUUM WARNING
~6G~A~58W2L!kt,RM
HIGH LIQUID ALARM
~6GM58~12L!kt,RM
HIGH LIQUID ALARM
NO VACUUM ALARM HIGH LIQUID ALARM HIGH LIQUID ALARM
HIGH LIQUID ALARM ND VACUUM ALARM HIGH LIQUID ALARM
~6GM58W2L!~t,RM
HIGH LIQUID ALARM
COMMUNICATION ALARM COMMUNICATION ALARM SENSOR FAULT ALARM
HIGH LIQUID ALARM NO VACUUM ALARM HIGH LIQUID ALARM
VOLUME % VOLUME TEST TYPE
Page 2
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST PASSED EACH MONTH:
TEST START TIME HOURS VOLUME % VOLUME TEST TYPE
TANK LEAK TEST HISTORY
T 3:Diesel
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST PASSED EACH MONTH:
TEST START TIME HOURS VOLUME % VOLUME TEST TYPE
131200 NOV 19, 2019 11:49 AM
!38200 NOV 19, 2019 11:49 AM
FOODS CO. 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1: 87 UNLEADED NOV 19, 2019 11:07 AM NOV 19, 2019 11: 00 AM NOV 19, 2019 10: 29 AM NOV 19, 2019 10:18 AM NOV 19, 2019 10: 17 AM NOV 19, 2019 10: 17 AM NOV 19, 2019 10: 16 AM
NOV H: m§ l:8:l:1 AM NOV AM NOV 19, 2019 10:13 AM
Q 2: 91 UNLEADED NOV 19, 2019 10: 49 AM NOV 19, 2019 10:49 AM NOV 19, 2019 10:29 AM
NOV 19, 2019 10: 18 AM NOV 19, 2019 10:17 AM
NOV 19, 2019 10: 17 AM NOV 19, 2019 10: 16 AM
NOV 19, 2019 10: 14 AM NOV 19, 2019 10: 13 AM NOV 19, 2019 10: 13 AM
Q 3 :DIESEL NOV 19, 2019 10:45 AM NOV 19, 2019 10:45 AM NOV 19, 2019 10:29 AM NOV 19, 2019 10:18 AM NOV 19, 2019 10: 17 AM
NOV 19, 2019 10:17 AM NOV 19, 2019 10:16 AM NOV 19, 2019 10:08 AM NOV 19, 2019 10:07 AM NOV 19, 2019 10: 06 AM
I38700 NOV 19, 2019 11:49 AM
I40200 NOV 19, 2019 11:49 AM
FOODS CO. 384 2501 HALEY
BAKERSFIELD CA. 661-873-9343
INPUT LOCATION 1 EMERGENCY SHUT OFF
NOV 15, 2019 11: 16 AM NOV 12, 2019 9:41 PM OCT 30, 2019 10: 56 PM NOV 15, 2019 11: 20 AM NOV 12, 2019 9: 5 3 PM OCT 30, 2019 11: 15 PM
120300 NOV 19, 2019 11:49 AM
FOODS CO. 384 2501 HALEY
BAKERSFIELD CA. 661-873-9343
TANK 1 Unleaded TEST STATUS: OFF
PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD PLLD PLLD PLLD
PLLD
SHUTDOWN ALARM SHUTDOWN ALARM SHUTDOWN ALARM SHUTDOWN ALARM
SHUTDOWN ALARM
EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT NORMAL EXTERN INPUT NORMAL
EXTERN INPUT NORMAL
LEAK DATA NOT AVAILABLE ON THIS TANK
Alarm History
TANK 2 Premuim TEST STATUS: OFF LEAK DATA NDT AVAILABLE ON THIS TANK
TANK 3 Diesel TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK
I25100 NOV 19, 2019 11:49 AM
FOODS CO. 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
CSLD TEST RESULTS TANK PRODUCT
200 FOODS CO. 384 2501 HALEY BAKERSFIELD CA, 661-873-9343
RESULT
NOV 19, 2019 11:49 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 2 3
210
FOODS CO. 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
TANK 1 Unleaded TEST STATUS: OFF
16649 6918 3196
LEAK DATA NOT AVAILABLE ON THIS TANK
TANK 2 Premuim TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK
TANK 3 Diesel TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK
I21300 NOV 19, 2019 11: 49 AM
FOODS CO, 384 2501 HALEY BAKERSFIELD CA, 661-873-9343
DELIVERY REPORT
T l:Unleaded
92.19 96. 81 42. 05
0.0 0.0 0.0
72 .3 71.8 77 .4
3133 983 7224
INCREASE DATE / TIME GALLONS TC GALLONS WATER TEMP DEG F HEIGHT
106. 4lND: NOV 19, 2019 11: 27 AM
lOlJ°/jART: NOV 19, 2019 11:20 AM
AMOUNT:
98 _82 END: NOV 19, 2019 3:13 AM
68 _2~TART: NOV 19, 2019 2:51 AM
AMOUNT:
96 _58 END: NOV 18, 2019 1:28 AM
57 _3~TART: NOV 18, 2019 1:00 AM
AMOUNT:
89 _49 END: NOV 16, 2019 5:22 PM
63.8HTART: NOV 16, 2019 4:59 PM
AMOUNT:
90 _05 END: NOV 15, 2019 7:27 PM
52.6ITART: NOV 15, 2019 7:08 PM
AMOUNT:
89 _88 END: NOV 14, 2019 4:01 PM
53,0~TART: NOV 14, 2019 3:36 PM
AMOUNT:
98_57 END: NOV 13, 2019 7:34 AM
63 , 3~TART: NOV 13, 2019 7: 13 AM
AMOUNT:
98_72 END: NOV 11, 2019 4:44 PM
59. 3~TART: NOV 11, 2019 4: 18 PM
AMOUNT:
84_94 END: NOV 10, 2019 3:04 PM
18818
18149
669
17748
11871
5877
17393
9499
7894
16167
10926
5241
16269
8456
7813
16238
8554
7684
17709
10809
6900
17732
9932
7800
15311
18678 o. 92
18017 0. 00
661
17595 0 .00
11759 0.00
5836
17238 0. 00
9398 0.00
7840
16004 0. 00
10819 0 .00
5185
16109 0.00
8359 0.00
7750
16056 0 .oo
8461 0.00
7595
17514 0.00
10672 o.oo
6842
17509 0.00
9812 0.00
7697
15131 0. 00
70.62
70.31
72. 26
73. 39
72.69
75 .16
74.32
73 .89
73. 99
76.43
75. 95
75. 52
75 .65
78.07
77 .95
77 .17
76. 72
Page 3
48 , 5§TART: NOV 10, 2019 2: 42 PM
AMOUNT:
82 _92 END: NOV 9, 2019 10:16 AM
58 _36TART: NOV 9, 2019 9:56 AM
AMOUNT:
T 2:Premuim INCREASE DATE / TIME HEIGHT
105_66END: NOV 19, 2019 11:30 AM
93 . 2~TART: NOV 19, 2019 11: 22 AM
AMOUNT:
98_ 50 END: NOV 19, 2019 3: 10 AM
59 _5~TART: NOV 19, 2019 2:53 AM
AMOUNT:
71. 64 END: NOV 18, 2019 1: 29 AM
59 _5~TART: NOV 18, 2019 1:21 AM
AMOUNT:
END: NOV 16, 2019 5 :16 PM 74. 38
62.2ITART: NOV 16, 2019 5:06 PM
AMOUNT:
73 _59 END: NOV 15, 2019 7:18 PM
61.4~TART: NOV 15, 2019 7:10 PM
AMOUNT:
77 , 56 END: NOV 14, 2019 3: 42 PM
65.2HTART: NOV 14, 2019 3:32 PM
AMOUNT:
84 _27 END: NOV 13, 2019 7:18 AM
60 _9~TART: NOV 13, 2019 7:07 AM
AMOUNT:
75 _60 END: NOV 11, 2019 4:27 PM
63 _3§TART: NOV 11, 2019 4:17 PM
AMOUNT:
75 _86 END: NOV 10, 2019 3:08 PM
63 _6~TART: NOV 10, 2019 2:58 PM
AMOUNT:
80 _49 END: NOV 9, 2019 10:13 AM
START: NOV 9, 2019 10: 03 AM 68.03 AMOUNT:
T 3:Diesel INCREASE DATE / TIME HEIGHT
99 .0l END: NOV 19, 2019 11:32 AM
85 , 86TART: NOV 19, 2019 11: 24 AM
AMOUNT:
48 _20 END: NOV 16, 2019 5:11 PM
29. 6HTART: NOV 16, 2019 4: 59 PM
AMOUNT:
53. 31 END: NOV 9, 2019 10:12 AM
35 _5~TART: NOV 9, 2019 9:57 AM
AMOUNT:
47 .02 END: NOV 6, 2019 3:16 AM
28 _2§TART: NOV 6, 2019 3:03 AM
AMOUNT:
35 _31 END: NOV 4, 2019 1:32 PM
34 _86TART: NOV 4, 2019 1:23 PM
AMOUNT:
35 _48 END: NOV 4, 2019 11:23 AM
34 _7~TART: NOV 4, 2019 11:16 AM
AMOUNT:
48 _50 END: OCT 31, 2019 2:59 PM
START: OCT 31, 2019 2:49 PM
Al arm Hi story
7587
7724
14918
9704
5214
7502 0.00
7629
14751 0.00
9589 0.00
5162
GALLONS TC GALLONS WATER
7445 7394 0.89
6677 6633 0. 00
768 761
7028
3995
3033
5007
3994
1013
5232
4219
1013
5168
4156
1012
5490
4478
1012
6018
4112
1906
5332
4319
1013
5353
4342
1011
5724
4708
6970 0.00
3951 0.00
3019
4952 0.00
3948 0,00
1004
5176 0.00
4173 0.00
1003
5110 0.00
4108 0.00
1002
5430 0.00
4429 0.00
1001
5953 0.00
4062 0,00
1891
5269 0.00
4268 0.00
1001
5291 o.oo
4292 0.00
999
5658 0.00
4652 0.00
1016 1006
75. 83
75. 93
76.92
TEMP DEG F
69. 75
69.27
71. 53
75. 55
75. 58
76.10
75.23
75. 60
75. 85
76.18
75.23
75.48
75. 23
77 .26
76.63
76.84
76. 34
76.54
76. 25
76.96
GALLONS TC GALLONS WATER TEMP DEG F
9413
8209
9316 0.72
8125 0. 73
1204 1191
3896
1898
1998
4494
2492
2002
3760
1765
1995
2467
2413
54
2484
2405
79
3931
1942
3866 0.00
1882 0.00
1984
4462 0.00
2473 0.00
1989
3734 0.00
1749 0.00
1985
2444 0.00
2391 0.00
53
2462 0.00
2383 0.00
79
3894 0.00
1923 0.00
82 .80
82. 58
77 .14
77 .68
75. 38
76.67
75. 28
79. 28
80.01
79.99
79. 73
79. 73
80,81
80.67
30,13 11: 23AM AMOUNT: 1989 1971 T 1 TANK unleaded PROBE OUT CLEAR 11-19-19 11: 22AM END: OCT 26, 2019 6: 57 PM 3835 3795 0.00 82.56 47 .67 T 1 TANK Unleaded OVERFILL ALARM CLEAR 11-19-19 11:21AM START: OCT 26, 2019 6: 45 PM 1840 1822 0.00 81. 73 29.08 T 1 TANK Unleaded PROBE OUT ALARM 11-19-19 AMOUNT: 1995 1973 11: 21AM
T 1 TANK Unleaded OVERFILL ALARM ALARM 11-19-19 END: OCT 22, 2019 4:36 PM 3700 3660 0.00 83, 99 11: 21AM 46, 50
START: 27, 62 OCT 22, 2019 4: 22 PM 1701 1686 T 3 TANK Diesel 0.00 79.41 11:19AM PROBE OUT CLEAR 11-19-19
AMOUNT: 1999 1974 T 3 TANK 11:18AM Diesel PROBE OUT ALARM 11-19-19
END: OCT 14, 2019 53 .28 3: 30 AM 4491 4455 0.00 77 .74 T 3 TANK Diesel 11:18AM PROBE OUT CLEAR 11-19-19
START: OCT 35. 55 14, 2019 3:18 AM 2492 2469 0.00 80.03 T 3 TANK Diesel SUDDEN LOSS ALARM CLEAR 11-19-19 11:18AM AMOUNT: 1999 1986 Q 3 OTHER DIESEL 11:17AM PLLD SHUTDOWN ALARM CLEAR 11-19-19
Q 3 OTHER DIESEL GROSS LINE FAIL CLEAR 11-19-19 11:17AM I31800 NOV 19, 2019 11:49 AM T 3 TANK Diesel PROBE OUT ALARM 11-19-19
v~ 11:17AM
T 1 TANK Unleaded PROBE OUT CLEAR 11-19-19 I37400 11:17AM NOV 19, 2019 11:49 AM Diesel T 3 TANK SUDDEN LOSS ALARM ALARM 11-19-19 FOODS CO, 384 11:16AM 2501 HALEY BAKERSFIELD CA, Q 2 OTHER 91 661-873-9343 11:15AM UNLEADED PLLD SHUTDOWN ALARM CLEAR 11-19-19
PRESSURE LINE LEAK TEST HISTORY Q 2 OTHER 11:15AM 91 UNLEADED GROSS LINE FAIL CLEAR 11-19-19
Q 1 OTHER 87 Q 1:87 UNLEADED 11:14AM UNLEADED PLLD SHUTDOWN ALARM CLEAR 11-19-19
LAST 3,0 PASS: NOV 19, 2019 11: 14 AM Q l OTHER 11:14AM 87 UNLEADED GROSS LINE FAIL CLEAR 11-19-19
FIRST O .10 PASS EACH MONTH: T 1 TANK Unleaded SUDDEN LOSS ALARM CLEAR 11-19-19 11:14AM FIRST O, 20 PASS EACH MONTH:
T 1 TANK unleaded PROBE OUT ALARM 11-19-19 Q 2: 91 UNLEADED 11:12AM
LAST 3.0 PASS: NOV 19, 2019 11: 15 AM T 1 TANK 11:12AM Unleaded SUDDEN LOSS ALARM ALARM 11-19-19
FIRST 0.10 PASS EACH MONTH: Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM ALARM 11-19-19 11:07AM FIRST 0.20 PASS EACH MONTH:
Q 1 OTHER 87 Q 3 :DIESEL 11:00AM UNLEADED GROSS LINE FAIL ALARM 11-19-19
LAST 3, 0 PASS: NOV 19, 2019 11:17 AM Q 2 OTHER 10:49AM 91 UNLEADED PLLD SHUTDOWN ALARM ALARM 11-19-19
Q 2 OTHER 91 UNLEADED GROSS LINE FAIL ALARM 11-19-19 FIRST 0.10 PASS EACH MONTH: 10:49AM
FIRST 0. 20 PASS EACH MONTH: Q 3 OTHER DIESEL 10:45AM PLLD SHUTDOWN ALARM ALARM 11-19-19
Q 3 OTHER DIESEL GROSS LINE FAIL ALARM 11-19-19 I38400 10:45AM NOV 19, 2019 11:49 AM
Q 2 OTHER 91 UNLEADED PLLD SHUTDOWN ALARM CLEAR 11-19-19 FOODS CO, 384 10:31AM 2501 HALEY BAKERSFIELD CA, Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM CLEAR 11-19-19 661-873-9343 10:31AM
PRESSURE LINE LEAK TEST HISTORY L 6 DISP PAN DISP 10:31AM 11-12 DUAL SENSOR OUT ALARM CLEAR 11-19-19
L 5 DISP PAN DISP Q 1: 87 UNLEADED 10:31AM 9-10 DUAL SENSOR OUT ALARM CLEAR 11-19-19
LAST 3, 0 PASS: NOV 19, 2019 11:14 AM Q 3 OTHER IO: 31AM DIESEL PLLD SHUTDOWN ALARM CLEAR 11-19-19
FIRST 0.10 PASS EACH MONTH: L 4 DISP PAN DISP 7-8 DUAL SENSOR OUT ALARM CLEAR 11-19-19 10:31AM Q 2: 91 UNLEADED
L 3 DISP PAN LAST 3.0 PASS: NOV 19, 2019 11: 15 AM 10:31AM DISP 5-6 DUAL SENSOR OUT ALARM CLEAR 11-19-19
L 2 DISP PAN DISP FIRST O .10 PASS EACH MONTH: 10:31AM 3-4 DUAL SENSOR OUT ALARM CLEAR 11-19-19
Q 3:DIESEL L15 PIPE 91 FILL SENSOR OUT ALARM CLEAR 11-19-19 10:31AM LAST 3,0 PASS: NOV 19, 2019 11: 17 AM L 8 STP SUMP 87 TURBINE SENSOR OUT ALARM CLEAR 11-19-19 10:31AM
FIRST O. 10 PASS EACH MONTH: L 7 DISP PAN DISP 10:31AM 13-14 DUAL SENSOR OUT ALARM CLEAR 11-19-19
I38900 L 1 DISP PAN DISP 1-2 DUAL SENSOR OUT ALARM CLEAR 11-19-19 NOV 19, 2019 11:49 AM 10:31AM
L20 PIPE DIESEL FILL SENSOR OUT ALARM CLEAR 11-19-19 10:31AM IlllOO NOV 19, 2019 11:49 AM Ll3 STP SUMP 91 TURBINE SENSOR OUT ALARM CLEAR 11-19-19
FOODS CO, 384 10:31AM
2501 HALEY Ll2 ANNULAR 87 ANNULAR SENSOR OUT ALARM CLEAR 11-19-19 BAKERSFIELD CA, 10:31AM 661-873-9343
LlO PIPE 87 FILL SENSOR OUT ALARM CLEAR 11-19-19 PRIORITY ALARM HISTORY 10:31AM ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 3 TANK Diesel PROBE OUT CLEAR 11-19-19 11: 26AM T 3 TANK Diesel OVERFILL ALARM CLEAR 11-19-19 I11200 11:25AM NOV 19, 2019 11:49 AM T 3 TANK Diesel PROBE OUT ALARM 11-19-19 11: 25AM FOODS CO, 384
Diesel 2501 HALEY T 3 TANK OVERFILL ALARM ALARM 11-19-19 BAKERSFIELD CA, 11: 25AM 661-873-9343
T 2 TANK Premuim PROBE OUT CLEAR 11-19-19 NON-PRIORITY ALARM HISTORY 11: 24AM ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE
T 2 TANK Prernuim TIME Diesel OVERFILL ALARM CLEAR 11-19-19 T 3 TANK LOW TEMP WARNING CLEAR 11-19-19 11: 23AM 11: 26AM
Premuim T 3 TANK Diesel LOW TEMP WARNING ALARM 11-19-19 T 2 TANK PROBE OUT ALARM 11-19-19 11:26AM 11: 23AM T 2 TANK Premuim LOW TEMP WARNING CLEAR 11-19-19
Premuim 11: 24AM T 2 TANK OVERFILL ALARM ALARM 11-19-19
Page 4 Alarm History
T 2 TANK 11: 24AM
T 1 TANK 11: 22AM
T 1 TANK 11:22AM
T 1 TANK 11: 22AM
T 1 TANK 11: 20AM
SYSTEM 6:22AM
SYSTEM 6: 22AM
SYSTEM 6:21AM
SYSTEM 6: 21AM
SYSTEM 6: 21AM
SYSTEM
6:21AM
SYSTEM 6:20AM
SYSTEM 6: 20AM
s 9 OTHER 10: 57PM
s 9 OTHER 10:21PM
hl2 OTHER
~wmHER 8:03AM
SYSTEM
3: OSPM
SYSTEM 3: OSPM SYSTEM
3 :OSPM
SYSTEM 3:04PM
OTHER 1:43PM
SYSTEM 5 :06AM
SYSTEM 5: 06AM
SYSTEM
5 :OSAM
SYSTEM 5: OSAM
OTHER
8:03AM
OTHER 8: 03AM
OTHER 8:02AM
OTHER
11: 22AM
OTHER 8:02AM
hl2 OTHER 8:00AM
hl2 OTHER 8:01AM
OTHER 12:27PM
OTHER
8:02AM SYSTEM 11:46AM
SYSTEM
11:46AM
SYSTEM 11:45AM
SYSTEM 11:45AM
hl2 OTHER 8:00AM
hl2 OTHER 8:04AM
OTHER 9:03AM
OTHER 8:03AM
h 7 OTHER 8:00AM
h 7 OTHER 8:03AM
SYSTEM 7:07AM
SYSTEM 7:07AM
111400
Premuim
Unleaded
unleaded
Unleaded
Unleaded
87 PRODUCT
87 PRODUCT
FP12: BLEND3
FP12: BLEND3
FP12: BLEND3
FP12: BLEND3
FP12: BLEND3
FP12: BLEND3
FP7: BLEND3
FP7: BLEND3
NOV 19, 2019 11: 50 AM
FOODS CO, 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
LOW TEMP WARNING ALARM 11-19-19
LOW TEMP WARNING CLEAR 11-19-19
LOW TEMP WARNING ALARM 11-19-19
HIGH PRODUCT ALARM CLEAR 11-19-19
HIGH PRODUCT ALARM ALARM 11-19-19
PRINTER ERROR CLEAR 11-12-19
PAPER OUT CLEAR 11-12-19
PRINTER ERROR ALARM 11-12-19
PAPER OUT ALARM 11-12-19
PRINTER ERROR CLEAR 11-12-19
PAPER OUT CLEAR 11-12-19
PAPER OUT ALARM 11-12-19
PRINTER ERROR ALARM 11-12-19
VACUUM WARNING
VACUUM WARNING
FLOW COLLECT WARN
FLOW COLLECT WARN
PRINTER ERROR
CLEAR 11-11-19
ALARM 11-11-19
CLEAR 10-10-19
ALARM 10-10-19
CLEAR 10-07-19
PAPER OUT CLEAR 10-07-19
PAPER OUT ALARM 10-07-19
PRINTER ERROR ALARM 10-07-19
ISD VAPOR LEAK WARN CLEAR 8-24-19
PRINTER ERROR CLEAR 8-22-19
PAPER OUT CLEAR 8-22-19
PAPER OUT ALARM 8-22-19
PRINTER ERROR ALARM 8-22-19
ISD VAPOR LEAK WARN ALARM 8-20-19
ISD VAPOR LEAK WARN CLEAR 8-14-19
ISD VAPOR LEAK WARN ALARM 8-07-19
ISD VAPOR LEAK WARN CLEAR 8-01-19
ISD VAPOR LEAK WARN ALARM 7-30-19
FLOW COLLECT WARN CLEAR 7-26-19
FLOW COLLECT WARN ALARM 7-25-19
ISD VAPOR LEAK WARN CLEAR 7-24-19
ISD VAPOR LEAK WARN ALARM 7-24-19
PRINTER ERROR CLEAR 7-10-19
PAPER OUT CLEAR 7-10-19
PRINTER ERROR ALARM 7-10-19
PAPER OUT ALARM 7-10-19
FLOW COLLECT WARN CLEAR 6-26-19
FLO\v COLLECT WARN ALARM 6-25-19
ISD SENSOR OUT WARN CLEAR 6-19-19
ISD SENSOR OUT WARN ALARM 6-19-19
FLOW COLLECT WARN
FLOW COLLECT WARN
PRINTER ERROR
PRINTER ERROR
CLEAR 6-07-19
ALARM 6-06-19
CLEAR 5-29-19
ALARM 5-29-19
Page S
CLEARED ALARMS REPORT
ID CATEGORY DESCRIPTION TIME T 3 TANK Diesel 11: 26AM T 3 TANK Diesel 11: 25AM T 2 TANK Premui m 11:24AM
T 2 TANK Premui m 11: 23AM
T 1 TANK Unleaded 11:22AM
T 1 TANK Unleaded 11: 21AM
T 3 TANK Diesel 11:19AM
T 3 TANK Diesel 11:18AM
T 3 TANK Diesel 11: 18AM
Q 3 OTHER DIESEL 11:17AM
Q 3 OTHER DIESEL 11: 17AM
T 1 TANK Unleaded 11:17AM
~171~I~ER
Q 2 OTHER
11:15AM
~1MmER
~1MmER
T 1 TANK 11:14AM
~oMmER
Q 1 OTHER 10:31AM
91 UNLEADED
91 UNLEADED
87 UNLEADED
87 UNLEADED
unleaded
91 UNLEADED
87 UNLEADED
L 6 DISP PAN DISP 11-12 DUAL 10:31AM
L 5 DISP PAN DISP 9-10 DUAL 10:31AM
~oMmER DIESEL
L 4 DISP PAN DISP 7-8 DUAL 10:31AM
L 3 DISP PAN DISP 5-6 DUAL 10:31AM
L 2 DISP PAN DISP 3-4 DUAL 10:31AM
Ll5 PIPE 10: 31AM 91 FILL
L 8 STP SUMP 87 TURBINE 10:31AM
L 7 DISP PAN DISP 13-14 DUAL 10: 31AM
L 1 DISP PAN DISP 1-2 DUAL 10:31AM
L20 PIPE 10:31AM DIESEL FILL
L13 STP SUMP 91 TURBINE 10:31AM
Ll2 ANNULAR 87 ANNULAR 10:31AM
LlO PIPE 87 FILL 10:31AM
T 3 TANK Diesel 11:26AM
T 2 TANK Premuim 11: 24AM
T 1 TANK Un 1 eaded 11:22AM
T 1 TANK unleaded 11: 22AM
SYSTEM 6: 22AM
SYSTEM 6: 22AM
SYSTEM 6:21AM
SYSTEM 6: 21AM
s 9 OTHER 10:57PM
hl2 OTHER 2: 35PM
SYSTEM 3 :05PM
SYSTEM 3:05PM
OTHER 1: 43PM
SYSTEM 5 :06AM
SYSTEM 5: 06AM
OTHER 8: 03AM
Alarm History
87 PRODUCT
FP12: BLEND3
ALARM TYPE STATE DATE
PROBE OUT CLEAR 11-19-19
OVERFILL ALARM CLEAR 11-19-19
PROBE OUT CLEAR 11-19-19
OVERFILL ALARM CLEAR 11-19-19
PROBE OUT CLEAR 11-19-19
OVERFILL ALARM CLEAR 11-19-19
PROBE OUT CLEAR 11-19-19
PROBE OUT CLEAR 11-19-19
SUDDEN LOSS ALARM CLEAR 11-19-19
PLLD SHUTDOWN ALARM CLEAR 11-19-19
GROSS LINE FAIL CLEAR 11-19-19
PROBE OUT CLEAR 11-19-19
PLLD SHUTDOWN ALARM CLEAR 11-19-19
GROSS LINE FAIL CLEAR 11-19-19
PLLD SHUTDOWN ALARM CLEAR 11-19-19
GROSS LINE FAIL CLEAR 11-19-19
SUDDEN LOSS ALARM CLEAR 11-19-19
PLLD SHUTDOWN ALARM CLEAR 11-19-19
PLLD SHUTDOWN ALARM CLEAR 11-19-19
SENSOR OUT ALARM CLEAR 11-19-19
SENSOR OUT ALARM CLEAR 11-19-19
PLLD SHUTDOWN ALARM CLEAR 11-19-19
SENSOR OUT ALARM CLEAR 11-19-19
SENSOR OUT ALARM CLEAR 11-19-19
SENSOR OUT ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM
CLEAR 11-19-19
CLEAR 11-19-19
CLEAR 11-19-19
CLEAR 11-19-19
SENSOR OUT ALARM CLEAR 11-19-19
SENSOR OUT ALARM CLEAR 11-19-19
SENSOR OUT ALARM CLEAR 11-19-19
SENSOR OUT ALARM CLEAR 11-19-19
SENSOR OUT ALARM CLEAR 11-19-19
LOW TEMP WARNING CLEAR 11-19-19
LOW TEMP WARNING CLEAR 11-19-19
LOW TEMP WARNING CLEAR 11-19-19
HIGH PRODUCT ALARM CLEAR 11-19-19
PRINTER ERROR CLEAR 11-12-19
PAPER OUT CLEAR 11-12-19
PRINTER ERROR
PAPER OUT
VACUUM WARNING
FLOW COLLECT WARN
PRINTER ERROR
PAPER OUT
CLEAR 11-12-19
CLEAR 11-12-19
CLEAR 11-11-19
CLEAR 10-10-19
CLEAR 10-07-19
CLEAR 10-07-19
ISD VAPOR LEAK WARN CLEAR 8-24-19
PRINTER ERROR
PAPER OUT
CLEAR
CLEAR
ISD VAPOR LEAK WARN CLEAR
8-22-19
8-22-19
8-14-19
OTHER 11: 22AM ISD VAPOR LEAK WARN CLEAR 8-01-19
hl2 OTHER 8:00AM FP12: BLEND3 FLOW COLLECT WARN CLEAR 7-26-19
OTHER
12: 27PM ISD VAPOR LEAK WARN CLEAR 7-24-19
SYSTEM 11:46AM PRINTER ERROR CLEAR 7-10-19
SYSTEM 11:46AM PAPER OUT CLEAR 7-10-19
hl2 OTHER 8:00AM FP12: BLEND3 FLOW COLLECT WARN CLEAR 6-26-19
OTHER ISD SENSOR OUT WARN 9:03AM CLEAR 6-19-19
h 7 OTHER
8:00AM FP7: BLEND3 FLOW COLLECT WARN CLEAR 6-07-19
SYSTEM 7:07AM PRINTER ERROR CLEAR 5-29-19
Il1300 NOV 19, 2019 11: so AM
FOODS CO. 384 2501 HALEY BAKERSFIELD CA. 661-873-9343
ACTIVE ALARMS REPORT
ID CATEGORY DESCRIPTION ALARM TYPE DATE TIME
Page 6 Al arm Hi story