HomeMy WebLinkAboutFMC 2019IMPACT VALVE LEAK DETECTOR MONITOR CERTIFICATION OVERFILL OPERABILITY SPILL BUCKET TEST 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 12/4/2019 BAKERSFIELD FIRE DEPARTMENT OFFICE OF ENVIRONMENTAL SERVICES INSPECTOR KRIS KARNS 1501 TRUXTUN AVE. BAKERSFIELD, CA 93301 Test Date: 10/23/2019 Order Number: 3448141 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 7-ELEVEN #22150 MARKET #2133 4012 WHITE LANE BAKERSFIELD, CA 93309 In an effort to keep all our record keeping and reporting requirements as current as possible, Tanknology kindly requests you notify Dawn Kohlmeyer in writing at dkohlmeyer@tanknology.com when your CUPA requires all records to be submitted electronically via the CERS database. Your assistance in this endeavor is greatly appreciated. Testing performed: Sincerely, Dawn Kohlmeyer Manager, Field Reporting LDT 5000 Field Test Apparatus Line Leak Detector Test Page 1 of 1 Work Order:3448141 Date:10/23/2019 Site Name / ID:7-ELEVEN #22150 / 22150 Address:MARKET #2133 4012 WHITE LANE City:BAKERSFIELD State:CA Zip:93309 Tank ID Product Product Line Tested From Existing/New Mechanical/Electronic Manufacturer/Model Serial No. Pump Operating Pressure (psi) Calibrated Leak (ml/min) Calibrated Leak (gph) Holding PSI *N/A for Electronic LD's Resiliency (ml) *N/A for Electronic LD's Metering PSI *N/A for Electronic LD's Opening Time (sec) *N/A for Electronic LD's Test Results T1 87 UNLEADED 1 3 Existing Mechanical Vaporless LD-2000 XXXXX 28.00 189.0 3.00 25.00 275.00 18 8 Pass T2 91 PREMIUM 1 3 Existing Mechanical Vaporless LD-2000 XXXXX 28.00 189.0 3.00 25.00 200.00 18 7 Pass T3 DSL Diesel 1 3 Existing Mechanical Vaporless LD-2000 XXXXX 32.00 189.0 3.00 30.00 500.00 18 8 Pass Technician Comments: Technician Name:Luis Navarro Certification #:147337 Technician Signature:Expire Date:11/27/2021 Environmental Compliance for Petroleum Systems © 2019 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Impact Valve Inspection Impact Valve Operational Inspection Work Order:3448141 Date:10/23/2019 Site Name/ID:7-ELEVEN #22150 Address:MARKET #2133 4012 WHITE LANE City:BAKERSFIELD State:CA Zip:93309 How Inspected: Line Test NFPA 30A PEI RP1200 Other Pump / Trip Dispenser Number Grade Secure Mount? Valve Lock?Pass/ Fail Comments 1/2 87 Pass Fail Not Tested 1/2 91 Pass Fail Not Tested 3/4 40 Pass Fail Not Tested 3/4 87 Pass Fail Not Tested 3/4 91 Pass Fail Not Tested 5/6 87 Pass Fail Not Tested 5/6 91 Pass Fail Not Tested 7/8 87 Pass Fail Not Tested 7/8 91 Pass Fail Not Tested 9/10 87 Pass Fail Not Tested 9/10 91 Pass Fail Not Tested 11/12 40 Pass Fail Not Tested 11/12 87 Pass Fail Not Tested 11/12 91 Pass Fail Not Tested Technician Comments: Technician Name:Luis Navarro Signature: Environmental Compliance for Petroleum Systems ©2019 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 1 of 6) This form must be used to document testing and servicing of underground storage tank (UST) monitoring equipment. A copy of this form must be provided to the UST owner or operator. The owner or operator must submit a copy of this form to the local agency regulating the USTs within 30 days of the date of the monitoring system certification. I. FACILITY INFORMATION CERS ID 10461655 Date of Monitoring System Certification 10/23/2019 Business Name (Same as Facility Name or DBA-Doing Business As.) 7-ELEVEN #22150 Building # Business Site Address MARKET #2133 4012 WHITE LANE City: BAKERSFIELD Zip: 93309 II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of Company Performing the Certification TANKNOLOGY INC. Phone # (800) 800-4633 Ext. Mailing Address 11000 N. Mopac Expressway #500, Austin, TX 78759 Name of UST Service Technician Performing the Certification (Print as shown on the ICC Certification.) Luis Navarro Contractor/Tank Tester License # Class A General Engineering 743160 ICC Certification # 8171123 ICC Certification Expiration Date 1/5/2021 Monitoring System Training and Certifications (List all applicable certifications.) Expiration Date Tanknology Certification Level III ATG Operability Training Certification Exam 147335 11/27/2021 Veeder Root VR Level 4 A28342 05/28/2020 Tanknology Certification Level III LDT-5000 FTA Certification Exam 147337 11/27/2021 III. RESULTS OF TESTING/SERVICING Indicate and attach the following reports if the monitoring equipment is capable of generating either. Monitoring System Set-up Alarm History Report Y N NA Was any monitoring equipment replaced? (If "Yes,"identify the specific devices replaced and list the manufacturer and model for all replacement parts in section IV below.) Was damage, debris, or liquid found inside any secondary containment systems? (If "Yes," describe what was found in section IV below.) Is all monitoring equipment operational per manufacturer's specifications? (If "No," describe why in section IV below.) IV. COMMENTS If directed to use this section, describe how and when the issues were or will be corrected. V. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING I hereby certify that the equipment identified in this document was inspected/serviced in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638 and all information contained herein is true and accurate. Attached to this certification is information (e.g., manufacturers' checklists, monitoring system set-up, alarm history report, etc.) necessary to verify that this information and the site plan showing the layout of UST system is complete and accurate. UST Service Technician Signature CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 2 of 6) VI. INVENTORY OF EQUIPMENT CERTIFIED A separate Monitoring System Certification Form must be prepared for each monitoring system control panel. Make of Monitoring System Control Panel Veeder Root Model of Monitoring System Control Panel TLS-350 Software Version Installed 335.00 Check the appropriate boxes to indicate specific equipment inspected/serviced. Monitoring Device Used Device Model # Tank ID: T1 87 Gasoline - Regular (By tank number, stored product, etc.) In-tank Gauging (SW Tank)846390-110 Annular Space or Vault Sensor 794380-303 VPH Sensor Product Piping Mechanical LLD LD-2000 Electronic LLD VPH Sensor (Piping) Sump Sensor 794380-208 VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor 794380-208 VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Monitoring Device Used Device Model # Tank ID: T2 91 Gasoline - Premium (By tank number, stored product, etc.) In-tank Gauging (SW Tank)846390-110 Annular Space or Vault Sensor 794380-303 VPH Sensor Product Piping Mechanical LLD LD-2000 Electronic LLD VPH Sensor (Piping) Sump Sensor 794380-208 VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor 794380-208 VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Monitoring Device Used Device Model # Tank ID: T3 DSL Diesel (By tank number, stored product, etc.) In-tank Gauging (SW Tank)846390-110 Annular Space or Vault Sensor 794380-303 VPH Sensor Product Piping Mechanical LLD LD-2000 Electronic LLD VPH Sensor (Piping) Sump Sensor 794380-208 VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor 794380-208 VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Monitoring Device Used Device Model # Tank ID: (By tank number, stored product, etc.) In-tank Gauging (SW Tank) Annular Space or Vault Sensor VPH Sensor Product Piping Mechanical LLD Electronic LLD VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 3 of 6) Monitoring Device Used Device Model #Monitoring Device Used Device Model # Vent/Transition Sump ID: Vent Sump Vent/Transition Sump ID: Sump Sensor 794380-208 Sump Sensor VPH Sensor VPH Sensor UDC ID: 1/2 Electronic Sensor 794380-208 Mechanical Device VPH Sensor UDC ID: 3/4 Electronic Sensor 794380-208 Mechanical Device VPH Sensor UDC ID: 5/6 Electronic Sensor 794380-208 Mechanical Device VPH Sensor UDC ID: 7/8 Electronic Sensor 794380-208 Mechanical Device VPH Sensor UDC ID: 9/10 Electronic Sensor 794380-208 Mechanical Device VPH Sensor UDC ID: 11/12 Electronic Sensor 794380-208 Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor Other Monitored Component ID: Other Monitored Component ID: Other(Specify in section VII) Other(Specify in section VII) Other Monitored Component ID: Other Monitored Component ID: Other(Specify in section VII) Other(Specify in section VII) Other Monitored Component ID: Other Monitored Component ID: Other(Specify in section VII) Other(Specify in section VII) Include information for every underground storage tank component monitored by this monitoring system control panel. If the monitoring system control panel monitors more components than this form accommodates, additoinal copies of these pages may be attached. VII. COMMENTS Use this section to provide any additional comments about the inventory of the equipment certified. CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 4 of 6) VIII. MONITORING SYSTEM AND PROGRAMMING This section must be completed if a monitoring panel is used to perform leak detection monitoring.Y N NA Are the visual and audible alarms operational? Were all sensors visually inspected for kinks and breaks in the cables and for residual buildup to ensure that floats move freely, functionally tested, and confirmed operational? Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Was monitoring system set-up reviewed to ensure proper settings? Was the monitoring panel's backup battery visually inspected, functionally tested, and confirmed operational? Does the flow of fuel stop at the dispenser if a leak is detected in the under-dispenser containment? Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? Does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak? Which sensors initiate positive shut down? (Check all that apply.) Sump Under-dispenser containment If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? For any answer of "N" above, describe in section IX how and when these deficiencies were or will be corrected. IX. COMMENTS Use this section to provide any additional comments about the inventory of the equipment certified. X. IN-TANK GAUGING TESTING Check this box if tank gauging is used only for inventory control. (Do not complete this section.) Check this box if NO tank gauging equipment is installed. (Do not complete this section.) This section must be completed if in-tank gauging is used to perform leak detection monitoring. Y N NA Has all input wiring been inspected for kinks and breaks in the cables and for proper entry and termination, including testing for ground faults? Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? Was accuracy of system's product level readings tested? Was accuracy of system's water level readings tested? Were all probes reinstalled properly? Were all items on the equipment manufacturer's maintenance checklist completed? For any answer of "N" above, describe in section XI how and when these deficiencies were or will be corrected. XI. COMMENTS Use this section to provide any additional comments about the inventory of the equipment certified. Y = Yes, N = No, NA = Not Applicable UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 5 of 6) XVI. LINE LEAK DETECTOR TESTING Check this box if line leak detectors (LLD) are NOT installed. (Do not complete this section.) This section must be completed if LLDs are installed.Y N NA Was a leak simulated to verify LLD performance? (Check all that apply.) Simulated leak rate verified: 3 GPH 1.1 GPH 0.2 GPH Was the testing apparatus properly calibrated? For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? For mechanical LLDs, does the LLD restrict the flow through the pipe when a leak is detected? For electronic LLDs, does the turbine automatically shut off when a leak is detected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? Were all items on the equipment manufacturer's maintenance checklist completed? Were all LLDs confirmed operational within regulatory requirements? For any answer of "N" above, describe in section XIII how and when these issues were or will be corrected. XIII. COMMENTS XIV. VACUUM / PRESSURE/ HYDROSTATIC MONITORING EQUIPMENT TESTING Check this box if VPH monitoring is NOT used. (Do not complete this section.) This section must be completed if VPH monitoring is used to perform leak detection monitoring. System Type (Mark all that apply.) Vacuum Pressure Hydrostatic Sensor ID Component(s) Monitored by this Sensor Sensor Functionality Test Interstitial Communication Test S:9 VPR-UDC's Pass Fail Pass Fail S:10 87 Sumps Pass Fail Pass Fail S:11 87 Products Pass Fail Pass Fail S:12 Vent Box Pass Fail Pass Fail S:13 91 Sumps Pass Fail Pass Fail S:14 91 Product Pass Fail Pass Fail S:15 DSL Vent Pass Fail Pass Fail S:16 DSL Sumps Pass Fail Pass Fail S:17 DSL Product Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail How was interstitial communication verified? Simulated leak at far ends of the interstitial space. Other (Describe the method in section XV below.) Visual Inspection Gauge Was the vacuum or pressure restored to operating levels in all interstitial spaces? Yes No (Describe the reason in section XV below.) For any answer of "N" above, describe in section XIII how and when these issues were or will be corrected. XV. COMMENTS GPH = Gallons per hour, Y = Yes, N = No, NA = Not applicable, VPH = Vacuum/Pressure/Hydrostatic, ID = Identification UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 6 of 6) XVI. MONITORING SITE PLAN Date site map was prepared: 10/23/2019 If you already have a site plan that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and piping and clearly identify locations of the following equipment, if installed: 1) monitoring system control panels; 2) in-tank liquid level probes (if used for leak detection); 3) devices monitoring tank annular spaces or vault; 4) devices monitoring product piping; 5) devices monitoring fill piping; 6) devices monitoring vent piping; 7) devices monitoring vapor recovery piping; 8) devices monitoring vent/transition sumps; 9) devices monitoring under-dispenser containment; 10) line leak detectors; and 11) devices monitoring any other secondary containment areas. SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 7-ELEVEN #22150 Date of Testing: 10/23/2019 Facility Address: MARKET #2133 4012 WHITE LANE, BAKERSFIELD, CA 93309 Facility Contact: MANAGER Phone: 661-834-8565 Date Local Agency Was Notified of Testing: 10/7/2019 Name of Local Agency Inspector (if present during testing): Kris Karns , BFD 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY INC. Technician Conducting Test: Luis Navarro Credentials1: CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s): 743160 / 8171123 3. SPILL BUCKET TESTING INFORMATION Test Method Used By: Hydrostatic Vacuum Other Test Equipment Used: LAKE TEST Equipment Resolution: 0.0625 in. Identify Spill Bucket (By Tank Number, Stored Product, etc.) Bucket Installation Type: Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test Test Start Time (TI): Initial Reading (RI): Test End Time(TF): Final Reading (RF): Test Duration(TF–TI): Change in Reading (RF–RI) : Pass/Fail Threshold or Criteria: Test Result: Spill Box # Tank T1 87 UNLEADED - Fill 1 - Direct - Below Grade in containment sump Direct Bury Contained in Sump 12.00 14.50 15 min 10:00:00 14.00 in. H20 11:00:00 14.00 in. H20 1 hr 0.00 in. H20 +/- 0.00 Pass Spill Box # Tank T2 91 PREMIUM - Fill 1 - Direct - Below Grade in containment sump Direct Bury Contained in Sump 12.00 14.50 15 min 10:00:00 14.00 in. H20 11:00:00 14.00 in. H20 1 hr 0.00 in. H20 +/- 0.00 Pass Spill Box # Tank T3 DSL Diesel - Fill 1 - Direct - Grade level in containment sump Direct Bury Contained in Sump 12.00 14.50 15 min 10:00:00 14.00 11:00:00 14.00 1 hr 0.00 +/- 0.00 Pass Spill Box # Direct Bury Contained in Sump min +/- Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature:Date:10/23/2019 1State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. WO: 3448141 UNDERGROUND STORAGE TANK SPILL CONTAINER TESTING REPORT FORM (Page 1 of 1) Type of Action Installation Test Repair Test 12 Month Test I. FACILITY INFORMATION CERS ID 10461655 Date of Spill Container Test: 10/23/2019 Business Name (Same as Facility Name or DBA-Doing Business As.) 7-ELEVEN #22150 Business Site Address MARKET #2133 4012 WHITE LANE City: BAKERSFIELD Zip: 93309 II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.) Luis Navarro Phone # (800) 800-4633 Contractor/Tank Tester License # Class A General Engineering 743160 ICC Certification # 8171123 ICC Certification Expiration Date 1/5/2021 Spill Container Testing Training and Certifications (List applicable certifications.) OPW - EVR Phase 1 101183 07/07/2020 III. SPILL CONTAINER TESTING INFORMATION Test Method Used: Manufacturer Guidelines: (Specify) Industry Code or Engineering Standard: (Specify) PEI RP 1200 Engineered Method: (Specify) Attach the testing procedures and all documentation required to determine the results. # of Attached Pages 2 Tank ID: (By tank number, stored product, etc.) Spill Container Manufacturer: Method of Cathodic Protection Inside Diameter of Spill Container: (Inches) Depth of Spill Container: (Inches) Does the spill container have a 5 gallon capacity? Method to Keep Spill Container Empty IV. Spill Container Test Results Fill T1 87 UNLEADED OPW Non-Metallic Isolation Other (Specify in section V) 12 14.5 Yes No Drain Valve Onsite Pump Other (Specify in section V) Fill T2 91 PREMIUM OPW Non-Metallic Isolation Other (Specify in section V) 12 14.5 Yes No Drain Valve Onsite Pump Other (Specify in section V) Fill T3 DSL Diesel OPW Non-Metallic Isolation Other (Specify in section V) 12 14.5 Yes No Drain Valve Onsite Pump Other (Specify in section V) Non-Metallic Isolation Other (Specify in section V) Yes No Drain Valve Onsite Pump Other (Specify in section V) SUMMARY OF TESTING RESULTS Pass Fail Pass Fail Pass Fail Pass Fail V. COMMENTS All items marked failed above must be explained in this section. Any additional comments may also be provided here. VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1 and all the information contained herein is accurate. UST Service Technician Signature If the facility has more components than this form accommodates, additional copies of this page may be attached. CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Page 1 of 1) Type of Action Installation Test Repair Test 36 Month Test I. FACILITY INFORMATION CERS ID 10461655 Date of Overfill Prevention Equipment Inspection: 10/23/2019 Business Name (Same as Facility Name or DBA-Doing Business As.) 7-ELEVEN #22150 Business Site Address MARKET #2133 4012 WHITE LANE City: BAKERSFIELD Zip: 93309 II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.) Luis Navarro Phone # (800) 800-4633 Contractor/Tank Tester License # Class A General Engineering 743160 ICC Certification # 8171123 ICC Certification Expiration Date 1/5/2021 Spill Container Testing Training and Certifications (List applicable certifications.) Veeder Root - VR Level 4 A28342 05/28/2020 III. OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION Test Method Used: Manufacturer Guidelines (Specify) Veeder Root Industry Code or Engineering Standard (Specify) PEI RP 1200 Engineered Method (Specify) Attach the testing procedures and all documentation required to determine the results. # of Attached Pages: 1 Tank ID: (By tank number, stored product, etc.) What is the tank inside diameter? (Inches) Is the fill piping secondarily contained? Is the vent piping secondarily contained? Overfill Prevention Equipment Manufacturer(s) What is the overfill prevention equipment response when activated? (Check all that apply.) Are flow restrictors installed on vent piping? At what level in the tank is the overfill prevention set to activate? (Inches from bottom of tank.) What is the percent capacity of the tank at which the overfill prevention equipment activates? Is the overfill prevention in proper operating condition to respond when the substance reaches the appropriate level? IV. Overfill Prevention Inspection Results T1 87 118.38 in. Yes No Yes No Veeder Root other Shuts Off Flow Restrict Flow A/V Alarm Yes No 99.125 89.980 Yes No (Specify in section V) T2 91 118.37 in. Yes No Yes No Veeder Root other Shuts Off Flow Restrict Flow A/V Alarm Yes No 99.750 89.912 Yes No (Specify in section V) T3 DSL 118.38 in. Yes No Yes No Veeder Root other Shuts Off Flow Restrict Flow A/V Alarm Yes No 98.625 89.969 Yes No (Specify in section V) Yes No Yes No Shuts Off Flow Restrict Flow A/V Alarm Yes No Yes No (Specify in section V) SUMMARY OF TESTING RESULTS Pass Fail Pass Fail Pass Fail Pass Fail V. COMMENTS All items marked failed above must be explained in this section. Any additional comments may also be provided here. VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1 and all the information contained herein is accurate. UST Service Technician Signature If the facility has more components than this form accommodates, additional copies of this page may be attached. CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:3448141 Site ID / Name:22150 / 7-ELEVEN #22150 Address:MARKET #2133 4012 WHITE LANE City:BAKERSFIELD State:CA Zip:93309 W.O.# SC1-3448141 Cust Ref#: 2219569 Responses Received: I10200 OCT 23, 2019 3:33 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 163767 163537 2 INTERSTITIAL BD 202157 202028 3 INTERSTITIAL BD 201906 201660 4 7SMARTSENSOR BD 507535 508546 5 8SMARTSENSOR BD 39370 39360 6 8SMARTSENSOR BD 39436 39427 7 UNUSED 9630658 9471762 8 UNUSED 9604492 9431548 9 RELAY BOARD 14912 14925 10 STP SENSE BOARD 33066 33082 11 UNUSED 9612236 9436743 12 UNUSED 9593361 9419408 13 UNUSED 9593471 9438466 14 UNUSED 9594938 9451341 15 UNUSED 9587712 9442441 16 UNUSED 9588544 9419076 COMM 1 ELEC DISP INT. 101074 101062 COMM 2 SERIAL SAT BD 9598244 480532 COMM 3 UNUSED 9587668 9429831 COMM 4 UNUSED 9586924 9421285 COMM 5 RS485 SERIAL BD 68405 68440 COMM 6 MT COMM BOARD 407925 408280 I90200 OCT 23, 2019 3:33 PM SOFTWARE REVISION LEVEL VERSION 335.00 SOFTWARE+ACM- 346335-100-A CREATED - 18.08.27.10.22 S-MODULE+ACM- 330160-104-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR ISD/APM I11100 OCT 23, 2019 3:33 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME s 9 OTHER VPR-UDCS NO VACUUM ALARM CLEAR 10-23-19 12:20PM s10 OTHER 87 SUMPS NO VACUUM ALARM CLEAR 10-23-19 12:19PM s10 OTHER 87 SUMPS NO VACUUM ALARM ALARM 10-23-19 12:17PM s 9 OTHER VPR-UDCS NO VACUUM ALARM ALARM 10-23-19 12:17PM s13 OTHER 91 SUMPS NO VACUUM ALARM CLEAR 10-23-19 12:16PM s13 OTHER 91 SUMPS NO VACUUM ALARM ALARM 10-23-19 12:14PM s17 OTHER DSL PRODUCT HIGH LIQUID ALARM CLEAR 10-23-19 11:47AM s16 OTHER DSL SUMPS HIGH LIQUID ALARM CLEAR 10-23-19 11:47AM s15 OTHER DSL VENT HIGH LIQUID ALARM CLEAR 10-23-19 11:47AM s15 OTHER DSL VENT HIGH LIQUID ALARM ALARM 10-23-19 11:46AM s17 OTHER DSL PRODUCT HIGH LIQUID ALARM ALARM 10-23-19 11:46AM s16 OTHER DSL SUMPS HIGH LIQUID ALARM ALARM 10-23-19 11:46AM s15 OTHER DSL VENT NO VACUUM ALARM CLEAR 10-23-19 11:46AM s15 OTHER DSL VENT NO VACUUM ALARM ALARM 10-23-19 11:46AM s17 OTHER DSL PRODUCT NO VACUUM ALARM CLEAR 10-23-19 11:46AM s17 OTHER DSL PRODUCT NO VACUUM ALARM ALARM 10-23-19 11:45AM s14 OTHER 91 PRODUCT HIGH LIQUID ALARM CLEAR 10-23-19 11:45AM s13 OTHER 91 SUMPS HIGH LIQUID ALARM CLEAR 10-23-19 11:45AM s13 OTHER 91 SUMPS HIGH LIQUID ALARM ALARM 10-23-19 11:44AM s14 OTHER 91 PRODUCT HIGH LIQUID ALARM ALARM 10-23-19 11:44AM s14 OTHER 91 PRODUCT NO VACUUM ALARM CLEAR 10-23-19 11:44AM s14 OTHER 91 PRODUCT NO VACUUM ALARM ALARM 10-23-19 11:44AM s12 OTHER VENT BOX NO VACUUM ALARM CLEAR 10-23-19 11:43AM s12 OTHER VENT BOX NO VACUUM ALARM ALARM 10-23-19 11:43AM s11 OTHER 87 PRODUCT HIGH LIQUID ALARM CLEAR 10-23-19 11:42AM s10 OTHER 87 SUMPS HIGH LIQUID ALARM CLEAR 10-23-19 11:42AM s 9 OTHER VPR-UDCS HIGH LIQUID ALARM CLEAR 10-23-19 11:42AM s11 OTHER 87 PRODUCT HIGH LIQUID ALARM ALARM 10-23-19 11:42AM s10 OTHER 87 SUMPS HIGH LIQUID ALARM ALARM 10-23-19 11:42AM s 9 OTHER VPR-UDCS HIGH LIQUID ALARM ALARM 10-23-19 11:42AM s11 OTHER 87 PRODUCT NO VACUUM ALARM CLEAR 10-23-19 11:41AM s11 OTHER 87 PRODUCT NO VACUUM ALARM ALARM 10-23-19 11:41AM T 1 TANK 87 MAX PRODUCT ALARM CLEAR 10-23-19 11:38AM T 1 TANK 87 PROBE OUT CLEAR 10-23-19 11:37AM T 1 TANK 87 OVERFILL ALARM CLEAR 10-23-19 11:37AM T 1 TANK 87 PROBE OUT ALARM 10-23-19 11:37AM T 1 TANK 87 MAX PRODUCT ALARM ALARM 10-23-19 11:35AM T 1 TANK 87 OVERFILL ALARM ALARM 10-23-19 11:35AM T 3 TANK DSL MAX PRODUCT ALARM CLEAR 10-23-19 11:33AM T 3 TANK DSL PROBE OUT CLEAR 10-23-19 11:33AM T 3 TANK DSL PROBE OUT ALARM 10-23-19 11:32AM T 3 TANK DSL OVERFILL ALARM CLEAR 10-23-19 11:32AM T 3 TANK DSL MAX PRODUCT ALARM ALARM 10-23-19 11:30AM T 3 TANK DSL OVERFILL ALARM ALARM 10-23-19 11:30AM T 2 TANK 91 MAX PRODUCT ALARM CLEAR 10-23-19 11:27AM T 2 TANK 91 PROBE OUT CLEAR 10-23-19 11:27AM T 2 TANK 91 PROBE OUT ALARM 10-23-19 11:23AM T 2 TANK 91 OVERFILL ALARM CLEAR 10-23-19 11:21AM T 2 TANK 91 MAX PRODUCT ALARM ALARM 10-23-19 11:19AM T 2 TANK 91 OVERFILL ALARM ALARM 10-23-19 11:19AM I11200 OCT 23, 2019 3:34 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME s 9 OTHER VPR-UDCS VACUUM WARNING ALARM 10-23-19 12:20PM s 9 OTHER VPR-UDCS VACUUM WARNING CLEAR 10-23-19 12:17PM s14 OTHER 91 PRODUCT VACUUM WARNING ALARM 10-23-19 11:44AM s14 OTHER 91 PRODUCT VACUUM WARNING CLEAR 10-23-19 11:44AM T 1 TANK 87 LOW TEMP WARNING CLEAR 10-23-19 11:39AM T 1 TANK 87 LOW TEMP WARNING ALARM 10-23-19 11:38AM T 1 TANK 87 HIGH PRODUCT ALARM CLEAR 10-23-19 11:38AM T 1 TANK 87 HIGH PRODUCT ALARM ALARM 10-23-19 11:35AM T 3 TANK DSL LOW TEMP WARNING CLEAR 10-23-19 11:33AM T 3 TANK DSL LOW TEMP WARNING ALARM 10-23-19 11:33AM T 3 TANK DSL HIGH PRODUCT ALARM CLEAR 10-23-19 11:33AM T 3 TANK DSL HIGH PRODUCT ALARM ALARM 10-23-19 11:30AM T 2 TANK 91 HIGH PRODUCT ALARM CLEAR 10-23-19 11:27AM T 2 TANK 91 HIGH PRODUCT ALARM ALARM 10-23-19 11:19AM T 2 TANK 91 HIGH WATER WARNING CLEAR 10-23-19 11:13AM T 2 TANK 91 HIGH WATER WARNING ALARM 10-23-19 11:07AM SYSTEM PRINTER ERROR CLEAR 10-23-19 11:06AM SYSTEM PRINTER ERROR ALARM 10-23-19 11:06AM SYSTEM PRINTER ERROR CLEAR 10-23-19 11:06AM SYSTEM PAPER OUT CLEAR 10-23-19 11:06AM SYSTEM PRINTER ERROR ALARM 10-23-19 11:05AM SYSTEM PAPER OUT ALARM 10-23-19 11:05AM T 3 TANK DSL HIGH WATER WARNING CLEAR 10-23-19 11:02AM T 2 TANK 91 HIGH WATER WARNING CLEAR 10-23-19 10:42AM T 1 TANK 87 HIGH WATER WARNING CLEAR 10-23-19 10:40AM T 3 TANK DSL DELIVERY NEEDED CLEAR 10-23-19 10:37AM T 1 TANK 87 DELIVERY NEEDED CLEAR 10-23-19 10:36AM T 2 TANK 91 HIGH WATER WARNING ALARM 10-23-19 10:29AM T 2 TANK 91 DELIVERY NEEDED CLEAR 10-23-19 10:26AM T 2 TANK 91 DELIVERY NEEDED ALARM 10-23-19 10:26AM T 1 TANK 87 HIGH WATER WARNING ALARM 10-23-19 10:25AM T 1 TANK 87 DELIVERY NEEDED ALARM 10-23-19 10:21AM T 3 TANK DSL HIGH WATER WARNING ALARM 10-23-19 10:20AM T 3 TANK DSL INVALID FUEL LEVEL CLEAR 10-23-19 10:16AM T 3 TANK DSL DELIVERY NEEDED ALARM 10-23-19 10:16AM T 3 TANK DSL INVALID FUEL LEVEL ALARM 10-23-19 10:16AM s13 OTHER 91 SUMPS VACUUM WARNING CLEAR 10-23-19 9:46AM s13 OTHER 91 SUMPS VACUUM WARNING ALARM 10-23-19 9:36AM s13 OTHER 91 SUMPS VACUUM WARNING CLEAR 10-23-19 9:28AM s13 OTHER 91 SUMPS VACUUM WARNING ALARM 10-23-19 9:20AM s14 OTHER 91 PRODUCT VACUUM WARNING ALARM 10-23-19 8:50AM s14 OTHER 91 PRODUCT VACUUM WARNING CLEAR 10-23-19 8:48AM s14 OTHER 91 PRODUCT VACUUM WARNING ALARM 10-23-19 8:34AM s14 OTHER 91 PRODUCT VACUUM WARNING CLEAR 10-23-19 8:34AM s10 OTHER 87 SUMPS VACUUM WARNING CLEAR 10-22-19 12:37PM s11 OTHER 87 PRODUCT VACUUM WARNING CLEAR 10-22-19 12:29PM s12 OTHER VENT BOX VACUUM WARNING CLEAR 10-22-19 11:17AM s17 OTHER DSL PRODUCT VACUUM WARNING CLEAR 10-22-19 8:59AM s17 OTHER DSL PRODUCT VACUUM WARNING ALARM 10-22-19 8:33AM s16 OTHER DSL SUMPS VACUUM WARNING CLEAR 10-22-19 8:15AM I20600 OCT 23, 2019 3:34 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 TANK ALARM HISTORY TANK 1 87 HIGH WATER ALARM OCT 23, 2019 10:25 AM OVERFILL ALARM OCT 23, 2019 11:35 AM LOW PRODUCT ALARM OCT 23, 2019 10:21 AM OCT 16, 2019 10:21 AM HIGH PRODUCT ALARM OCT 23, 2019 11:35 AM PROBE OUT OCT 23, 2019 11:37 AM OCT 23, 2019 10:19 AM OCT 18, 2019 8:17 AM HIGH WATER WARNING OCT 23, 2019 10:25 AM DELIVERY NEEDED OCT 23, 2019 10:21 AM OCT 16, 2019 10:21 AM MAX PRODUCT ALARM OCT 23, 2019 11:35 AM LOW TEMP WARNING OCT 23, 2019 11:38 AM TANK 2 91 SETUP DATA WARNING OCT 16, 2019 10:21 AM HIGH WATER ALARM OCT 23, 2019 10:29 AM OVERFILL ALARM OCT 23, 2019 11:19 AM OCT 23, 2019 11:08 AM LOW PRODUCT ALARM OCT 16, 2019 10:51 AM HIGH PRODUCT ALARM OCT 23, 2019 11:19 AM OCT 16, 2019 10:21 AM PROBE OUT OCT 23, 2019 11:23 AM OCT 23, 2019 10:23 AM HIGH WATER WARNING OCT 23, 2019 11:07 AM OCT 23, 2019 10:29 AM DELIVERY NEEDED OCT 23, 2019 10:26 AM OCT 16, 2019 10:51 AM MAX PRODUCT ALARM OCT 23, 2019 11:19 AM TANK 3 DSL SETUP DATA WARNING OCT 16, 2019 10:21 AM HIGH WATER ALARM OCT 23, 2019 10:20 AM OVERFILL ALARM OCT 23, 2019 11:30 AM LOW PRODUCT ALARM OCT 23, 2019 10:16 AM OCT 16, 2019 11:05 AM HIGH PRODUCT ALARM OCT 23, 2019 11:30 AM OCT 16, 2019 10:21 AM INVALID FUEL LEVEL OCT 23, 2019 10:16 AM OCT 16, 2019 10:09 AM PROBE OUT OCT 23, 2019 11:32 AM OCT 23, 2019 10:13 AM HIGH WATER WARNING OCT 23, 2019 10:20 AM DELIVERY NEEDED OCT 23, 2019 10:16 AM OCT 16, 2019 11:05 AM MAX PRODUCT ALARM OCT 23, 2019 11:30 AM LOW TEMP WARNING OCT 23, 2019 11:33 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 OCT 23, 2019 3:34 PM I30200 OCT 23, 2019 3:34 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 ANNULAR OCT 23, 2019 10:00 AM SENSOR OUT ALARM OCT 23, 2019 9:31 AM LOW LIQUID ALARM OCT 23, 2019 9:31 AM HIGH LIQUID ALARM 2 87 STP OCT 23, 2019 10:00 AM SENSOR OUT ALARM OCT 23, 2019 9:25 AM FUEL ALARM SEP 2, 2018 1:50 AM SETUP DATA WARNING 3 87 FILL OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:29 AM FUEL ALARM SEP 2, 2018 1:50 AM SETUP DATA WARNING 4 DSL-91 ANNULAR OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:37 AM LOW LIQUID ALARM OCT 23, 2019 9:37 AM HIGH LIQUID ALARM 5 91 STP OCT 23, 2019 10:00 AM SENSOR OUT ALARM OCT 23, 2019 9:37 AM FUEL ALARM SEP 2, 2018 1:50 AM SETUP DATA WARNING 6 91 FILL OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:38 AM FUEL ALARM SEP 2, 2018 1:50 AM SETUP DATA WARNING 7 DSL STP OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:31 AM FUEL ALARM SEP 2, 2018 1:50 AM SETUP DATA WARNING 8 DSL FILL OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:32 AM FUEL ALARM SEP 2, 2018 1:50 AM SETUP DATA WARNING 9 UDC 1-2 OCT 23, 2019 10:03 AM SENSOR OUT ALARM OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:39 AM FUEL ALARM 10 UDC 3-4 OCT 23, 2019 10:03 AM SENSOR OUT ALARM OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:46 AM FUEL ALARM 11 UDC 5-6 OCT 23, 2019 10:03 AM SENSOR OUT ALARM OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:41 AM FUEL ALARM 12 UDC 7-8 OCT 23, 2019 10:03 AM SENSOR OUT ALARM OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:42 AM FUEL ALARM 13 UDC 9-10 OCT 23, 2019 10:00 AM SENSOR OUT ALARM OCT 23, 2019 9:43 AM FUEL ALARM SEP 2, 2018 1:50 AM SETUP DATA WARNING 14 UDC 11-12 OCT 23, 2019 10:03 AM SENSOR OUT ALARM OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:45 AM FUEL ALARM 15 VENT SUMP OCT 23, 2019 10:01 AM SENSOR OUT ALARM OCT 23, 2019 9:47 AM FUEL ALARM SEP 2, 2018 1:50 AM SETUP DATA WARNING I31600 OCT 23, 2019 3:34 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 1-2 VFM 2 3-4 VFM 3 5-6 VFM OCT 16, 2019 11:12 AM COMMUNICATION ALARM 4 7-8 VFM OCT 16, 2019 11:12 AM COMMUNICATION ALARM 5 9-10 VFM OCT 16, 2019 11:12 AM COMMUNICATION ALARM 6 11-12 VFM OCT 16, 2019 11:12 AM COMMUNICATION ALARM 7 9-10 VPS OCT 16, 2019 11:12 AM COMMUNICATION ALARM 8 ATM P SNSR 9 VPR-UDCS OCT 23, 2019 12:20 PM VACUUM WARNING OCT 23, 2019 12:17 PM NO VACUUM ALARM OCT 23, 2019 11:42 AM HIGH LIQUID ALARM 10 87 SUMPS OCT 23, 2019 12:17 PM NO VACUUM ALARM OCT 23, 2019 11:42 AM HIGH LIQUID ALARM OCT 22, 2019 6:24 AM VACUUM WARNING 11 87 PRODUCT OCT 23, 2019 11:42 AM HIGH LIQUID ALARM OCT 23, 2019 11:41 AM NO VACUUM ALARM OCT 22, 2019 6:27 AM VACUUM WARNING 12 VENT BOX OCT 23, 2019 11:43 AM NO VACUUM ALARM OCT 23, 2019 9:36 AM HIGH LIQUID ALARM OCT 23, 2019 8:53 AM HIGH LIQUID ALARM 13 91 SUMPS OCT 23, 2019 12:14 PM NO VACUUM ALARM OCT 23, 2019 11:44 AM HIGH LIQUID ALARM OCT 23, 2019 9:36 AM VACUUM WARNING 14 91 PRODUCT OCT 23, 2019 11:44 AM HIGH LIQUID ALARM OCT 23, 2019 11:44 AM VACUUM WARNING OCT 23, 2019 11:44 AM NO VACUUM ALARM 15 DSL VENT OCT 23, 2019 11:46 AM HIGH LIQUID ALARM OCT 23, 2019 11:46 AM NO VACUUM ALARM OCT 22, 2019 7:24 AM VACUUM WARNING 16 DSL SUMPS OCT 23, 2019 11:46 AM HIGH LIQUID ALARM OCT 22, 2019 8:09 AM VACUUM WARNING OCT 21, 2019 10:37 AM HIGH LIQUID ALARM 17 DSL PRODUCT OCT 23, 2019 11:46 AM HIGH LIQUID ALARM OCT 23, 2019 11:45 AM NO VACUUM ALARM OCT 22, 2019 8:33 AM VACUUM WARNING I40200 OCT 23, 2019 3:34 PM I40300 OCT 23, 2019 3:34 PM I34200 OCT 23, 2019 3:34 PM I34700 OCT 23, 2019 3:34 PM IV0100 OCT 23, 2019 3:34 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :NOTEST EVR VAPOR CONTAINMENT :NOTEST ISD MONITOR UP-TIME : 99+ACU- EVR/ISD PASS TIME : 0+ACU- WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 19-10-23 00:00:09 SENSOR OUT SELFTEST E 1 19-10-23 00:00:09 SETUP SELFTEST MISSING VAPOR PRESSURE SENSE(S) 19-10-23 00:00:09 SETUP SELFTEST MISSING VAPOR FLOW METER(S) 19-10-23 00:00:09 SETUP SELFTEST MISSING HOSE(S) 19-10-23 00:00:09 SETUP SELFTEST MISSING SHUTDOWN RELAY(S) 19-10-22 00:00:09 SENSOR OUT SELFTEST E 1 19-10-22 00:00:09 SETUP SELFTEST MISSING VAPOR PRESSURE SENSE(S) 19-10-22 00:00:09 SETUP SELFTEST MISSING VAPOR FLOW METER(S) 19-10-22 00:00:09 SETUP SELFTEST MISSING HOSE(S) 19-10-22 00:00:09 SETUP SELFTEST MISSING SHUTDOWN RELAY(S) FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE SHUTDOWN +ACY- MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 19-10-23 09:57:39 READINESS ISD:FN EVR:NNN CHECK SETUP CONFIGURATION 19-10-23 09:57:39 ISD STARTUP 19-10-23 09:55:51 ISD SHUTDOWN 19-10-23 00:00:09 READINESS ISD:FN EVR:NNN CHECK SETUP CONFIGURATION 19-10-22 23:13:10 READINESS ISD:FN EVR:NNN CHECK SETUP CONFIGURATION 19-10-22 23:13:10 ISD STARTUP 19-10-22 23:13:06 ISD SHUTDOWN 19-10-22 00:00:09 READINESS ISD:FN EVR:NNN CHECK SETUP CONFIGURATION 19-10-21 07:07:42 READINESS ISD:FN EVR:NNN CHECK SETUP CONFIGURATION 19-10-21 07:07:42 ISD STARTUP W.O.# SC1-3448141 Cust Ref#: 2219569 Responses Received: 200 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 OCT 23, 2019 3:35 PM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 87 8259 51.71 0.7 74.3 11523 2 91 3425 52.90 0.8 78.1 4476 3 DSL 3873 43.60 0.0 79.9 8031 I90500 OCT 23, 2019 3:35 PM SOFTWARE REVISION LEVEL VERSION 335.00 SOFTWARE+ACM- 346335-100-A CREATED - 18.08.27.10.22 S-MODULE+ACM- 330160-104-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR ISD/APM I50500 OCT 23, 2019 3:35 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 OCT 23, 2019 3:35 PM SHIFT TIME 1 : DISABLED I50202 OCT 23, 2019 3:35 PM SHIFT TIME 2 : DISABLED I50203 OCT 23, 2019 3:35 PM SHIFT TIME 3 : DISABLED I50204 OCT 23, 2019 3:35 PM SHIFT TIME 4 : DISABLED I54600 OCT 23, 2019 3:35 PM TANK PER TST NEEDED WRN: DISABLED I54900 OCT 23, 2019 3:35 PM TANK ANN TST NEEDED WRN: DISABLED I55300 OCT 23, 2019 3:35 PM LINE RE-ENABLE METHOD PASS LINE TEST I55600 OCT 23, 2019 3:35 PM LINE PER TST NEEDED WRN: DISABLED I55900 OCT 23, 2019 3:35 PM LINE ANN TST NEEDED WRN: DISABLED I50D00 OCT 23, 2019 3:35 PM PRINT TC VOLUMES ENABLED I50E00 OCT 23, 2019 3:35 PM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 OCT 23, 2019 3:35 PM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 OCT 23, 2019 3:35 PM H-PROTOCOL DATA FORMAT HEIGHT I51A01 OCT 23, 2019 3:35 PM DAYLIGHT SAVING TIME ENABLED ON I51B00 OCT 23, 2019 3:35 PM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 OCT 23, 2019 3:35 PM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 OCT 23, 2019 3:35 PM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 OCT 23, 2019 3:35 PM TANK CHART SECURITY DISABLED I5BD00 OCT 23, 2019 3:35 PM CUSTOM ALARM LABELS DISABLED I56000 OCT 23, 2019 3:35 PM MASS/DENSITY DISABLED I88101 OCT 23, 2019 3:35 PM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 OCT 23, 2019 3:35 PM PORT SETTINGS: COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88103 OCT 23, 2019 3:35 PM I88104 OCT 23, 2019 3:35 PM I88105 OCT 23, 2019 3:35 PM PORT SETTINGS: COMM BOARD : 5 (RS-485) BAUD RATE : 2400 PARITY : EVEN STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88106 OCT 23, 2019 3:35 PM PORT SETTINGS: COMM BOARD : 6 (MTCOMM) BAUD RATE : 9600 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I52000 OCT 23, 2019 3:35 PM RECEIVER AUTO DIAL TYPE +ACY- START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE OCT 23, 2019 DISABLED 2 ON DATE OCT 23, 2019 DISABLED 3 ON DATE OCT 23, 2019 DISABLED 4 ON DATE OCT 23, 2019 DISABLED 5 ON DATE OCT 23, 2019 DISABLED 6 ON DATE OCT 23, 2019 DISABLED 7 ON DATE OCT 23, 2019 DISABLED 8 VEEDER ROOT (FMS) ON DATE OCT 22, 2019 11:49 AM I60100 OCT 23, 2019 3:35 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 87 ON 2 91 ON 3 DSL ON 4 OFF I60200 OCT 23, 2019 3:35 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 87 2 91 3 DSL 4 I60300 OCT 23, 2019 3:35 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 87 1 2 91 2 3 DSL 3 4 4 I60900 OCT 23, 2019 3:35 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 87 0.000690 2 91 0.000690 3 DSL 0.000450 4 0.000000 I60700 OCT 23, 2019 3:35 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 87 118.38 2 91 118.38 3 DSL 118.38 4 0.00 I60A00 OCT 23, 2019 3:35 PM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 87 4 PTS 19782 2 91 4 PTS 7901 3 DSL 4 PTS 11904 4 1 PT 0 I60400 OCT 23, 2019 3:35 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 87 19782 2 91 7901 3 DSL 11904 4 0 I60500 OCT 23, 2019 3:35 PM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 87 19782 16056 9897 3741 2 91 7901 6375 3954 1560 3 DSL 11904 9626 5944 2186 4 0 0 0 0 I60600 OCT 23, 2019 3:35 PM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 87 19782 0 0 0 0 16056 0 0 0 0 9897 0 0 0 0 3741 0 0 0 0 2 91 7901 0 0 0 0 6375 0 0 0 0 3954 0 0 0 0 1560 0 0 0 0 3 DSL 11904 0 0 0 0 9626 0 0 0 0 5944 0 0 0 0 2186 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 OCT 23, 2019 3:35 PM TANK PRODUCT LABEL METER DATA 1 87 YES 2 91 YES 3 DSL YES 4 NO I62F00 OCT 23, 2019 3:35 PM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 87 3.0 IN. 2 91 3.0 IN. 3 DSL 3.0 IN. I62700 OCT 23, 2019 3:35 PM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 87 0.8 2 91 0.8 3 DSL 0.8 I64200 OCT 23, 2019 3:35 PM WATER ALARM FILTER TANK PRODUCT LABEL 1 87 LOW 2 91 LOW 3 DSL LOW I62400 OCT 23, 2019 3:35 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 87 1.0 2 91 1.0 3 DSL 1.0 I62800 OCT 23, 2019 3:35 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 87 19782 2 91 7901 3 DSL 11904 4 0 I62300 OCT 23, 2019 3:35 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 87 17804 2 91 7111 3 DSL 10714 4 0 I62200 OCT 23, 2019 3:35 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 87 18793 2 91 7506 3 DSL 11309 4 0 I62900 OCT 23, 2019 3:35 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 87 2769 2 91 1185 3 DSL 1786 4 0 I62100 OCT 23, 2019 3:35 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 87 900 2 91 500 3 DSL 500 4 0 I62600 OCT 23, 2019 3:35 PM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 87 99 2 91 99 3 DSL 99 4 99 I62500 OCT 23, 2019 3:35 PM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 87 99 2 91 99 3 DSL 99 4 99 I60800 OCT 23, 2019 3:36 PM TANK TILT TANK PRODUCT LABEL INCHES 1 87 0.00 2 91 0.00 3 DSL 0.00 4 0.00 I60B00 OCT 23, 2019 3:36 PM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 OCT 23, 2019 3:36 PM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 87 0.00 2 91 0.00 3 DSL 0.00 4 0.00 I61200 OCT 23, 2019 3:36 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 87 NONE NONE 2 91 NONE NONE 3 DSL NONE NONE 4 NONE NONE I63600 OCT 23, 2019 3:36 PM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 87 0 2 91 0 3 DSL 0 4 0 I62A00 OCT 23, 2019 3:36 PM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 87 0 2 91 0 3 DSL 0 4 0 I62C00 OCT 23, 2019 3:36 PM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 87 STANDARD 2 91 STANDARD 3 DSL STANDARD 4 STANDARD I62D00 OCT 23, 2019 3:36 PM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 87 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 91 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DSL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 OCT 23, 2019 3:36 PM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 87 OFF OFF 2 91 OFF OFF 3 DSL OFF OFF 4 OFF OFF I63000 OCT 23, 2019 3:36 PM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 87 OFF 2 91 OFF 3 DSL OFF 4 OFF I63200 OCT 23, 2019 3:36 PM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 87 OFF 2 91 OFF 3 DSL OFF 4 OFF I61000 OCT 23, 2019 3:36 PM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 87 1 2 91 1 3 DSL 1 4 1 I63A00 OCT 23, 2019 3:36 PM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 87 10.00+ACU- 2 91 10.00+ACU- 3 DSL 10.00+ACU- 4 10.00+ACU- I61100 OCT 23, 2019 3:36 PM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK AUG 27, 2018 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 OCT 23, 2019 3:36 PM CSLD PROBABLITY OF DETECTION I61400 OCT 23, 2019 3:36 PM CSLD CLIMATE FACTOR I61600 OCT 23, 2019 3:36 PM TANK PRODUCT LABEL CAL UPDATE 1 87 IMMEDIATE 2 91 IMMEDIATE 3 DSL IMMEDIATE 4 IMMEDIATE I61A00 OCT 23, 2019 3:36 PM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 87 DISABLED 2 91 DISABLED 3 DSL DISABLED 4 DISABLED I61B00 OCT 23, 2019 3:36 PM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 OCT 23, 2019 3:36 PM CSLD REPORT ONLY I62B00 OCT 23, 2019 3:36 PM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 87 ??? 0, 0 2 91 ??? 0, 0 3 DSL ??? 0, 0 4 ??? 0, 0 I63300 OCT 23, 2019 3:36 PM LEAK TEST REPORT FORMAT: NORMAL I63400 OCT 23, 2019 3:36 PM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 87 0 2 91 0 3 DSL 0 4 0 I63500 OCT 23, 2019 3:36 PM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 87 1 2 91 1 3 DSL 1 4 1 I63900 OCT 23, 2019 3:36 PM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 87 END FACTOR: HEMISPHER 2 91 END FACTOR: FLAT 3 DSL END FACTOR: HEMISPHER 4 END FACTOR: NONE I78000 OCT 23, 2019 3:36 PM I77700 OCT 23, 2019 3:36 PM I77800 OCT 23, 2019 3:36 PM I78C00 OCT 23, 2019 3:36 PM I78300 OCT 23, 2019 3:36 PM I78F00 OCT 23, 2019 3:36 PM I78700 OCT 23, 2019 3:36 PM I70200 OCT 23, 2019 3:36 PM LIQUID LABEL DEVICE LABEL 1 87 ANNULAR 2 87 STP 3 87 FILL 4 DSL-91 ANNULAR 5 91 STP 6 91 FILL 7 DSL STP 8 DSL FILL 9 UDC 1-2 10 UDC 3-4 11 UDC 5-6 12 UDC 7-8 13 UDC 9-10 14 UDC 11-12 15 VENT SUMP 16 I70300 OCT 23, 2019 3:36 PM LIQUID TYPE SENSOR LOCATION TYPE 1 87 ANNULAR DUAL POINT HYDROSTATIC 2 87 STP TRI-STATE (SINGLE FLOAT) 3 87 FILL TRI-STATE (SINGLE FLOAT) 4 DSL-91 ANNULAR DUAL POINT HYDROSTATIC 5 91 STP TRI-STATE (SINGLE FLOAT) 6 91 FILL TRI-STATE (SINGLE FLOAT) 7 DSL STP TRI-STATE (SINGLE FLOAT) 8 DSL FILL TRI-STATE (SINGLE FLOAT) 9 UDC 1-2 TRI-STATE (SINGLE FLOAT) 10 UDC 3-4 TRI-STATE (SINGLE FLOAT) 11 UDC 5-6 TRI-STATE (SINGLE FLOAT) 12 UDC 7-8 TRI-STATE (SINGLE FLOAT) 13 UDC 9-10 TRI-STATE (SINGLE FLOAT) 14 UDC 11-12 TRI-STATE (SINGLE FLOAT) 15 VENT SUMP TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 OCT 23, 2019 3:36 PM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 87 ANNULAR ANNULAR SPACE 2 87 STP STP SUMP 3 87 FILL PIPING SUMP 4 DSL-91 ANNULAR ANNULAR SPACE 5 91 STP STP SUMP 6 91 FILL PIPING SUMP 7 DSL STP STP SUMP 8 DSL FILL PIPING SUMP 9 UDC 1-2 DISPENSER PAN 10 UDC 3-4 DISPENSER PAN 11 UDC 5-6 DISPENSER PAN 12 UDC 7-8 DISPENSER PAN 13 UDC 9-10 DISPENSER PAN 14 UDC 11-12 DISPENSER PAN 15 VENT SUMP OTHER SENSORS 16 OTHER SENSORS I74200 OCT 23, 2019 3:36 PM I74300 OCT 23, 2019 3:36 PM I74400 OCT 23, 2019 3:36 PM I74700 OCT 23, 2019 3:36 PM I74800 OCT 23, 2019 3:36 PM I74900 OCT 23, 2019 3:36 PM I7BC00 OCT 23, 2019 3:36 PM I80200 OCT 23, 2019 3:36 PM I80300 OCT 23, 2019 3:36 PM I80400 OCT 23, 2019 3:36 PM I80700 OCT 23, 2019 3:36 PM RELAY LABEL DEVICE LABEL 1 87 2 91 3 DSL 4 OVERFILL I80900 OCT 23, 2019 3:36 PM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 87 NORMALLY OPEN 2 91 NORMALLY OPEN 3 DSL NORMALLY OPEN 4 OVERFILL NORMALLY OPEN I80B00 OCT 23, 2019 3:36 PM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 87 1 2 91 2 3 DSL 3 4 OVERFILL NONE I80A00 OCT 23, 2019 3:36 PM RELAY TYPE RELAY DESIGNATION TYPE 1 87 PUMP CONTROL OUTPUT 2 91 PUMP CONTROL OUTPUT 3 DSL PUMP CONTROL OUTPUT 4 OVERFILL STANDARD I80C00 OCT 23, 2019 3:36 PM I80800 OCT 23, 2019 3:36 PM RELAY SETUP REPORT R 1:87 TYPE: PUMP CONTROL OUTPUT TANK +ACM-: 1 LIQUID SENSOR ALMS L 2:FUEL ALARM L 3:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L 2:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM R 2:91 TYPE: PUMP CONTROL OUTPUT TANK +ACM-: 2 LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L 5:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM R 3:DSL TYPE: PUMP CONTROL OUTPUT TANK +ACM-: 3 LIQUID SENSOR ALMS L 7:FUEL ALARM L 8:FUEL ALARM L10:FUEL ALARM L14:FUEL ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 8:SHORT ALARM L10:SHORT ALARM L14:SHORT ALARM R 4:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK +ACM-: NONE IN-TANK ALARMS ALL:OVERFILL ALARM I79000 OCT 23, 2019 3:37 PM EDIM:1 VR:349867-001-D TD:17.02.14.08.38 I79100 OCT 23, 2019 3:37 PM I72300 OCT 23, 2019 3:37 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 1-2 VFM AIR FLOW METER 02 3-4 VFM AIR FLOW METER 03 5-6 VFM AIR FLOW METER 04 7-8 VFM AIR FLOW METER 05 9-10 VFM AIR FLOW METER 06 11-12 VFM AIR FLOW METER 07 9-10 VPS VAPOR PRESSURE 08 ATM P SNSR ATM P SENSOR 09 VPR-UDCS VAC SENSOR 10 87 SUMPS VAC SENSOR 11 87 PRODUCT VAC SENSOR 12 VENT BOX VAC SENSOR 13 91 SUMPS VAC SENSOR 14 91 PRODUCT VAC SENSOR 15 DSL VENT VAC SENSOR 16 DSL SUMPS VAC SENSOR 17 DSL PRODUCT VAC SENSOR 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN I72A00 OCT 23, 2019 3:37 PM VACUUM SENSOR VOLUME DEVICE LABEL VOLUME 9 VPR-UDCS 25.0 GALLONS 10 87 SUMPS 10.0 GALLONS 11 87 PRODUCT 25.0 GALLONS 12 VENT BOX 30.0 GALLONS 13 91 SUMPS 10.0 GALLONS 14 91 PRODUCT 25.0 GALLONS 15 DSL VENT 15.0 GALLONS 16 DSL SUMPS 25.0 GALLONS 17 DSL PRODUCT 25.0 GALLONS IV4E00 OCT 23, 2019 3:37 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 EVR/ISD SETUP TYPE: BALANCE IV4F00 OCT 23, 2019 3:37 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 OCT 23, 2019 3:37 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 VAPOR PROCESSOR TYPE NONE IV4700 OCT 23, 2019 3:37 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 ASSESSMENT TIME START TIME: 11:59 PM TIME DELAY MINUTES: 1 IV5200 OCT 23, 2019 3:37 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 ACCEPT HIGH ORVR: NO IV4A00 OCT 23, 2019 3:37 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL TABLE EMPTY IV4B00 OCT 23, 2019 3:37 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 IV4900 OCT 23, 2019 3:37 PM 177218 7-11 22150 4012 WHITE LN Bakersfield,CA 93309 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 OCT 23, 2019 3:37 PM ISD VERSION: 01.05 Test Duration Test Pressure P/F Threshold Tank Annular - Vacuum 1 hr, 20k or less tank 10" hg 0 loss, int dry before and after test Tank Annular - Vacuum 2 hr, >20k tank 10" hg 0 loss, int dry before and after test Line Annular - Pressure 1 hr 5 psi 0 loss STP Sump - Hydro 1 hr 4" above highest penetration or sidewall seam less than 1/8" over hour, settle time of 15 minutes minimum prior to starting the test UDC Sump - Hydro 1 hr 4" above highest penetration or sidewall seam less than 1/8" over hour, settle time of 15 minutes minimum prior to starting the test Spill Bucket - SW Vac 1 min 30" wc no greater than 4" wc vaccum decay - bucket must be dry Spill Bucket - SW Hydro 1 hr within 1.5" of top of the bucket less than 1/8" over hour, settle time of 5 minutest minimum prior to starting the test Spill Bucket - DW Vac 1 min 15" wc no greater than 3" wc vaccum decay - int must be dry W.O.# SC1-3448141 Cust Ref#: 2219569 87 Tanks chart W.O.# SC1-3448141 Cust Ref#: 2219569 91 Tank chart W.O.# SC1-3448141 Cust Ref#: 2219569 Diesel tank chart W.O.# SC1-3448141 Cust Ref#: 2219569 Veeder root overfill W.O.# SC1-3448141 Cust Ref#: 2219569