HomeMy WebLinkAboutSB-989 2018CERS = California Environmental Reporting System, ID = Identification, UST = Underground storage tank, ICC = International Code Council,
NA = Not applicable, UDC = Under-dispenser containment
UNDERGROUND STORAGE TANK
SECONDARY CONTAINMENT TESTING REPORT FORM (Page 1 of 6)
Type of Action Installation Test Repair Test Six Month Test 36 Month Test
I. FACILITY INFORMATION
CERS ID
10132288
Date of Secondary Containment Test
10/17/2018
Business Name (Same as Facility Name or DBA-Doing Business As)
VG MINI MARKET
Business Site Address
6501 S Union Ave
City
Bakersfield
ZIP Code
93307
II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION
Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.)
Bradley Hinsley
Phone #
(661)706 - 4321 Ext.
Contractor/Tank Tester License #
971259
ICC Certification #
8373948
ICC Certification Expiration Date
8/23/2019
III. SUMMARY OF SECONDARY CONTAINMENT TESTING RESULTS
Tank ID: (By tank number, stored product, etc.) A 87 B 91 C Diesel D
Tank Containment
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Product Piping Containment
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Communication Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Remote Fill Piping Containment
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Communication Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Vent Piping Containment
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Communication Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Vapor Recovery Piping Containment
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Communication Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Turbine / Product Piping Sump
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Fill Riser Sump
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
Vent / Transition Sump ID: a b c d
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
UDC ID: 1 1/2 2 3/4 3 5/6 4
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
UDC ID: 5 6 7 8
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
UDC ID: 9 10 11 12
Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA
All items marked “Fail” or “N/A” must be explained in their respective “COMMENTS” section.
IV. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING
I hereby certify that the secondary containment was tested in accordance with California Code of Regulations, title 23,
division 3, chapter 16, section 2637 and all the information contained herein is accurate.
UST Service Technician Signature
ID = Identification
UNDERGROUND STORAGE TANK
SECONDARY CONTAINMENT TESTING REPORT FORM (Page 2 of 6)
V. TANK CONTAINMENT TESTING INFORMATION
Manufacturer Identify Tank ID from section III for each Manufacturer
Unknown A B C D
A B C D
Test Method Used: Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify) PEI RP1200-17
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Tank Containment Testing Training and Certifications (List applicable certifications.) Expiration Date
ICC Service Techican 8/23/2019
INCON STS 10/13/2019
VI. COMMENTS
Provide any additional comments here.
BOTH ANNULARS PASSED.
VII. PRODUCT PIPING CONTAINMENT TESTING INFORMATION
Manufacturer Identify Tank ID from section III for each Manufacturer
Unknown A B C D
A B C D
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify) PEI RP1200-17
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Product Piping Containment Testing Training and Certifications (List applicable certifications.) Expiration Date
ICC Service Techican 8/23/2019
INCON STS 10/13/2019
Interstitial Communication Verification Method Used:
VIII. COMMENTS
Provide any additional comments here.
ALL PRODUCT LINES FAILED.
ID = Identification
UNDERGROUND STORAGE TANK
SECONDARY CONTAINMENT TESTING REPORT FORM (Page 3 of 6)
IX. REMOTE FILL PIPING CONTAINMENT TESTING INFORMATION
Manufacturer Identify Tank ID from section III for each Manufacturer
A B C D
A B C D
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify)
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Remote Fill Piping Containment Testing Training and Certifications (List applicable certifications.) Expiration Date
Interstitial Communication Verification Method Used:
X. COMMENTS
Provide any additional comments here.
XI. VENT PIPING CONTAINMENT TESTING INFORMATION
Manufacturer Identify Tank ID from section III for each Manufacturer
A B C D
A B C D
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify)
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Vent Piping Containment Testing Training and Certifications (List applicable certifications.) Expiration Date
Interstitial Communication Verification Method Used:
XII. COMMENTS
Provide any additional comments here.
ID = Identification
UNDERGROUND STORAGE TANK
SECONDARY CONTAINMENT TESTING REPORT FORM (Page 4 of 6)
XIII. VAPOR RECOVERY PIPING CONTAINMENT TESTING INFORMATION
Manufacturer Identify Tank ID from section III for each Manufacturer
A B C D
A B C D
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify)
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Vapor Recovery Piping Containment Testing Training and Certifications (List applicable certifications.) Expiration Date
Interstitial Communication Verification Method Used:
XIV. COMMENTS
Provide any additional comments here.
XV. TURBINE / PRODUCT PIPING SUMP TESTING INFORMATION
Manufacturer Identify Tank ID from section III for each Manufacturer
Unknown A B C D
A B C D
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify) PEI RP1200-17
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Turbine / Product Piping Sump Testing Training and Certifications (List applicable certifications.) Expiration Date
ICC Service Techican 8/23/2019
INCON STS 10/13/2019
XVI. COMMENTS
Provide any additional comments here.
All STPs Passed.
ID = Identification
UNDERGROUND STORAGE TANK
SECONDARY CONTAINMENT TESTING REPORT FORM (Page 5 of 6)
XVII. FILL RISER SUMP TESTING INFORMATION
Manufacturer Identify Tank ID from section III for each Manufacturer
A B C D
A B C D
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify)
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Fill Riser Sump Testing Training and Certifications (List applicable certifications.) Expiration Date
XVIII. COMMENTS
Provide any additional comments here.
XIX. VENT / TRANSITION PIPING SUMP TESTING INFORMATION
Manufacturer Identify Vent / Transition Sump ID from
section III for each Manufacturer
a b c d
a b c d
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify)
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Vent / Transition Piping Sump Testing Training and Certifications (List applicable certifications.) Expiration Date
XX. COMMENTS
Provide any additional comments here.
UDC = Under-dispenser containment, ID = Identification
UNDERGROUND STORAGE TANK
SECONDARY CONTAINMENT TESTING REPORT FORM (Page 6 of 6)
XXI. UNDER-DISPENSER CONTAINMENT TESTING INFORMATION
Manufacturer(s): Identify UDC ID from section III for each Manufacturer
Gilbarco 1 2 3 4 5 6
7 8 9 10 11 12
1 2 3 4 5 6
7 8 9 10 11 12
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify) PEI RP1200-17
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
UDC Testing Training and Certifications (List applicable certifications.) Expiration Date
ICC Service Techican 8/23/2019
INCON STS 10/13/2019
XXII. COMMENTS
Provide any additional comments here.
Dispenser 3/4 and 5/6 Failed.
If the facility has more components than this form accommodates, additional copies of these pages may be attached.
CERS = California Environmental Reporting System, ID = Identification, UST = Underground storage tank, ICC = International Code Council
UNDERGROUND STORAGE TANK
SPILL CONTAINER TESTING REPORT FORM (Page 1 of 1)
Type of Action Installation Test Repair Test 12 Month Test
I. FACILITY INFORMATION
CERS ID
10132288
Date of Spill Container Test
10/17/2018
Business Name (Same as Facility Name or DBA-Doing Business As.)
VG MINI MARKET
Business Site Address
6501 S Union Ave
City
Bakersfield
ZIP Code
93307
II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION
Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.)
Bradley Hinsley
Phone #
(661) 706 - 4321 Ext.
Contractor/Tank Tester License #
971259
ICC Certification #
8373948
ICC Certification Expiration Date
8/23/2019
Spill Container Testing Training and Certifications (List applicable certifications.)
8/23/2019
III. SPILL CONTAINER TESTING INFORMATION
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify) PEI RP1200-17
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Tank ID: (By tank number, stored product, etc.) 87FB 91FB DieselFB 87VB
Spill Container Manufacturer: OPW OPW OPW OPW
Method of Cathodic Protection
Non-Metallic Non-Metallic Non-Metallic Non-Metallic
Isolation Isolation Isolation Isolation
Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.)
Inside Diameter of Spill Container: (Inches) 15" 15" 15" 15"
Depth of Spill Container: (Inches) 18" 18" 18" 18"
Does the spill container have a 5 gallon capacity? Yes No Yes No Yes No Yes No
Method to Keep Spill Container Empty
Drain Valve Drain Valve Drain Valve Drain Valve
Onsite Pump Onsite Pump Onsite Pump Onsite Pump
Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.)
IV. SUMMARY OF TESTING RESULTS
Spill Container Test Results Pass Fail Pass Fail Pass Fail Pass Fail
V. COMMENTS
All items marked “Fail” above must be explained in this section. Any additional comments may also be provided here.
87 Fill Bucket and Vapor Bucket Failed SB989 Testing.
VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING
I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section
2637.1 and all the information contained herein is accurate.
UST Service Technician Signature
If the facility has more components than this form accommodates, additional copies of this page may be attached.
CERS = California Environmental Reporting System, ID = Identification, UST = Underground storage tank, ICC = International Code Council
UNDERGROUND STORAGE TANK
SPILL CONTAINER TESTING REPORT FORM (Page 1 of 1)
Type of Action Installation Test Repair Test 12 Month Test
I. FACILITY INFORMATION
CERS ID
10132288
Date of Spill Container Test
10/17/2018
Business Name (Same as Facility Name or DBA-Doing Business As.)
VG MINI MARKET
Business Site Address
6501 S Union Ave
City
Bakersfield
ZIP Code
93307
II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION
Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.)
Bradley Hinsley
Phone #
(661) 706 - 4321 Ext.
Contractor/Tank Tester License #
971259
ICC Certification #
8373948
ICC Certification Expiration Date
8/23/2019
Spill Container Testing Training and Certifications (List applicable certifications.)
8/23/2019
III. SPILL CONTAINER TESTING INFORMATION
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify) PEI RP1200-17
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Tank ID: (By tank number, stored product, etc.) 91VB
Spill Container Manufacturer: OPW
Method of Cathodic Protection
Non-Metallic Non-Metallic Non-Metallic Non-Metallic
Isolation Isolation Isolation Isolation
Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.)
Inside Diameter of Spill Container: (Inches) 15"
Depth of Spill Container: (Inches) 18"
Does the spill container have a 5 gallon capacity? Yes No Yes No Yes No Yes No
Method to Keep Spill Container Empty
Drain Valve Drain Valve Drain Valve Drain Valve
Onsite Pump Onsite Pump Onsite Pump Onsite Pump
Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.)
IV. SUMMARY OF TESTING RESULTS
Spill Container Test Results Pass Fail Pass Fail Pass Fail Pass Fail
V. COMMENTS
All items marked “Fail” above must be explained in this section. Any additional comments may also be provided here.
VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING
I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section
2637.1 and all the information contained herein is accurate.
UST Service Technician Signature
If the facility has more components than this form accommodates, additional copies of this page may be attached.