Loading...
HomeMy WebLinkAboutFMC 2020IMPACT VALVE LEAK DETECTOR LINE TEST MONITOR CERTIFICATION SPILL BUCKET TEST 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 2/27/2020 BAKERSFIELD FIRE DEPARTMENT OFFICE OF ENVIRONMENTAL SERVICES INSPECTOR KRIS KARNS 1501 TRUXTUN AVE. BAKERSFIELD, CA 93301 Test Date: 2/21/2020 Order Number: 3447815 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: CARMAX #7281 (CMX7281) 6801 Colony St Bakersfield, CA 93307 In an effort to keep all our record keeping and reporting requirements as current as possible, Tanknology kindly requests you notify Dawn Kohlmeyer in writing at dkohlmeyer@tanknology.com when your CUPA requires all records to be submitted electronically via the CERS database. Your assistance in this endeavor is greatly appreciated. Testing performed: Sincerely, Dawn Kohlmeyer Manager, Field Reporting Product Line Tightness Test Page 1 of 1 Work Order: 3447815 Date: 2/21/2020 Site Name/ID: CARMAX #7281 / CMX7281 Address: 6801 Colony St City: Bakersfield State: CA Zip: 93307 Tank Information Test Method Customer Tank ID Product Name Delivery Type Test Pressure Test Start Time Test End Time Final Leak Rate Test Result(P/F/I) Test was performed per 3rd party certifications as specified in 40 CFR parts 280 and 281 Tank # 1 Line # 1 TLD-1 1 UNLEADED UNLEADED Pressure 50 09:12 09:42 0.00 Pass Yes Tank # Line # Tank # Line # Tank # Line # Tank # Line # Tank # Line # Technician Comments: Technician Name:Patrick Pfrang Certification #:44642 exp: 4/6/2022 Technician Signature: Environmental Compliance for Petroleum Systems ©2020 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com LDT 5000 Field Test Apparatus Line Leak Detector Test Page 1 of 1 Work Order:3447815 Date:2/21/2020 Site Name / ID:CARMAX #7281 / CMX7281 Address:6801 Colony St City:Bakersfield State:CA Zip:93307 Tank ID Product Product Line Tested From Existing/New Mechanical/Electronic Manufacturer/Model Serial No. Pump Operating Pressure (psi) Calibrated Leak (ml/min) Calibrated Leak (gph) Holding PSI *N/A for Electronic LD's Resiliency (ml) *N/A for Electronic LD's Metering PSI *N/A for Electronic LD's Opening Time (sec) *N/A for Electronic LD's Test Results 1 UNLEADED UNLEADED 1 1 Existing Electronic Veeder Root PLLD 312121 30.00 189.0 3.00 Pass Technician Comments: Technician Name:Patrick Pfrang Certification #:44637 Technician Signature:Expire Date:4/6/2022 Environmental Compliance for Petroleum Systems © 2020 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Impact Valve Inspection Impact Valve Operational Inspection Work Order:3447815 Date:2/21/2020 Site Name/ID:CARMAX #7281 Address:6801 Colony St City:Bakersfield State:CA Zip:93307 How Inspected: Line Test NFPA 30A PEI RP1200 Other Dispenser Number Grade Secure Mount? Valve Lock?Pass/ Fail Comments 1/ 87 Pass Fail Not Tested Technician Comments: Technician Name:Patrick Pfrang Signature: Environmental Compliance for Petroleum Systems ©2020 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 1 of 6) This form must be used to document testing and servicing of underground storage tank (UST) monitoring equipment. A copy of this form must be provided to the UST owner or operator. The owner or operator must submit a copy of this form to the local agency regulating the USTs within 30 days of the date of the monitoring system certification. I. FACILITY INFORMATION CERS ID 10135189 Date of Monitoring System Certification 2/21/2020 Business Name (Same as Facility Name or DBA-Doing Business As.) CARMAX #7281 Building # Business Site Address 6801 Colony St City: Bakersfield Zip: 93307 II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of Company Performing the Certification TANKNOLOGY INC. Phone # (800) 800-4633 Ext. Mailing Address 11000 N. Mopac Expressway #500, Austin, TX 78759 Name of UST Service Technician Performing the Certification (Print as shown on the ICC Certification.) Patrick Pfrang Contractor/Tank Tester License # Class A General Engineering 743160 ICC Certification # 8202676 ICC Certification Expiration Date 2/8/2021 Monitoring System Training and Certifications (List all applicable certifications.) Expiration Date Tanknology Certification Level III ATG Operability Training Certification Exam 44635 01/30/2022 ICC CA UST Service Technician 8202676 02/08/2021 Veeder Root VR Level 4 A29052 09/06/2021 III. RESULTS OF TESTING/SERVICING Indicate and attach the following reports if the monitoring equipment is capable of generating either. Monitoring System Set-up Alarm History Report Y N NA Was any monitoring equipment replaced? (If "Yes,"identify the specific devices replaced and list the manufacturer and model for all replacement parts in section IV below.) Was damage, debris, or liquid found inside any secondary containment systems? (If "Yes," describe what was found in section IV below.) Is all monitoring equipment operational per manufacturer's specifications? (If "No," describe why in section IV below.) IV. COMMENTS If directed to use this section, describe how and when the issues were or will be corrected. V. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING I hereby certify that the equipment identified in this document was inspected/serviced in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638 and all information contained herein is true and accurate. Attached to this certification is information (e.g., manufacturers' checklists, monitoring system set-up, alarm history report, etc.) necessary to verify that this information and the site plan showing the layout of UST system is complete and accurate. UST Service Technician Signature CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 2 of 6) VI. INVENTORY OF EQUIPMENT CERTIFIED A separate Monitoring System Certification Form must be prepared for each monitoring system control panel. Make of Monitoring System Control Panel Veeder Root Model of Monitoring System Control Panel TLS-350 PLUS Software Version Installed 132.00 Check the appropriate boxes to indicate specific equipment inspected/serviced. Monitoring Device Used Device Model # Tank ID: 1 UNLEADED Gasoline - Regular (By tank number, stored product, etc.) In-tank Gauging (SW Tank) Annular Space or Vault Sensor 794380-303 VPH Sensor Product Piping Mechanical LLD Electronic LLD 848480-001 VPH Sensor (Piping)330020-485 (s1) Sump Sensor 794380-323/304 VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor 794380-323/304 VPH Sensor (Sump) Vent Piping VPH Sensor (Piping)330020-485 (s2) Sump Sensor 794380-323 VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping)330020-485 (s3) Sump Sensor VPH Sensor (Sump) Monitoring Device Used Device Model # Tank ID: (By tank number, stored product, etc.) In-tank Gauging (SW Tank) Annular Space or Vault Sensor VPH Sensor Product Piping Mechanical LLD Electronic LLD VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Monitoring Device Used Device Model # Tank ID: (By tank number, stored product, etc.) In-tank Gauging (SW Tank) Annular Space or Vault Sensor VPH Sensor Product Piping Mechanical LLD Electronic LLD VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Monitoring Device Used Device Model # Tank ID: (By tank number, stored product, etc.) In-tank Gauging (SW Tank) Annular Space or Vault Sensor VPH Sensor Product Piping Mechanical LLD Electronic LLD VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 3 of 6) Monitoring Device Used Device Model #Monitoring Device Used Device Model # Vent/Transition Sump ID: Vent sump Vent/Transition Sump ID: Sump Sensor 794380-323/304 Sump Sensor VPH Sensor VPH Sensor UDC ID: 1 Electronic Sensor 794380-323/304 Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor Other Monitored Component ID: Other Monitored Component ID: Other(Specify in section VII) Other(Specify in section VII) Other Monitored Component ID: Other Monitored Component ID: Other(Specify in section VII) Other(Specify in section VII) Other Monitored Component ID: Other Monitored Component ID: Other(Specify in section VII) Other(Specify in section VII) Include information for every underground storage tank component monitored by this monitoring system control panel. If the monitoring system control panel monitors more components than this form accommodates, additoinal copies of these pages may be attached. VII. COMMENTS Use this section to provide any additional comments about the inventory of the equipment certified. CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 4 of 6) VIII. MONITORING SYSTEM AND PROGRAMMING This section must be completed if a monitoring panel is used to perform leak detection monitoring.Y N NA Are the visual and audible alarms operational? Were all sensors visually inspected for kinks and breaks in the cables and for residual buildup to ensure that floats move freely, functionally tested, and confirmed operational? Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Was monitoring system set-up reviewed to ensure proper settings? Was the monitoring panel's backup battery visually inspected, functionally tested, and confirmed operational? Does the flow of fuel stop at the dispenser if a leak is detected in the under-dispenser containment? Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? Does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak? Which sensors initiate positive shut down? (Check all that apply.) Sump Under-dispenser containment If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? For any answer of "N" above, describe in section IX how and when these deficiencies were or will be corrected. IX. COMMENTS Use this section to provide any additional comments about the inventory of the equipment certified. X. IN-TANK GAUGING TESTING Check this box if tank gauging is used only for inventory control. (Do not complete this section.) Check this box if NO tank gauging equipment is installed. (Do not complete this section.) This section must be completed if in-tank gauging is used to perform leak detection monitoring. Y N NA Has all input wiring been inspected for kinks and breaks in the cables and for proper entry and termination, including testing for ground faults? Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? Was accuracy of system's product level readings tested? Was accuracy of system's water level readings tested? Were all probes reinstalled properly? Were all items on the equipment manufacturer's maintenance checklist completed? For any answer of "N" above, describe in section XI how and when these deficiencies were or will be corrected. XI. COMMENTS Use this section to provide any additional comments about the inventory of the equipment certified. Y = Yes, N = No, NA = Not Applicable UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 5 of 6) XVI. LINE LEAK DETECTOR TESTING Check this box if line leak detectors (LLD) are NOT installed. (Do not complete this section.) This section must be completed if LLDs are installed.Y N NA Was a leak simulated to verify LLD performance? (Check all that apply.) Simulated leak rate verified: 3 GPH 1.1 GPH 0.2 GPH Was the testing apparatus properly calibrated? For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? For mechanical LLDs, does the LLD restrict the flow through the pipe when a leak is detected? For electronic LLDs, does the turbine automatically shut off when a leak is detected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? Were all items on the equipment manufacturer's maintenance checklist completed? Were all LLDs confirmed operational within regulatory requirements? For any answer of "N" above, describe in section XIII how and when these issues were or will be corrected. XIII. COMMENTS XIV. VACUUM / PRESSURE/ HYDROSTATIC MONITORING EQUIPMENT TESTING Check this box if VPH monitoring is NOT used. (Do not complete this section.) This section must be completed if VPH monitoring is used to perform leak detection monitoring. System Type (Mark all that apply.) Vacuum Pressure Hydrostatic Sensor ID Component(s) Monitored by this Sensor Sensor Functionality Test Interstitial Communication Test s1 PRODUCT Pass Fail Pass Fail s2 VENT Pass Fail Pass Fail s3 VAPOR PIPE Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail How was interstitial communication verified? Simulated leak at far ends of the interstitial space. Other (Describe the method in section XV below.) Visual Inspection Gauge Was the vacuum or pressure restored to operating levels in all interstitial spaces? Yes No (Describe the reason in section XV below.) For any answer of "N" above, describe in section XIII how and when these issues were or will be corrected. XV. COMMENTS GPH = Gallons per hour, Y = Yes, N = No, NA = Not applicable, VPH = Vacuum/Pressure/Hydrostatic, ID = Identification UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 6 of 6) XVI. MONITORING SITE PLAN Date site map was prepared: If you already have a site plan that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and piping and clearly identify locations of the following equipment, if installed: 1) monitoring system control panels; 2) in-tank liquid level probes (if used for leak detection); 3) devices monitoring tank annular spaces or vault; 4) devices monitoring product piping; 5) devices monitoring fill piping; 6) devices monitoring vent piping; 7) devices monitoring vapor recovery piping; 8) devices monitoring vent/transition sumps; 9) devices monitoring under-dispenser containment; 10) line leak detectors; and 11) devices monitoring any other secondary containment areas. UNDERGROUND STORAGE TANK SPILL CONTAINER TESTING REPORT FORM (Page 1 of 1) Type of Action Installation Test Repair Test 12 Month Test I. FACILITY INFORMATION CERS ID 10135189 Date of Spill Container Test: 2/21/2020 Business Name (Same as Facility Name or DBA-Doing Business As.) CARMAX #7281 Business Site Address 6801 Colony St City: Bakersfield Zip: 93307 II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.) Patrick Pfrang Phone # (800) 800-4633 Contractor/Tank Tester License # Class A General Engineering 743160 ICC Certification # 8202676 ICC Certification Expiration Date 2/8/2021 Spill Container Testing Training and Certifications (List applicable certifications.) OPW - EVR Phase 1 903800 03/13/2021 III. SPILL CONTAINER TESTING INFORMATION Test Method Used: Manufacturer Guidelines: (Specify) Industry Code or Engineering Standard: (Specify) PEI RP 1200 Engineered Method: (Specify) Attach the testing procedures and all documentation required to determine the results. # of Attached Pages 2 Tank ID: (By tank number, stored product, etc.) Spill Container Manufacturer: Method of Cathodic Protection Inside Diameter of Spill Container: (Inches) Depth of Spill Container: (Inches) Does the spill container have a 5 gallon capacity? Method to Keep Spill Container Empty IV. Spill Container Test Results Fill 1 UNLEADED UNLEADED OPW Non-Metallic Isolation Other (Specify in section V) 12 15 Yes No Drain Valve Onsite Pump Other (Specify in section V) Non-Metallic Isolation Other (Specify in section V) Yes No Drain Valve Onsite Pump Other (Specify in section V) Non-Metallic Isolation Other (Specify in section V) Yes No Drain Valve Onsite Pump Other (Specify in section V) Non-Metallic Isolation Other (Specify in section V) Yes No Drain Valve Onsite Pump Other (Specify in section V) SUMMARY OF TESTING RESULTS Pass Fail Pass Fail Pass Fail Pass Fail V. COMMENTS All items marked failed above must be explained in this section. Any additional comments may also be provided here. Fill bucket pass. VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1 and all the information contained herein is accurate. UST Service Technician Signature If the facility has more components than this form accommodates, additional copies of this page may be attached. CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: CARMAX #7281 Date of Testing: 2/21/2020 Facility Address: 6801 Colony St , Bakersfield, CA 93307 Facility Contact: Josh Martin - See e-mail Phone: 661-282-3016 Date Local Agency Was Notified of Testing: 1/15/2020 Name of Local Agency Inspector (if present during testing): Kris Karns 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY INC. Technician Conducting Test: Patrick Pfrang Credentials1: CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s): 743160 3. SPILL BUCKET TESTING INFORMATION Test Method Used By: Hydrostatic Vacuum Other Test Equipment Used: LAKE TEST Equipment Resolution: 0.0625 in. Identify Spill Bucket (By Tank Number, Stored Product, etc.) Bucket Installation Type: Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test Test Start Time (TI): Initial Reading (RI): Test End Time(TF): Final Reading (RF): Test Duration(TF–TI): Change in Reading (RF–RI) : Pass/Fail Threshold or Criteria: Test Result: Spill Box # Tank 1 UNLEADED UNLEADED - Fill 1 - Direct - Below Grade in containment sump Direct Bury Contained in Sump 12.00 15.00 15 min 09:38:00 13.50 in. 10:38:00 13.50 in. 1 hr 0.00 in. +/- 0.00 Pass Spill Box # Direct Bury Contained in Sump min +/- Spill Box # Direct Bury Contained in Sump min +/- Spill Box # Direct Bury Contained in Sump min +/- Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature:Date:2/21/2020 1State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. WO: 3447815 Fill bucket pass. Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:3447815 Site ID / Name:CMX7281 / CARMAX #7281 Address:6801 Colony St City:Bakersfield State:CA Zip:93307 Test Duration Test Pressure P/F Threshold Tank Annular - Vacuum 1 hr, 20k or less tank 10" hg 0 loss, int dry before and after test Tank Annular - Vacuum 2 hr, >20k tank 10" hg 0 loss, int dry before and after test Line Annular - Pressure 1 hr 5 psi 0 loss STP Sump - Hydro 1 hr 4" above highest penetration or sidewall seam less than 1/8" over hour, settle time of 15 minutes minimum prior to starting the test UDC Sump - Hydro 1 hr 4" above highest penetration or sidewall seam less than 1/8" over hour, settle time of 15 minutes minimum prior to starting the test Spill Bucket - SW Vac 1 min 30" wc no greater than 4" wc vaccum decay - bucket must be dry Spill Bucket - SW Hydro 1 hr within 1.5" of top of the bucket less than 1/8" over hour, settle time of 5 minutest minimum prior to starting the test Spill Bucket - DW Vac 1 min 15" wc no greater than 3" wc vaccum decay - int must be dry W.O.# SC1-3447815 Cust Ref#: CMX-133508604/M-114597 +AAE- I50301 FEB 21, 2020 12:10 PM +ACM- 1:CARMAX +AAM- +AAE- I50302 FEB 21, 2020 12:10 PM +ACM- 2:6801 COLONY ST. +AAM- +AAE- I50303 FEB 21, 2020 12:10 PM +ACM- 3:BAKERSFIELD,CA 93307 +AAM- +AAE- I50304 FEB 21, 2020 12:10 PM +ACM- 4: +AAM- +AAE- I51700 FEB 21, 2020 12:10 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM +AAM- +AAE- I50F00 FEB 21, 2020 12:10 PM MON DD YYYY HH:MM:SS xM +AAM- +AAE- I10200 FEB 21, 2020 12:10 PM CARMAX 6801 COLONY ST. BAKERSFIELD,CA 93307 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 162334 162175 2 PLLD SENSOR BD 3893 3885 3 INTERSTITIAL BD 200197 200252 4 INTERSTITIAL BD 199838 199732 5 7SMARTSENSOR BD 505934 505941 6 UNUSED 9315975 8962402 7 UNUSED 9310880 8957984 8 UNUSED 9310751 8953870 9 PLLD POWER BD 100396 100410 10 RELAY BOARD 14999 14956 11 UNUSED 9311493 8957317 12 UNUSED 9315901 8953527 13 UNUSED 9308418 8953484 14 UNUSED 9315277 8955931 15 UNUSED 9307386 8952921 16 UNUSED 9307558 8953181 COMM 1 UNUSED 9315148 8957144 COMM 2 FAXMODEM BOARD 40240 40252 COMM 3 RS232 SERIAL BD 9316116 14847 COMM 4 UNUSED 9307601 8966585 COMM 5 UNUSED 9311493 8954545 COMM 6 UNUSED 9309902 8959807 +AAM- +AAE- I60100 FEB 21, 2020 12:10 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED ON 2 OFF 3 OFF 4 OFF +AAM- +AAE- I60200 FEB 21, 2020 12:10 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 2 3 4 +AAM- +AAE- I60300 FEB 21, 2020 12:10 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 2 2 3 3 4 4 +AAM- +AAE- I60400 FEB 21, 2020 12:10 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 11608 2 0 3 0 4 0 +AAM- +AAE- I60700 FEB 21, 2020 12:10 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 120.00 2 0.00 3 0.00 4 0.00 +AAM- +AAE- I60900 FEB 21, 2020 12:10 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 0.000700 2 0.000000 3 0.000000 4 0.000000 +AAM- +AAE- I61200 FEB 21, 2020 12:10 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NONE NONE 2 NONE NONE 3 NONE NONE 4 NONE NONE +AAM- +AAE- I62100 FEB 21, 2020 12:10 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 700 2 0 3 0 4 0 +AAM- +AAE- I62200 FEB 21, 2020 12:10 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11027 2 0 3 0 4 0 +AAM- +AAE- I62300 FEB 21, 2020 12:10 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 10447 2 0 3 0 4 0 +AAM- +AAE- I62400 FEB 21, 2020 12:10 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 1.0 +AAM- +AAE- I62800 FEB 21, 2020 12:10 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11608 2 0 3 0 4 0 +AAM- +AAE- I62900 FEB 21, 2020 12:10 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1160 2 0 3 0 4 0 +AAM- +AAE- I70300 FEB 21, 2020 12:10 PM LIQUID TYPE SENSOR LOCATION TYPE 1 STP-SUMP SENSOR TRI-STATE (SINGLE FLOAT) 2 STP HYDRO SENSOR TRI-STATE (SINGLE FLOAT) 3 ANNULAR DUAL POINT HYDROSTATIC 4 FILL-SUMP SENSOR TRI-STATE (SINGLE FLOAT) 5 FILL HYDRO SENSOR TRI-STATE (SINGLE FLOAT) 6 VENT-BOX SENSOR TRI-STATE (SINGLE FLOAT) 7 VENT HYDRO SENSOR TRI-STATE (SINGLE FLOAT) 8 DISPENSOR-PAN SENSOR TRI-STATE (SINGLE FLOAT) 9 DISPENSOR HYDRO SENS TRI-STATE (SINGLE FLOAT) 10 TRI-STATE (SINGLE FLOAT) 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) +AAM- +AAE- I72100 FEB 21, 2020 12:10 PM SMART SENSOR CONFIGURATION DEVICE LABEL CONFIGURED 1 PRODUCT ON 2 VENT ON 3 VAPOR PIPE ON 4 OFF 5 OFF 6 OFF 7 OFF 8 ATMP ON +AAM- +AAE- I72200 FEB 21, 2020 12:10 PM SMART SENSOR LABEL DEVICE LABEL 1 PRODUCT 2 VENT 3 VAPOR PIPE 4 5 6 7 8 ATMP +AAM- +AAE- I78500 FEB 21, 2020 12:10 PM PRESSURE LINE LEAK TANK NUMBER LINE TANK NUMBER Q 1:UNLEADED 1 Q 2:UNLEADED 1 Q 3: NONE +AAM- +AAE- I72900 FEB 21, 2020 12:10 PM VACUUM SENSOR PUMP NUMBER DEVICE LABEL PUMP NUMBER 1 PRODUCT Q 2:UNLEADED 2 VENT Q 2:UNLEADED 3 VAPOR PIPE Q 2:UNLEADED +AAM- +AAE- I72A00 FEB 21, 2020 12:10 PM VACUUM SENSOR VOLUME DEVICE LABEL VOLUME 1 PRODUCT 104.9 GALLONS 2 VENT 13.8 GALLONS 3 VAPOR PIPE 55.2 GALLONS +AAM- +AAE- I72B00 FEB 21, 2020 12:10 PM VACUUM SENSOR RELIEF VALVE PRESENT DEVICE LABEL RELIEF VALVE 1 PRODUCT NO 2 VENT NO 3 VAPOR PIPE NO +AAM- +AAE- I72C00 FEB 21, 2020 12:10 PM VACUUM SENSOR RELIEF VALVE PRESSURE DEVICE LABEL RELIEF VALVE PRESSURE 1 PRODUCT -9.0 PSI 2 VENT -9.0 PSI 3 VAPOR PIPE -9.0 PSI +AAM- +AAE- I90200 FEB 21, 2020 12:10 PM SOFTWARE REVISION LEVEL VERSION 132.00 SOFTWARE+ACM- 346132-100-A CREATED - 11.05.27.16.29 S-MODULE+ACM- 330160-060-A SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETITIV +AAM- +AAE- I20600 FEB 21, 2020 12:10 PM CARMAX 6801 COLONY ST. BAKERSFIELD,CA 93307 TANK ALARM HISTORY TANK 1 UNLEADED HIGH WATER ALARM FEB 21, 2020 10:42 AM FEB 7, 2019 10:15 AM JAN 16, 2018 10:48 AM OVERFILL ALARM FEB 21, 2020 11:00 AM FEB 7, 2019 10:20 AM JAN 16, 2018 11:18 AM LOW PRODUCT ALARM FEB 21, 2020 11:06 AM FEB 21, 2020 10:37 AM FEB 7, 2019 10:37 AM SUDDEN LOSS ALARM FEB 21, 2020 11:22 AM FEB 21, 2020 10:37 AM FEB 7, 2019 10:11 AM HIGH PRODUCT ALARM FEB 21, 2020 11:01 AM FEB 7, 2019 10:21 AM JAN 16, 2018 11:18 AM PROBE OUT FEB 21, 2020 11:28 AM JAN 16, 2018 10:43 AM HIGH WATER WARNING FEB 21, 2020 10:42 AM FEB 7, 2019 10:15 AM JAN 16, 2018 10:48 AM DELIVERY NEEDED FEB 21, 2020 11:06 AM FEB 21, 2020 10:37 AM FEB 7, 2019 10:37 AM MAX PRODUCT ALARM FEB 21, 2020 11:01 AM FEB 7, 2019 10:21 AM JAN 16, 2018 11:18 AM LOW TEMP WARNING FEB 7, 2019 10:12 AM TANK 5 TANK 6 TANK 7 TANK 8 +AAM- +AAE- I30200 FEB 21, 2020 12:11 PM CARMAX 6801 COLONY ST. BAKERSFIELD,CA 93307 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 STP-SUMP SENSOR FEB 21, 2020 9:05 AM FUEL ALARM FEB 21, 2020 8:42 AM SENSOR OUT ALARM SEP 4, 2019 5:01 PM FUEL ALARM 2 STP HYDRO SENSOR FEB 21, 2020 9:05 AM FUEL ALARM FEB 21, 2020 8:42 AM SENSOR OUT ALARM NOV 20, 2019 3:37 AM FUEL ALARM 3 ANNULAR FEB 21, 2020 9:36 AM HIGH LIQUID ALARM FEB 21, 2020 9:36 AM LOW LIQUID ALARM FEB 21, 2020 8:42 AM SENSOR OUT ALARM 4 FILL-SUMP SENSOR FEB 21, 2020 9:35 AM FUEL ALARM FEB 21, 2020 8:42 AM SENSOR OUT ALARM FEB 7, 2019 9:30 AM SENSOR OUT ALARM 5 FILL HYDRO SENSOR FEB 21, 2020 10:29 AM FUEL ALARM FEB 21, 2020 8:42 AM SENSOR OUT ALARM FEB 7, 2019 9:28 AM SENSOR OUT ALARM 6 VENT-BOX SENSOR FEB 21, 2020 9:42 AM FUEL ALARM FEB 21, 2020 8:42 AM SENSOR OUT ALARM FEB 7, 2019 9:28 AM SENSOR OUT ALARM 7 VENT HYDRO SENSOR FEB 21, 2020 9:42 AM FUEL ALARM FEB 21, 2020 8:42 AM SENSOR OUT ALARM SEP 17, 2019 4:57 AM FUEL ALARM 8 DISPENSOR-PAN SENSOR FEB 21, 2020 8:50 AM FUEL ALARM FEB 21, 2020 8:42 AM SENSOR OUT ALARM FEB 7, 2019 9:30 AM SENSOR OUT ALARM 9 DISPENSOR HYDRO SENS FEB 21, 2020 8:55 AM FUEL ALARM FEB 21, 2020 8:42 AM SENSOR OUT ALARM FEB 7, 2019 9:28 AM SENSOR OUT ALARM +AAM- +AAE- I31600 FEB 21, 2020 12:11 PM CARMAX