HomeMy WebLinkAboutFMC 2020IMPACT VALVE LEAK DETECTOR MONITOR CERTIFICATION OVERFILL OPERABILITY SPILL BUCKET TEST 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 3/9/2020 BAKERSFIELD FIRE DEPARTMENT OFFICE OF ENVIRONMENTAL SERVICES INSPECTOR KRIS KARNS 1501 TRUXTUN AVE. BAKERSFIELD, CA 93301 Test Date: 3/5/2020 Order Number: 3447824 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 7-ELEVEN #32376, MKT 2368 9600 BRIMHALL RD. BAKERSFIELD, CA 93312 In an effort to keep all our record keeping and reporting requirements as current as possible, Tanknology kindly requests you notify Dawn Kohlmeyer in writing at dkohlmeyer@tanknology.com when your CUPA requires all records to be submitted electronically via the CERS database. Your assistance in this endeavor is greatly appreciated. Testing performed: Sincerely, Dawn Kohlmeyer Manager, Field Reporting LDT 5000 Field Test Apparatus Line Leak Detector Test Page 1 of 1 Work Order:3447824 Date:3/5/2020 Site Name / ID:7-ELEVEN #32376, MKT 2368 / 32376 Address:9600 BRIMHALL RD. City:BAKERSFIELD State:CA Zip:93312 Tank ID Product Product Line Tested From Existing/New Mechanical/Electronic Manufacturer/Model Serial No. Pump Operating Pressure (psi) Calibrated Leak (ml/min) Calibrated Leak (gph) Holding PSI *N/A for Electronic LD's Resiliency (ml) *N/A for Electronic LD's Metering PSI *N/A for Electronic LD's Opening Time (sec) *N/A for Electronic LD's Test Results T2 RUL RUL 1 3 Existing Mechanical Vaporless LD-2000 02164 28.00 189.0 3.00 28.00 200.00 20 12 Pass T3 PUL PUL 1 3 Existing Mechanical Vaporless LD-2000 08041485 27.00 189.0 2.00 27.00 275.00 15 20 Pass Technician Comments: Technician Name:Edwin Pineda Certification #:2344 Technician Signature:Expire Date:12/18/2020 Environmental Compliance for Petroleum Systems © 2020 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Impact Valve Inspection Impact Valve Operational Inspection Work Order:3447824 Date:3/5/2020 Site Name/ID:7-ELEVEN #32376, MKT 2368 Address:9600 BRIMHALL RD. City:BAKERSFIELD State:CA Zip:93312 How Inspected: Line Test NFPA 30A PEI RP1200 Other Dispenser Number Grade Secure Mount? Valve Lock?Pass/ Fail Comments 1/2 87 Pass Fail Not Tested 1/2 91 Pass Fail Not Tested 3/4 87 Pass Fail Not Tested 3/4 91 Pass Fail Not Tested 5/6 87 Pass Fail Not Tested 5/6 91 Pass Fail Not Tested 7/8 87 Pass Fail Not Tested 7/8 91 Pass Fail Not Tested 9/10 87 Pass Fail Not Tested 9/10 91 Pass Fail Not Tested 11/12 87 Pass Fail Not Tested 11/12 91 Pass Fail Not Tested Technician Comments: Technician Name:Edwin Pineda Signature: Environmental Compliance for Petroleum Systems ©2020 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 1 of 6) This form must be used to document testing and servicing of underground storage tank (UST) monitoring equipment. A copy of this form must be provided to the UST owner or operator. The owner or operator must submit a copy of this form to the local agency regulating the USTs within 30 days of the date of the monitoring system certification. I. FACILITY INFORMATION CERS ID 10024396 Date of Monitoring System Certification 3/5/2020 Business Name (Same as Facility Name or DBA-Doing Business As.) 7-ELEVEN #32376, MKT 2368 Building # Business Site Address 9600 BRIMHALL RD. City: BAKERSFIELD Zip: 93312 II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of Company Performing the Certification TANKNOLOGY INC. Phone # (800) 800-4633 Ext. Mailing Address 11000 N. Mopac Expressway #500, Austin, TX 78759 Name of UST Service Technician Performing the Certification (Print as shown on the ICC Certification.) Edwin Pineda Contractor/Tank Tester License # Class A General Engineering 743160 ICC Certification # 8373052 ICC Certification Expiration Date 6/17/2021 Monitoring System Training and Certifications (List all applicable certifications.) Expiration Date Tanknology Certification Level III ATG Operability Training Certification Exam 63535 06/24/2021 ICC CA UST Service Technician 8373052 06/17/2021 Veeder Root VR Level 4 B37453 12/11/2020 VMI TLDT-5000 Tester 2344 12/18/2020 III. RESULTS OF TESTING/SERVICING Indicate and attach the following reports if the monitoring equipment is capable of generating either. Monitoring System Set-up Alarm History Report Y N NA Was any monitoring equipment replaced? (If "Yes,"identify the specific devices replaced and list the manufacturer and model for all replacement parts in section IV below.) Was damage, debris, or liquid found inside any secondary containment systems? (If "Yes," describe what was found in section IV below.) Is all monitoring equipment operational per manufacturer's specifications? (If "No," describe why in section IV below.) IV. COMMENTS If directed to use this section, describe how and when the issues were or will be corrected. V. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING I hereby certify that the equipment identified in this document was inspected/serviced in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638 and all information contained herein is true and accurate. Attached to this certification is information (e.g., manufacturers' checklists, monitoring system set-up, alarm history report, etc.) necessary to verify that this information and the site plan showing the layout of UST system is complete and accurate. UST Service Technician Signature CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 2 of 6) VI. INVENTORY OF EQUIPMENT CERTIFIED A separate Monitoring System Certification Form must be prepared for each monitoring system control panel. Make of Monitoring System Control Panel Veeder Root Model of Monitoring System Control Panel TLS-350 Software Version Installed 329.02 Check the appropriate boxes to indicate specific equipment inspected/serviced. Monitoring Device Used Device Model # Tank ID: T2 RUL Gasoline - Regular (By tank number, stored product, etc.) In-tank Gauging (SW Tank)846390-107 Annular Space or Vault Sensor 794390-420 VPH Sensor Product Piping Mechanical LLD LD-2000 Electronic LLD VPH Sensor (Piping) Sump Sensor 794380-352 VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor 794380-208 VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Monitoring Device Used Device Model # Tank ID: T3 PUL Gasoline - Premium (By tank number, stored product, etc.) In-tank Gauging (SW Tank)846390-107 Annular Space or Vault Sensor 794390-420 VPH Sensor Product Piping Mechanical LLD LD-2000 Electronic LLD VPH Sensor (Piping) Sump Sensor 794380-352 VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor 794380-208 VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Monitoring Device Used Device Model # Tank ID: (By tank number, stored product, etc.) In-tank Gauging (SW Tank) Annular Space or Vault Sensor VPH Sensor Product Piping Mechanical LLD Electronic LLD VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Monitoring Device Used Device Model # Tank ID: (By tank number, stored product, etc.) In-tank Gauging (SW Tank) Annular Space or Vault Sensor VPH Sensor Product Piping Mechanical LLD Electronic LLD VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Fill Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vent Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) Vapor Recovery Piping VPH Sensor (Piping) Sump Sensor VPH Sensor (Sump) CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 3 of 6) Monitoring Device Used Device Model #Monitoring Device Used Device Model # Vent/Transition Sump ID: Vent/Transition Sump ID: Sump Sensor Sump Sensor VPH Sensor VPH Sensor UDC ID: 1/2 Electronic Sensor 794380-352 Mechanical Device VPH Sensor UDC ID: 3/4 Electronic Sensor 794380-352 Mechanical Device VPH Sensor UDC ID: 5/6 Electronic Sensor 794380-352 Mechanical Device VPH Sensor UDC ID: 7/8 Electronic Sensor 794380-352 Mechanical Device VPH Sensor UDC ID: 9/10 Electronic Sensor 794380-208 Mechanical Device VPH Sensor UDC ID: 11/12 Electronic Sensor 794380-352 Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor UDC ID: Electronic Sensor Mechanical Device VPH Sensor Other Monitored Component ID: Other Monitored Component ID: Other(Specify in section VII) Other(Specify in section VII) Other Monitored Component ID: Other Monitored Component ID: Other(Specify in section VII) Other(Specify in section VII) Other Monitored Component ID: Other Monitored Component ID: Other(Specify in section VII) Other(Specify in section VII) Include information for every underground storage tank component monitored by this monitoring system control panel. If the monitoring system control panel monitors more components than this form accommodates, additoinal copies of these pages may be attached. VII. COMMENTS Use this section to provide any additional comments about the inventory of the equipment certified. CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 4 of 6) VIII. MONITORING SYSTEM AND PROGRAMMING This section must be completed if a monitoring panel is used to perform leak detection monitoring.Y N NA Are the visual and audible alarms operational? Were all sensors visually inspected for kinks and breaks in the cables and for residual buildup to ensure that floats move freely, functionally tested, and confirmed operational? Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Was monitoring system set-up reviewed to ensure proper settings? Was the monitoring panel's backup battery visually inspected, functionally tested, and confirmed operational? Does the flow of fuel stop at the dispenser if a leak is detected in the under-dispenser containment? Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? Does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak? Which sensors initiate positive shut down? (Check all that apply.) Sump Under-dispenser containment If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? For any answer of "N" above, describe in section IX how and when these deficiencies were or will be corrected. IX. COMMENTS Use this section to provide any additional comments about the inventory of the equipment certified. X. IN-TANK GAUGING TESTING Check this box if tank gauging is used only for inventory control. (Do not complete this section.) Check this box if NO tank gauging equipment is installed. (Do not complete this section.) This section must be completed if in-tank gauging is used to perform leak detection monitoring. Y N NA Has all input wiring been inspected for kinks and breaks in the cables and for proper entry and termination, including testing for ground faults? Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? Was accuracy of system's product level readings tested? Was accuracy of system's water level readings tested? Were all probes reinstalled properly? Were all items on the equipment manufacturer's maintenance checklist completed? For any answer of "N" above, describe in section XI how and when these deficiencies were or will be corrected. XI. COMMENTS Use this section to provide any additional comments about the inventory of the equipment certified. Y = Yes, N = No, NA = Not Applicable UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 5 of 6) XVI. LINE LEAK DETECTOR TESTING Check this box if line leak detectors (LLD) are NOT installed. (Do not complete this section.) This section must be completed if LLDs are installed.Y N NA Was a leak simulated to verify LLD performance? (Check all that apply.) Simulated leak rate verified: 3 GPH 1.1 GPH 0.2 GPH Was the testing apparatus properly calibrated? For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? For mechanical LLDs, does the LLD restrict the flow through the pipe when a leak is detected? For electronic LLDs, does the turbine automatically shut off when a leak is detected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? Were all items on the equipment manufacturer's maintenance checklist completed? Were all LLDs confirmed operational within regulatory requirements? For any answer of "N" above, describe in section XIII how and when these issues were or will be corrected. XIII. COMMENTS XIV. VACUUM / PRESSURE/ HYDROSTATIC MONITORING EQUIPMENT TESTING Check this box if VPH monitoring is NOT used. (Do not complete this section.) This section must be completed if VPH monitoring is used to perform leak detection monitoring. System Type (Mark all that apply.) Vacuum Pressure Hydrostatic Sensor ID Component(s) Monitored by this Sensor Sensor Functionality Test Interstitial Communication Test Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail How was interstitial communication verified? Simulated leak at far ends of the interstitial space. Other (Describe the method in section XV below.) Visual Inspection Gauge Was the vacuum or pressure restored to operating levels in all interstitial spaces? Yes No (Describe the reason in section XV below.) For any answer of "N" above, describe in section XIII how and when these issues were or will be corrected. XV. COMMENTS GPH = Gallons per hour, Y = Yes, N = No, NA = Not applicable, VPH = Vacuum/Pressure/Hydrostatic, ID = Identification UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION FORM (Page 6 of 6) XVI. MONITORING SITE PLAN Date site map was prepared: If you already have a site plan that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and piping and clearly identify locations of the following equipment, if installed: 1) monitoring system control panels; 2) in-tank liquid level probes (if used for leak detection); 3) devices monitoring tank annular spaces or vault; 4) devices monitoring product piping; 5) devices monitoring fill piping; 6) devices monitoring vent piping; 7) devices monitoring vapor recovery piping; 8) devices monitoring vent/transition sumps; 9) devices monitoring under-dispenser containment; 10) line leak detectors; and 11) devices monitoring any other secondary containment areas. UNDERGROUND STORAGE TANK SPILL CONTAINER TESTING REPORT FORM (Page 1 of 1) Type of Action Installation Test Repair Test 12 Month Test I. FACILITY INFORMATION CERS ID 10024396 Date of Spill Container Test: 3/5/2020 Business Name (Same as Facility Name or DBA-Doing Business As.) 7-ELEVEN #32376, MKT 2368 Business Site Address 9600 BRIMHALL RD. City: BAKERSFIELD Zip: 93312 II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.) Edwin Pineda Phone # (800) 800-4633 Contractor/Tank Tester License # Class A General Engineering 743160 ICC Certification # 8373052 ICC Certification Expiration Date 6/17/2021 Spill Container Testing Training and Certifications (List applicable certifications.) ICC - CA UST Service Technician 8373052 06/17/2021 OPW - EVR Phase 1 100776 01/05/2021 III. SPILL CONTAINER TESTING INFORMATION Test Method Used: Manufacturer Guidelines: (Specify) Industry Code or Engineering Standard: (Specify) PEI RP 1200 Engineered Method: (Specify) Attach the testing procedures and all documentation required to determine the results. # of Attached Pages 2 Tank ID: (By tank number, stored product, etc.) Spill Container Manufacturer: Method of Cathodic Protection Inside Diameter of Spill Container: (Inches) Depth of Spill Container: (Inches) Does the spill container have a 5 gallon capacity? Method to Keep Spill Container Empty IV. Spill Container Test Results Fill T2 RUL RUL OPW Non-Metallic Isolation Other (Specify in section V) 12 15 Yes No Drain Valve Onsite Pump Other (Specify in section V) Fill T3 PUL PUL OPW Non-Metallic Isolation Other (Specify in section V) 12 15 Yes No Drain Valve Onsite Pump Other (Specify in section V) Non-Metallic Isolation Other (Specify in section V) Yes No Drain Valve Onsite Pump Other (Specify in section V) Non-Metallic Isolation Other (Specify in section V) Yes No Drain Valve Onsite Pump Other (Specify in section V) SUMMARY OF TESTING RESULTS Pass Fail Pass Fail Pass Fail Pass Fail V. COMMENTS All items marked failed above must be explained in this section. Any additional comments may also be provided here. VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1 and all the information contained herein is accurate. UST Service Technician Signature If the facility has more components than this form accommodates, additional copies of this page may be attached. CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 7-ELEVEN #32376, MKT 2368 Date of Testing: 3/5/2020 Facility Address: 9600 BRIMHALL RD. , BAKERSFIELD, CA 93312 Facility Contact: Joseph or Kuldip 3/26/15 Phone: 661-588-4059 Date Local Agency Was Notified of Testing: 1/30/2020 Name of Local Agency Inspector (if present during testing): Kris Karns 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY INC. Technician Conducting Test: Edwin Pineda Credentials1: CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s): A-743160-UST 8026748 3. SPILL BUCKET TESTING INFORMATION Test Method Used By: Hydrostatic Vacuum Other Test Equipment Used: LAKE TEST Equipment Resolution: 0.0625 in. Identify Spill Bucket (By Tank Number, Stored Product, etc.) Bucket Installation Type: Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test Test Start Time (TI): Initial Reading (RI): Test End Time(TF): Final Reading (RF): Test Duration(TF–TI): Change in Reading (RF–RI) : Pass/Fail Threshold or Criteria: Test Result: Spill Box # Tank T2 RUL RUL - Fill 1 - Direct - Below Grade in containment sump Direct Bury Contained in Sump 12.00 15.00 10 min 09:30:00 15.00 in. H20 10:30:00 15.00 in. H20 1 hr 0.00 in. H20 +/- 0.00 Pass Spill Box # Tank T3 PUL PUL - Fill 1 - Direct - Below Grade in containment sump Direct Bury Contained in Sump 12.00 15.00 10 min 09:30:00 15.00 in. H20 10:30:00 15.00 in. H20 1 hr 0.00 in. H20 +/- 0.00 Pass Spill Box # Direct Bury Contained in Sump min +/- Spill Box # Direct Bury Contained in Sump min +/- Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature:Date:3/5/2020 1State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. WO: 3447824 UNDERGROUND STORAGE TANK OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Page 1 of 1) Type of Action Installation Test Repair Test 36 Month Test I. FACILITY INFORMATION CERS ID 10024396 Date of Overfill Prevention Equipment Inspection: 3/5/2020 Business Name (Same as Facility Name or DBA-Doing Business As.) 7-ELEVEN #32376, MKT 2368 Business Site Address 9600 BRIMHALL RD. City: BAKERSFIELD Zip: 93312 II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.) Edwin Pineda Phone # (800) 800-4633 Contractor/Tank Tester License # Class A General Engineering 743160 ICC Certification # 8373052 ICC Certification Expiration Date 6/17/2021 Spill Container Testing Training and Certifications (List applicable certifications.) Veeder Root - VR Level 4 B37453 12/11/2020 ICC - CA UST Service Technician 8373052 06/17/2021 III. OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION Test Method Used: Manufacturer Guidelines (Specify) Veeder Root Industry Code or Engineering Standard (Specify) PEI RP 1200 Engineered Method (Specify) Attach the testing procedures and all documentation required to determine the results. # of Attached Pages: 1 Tank ID: (By tank number, stored product, etc.) What is the tank inside diameter? (Inches) Is the fill piping secondarily contained? Is the vent piping secondarily contained? Overfill Prevention Equipment Manufacturer(s) What is the overfill prevention equipment response when activated? (Check all that apply.) Are flow restrictors installed on vent piping? At what level in the tank is the overfill prevention set to activate? (Inches from bottom of tank.) What is the percent capacity of the tank at which the overfill prevention equipment activates? Is the overfill prevention in proper operating condition to respond when the substance reaches the appropriate level? IV. Overfill Prevention Inspection Results T2 RUL 95.88 in. Yes No Yes No Unknown other Shuts Off Flow Restrict Flow A/V Alarm Yes No 81.00" 90.0% Yes No (Specify in section V) T3 PUL 95.88 in. Yes No Yes No Unknown other Shuts Off Flow Restrict Flow A/V Alarm Yes No 81.00" 90.0% Yes No (Specify in section V) Yes No Yes No Shuts Off Flow Restrict Flow A/V Alarm Yes No Yes No (Specify in section V) Yes No Yes No Shuts Off Flow Restrict Flow A/V Alarm Yes No Yes No (Specify in section V) SUMMARY OF TESTING RESULTS Pass Fail Pass Fail Pass Fail Pass Fail V. COMMENTS All items marked failed above must be explained in this section. Any additional comments may also be provided here. Tested Overfill on Veeder Root only. VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1 and all the information contained herein is accurate. UST Service Technician Signature If the facility has more components than this form accommodates, additional copies of this page may be attached. CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:3447824 Site ID / Name:32376 / 7-ELEVEN #32376, MKT 2368 Address:9600 BRIMHALL RD. City:BAKERSFIELD State:CA Zip:93312 W.O.# SC1-3447824 SITE PIPING AND SENSOR LOCATIOS. W.O.# SC1-3447824 SETUP TAPES W.O.# SC1-3447824 W.O.# SC1-3447824 W.O.# SC1-3447824 W.O.# SC1-3447824 W.O.# SC1-3447824 ALARM HISTORY W.O.# SC1-3447824 W.O.# SC1-3447824 W.O.# SC1-3447824 PEI RP200 Modern Welding Company Subsidiaries Nationwide www.modweldco.com modern@modweldco.com Tank Calibration Chart Cylindrical Tank / Horizontal Orientation Striker Plate: 0 inches Diameter: 96.00 inchesLength: 320.04 inches Total Volume: 10,028 gallons Depth (inches) Volume (gallons) 0.000 0 0.125 1 0.250 2 0.375 4 0.500 6 0.625 9 0.750 12 0.875 15 1.000 18 1.125 22 1.250 25 1.375 29 1.500 33 1.625 37 1.750 42 1.875 46 2.000 51 2.125 56 2.250 61 2.375 66 2.500 71 2.625 76 2.750 82 2.875 87 3.000 93 3.125 99 3.250 105 3.375 111 3.500 117 3.625 123 3.750 130 3.875 136 4.000 143 4.125 150 4.250 156 4.375 163 Depth (inches) Volume (gallons) 4.500 170 4.625 177 4.750 185 4.875 192 5.000 199 5.125 207 5.250 214 5.375 222 5.500 229 5.625 237 5.750 245 5.875 253 6.000 261 6.125 269 6.250 277 6.375 285 6.500 294 6.625 302 6.750 311 6.875 319 7.000 328 7.125 336 7.250 345 7.375 354 7.500 363 7.625 372 7.750 381 7.875 390 8.000 399 8.125 408 8.250 418 8.375 427 8.500 436 8.625 446 8.750 455 8.875 465 Depth (inches) Volume (gallons) 9.000 475 9.125 484 9.250 494 9.375 504 9.500 514 9.625 524 9.750 534 9.875 544 10.000 554 10.125 564 10.250 575 10.375 585 10.500 595 10.625 606 10.750 616 10.875 627 11.000 637 11.125 648 11.250 658 11.375 669 11.500 680 11.625 691 11.750 702 11.875 713 12.000 724 12.125 735 12.250 746 12.375 757 12.500 768 12.625 779 12.750 790 12.875 802 13.000 813 13.125 824 13.250 836 13.375 847 Depth (inches) Volume (gallons) 13.500 859 13.625 870 13.750 882 13.875 894 14.000 905 14.125 917 14.250 929 14.375 941 14.500 953 14.625 965 14.750 977 14.875 989 15.000 1,001 15.125 1,013 15.250 1,025 15.375 1,037 15.500 1,049 15.625 1,062 15.750 1,074 15.875 1,086 16.000 1,099 16.125 1,111 16.250 1,123 16.375 1,136 16.500 1,148 16.625 1,161 16.750 1,174 16.875 1,186 17.000 1,199 17.125 1,212 17.250 1,224 17.375 1,237 17.500 1,250 17.625 1,263 17.750 1,276 17.875 1,289 Depth (inches) Volume (gallons) 18.000 1,302 18.125 1,315 18.250 1,328 18.375 1,341 18.500 1,354 18.625 1,367 18.750 1,380 18.875 1,393 19.000 1,407 19.125 1,420 19.250 1,433 19.375 1,446 19.500 1,460 19.625 1,473 19.750 1,487 19.875 1,500 20.000 1,514 20.125 1,527 20.250 1,541 20.375 1,554 20.500 1,568 20.625 1,581 20.750 1,595 20.875 1,609 21.000 1,623 21.125 1,636 21.250 1,650 21.375 1,664 21.500 1,678 21.625 1,692 21.750 1,706 21.875 1,720 22.000 1,733 22.125 1,747 22.250 1,761 22.375 1,776 Depth (inches) Volume (gallons) 22.500 1,790 22.625 1,804 22.750 1,818 22.875 1,832 23.000 1,846 23.125 1,860 23.250 1,875 23.375 1,889 23.500 1,903 23.625 1,917 23.750 1,932 23.875 1,946 24.000 1,961 24.125 1,975 24.250 1,989 24.375 2,004 24.500 2,018 24.625 2,033 24.750 2,047 24.875 2,062 25.000 2,077 25.125 2,091 25.250 2,106 25.375 2,120 25.500 2,135 25.625 2,150 25.750 2,164 25.875 2,179 26.000 2,194 26.125 2,209 26.250 2,224 26.375 2,238 26.500 2,253 26.625 2,268 26.750 2,283 26.875 2,298 Depth (inches) Volume (gallons) 27.000 2,313 27.125 2,328 27.250 2,343 27.375 2,358 27.500 2,373 27.625 2,388 27.750 2,403 27.875 2,418 28.000 2,433 28.125 2,448 28.250 2,463 28.375 2,479 28.500 2,494 28.625 2,509 28.750 2,524 28.875 2,539 29.000 2,555 29.125 2,570 29.250 2,585 29.375 2,601 29.500 2,616 29.625 2,631 29.750 2,647 29.875 2,662 30.000 2,677 30.125 2,693 30.250 2,708 30.375 2,724 30.500 2,739 30.625 2,755 30.750 2,770 30.875 2,786 31.000 2,801 31.125 2,817 31.250 2,832 31.375 2,848 Page 1 of 3 This volumetric tank chart is supplied to you for informational purposes only. These capacity calculations are based on theoretical volumes not actual volumes, and do not reflect atmospheric conditions or thermal expansion/contraction due to temperature changes. If internal accessories such as pumps are present, displacement of these accessories must be considered. Therefore, neither Modern Welding Company nor its officers, directors, employee affiliates or subsidiaries shall be liable for the use of this information covered within. This information is advisory only and the use of the material and methods issolely at the risk of the user. Depth (inches) Volume (gallons) 31.500 2,864 31.625 2,879 31.750 2,895 31.875 2,910 32.000 2,926 32.125 2,942 32.250 2,958 32.375 2,973 32.500 2,989 32.625 3,005 32.750 3,020 32.875 3,036 33.000 3,052 33.125 3,068 33.250 3,084 33.375 3,099 33.500 3,115 33.625 3,131 33.750 3,147 33.875 3,163 34.000 3,179 34.125 3,195 34.250 3,211 34.375 3,227 34.500 3,243 34.625 3,258 34.750 3,274 34.875 3,290 35.000 3,306 35.125 3,322 35.250 3,338 35.375 3,355 35.500 3,371 35.625 3,387 35.750 3,403 35.875 3,419 36.000 3,435 36.125 3,451 36.250 3,467 36.375 3,483 36.500 3,499 36.625 3,515 36.750 3,532 Depth (inches) Volume (gallons) 36.875 3,548 37.000 3,564 37.125 3,580 37.250 3,596 37.375 3,613 37.500 3,629 37.625 3,645 37.750 3,661 37.875 3,678 38.000 3,694 38.125 3,710 38.250 3,726 38.375 3,743 38.500 3,759 38.625 3,775 38.750 3,791 38.875 3,808 39.000 3,824 39.125 3,840 39.250 3,857 39.375 3,873 39.500 3,890 39.625 3,906 39.750 3,922 39.875 3,939 40.000 3,955 40.125 3,971 40.250 3,988 40.375 4,004 40.500 4,021 40.625 4,037 40.750 4,054 40.875 4,070 41.000 4,086 41.125 4,103 41.250 4,119 41.375 4,136 41.500 4,152 41.625 4,169 41.750 4,185 41.875 4,202 42.000 4,218 42.125 4,235 Depth (inches) Volume (gallons) 42.250 4,251 42.375 4,268 42.500 4,284 42.625 4,301 42.750 4,317 42.875 4,334 43.000 4,350 43.125 4,367 43.250 4,383 43.375 4,400 43.500 4,416 43.625 4,433 43.750 4,450 43.875 4,466 44.000 4,483 44.125 4,499 44.250 4,516 44.375 4,532 44.500 4,549 44.625 4,566 44.750 4,582 44.875 4,599 45.000 4,615 45.125 4,632 45.250 4,649 45.375 4,665 45.500 4,682 45.625 4,698 45.750 4,715 45.875 4,732 46.000 4,748 46.125 4,765 46.250 4,781 46.375 4,798 46.500 4,815 46.625 4,831 46.750 4,848 46.875 4,865 47.000 4,881 47.125 4,898 47.250 4,914 47.375 4,931 47.500 4,948 Depth (inches) Volume (gallons) 47.625 4,964 47.750 4,981 47.875 4,997 48.000 5,014 48.125 5,031 48.250 5,047 48.375 5,064 48.500 5,081 48.625 5,097 48.750 5,114 48.875 5,130 49.000 5,147 49.125 5,164 49.250 5,180 49.375 5,197 49.500 5,214 49.625 5,230 49.750 5,247 49.875 5,263 50.000 5,280 50.125 5,297 50.250 5,313 50.375 5,330 50.500 5,346 50.625 5,363 50.750 5,380 50.875 5,396 51.000 5,413 51.125 5,429 51.250 5,446 51.375 5,463 51.500 5,479 51.625 5,496 51.750 5,512 51.875 5,529 52.000 5,546 52.125 5,562 52.250 5,579 52.375 5,595 52.500 5,612 52.625 5,628 52.750 5,645 52.875 5,661 Depth (inches) Volume (gallons) 53.000 5,678 53.125 5,694 53.250 5,711 53.375 5,728 53.500 5,744 53.625 5,761 53.750 5,777 53.875 5,794 54.000 5,810 54.125 5,827 54.250 5,843 54.375 5,860 54.500 5,876 54.625 5,892 54.750 5,909 54.875 5,925 55.000 5,942 55.125 5,958 55.250 5,975 55.375 5,991 55.500 6,008 55.625 6,024 55.750 6,040 55.875 6,057 56.000 6,073 56.125 6,090 56.250 6,106 56.375 6,122 56.500 6,139 56.625 6,155 56.750 6,171 56.875 6,188 57.000 6,204 57.125 6,220 57.250 6,237 57.375 6,253 57.500 6,269 57.625 6,286 57.750 6,302 57.875 6,318 58.000 6,334 58.125 6,351 58.250 6,367 Depth (inches) Volume (gallons) 58.375 6,383 58.500 6,399 58.625 6,416 58.750 6,432 58.875 6,448 59.000 6,464 59.125 6,480 59.250 6,497 59.375 6,513 59.500 6,529 59.625 6,545 59.750 6,561 59.875 6,577 60.000 6,593 60.125 6,609 60.250 6,626 60.375 6,642 60.500 6,658 60.625 6,674 60.750 6,690 60.875 6,706 61.000 6,722 61.125 6,738 61.250 6,754 61.375 6,770 61.500 6,786 61.625 6,802 61.750 6,818 61.875 6,834 62.000 6,849 62.125 6,865 62.250 6,881 62.375 6,897 62.500 6,913 62.625 6,929 62.750 6,945 62.875 6,960 63.000 6,976 63.125 6,992 63.250 7,008 63.375 7,024 63.500 7,039 63.625 7,055 Depth (inches) Volume (gallons) 63.750 7,071 63.875 7,086 64.000 7,102 64.125 7,118 64.250 7,133 64.375 7,149 64.500 7,165 64.625 7,180 64.750 7,196 64.875 7,211 65.000 7,227 65.125 7,243 65.250 7,258 65.375 7,274 65.500 7,289 65.625 7,305 65.750 7,320 65.875 7,335 66.000 7,351 66.125 7,366 66.250 7,382 66.375 7,397 66.500 7,412 66.625 7,428 66.750 7,443 66.875 7,458 67.000 7,474 67.125 7,489 67.250 7,504 67.375 7,519 67.500 7,534 67.625 7,550 67.750 7,565 67.875 7,580 68.000 7,595 68.125 7,610 68.250 7,625 68.375 7,640 68.500 7,655 68.625 7,670 68.750 7,685 68.875 7,700 69.000 7,715 Cylindrical Tank / Horizontal OrientationStriker Plate: 0 Arraydepth | Diameter: 96.00 inches | Length: 320.04 inches | Total Volume: 10,028 gallons Page 2 of 3 Depth (inches) Volume (gallons) 69.125 7,730 69.250 7,745 69.375 7,760 69.500 7,775 69.625 7,790 69.750 7,805 69.875 7,819 70.000 7,834 70.125 7,849 70.250 7,864 70.375 7,878 70.500 7,893 70.625 7,908 70.750 7,923 70.875 7,937 71.000 7,952 71.125 7,966 71.250 7,981 71.375 7,995 71.500 8,010 71.625 8,024 71.750 8,039 71.875 8,053 72.000 8,068 72.125 8,082 72.250 8,096 72.375 8,111 72.500 8,125 72.625 8,139 72.750 8,154 72.875 8,168 73.000 8,182 73.125 8,196 73.250 8,210 73.375 8,225 73.500 8,239 73.625 8,253 73.750 8,267 73.875 8,281 74.000 8,295 74.125 8,309 74.250 8,323 74.375 8,337 Depth (inches) Volume (gallons) 74.500 8,350 74.625 8,364 74.750 8,378 74.875 8,392 75.000 8,406 75.125 8,419 75.250 8,433 75.375 8,447 75.500 8,460 75.625 8,474 75.750 8,488 75.875 8,501 76.000 8,515 76.125 8,528 76.250 8,542 76.375 8,555 76.500 8,568 76.625 8,582 76.750 8,595 76.875 8,608 77.000 8,622 77.125 8,635 77.250 8,648 77.375 8,661 77.500 8,674 77.625 8,687 77.750 8,701 77.875 8,714 78.000 8,727 78.125 8,740 78.250 8,752 78.375 8,765 78.500 8,778 78.625 8,791 78.750 8,804 78.875 8,817 79.000 8,829 79.125 8,842 79.250 8,855 79.375 8,867 79.500 8,880 79.625 8,892 79.750 8,905 Depth (inches) Volume (gallons) 79.875 8,917 80.000 8,930 80.125 8,942 80.250 8,954 80.375 8,967 80.500 8,979 80.625 8,991 80.750 9,003 80.875 9,015 81.000 9,028 81.125 9,040 81.250 9,052 81.375 9,064 81.500 9,075 81.625 9,087 81.750 9,099 81.875 9,111 82.000 9,123 82.125 9,134 82.250 9,146 82.375 9,158 82.500 9,169 82.625 9,181 82.750 9,192 82.875 9,204 83.000 9,215 83.125 9,227 83.250 9,238 83.375 9,249 83.500 9,260 83.625 9,272 83.750 9,283 83.875 9,294 84.000 9,305 84.125 9,316 84.250 9,327 84.375 9,338 84.500 9,348 84.625 9,359 84.750 9,370 84.875 9,380 85.000 9,391 85.125 9,402 Depth (inches) Volume (gallons) 85.250 9,412 85.375 9,423 85.500 9,433 85.625 9,443 85.750 9,454 85.875 9,464 86.000 9,474 86.125 9,484 86.250 9,494 86.375 9,504 86.500 9,514 86.625 9,524 86.750 9,534 86.875 9,544 87.000 9,554 87.125 9,563 87.250 9,573 87.375 9,582 87.500 9,592 87.625 9,601 87.750 9,611 87.875 9,620 88.000 9,629 88.125 9,638 88.250 9,647 88.375 9,656 88.500 9,665 88.625 9,674 88.750 9,683 88.875 9,692 89.000 9,700 89.125 9,709 89.250 9,718 89.375 9,726 89.500 9,734 89.625 9,743 89.750 9,751 89.875 9,759 90.000 9,767 90.125 9,775 90.250 9,783 90.375 9,791 90.500 9,799 Depth (inches) Volume (gallons) 90.625 9,807 90.750 9,814 90.875 9,822 91.000 9,829 91.125 9,836 91.250 9,844 91.375 9,851 91.500 9,858 91.625 9,865 91.750 9,872 91.875 9,879 92.000 9,885 92.125 9,892 92.250 9,898 92.375 9,905 92.500 9,911 92.625 9,917 92.750 9,923 92.875 9,929 93.000 9,935 93.125 9,941 93.250 9,946 93.375 9,952 93.500 9,957 93.625 9,962 93.750 9,968 93.875 9,973 94.000 9,977 94.125 9,982 94.250 9,987 94.375 9,991 94.500 9,995 94.625 9,999 94.750 10,003 94.875 10,007 95.000 10,010 95.125 10,013 95.250 10,017 95.375 10,019 95.500 10,022 95.625 10,024 95.750 10,026 95.875 10,027 Depth (inches) Volume (gallons) 96.000 10,028 Cylindrical Tank / Horizontal OrientationStriker Plate: 0 Arraydepth | Diameter: 96.00 inches | Length: 320.04 inches | Total Volume: 10,028 gallons