81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
7KLVIRUPPXVWEHXVHGWRGRFXPHQWWHVWLQJDQGVHUYLFLQJRIXQGHUJURXQGVWRUDJHWDQN867PRQLWRULQJHTXLSPHQW$FRS\
RIWKLVIRUPPXVWEHSURYLGHGWRWKH867RZQHURURSHUDWRU7KHRZQHURURSHUDWRUPXVWVXEPLWDFRS\RIWKLVIRUPWRWKHORFDO
DJHQF\UHJXODWLQJWKH867VZLWKLQGD\VRIWKHGDWHRIWKHPRQLWRULQJV\VWHPFHUWLILFDWLRQ
, )$&,/,7<,1)250$7,21
&(56,''DWHRI0RQLWRULQJ6\VWHP&HUWLILFDWLRQ
%XVLQHVV1DPH(Same as Facility Name or DBA-Doing Business As)
%XVLQHVV6LWH$GGUHVV &LW\ =,3&RGH
,, 81'(5*5281'6725$*(7$1.6(59,&(7(&+1,&,$1,1)250$7,21
1DPHRI&RPSDQ\3HUIRUPLQJWKH&HUWLILFDWLRQ 3KRQH
0DLOLQJ$GGUHVV
1DPHRI8676HUYLFH7HFKQLFLDQ3HUIRUPLQJWKH&HUWLILFDWLRQ(Print as shown on the ICC Certification)
&RQWUDFWRU7DQN7HVWHU/LFHQVH ,&&&HUWLILFDWLRQ ,&&&HUWLILFDWLRQ([SLUDWLRQ'DWH
0RQLWRULQJ6\VWHP7UDLQLQJDQG&HUWLILFDWLRQV(List all applicable certifications.) ([SLUDWLRQ'DWH
,,, 5(68/762)7(67,1*6(59,&,1*
Indicate and attach the following reports if the monitoring equipment is capable of generating either.<11$0RQLWRULQJ6\VWHP6HWXS$ODUP+LVWRU\5HSRUW
:DVDQ\PRQLWRULQJHTXLSPHQWUHSODFHG"
(If “Yes,” identify the specific devices replaced and list the manufacturer and model for all replacement parts in section IV below.)
:DVGDPDJHGHEULVRUOLTXLGIRXQGLQVLGHDQ\VHFRQGDU\FRQWDLQPHQWV\VWHPV"
(If “Yes,” describe what was found in section IV below.)
,VDOOPRQLWRULQJHTXLSPHQWRSHUDWLRQDOSHUPDQXIDFWXUHU¶VVSHFLILFDWLRQV"
(If “No,” describe why in section IV below.)
,9 &200(176
If directed to use this section, describe how and when the issues were or will be corrected.
9 &(57,),&$7,21%<8676(59,&(7(&+1,&,$1&21'8&7,1*7+,67(67,1*
,KHUHE\FHUWLI\WKDWWKHHTXLSPHQWLGHQWLILHGLQWKLVGRFXPHQWZDVLQVSHFWHGVHUYLFHGLQDFFRUGDQFHZLWK&DOLIRUQLD&RGHRI
5HJXODWLRQV7LWOH'LYLVLRQ&KDSWHU6HFWLRQDQGDOOLQIRUPDWLRQFRQWDLQHGKHUHLQLVWUXHDQGDFFXUDWH$WWDFKHGWR
WKLVFHUWLILFDWLRQLVLQIRUPDWLRQHJPDQXIDFWXUHUV
FKHFNOLVWVPRQLWRULQJV\VWHPVHWXSDODUPKLVWRU\UHSRUWHWFQHFHVVDU\
WRYHULI\WKDWWKLVLQIRUPDWLRQDQGWKHVLWHSODQVKRZLQJWKHOD\RXWRI867V\VWHPLVFRPSOHWHDQGDFFXUDWH
8676HUYLFH7HFKQLFLDQ6LJQDWXUH
%XLOGLQJ
10026730 8/21/2019
Circle K (Mobil)
2601 White Lane Bakersfield 93304
16250 Meacham Road, Bakersfield, CA 93314
Matthew Story
804904 9118985 3/30/2021
Veeder Root C26845 6/5/2021
Replaced Veeder Root 794380-208 sensor in 87 STP sump retested with pass
Confidence UST Services, Inc. (800) 339-9930
,' ,GHQWLILFDWLRQ6: 6LQJOH:DOOHG93+ 9DFXXP3UHVVXUH+\GURVWDWLF//' /LQH/HDN'HWHFWRU
81 ZZZXQLGRFVRUJ 5HY
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
9, ,19(1725<2)(48,30(17&(57,),('
A separate Monitoring System Certification Form must be prepared for each monitoring system control panel.
0DNHRI0RQLWRULQJ6\VWHP&RQWURO3DQHO
0RGHORI0RQLWRULQJ6\VWHP&RQWURO3DQHO
6RIWZDUH9HUVLRQ,QVWDOOHG
Check the appropriate boxes to indicate specific equipment inspected/serviced.
0RQLWRULQJ'HYLFH8VHG'HYLFH0RGHO0RQLWRULQJ'HYLFH8VHG'HYLFH0RGHO
7$1.,'
(By tank number, stored product, etc.)
7$1.,'
(By tank number, stored product, etc.)
,Q7DQN*DXJLQJ(SW Tank),Q7DQN*DXJLQJ(SW Tank)
$QQXODU6SDFHRU9DXOW6HQVRU$QQXODU6SDFHRU9DXOW6HQVRU
93+6HQVRU93+6HQVRU
3URGXFW3LSLQJ3URGXFW3LSLQJ
0HFKDQLFDO//'0HFKDQLFDO//'
(OHFWURQLF//'(OHFWURQLF//'
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
)LOO3LSLQJ)LOO3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
9HQW3LSLQJ9HQW3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
9DSRU5HFRYHU\3LSLQJ9DSRU5HFRYHU\3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
0RQLWRULQJ'HYLFH8VHG
'HYLFH0RGHO0RQLWRULQJ'HYLFH8VHG
'HYLFH0RGHO
7$1.,'
(By tank number, stored product, etc.)
7$1.,'
(By tank number, stored product, etc.)
,Q7DQN*DXJLQJ(SW Tank),Q7DQN*DXJLQJ(SW Tank)
$QQXODU6SDFHRU9DXOW6HQVRU$QQXODU6SDFHRU9DXOW6HQVRU
93+6HQVRU93+6HQVRU
3URGXFW3LSLQJ3URGXFW3LSLQJ
0HFKDQLFDO//'0HFKDQLFDO//'
(OHFWURQLF//'(OHFWURQLF//'
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
)LOO3LSLQJ)LOO3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
9HQW3LSLQJ9HQW3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
9DSRU5HFRYHU\3LSLQJ9DSRU5HFRYHU\3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
Veeder Root TLS-350 334.01
T1;87
847390-107
794390-420
FX1V
794380-208
794380-208
794380-208
794380-208
T2;91
847390-107
794390-420
FX1V
794380-208
794380-208
794380-208
794380-208
,' ,GHQWLILFDWLRQ93+ 9DFXXP3UHVVXUH+\GURVWDWLF8'& 8QGHU'LVSHQVHU&RQWDLQPHQW
81 ZZZXQLGRFVRUJ 5HY
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
0RQLWRULQJ'HYLFH8VHG'HYLFH0RGHO0RQLWRULQJ'HYLFH8VHG'HYLFH0RGHO
9(1775$16,7,216803,'9(1775$16,7,216803,'
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU93+6HQVRU
8'&,'8'&,'
(OHFWURQLF6HQVRU(OHFWURQLF6HQVRU
0HFKDQLFDO'HYLFH0HFKDQLFDO'HYLFH
93+6HQVRU93+6HQVRU
8'&,'8'&,'
(OHFWURQLF6HQVRU(OHFWURQLF6HQVRU
0HFKDQLFDO'HYLFH0HFKDQLFDO'HYLFH
93+6HQVRU93+6HQVRU
8'&,'8'&,'
(OHFWURQLF6HQVRU(OHFWURQLF6HQVRU
0HFKDQLFDO'HYLFH0HFKDQLFDO'HYLFH
93+6HQVRU93+6HQVRU
8'&,'8'&,'
(OHFWURQLF6HQVRU(OHFWURQLF6HQVRU
0HFKDQLFDO'HYLFH0HFKDQLFDO'HYLFH
93+6HQVRU93+6HQVRU
2WKHU0RQLWRUHG&RPSRQHQW,'2WKHU0RQLWRUHG&RPSRQHQW,'
2WKHU(Specify in section VII.)2WKHU(Specify in section VII.)
2WKHU0RQLWRUHG&RPSRQHQW,'2WKHU0RQLWRUHG&RPSRQHQW,'
2WKHU(Specify in section VII.)2WKHU(Specify in section VII.)
2WKHU0RQLWRUHG&RPSRQHQW,'2WKHU0RQLWRUHG&RPSRQHQW,'
2WKHU(Specify in section VII.)2WKHU(Specify in section VII.)
Include information for every underground storage tank component monitored by this monitoring system control panel. If the monitoring system
control panel monitors more components than this form accommodates, additional copies of these pages may be attached.
9,, &200(176
Use this section to provide additional comments about the inventory of the equipment certified.
1/2
794380-208
3/4
794380-208
5/6
794380-208
7/8
794380-208
< <HV1 1R1$ 1RW$SSOLFDEOH
81 ZZZXQLGRFVRUJ 5HY
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
9,,, 021,725,1*6<67(0$1'352*5$00,1*
This section must be completed if a monitoring panel is used to perform leak detection monitoring.<11$
$UHWKHYLVXDODQGDXGLEOHDODUPVRSHUDWLRQDO"
:HUHDOOVHQVRUVYLVXDOO\LQVSHFWHGIRUNLQNVDQGEUHDNVLQWKHFDEOHVDQGIRUUHVLGXDOEXLOGXSWRHQVXUHWKDWIORDWVPRYHIUHHO\
IXQFWLRQDOO\WHVWHGDQGFRQILUPHGRSHUDWLRQDO"
:HUHDOOVHQVRUVLQVWDOOHGDWORZHVWSRLQWRIVHFRQGDU\FRQWDLQPHQWDQGSRVLWLRQHGVRWKDWRWKHUHTXLSPHQWZLOOQRWLQWHUIHUHZLWK
WKHLUSURSHURSHUDWLRQ"
:DVPRQLWRULQJV\VWHPVHWXSUHYLHZHGWRHQVXUHSURSHUVHWWLQJV"
:DVWKHPRQLWRULQJSDQHO¶VEDFNXSEDWWHU\YLVXDOO\LQVSHFWHGIXQFWLRQDOO\WHVWHGDQGFRQILUPHGRSHUDWLRQDO"
'RHVWKHIORZRIIXHOVWRSDWWKHGLVSHQVHULIDOHDNLVGHWHFWHGLQWKHXQGHUGLVSHQVHUFRQWDLQPHQW"
'RHVWKHWXUELQHDXWRPDWLFDOO\VKXWGRZQLIWKHSLSLQJVHFRQGDU\FRQWDLQPHQWPRQLWRULQJV\VWHPIDLOVWRRSHUDWHRULVHOHFWULFDOO\
GLVFRQQHFWHG"
'RHVWKHWXUELQHDXWRPDWLFDOO\VKXWGRZQLIWKHSLSLQJVHFRQGDU\FRQWDLQPHQWPRQLWRULQJV\VWHPGHWHFWVDOHDN"
:KLFKVHQVRUVLQLWLDWHSRVLWLYHVKXWGRZQ"(Check all that apply.)6XPS8QGHU'LVSHQVHU&RQWDLQPHQW
,IDODUPVDUHUHOD\HGWRDUHPRWHPRQLWRULQJVWDWLRQLVDOOFRPPXQLFDWLRQVHTXLSPHQWHJPRGHPRSHUDWLRQDO"
For any answer of “N” above, describe in Section IX how and when these deficiencies were or will be corrected.
,; &200(176
; ,17$1.*$8*,1*7(67,1*
&KHFNWKLVER[LIWDQNJDXJLQJLVXVHGRQO\IRULQYHQWRU\FRQWURO(Do not complete this section.)
<11$&KHFNWKLVER[LI12WDQNJDXJLQJHTXLSPHQWLVLQVWDOOHG (Do not complete this section.)
This section must be completed if in-tank gauging is used to perform leak detection monitoring.
+DVDOOLQSXWZLULQJEHHQLQVSHFWHGIRUNLQNVDQGEUHDNVLQWKHFDEOHVDQGIRUSURSHUHQWU\DQGWHUPLQDWLRQLQFOXGLQJWHVWLQJIRU
JURXQGIDXOWV"
:HUHDOOLQWDQNJDXJLQJSUREHVYLVXDOO\LQVSHFWHGIRUGDPDJHDQGUHVLGXHEXLOGXSWRHQVXUHWKDWIORDWVPRYHIUHHO\IXQFWLRQDOO\
WHVWHGDQGFRQILUPHGRSHUDWLRQDO"
:DVDFFXUDF\RIV\VWHP¶VSURGXFWOHYHOUHDGLQJVWHVWHG"
:DVDFFXUDF\RIV\VWHP¶VZDWHUOHYHOUHDGLQJVWHVWHG"
:HUHDOOSUREHVUHLQVWDOOHGSURSHUO\"
:HUHDOOLWHPVRQWKHHTXLSPHQWPDQXIDFWXUHU¶VPDLQWHQDQFHFKHFNOLVWFRPSOHWHG"
For any answer of “N” above, describe in Section XI how and when these deficiencies were or will be corrected.
;, &200(176
*3+ *DOORQV3HU+RXU< <HV1 1R1$ 1RW$SSOLFDEOH93+ 9DFXXP3UHVVXUH+\GURVWDWLF,' ,GHQWLILFDWLRQ
81 ZZZXQLGRFVRUJ5HY
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
;,, /,1(/($.'(7(&7257(67,1*
&KHFNWKLVER[LIOLQHOHDNGHWHFWRUV//'DUH127LQVWDOOHG(Do not complete this section.)<11$This section must be completed if LLDs are installed.
:DVDOHDNVLPXODWHGWRYHULI\//'SHUIRUPDQFH"
(Check all that apply.)6LPXODWHGOHDNUDWHYHULILHG*3+*3+*3+
:DVWKHWHVWLQJDSSDUDWXVSURSHUO\FDOLEUDWHG"
)RUHPHUJHQF\JHQHUDWRUWDQNV\VWHPVGRHVWKH//'FUHDWHDQDXGLEOHDQGYLVXDODODUPZKHQDOHDNLVGHWHFWHG"
)RUPHFKDQLFDO//'VGRHVWKH//'UHVWULFWWKHIORZWKURXJKWKHSLSHZKHQDOHDNLVGHWHFWHG"
)RUHOHFWURQLF//'VGRHVWKHWXUELQHDXWRPDWLFDOO\VKXWRIIZKHQDOHDNLVGHWHFWHG"
)RUHOHFWURQLF//'VGRHVWKHWXUELQHDXWRPDWLFDOO\VKXWRIILIDQ\SRUWLRQRIWKHPRQLWRULQJV\VWHPLVGLVDEOHGRUGLVFRQQHFWHG"
)RUHOHFWURQLF//'VGRHVWKHWXUELQHDXWRPDWLFDOO\VKXWRIILIDQ\SRUWLRQRIWKHPRQLWRULQJV\VWHPPDOIXQFWLRQVRUIDLOVDWHVW"
)RUHOHFWURQLF//'VKDYHDOODFFHVVLEOHZLULQJFRQQHFWLRQVEHHQYLVXDOO\LQVSHFWHGIRUNLQNVDQGEUHDNV"
:HUHDOOLWHPVRQWKHHTXLSPHQWPDQXIDFWXUHU¶VPDLQWHQDQFHFKHFNOLVWFRPSOHWHG"
:HUHDOO//'VFRQILUPHGRSHUDWLRQDOZLWKLQUHJXODWRU\UHTXLUHPHQWV"
For any answer of “N” above, describe in Section XIII how and when these issues were or will be corrected.
;,,, &200(176
;,9 9$&88035(6685(+<'5267$7,&021,725,1*(48,30(177(67,1*
&KHFNWKLVER[LI93+PRQLWRULQJLV127XVHG(Do not complete this section.)
This section must be completed if VPH monitoring is used to perform leak detection monitoring.
6\VWHP7\SH0DUNDOOWKDWDSSO\9DFXXP3UHVVXUH+\GURVWDWLF
6HQVRU,'&RPSRQHQW60RQLWRUHG%\7KLV6HQVRU 6HQVRU)XQFWLRQDOLW\
7HVW
,QWHUVWLWLDO&RPPXQLFDWLRQ
7HVW
3DVV )DLO 3DVV )DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
+RZZDVLQWHUVWLWLDOFRPPXQLFDWLRQYHULILHG"6LPXODWHG/HDNDW)DU(QGVRIWKH,QWHUVWLWLDO6SDFH9LVXDO,QVSHFWLRQ
2WKHU(Describe the method in section XV below.)*DXJH
:DVWKHYDFXXPRUSUHVVXUHUHVWRUHGWRRSHUDWLQJOHYHOVLQDOOLQWHUVWLWLDOVSDFHV"<HV1R(Describe the reason in section XV below.)
For any answer of “Fail” above, describe in Section XV how and when these issues were or will be corrected.
;9 &200(176
Setup
Responses Received:
200
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
AUG 21, 2019 8:37 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 PREM 91 2753 42.89 0.0 90.7 5247
2 UNLEADED 87 5133 50.52 0.0 90.8 6867
I90500
AUG 21, 2019 8:37 AM
SOFTWARE REVISION LEVEL
VERSION 334.01
SOFTWARE# 346334-100-B
CREATED - 17.01.09.16.10
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
AUG 21, 2019 8:37 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
AUG 21, 2019 8:37 AM
SHIFT TIME 1 : 12:00 AM
I50202
AUG 21, 2019 8:37 AM
SHIFT TIME 2 : DISABLED
I50203
AUG 21, 2019 8:37 AM
SHIFT TIME 3 : DISABLED
I50204
AUG 21, 2019 8:37 AM
SHIFT TIME 4 : DISABLED
I54600
AUG 21, 2019 8:37 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
AUG 21, 2019 8:37 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
AUG 21, 2019 8:37 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
AUG 21, 2019 8:37 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
AUG 21, 2019 8:37 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
AUG 21, 2019 8:37 AM
PRINT TC VOLUMES
ENABLED
I50E00
AUG 21, 2019 8:37 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
AUG 21, 2019 8:37 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
AUG 21, 2019 8:37 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
AUG 21, 2019 8:37 AM
DAYLIGHT SAVING TIME
DISABLED
I51B00
AUG 21, 2019 8:37 AM
I51600
AUG 21, 2019 8:37 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
AUG 21, 2019 8:37 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
AUG 21, 2019 8:37 AM
TANK CHART SECURITY
DISABLED
I5BD00
AUG 21, 2019 8:37 AM
CUSTOM ALARM LABELS
DISABLED
I56000
AUG 21, 2019 8:37 AM
MASS/DENSITY
DISABLED
I88101
AUG 21, 2019 8:37 AM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88102
AUG 21, 2019 8:37 AM
PORT SETTINGS:
COMM BOARD : 2 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88103
AUG 21, 2019 8:37 AM
I88104
AUG 21, 2019 8:37 AM
I88105
AUG 21, 2019 8:37 AM
I88106
AUG 21, 2019 8:37 AM
I52000
AUG 21, 2019 8:37 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE AUG 21, 2017 DISABLED
2 ON DATE AUG 21, 2017 DISABLED
3 ON DATE AUG 21, 2017 DISABLED
4 ON DATE AUG 21, 2017 DISABLED
5 ON DATE AUG 21, 2017 DISABLED
6 ON DATE AUG 21, 2017 DISABLED
7 ON DATE AUG 21, 2017 DISABLED
8 ON DATE AUG 21, 2017 DISABLED
I60100
AUG 21, 2019 8:37 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 PREM 91 ON
2 UNLEADED 87 ON
3 OFF
4 OFF
I60200
AUG 21, 2019 8:37 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 PREM 91
2 UNLEADED 87
3
4
I60300
AUG 21, 2019 8:37 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 PREM 91 2
2 UNLEADED 87 1
3 3
4 4
I60900
AUG 21, 2019 8:37 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 PREM 91 0.000700
2 UNLEADED 87 0.000700
3 0.000000
4 0.000000
I60700
AUG 21, 2019 8:37 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 PREM 91 114.00
2 UNLEADED 87 114.00
3 0.00
4 0.00
I60A00
AUG 21, 2019 8:37 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 PREM 91 1 PT 8000 2 UNLEADED 87 1 PT 12000 3
1 PT 0 4 1 PT 0
I60400
AUG 21, 2019 8:37 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 PREM 91 8000
2 UNLEADED 87 12000
3 0
4 0
I60500
AUG 21, 2019 8:37 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 PREM 91 8000 0 0 0
2 UNLEADED 87 12000 0 0 0
3 0 0 0 0
4 0 0 0 0
I60600
AUG 21, 2019 8:37 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 PREM 91 8000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 UNLEADED 87 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
AUG 21, 2019 8:37 AM
TANK PRODUCT LABEL METER DATA
1 PREM 91 NO
2 UNLEADED 87 NO
3 NO
4 NO
I62F00
AUG 21, 2019 8:37 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 PREM 91 4.0 IN.
2 UNLEADED 87 4.0 IN.
I62700
AUG 21, 2019 8:37 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 PREM 91 2.0
2 UNLEADED 87 2.0
I64200
AUG 21, 2019 8:37 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 PREM 91 LOW
2 UNLEADED 87 LOW
I62400
AUG 21, 2019 8:37 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 PREM 91 2.5
2 UNLEADED 87 2.5
I62800
AUG 21, 2019 8:37 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 8000
2 UNLEADED 87 12000
3 0
4 0
I62300
AUG 21, 2019 8:37 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 7200
2 UNLEADED 87 10800
3 0
4 0
I62200
AUG 21, 2019 8:37 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 7600
2 UNLEADED 87 11400
3 0
4 0
I62900
AUG 21, 2019 8:37 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 2000
2 UNLEADED 87 2040
3 0
4 0
I62100
AUG 21, 2019 8:37 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 500
2 UNLEADED 87 600
3 0
4 0
I62600
AUG 21, 2019 8:37 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 99
2 UNLEADED 87 99
3 99
4 99
I62500
AUG 21, 2019 8:37 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 99
2 UNLEADED 87 99
3 99
4 99
I60800
AUG 21, 2019 8:37 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 PREM 91 0.00
2 UNLEADED 87 0.00
3 0.00
4 0.00
I60B00
AUG 21, 2019 8:37 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
AUG 21, 2019 8:37 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 PREM 91 0.00
2 UNLEADED 87 0.00
3 0.00
4 0.00
I61200
AUG 21, 2019 8:37 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 PREM 91 NONE NONE
2 UNLEADED 87 NONE NONE
3 NONE NONE
4 NONE NONE
I63600
AUG 21, 2019 8:37 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 PREM 91 0
2 UNLEADED 87 0
3 0
4 0
I62A00
AUG 21, 2019 8:37 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 PREM 91 0
2 UNLEADED 87 0
3 0
4 0
I62C00
AUG 21, 2019 8:37 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 PREM 91 STANDARD
2 UNLEADED 87 STANDARD
3 STANDARD
4 STANDARD
I62D00
AUG 21, 2019 8:37 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 PREM 91 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 UNLEADED 87 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
AUG 21, 2019 8:37 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 PREM 91 OFF OFF
2 UNLEADED 87 OFF OFF
3 OFF OFF
4 OFF OFF
I63000
AUG 21, 2019 8:37 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 PREM 91 OFF
2 UNLEADED 87 OFF
3 OFF
4 OFF
I63200
AUG 21, 2019 8:37 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 PREM 91 OFF
2 UNLEADED 87 OFF
3 OFF
4 OFF
I61000
AUG 21, 2019 8:37 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 PREM 91 1
2 UNLEADED 87 1
3 1
4 1
I63A00
AUG 21, 2019 8:37 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 PREM 91 10.00%
2 UNLEADED 87 10.00%
3 10.00%
4 10.00%
I61100
AUG 21, 2019 8:37 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JAN 9, 2017
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
AUG 21, 2019 8:37 AM
CSLD PROBABLITY OF DETECTION
I61400
AUG 21, 2019 8:37 AM
CSLD CLIMATE FACTOR
I61600
AUG 21, 2019 8:38 AM
TANK PRODUCT LABEL CAL UPDATE
1 PREM 91 IMMEDIATE
2 UNLEADED 87 IMMEDIATE
3 IMMEDIATE
4 IMMEDIATE
I61A00
AUG 21, 2019 8:38 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 PREM 91 DISABLED
2 UNLEADED 87 DISABLED
3 DISABLED
4 DISABLED
I61B00
AUG 21, 2019 8:38 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
AUG 21, 2019 8:38 AM
CSLD REPORT ONLY
I62B00
AUG 21, 2019 8:38 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 PREM 91 ??? 0, 0
2 UNLEADED 87 ??? 0, 0
3 ??? 0, 0
4 ??? 0, 0
I63300
AUG 21, 2019 8:38 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
AUG 21, 2019 8:38 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 0
2 UNLEADED 87 0
3 0
4 0
I63500
AUG 21, 2019 8:38 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 1
2 UNLEADED 87 1
3 1
4 1
I63900
AUG 21, 2019 8:38 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 PREM 91
END FACTOR: NONE
2 UNLEADED 87
END FACTOR: NONE
3
END FACTOR: NONE
4
END FACTOR: NONE
I78000
AUG 21, 2019 8:38 AM
I77700
AUG 21, 2019 8:38 AM
I77800
AUG 21, 2019 8:38 AM
I78C00
AUG 21, 2019 8:38 AM
I78300
AUG 21, 2019 8:38 AM
I78F00
AUG 21, 2019 8:38 AM
I78700
AUG 21, 2019 8:38 AM
I70200
AUG 21, 2019 8:38 AM
LIQUID LABEL
DEVICE LABEL
1 91 STP
2 91 FILL SUMP
3 87 STP
4 87 FILL SUMP
5 UDC 1-2
6 UDC 3-4
7 UDC 5-6
8 UDC 7-8
9 ANNULAR 87-91
10
11
12
13
14
15
16
I70300
AUG 21, 2019 8:38 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 91 STP TRI-STATE (SINGLE FLOAT)
2 91 FILL SUMP TRI-STATE (SINGLE FLOAT)
3 87 STP TRI-STATE (SINGLE FLOAT)
4 87 FILL SUMP TRI-STATE (SINGLE FLOAT)
5 UDC 1-2 TRI-STATE (SINGLE FLOAT)
6 UDC 3-4 TRI-STATE (SINGLE FLOAT)
7 UDC 5-6 TRI-STATE (SINGLE FLOAT)
8 UDC 7-8 TRI-STATE (SINGLE FLOAT)
9 ANNULAR 87-91 TRI-STATE (SINGLE FLOAT)
10 TRI-STATE (SINGLE FLOAT)
11 TRI-STATE (SINGLE FLOAT)
12 TRI-STATE (SINGLE FLOAT)
13 TRI-STATE (SINGLE FLOAT)
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
AUG 21, 2019 8:38 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 91 STP STP SUMP
2 91 FILL SUMP PIPING SUMP
3 87 STP STP SUMP
4 87 FILL SUMP PIPING SUMP
5 UDC 1-2 DISPENSER PAN
6 UDC 3-4 DISPENSER PAN
7 UDC 5-6 DISPENSER PAN
8 UDC 7-8 DISPENSER PAN
9 ANNULAR 87-91 ANNULAR SPACE
10 OTHER SENSORS
11 OTHER SENSORS
12 OTHER SENSORS
13 OTHER SENSORS
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
AUG 21, 2019 8:38 AM
I74300
AUG 21, 2019 8:38 AM
I74400
AUG 21, 2019 8:38 AM
I74700
AUG 21, 2019 8:38 AM
I74800
AUG 21, 2019 8:38 AM
I74900
AUG 21, 2019 8:38 AM
I7BC00
AUG 21, 2019 8:38 AM
I80200
AUG 21, 2019 8:38 AM
I80300
AUG 21, 2019 8:38 AM
I80400
AUG 21, 2019 8:38 AM
I80700
AUG 21, 2019 8:38 AM
RELAY LABEL
DEVICE LABEL
1 87 UNLEADED
2 PREM 91
3
4
I80900
AUG 21, 2019 8:38 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 87 UNLEADED NORMALLY CLOSED
2 PREM 91 NORMALLY CLOSED
3 NORMALLY OPEN
4 NORMALLY OPEN
I80B00
AUG 21, 2019 8:38 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 87 UNLEADED 2
2 PREM 91 1
3 NONE
4 NONE
I80A00
AUG 21, 2019 8:38 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 87 UNLEADED STANDARD
2 PREM 91 STANDARD
3 STANDARD
4 STANDARD
I80C00
AUG 21, 2019 8:38 AM
I80800
AUG 21, 2019 8:38 AM
RELAY SETUP REPORT
R 1:87 UNLEADED
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
IN-TANK ALARMS
T 2:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:PREM 91
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
IN-TANK ALARMS
T 1:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 1:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
PMC ALARMS
VP EMISSIONS FAIL
R 3:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
AUG 21, 2019 8:38 AM
EDIM:1 VR:349867-001-D TD:17.02.14.08.38
I79100
AUG 21, 2019 8:38 AM
I72300
AUG 21, 2019 8:38 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VAPOR PRESSURE VAPOR PRESSURE
02 FLOW METER 1-2 AIR FLOW METER
03 FLOW METER 3-4 AIR FLOW METER
04 FLOW METER 5-6 AIR FLOW METER
05 FLOW METER 7-8 AIR FLOW METER
06 VP UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
AUG 21, 2019 8:38 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
AUG 21, 2019 8:38 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
AUG 21, 2019 8:38 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
VAPOR PROCESSOR TYPE
NONE
IV4700
AUG 21, 2019 8:38 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
AUG 21, 2019 8:38 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
ACCEPT HIGH ORVR: NO
IV4A00
AUG 21, 2019 8:38 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
IV4B00
AUG 21, 2019 8:38 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 01/01 09/01 xx/xx
02 01 02/02 01/02 09/02 xx/xx
03 02 02/03 01/03 09/03 xx/xx
04 02 02/04 01/04 09/04 xx/xx
05 03 02/05 01/05 09/05 xx/xx
06 03 02/06 01/06 09/06 xx/xx
07 04 02/07 01/07 09/07 xx/xx
08 04 02/08 01/08 09/08 xx/xx
IV4900
AUG 21, 2019 8:38 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
AUG 21, 2019 8:38 AM
ISD VERSION: 01.05
Alarm History (Before)
Responses Received:
I10200
AUG 21, 2019 8:41 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164738 163786
2 INTERSTITIAL BD 202007 201216
3 INTERSTITIAL BD 202007 201281
4 7SMARTSENSOR BD 507999 505729
5 UNUSED 9903073 9753909
6 UNUSED 9868832 9732643
7 UNUSED 9858988 9731113
8 UNUSED 9856420 9729102
9 RELAY BOARD 14987 14965
10 UNUSED 9859521 9737017
11 UNUSED 9850410 9725200
12 UNUSED 9848494 9725640
13 UNUSED 9844907 9727505
14 UNUSED 9838935 9722833
15 UNUSED 9845213 9723671
16 UNUSED 9841504 9721408
COMM 1 RS232 SERIAL BD 14946 14944
COMM 2 ELEC DISP INT. 101209 101023
COMM 3 UNUSED 9847618 9737709
COMM 4 UNUSED 9841748 9722791
COMM 5 UNUSED 9837448 9726269
COMM 6 UNUSED 9840158 9721366
I90200
AUG 21, 2019 8:41 AM
SOFTWARE REVISION LEVEL
VERSION 334.01
SOFTWARE# 346334-100-B
CREATED - 17.01.09.16.10
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 21, 2019 8:41 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
E 1 OTHER COMMUNICATION ALARM CLEAR 8-19-19 2:06AM
E 1 OTHER COMMUNICATION ALARM ALARM 8-19-19 2:04AM
E 1 OTHER COMMUNICATION ALARM CLEAR 8-12-19 2:07AM
E 1 OTHER COMMUNICATION ALARM ALARM 8-12-19 2:05AM
E 1 OTHER COMMUNICATION ALARM CLEAR 8-05-19 7:04AM
E 1 OTHER COMMUNICATION ALARM ALARM 8-05-19 7:02AM
E 1 OTHER COMMUNICATION ALARM CLEAR 8-05-19 2:10AM
E 1 OTHER COMMUNICATION ALARM ALARM 8-05-19 2:07AM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-29-19 2:06AM
E 1 OTHER COMMUNICATION ALARM ALARM 7-29-19 2:03AM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-22-19 2:16AM
E 1 OTHER COMMUNICATION ALARM ALARM 7-22-19 2:14AM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-19-19 6:20AM
E 1 OTHER COMMUNICATION ALARM ALARM 7-19-19 6:17AM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-19-19 6:11AM
E 1 OTHER COMMUNICATION ALARM ALARM 7-19-19 6:08AM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-15-19 2:10AM
E 1 OTHER COMMUNICATION ALARM ALARM 7-15-19 2:08AM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-08-19 2:04AM
E 1 OTHER COMMUNICATION ALARM ALARM 7-08-19 2:02AM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-01-19 2:16AM
E 1 OTHER COMMUNICATION ALARM ALARM 7-01-19 2:13AM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-24-19 2:07AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-24-19 2:05AM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-17-19 2:03AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-17-19 2:01AM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-15-19 1:54PM
E 1 OTHER COMMUNICATION ALARM ALARM 6-15-19 1:52PM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-10-19 2:03AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-10-19 2:01AM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-03-19 2:04AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-03-19 2:02AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-27-19 5:07AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-27-19 5:04AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-27-19 2:12AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-27-19 2:09AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-20-19 2:10AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-20-19 2:08AM
T 2 TANK UNLEADED 87 LOW PRODUCT ALARM CLEAR 5-18-19 8:31AM
T 2 TANK UNLEADED 87 LOW PRODUCT ALARM ALARM 5-18-19 7:09AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-13-19 11:58AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-13-19 11:55AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-13-19 11:15AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-13-19 11:13AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-13-19 7:15AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-13-19 7:13AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-13-19 6:49AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-13-19 6:47AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-13-19 5:38AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-13-19 5:36AM
I11200
AUG 21, 2019 8:41 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-19-19 2:06PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 8-16-19 10:47AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 8-16-19 7:17AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 8-13-19 10:12PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-12-19 5:36AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 8-10-19 6:29PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 8-09-19 4:57AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-09-19 4:51AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 8-08-19 8:42PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 8-07-19 7:16AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 8-05-19 3:23PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-05-19 3:23PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 8-05-19 7:23AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 8-03-19 2:40PM
SYSTEM PRINTER ERROR CLEAR 8-03-19 7:56AM
SYSTEM PRINTER ERROR ALARM 8-03-19 7:56AM
SYSTEM PRINTER ERROR CLEAR 8-03-19 7:56AM
SYSTEM PRINTER ERROR ALARM 8-03-19 7:56AM
SYSTEM PRINTER ERROR CLEAR 8-03-19 7:54AM
SYSTEM PAPER OUT CLEAR 8-03-19 7:54AM
SYSTEM PRINTER ERROR ALARM 8-03-19 7:54AM
SYSTEM PAPER OUT ALARM 8-03-19 7:54AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 8-02-19 2:12AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-02-19 2:05AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 8-01-19 9:40PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-31-19 1:24PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-29-19 4:59PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 7-29-19 4:34PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 7-29-19 5:56AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-28-19 6:42AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-25-19 4:31PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-24-19 7:45PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 7-23-19 12:22PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-23-19 12:15PM
SYSTEM PRINTER ERROR CLEAR 7-23-19 8:54AM
SYSTEM PRINTER ERROR ALARM 7-23-19 8:54AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 7-22-19 4:54PM
SYSTEM PRINTER ERROR CLEAR 7-22-19 12:27PM
SYSTEM PAPER OUT CLEAR 7-22-19 12:27PM
SYSTEM PAPER OUT ALARM 7-22-19 12:27PM
SYSTEM PRINTER ERROR ALARM 7-22-19 12:27PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-21-19 12:27AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 7-19-19 12:48PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-19-19 12:40PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 7-19-19 7:33AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-17-19 7:23PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-14-19 2:47PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-13-19 7:22PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-10-19 7:49PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-08-19 10:03AM
I20600
AUG 21, 2019 8:41 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
TANK ALARM HISTORY
TANK 1 PREM 91
DELIVERY NEEDED AUG 13, 2019 10:12 PM
AUG 10, 2019 6:29 PM
AUG 7, 2019 7:16 AM
TANK 2 UNLEADED 87
OVERFILL ALARM OCT 19, 2018 9:00 PM
SEP 2, 2018 9:30 AM
JUN 7, 2018 5:09 PM
LOW PRODUCT ALARM MAY 18, 2019 7:09 AM
JAN 14, 2019 5:41 PM
JAN 14, 2019 9:37 AM
DELIVERY NEEDED AUG 16, 2019 7:17 AM
AUG 8, 2019 8:42 PM
AUG 5, 2019 7:23 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
AUG 21, 2019 8:41 AM
I30200
AUG 21, 2019 8:41 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 91 STP
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
AUG 28, 2018 9:41 AM FUEL ALARM
MAR 5, 2018 11:57 AM FUEL ALARM
2 91 FILL SUMP
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
AUG 28, 2018 9:43 AM FUEL ALARM
FEB 12, 2018 8:29 AM SENSOR OUT ALARM
3 87 STP
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
AUG 28, 2018 9:43 AM FUEL ALARM
MAR 5, 2018 11:53 AM FUEL ALARM
4 87 FILL SUMP
AUG 28, 2018 10:51 AM FUEL ALARM
AUG 28, 2018 10:48 AM SENSOR OUT ALARM
AUG 28, 2018 10:48 AM FUEL ALARM
5 UDC 1-2
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
AUG 28, 2018 9:51 AM FUEL ALARM
MAR 5, 2018 12:07 PM FUEL ALARM
6 UDC 3-4
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
AUG 28, 2018 9:50 AM FUEL ALARM
MAR 5, 2018 12:09 PM FUEL ALARM
7 UDC 5-6
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
AUG 28, 2018 9:52 AM FUEL ALARM
MAR 5, 2018 12:03 PM FUEL ALARM
8 UDC 7-8
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
AUG 28, 2018 9:54 AM FUEL ALARM
MAR 5, 2018 12:05 PM FUEL ALARM
9 ANNULAR 87-91
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
AUG 28, 2018 9:47 AM FUEL ALARM
FEB 12, 2018 8:29 AM SENSOR OUT ALARM
I31600
AUG 21, 2019 8:41 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VAPOR PRESSURE
DEC 22, 2017 10:25 AM COMMUNICATION ALARM
DEC 22, 2017 9:52 AM COMMUNICATION ALARM
DEC 22, 2017 9:49 AM COMMUNICATION ALARM
2 FLOW METER 1-2
DEC 22, 2017 10:00 AM COMMUNICATION ALARM
3 FLOW METER 3-4
DEC 22, 2017 10:00 AM COMMUNICATION ALARM
AUG 21, 2017 2:18 PM COMMUNICATION ALARM
4 FLOW METER 5-6
DEC 22, 2017 10:00 AM COMMUNICATION ALARM
AUG 22, 2017 10:48 AM COMMUNICATION ALARM
AUG 21, 2017 2:18 PM COMMUNICATION ALARM
5 FLOW METER 7-8
DEC 22, 2017 10:00 AM COMMUNICATION ALARM
AUG 21, 2017 2:18 PM COMMUNICATION ALARM
I40200
AUG 21, 2019 8:41 AM
I40300
AUG 21, 2019 8:41 AM
I34200
AUG 21, 2019 8:41 AM
I34700
AUG 21, 2019 8:41 AM
IV0100
AUG 21, 2019 8:41 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
19-06-06 10:08:18 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 0.60
19-05-25 10:05:07 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 0.54
19-03-08 10:03:03 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 BLKD
18-09-18 10:06:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 6 BLEND3 0.60
18-08-06 10:08:38 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 0.56
18-06-15 10:07:19 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 BLKD
18-06-10 10:07:03 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 BLKD
18-05-16 10:05:32 SENSOR OUT SELFTEST E 1
18-03-11 10:04:55 FLOW PERFORMANCE HOSE BLOCKAGE FP 6 BLEND3 0.59
18-02-26 10:06:06 SENSOR OUT SELFTEST E 1
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
18-08-07 10:08:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3
18-06-12 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
18-06-11 10:06:56 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
17-12-27 10:04:24 SENSOR OUT SELFTEST E 1
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
19-07-28 10:05:26 READINESS ISD:PP EVR:PP ISD & EVR READY
19-07-27 12:24:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING
19-07-27 12:24:39 ISD STARTUP
19-07-27 12:20:51 ISD SHUTDOWN
19-05-13 10:06:16 READINESS ISD:PP EVR:PP ISD & EVR READY
19-05-12 14:40:12 READINESS ISD:PP EVR:NN EVR READINESS PENDING
19-05-12 14:40:12 ISD STARTUP
19-05-12 14:23:07 ISD SHUTDOWN
19-04-04 10:05:04 READINESS ISD:PP EVR:PP ISD & EVR READY
19-04-03 21:21:04 READINESS ISD:PP EVR:NN EVR READINESS PENDING
Alarm History (After)
Responses Received:
I10200
AUG 21, 2019 11:24 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164738 163786
2 INTERSTITIAL BD 202007 201216
3 INTERSTITIAL BD 202007 201281
4 7SMARTSENSOR BD 507999 505729
5 UNUSED 9903073 9753909
6 UNUSED 9868832 9732643
7 UNUSED 9858988 9731113
8 UNUSED 9856420 9729102
9 RELAY BOARD 14987 14965
10 UNUSED 9859521 9737017
11 UNUSED 9850410 9725200
12 UNUSED 9848494 9725640
13 UNUSED 9844907 9727505
14 UNUSED 9838935 9722833
15 UNUSED 9845213 9723671
16 UNUSED 9841504 9721408
COMM 1 RS232 SERIAL BD 14946 14944
COMM 2 ELEC DISP INT. 101209 101023
COMM 3 UNUSED 9847618 9737709
COMM 4 UNUSED 9841748 9722791
COMM 5 UNUSED 9837448 9726269
COMM 6 UNUSED 9840158 9721366
I90200
AUG 21, 2019 11:24 AM
SOFTWARE REVISION LEVEL
VERSION 334.01
SOFTWARE# 346334-100-B
CREATED - 17.01.09.16.10
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 21, 2019 11:24 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 3 STP SUMP 87 STP FUEL ALARM CLEAR 8-21-19 10:00AM
L 3 STP SUMP 87 STP FUEL ALARM ALARM 8-21-19 10:00AM
L 3 STP SUMP 87 STP FUEL ALARM CLEAR 8-21-19 9:59AM
L 3 STP SUMP 87 STP FUEL ALARM ALARM 8-21-19 9:50AM
L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 8-21-19 9:50AM
L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 8-21-19 9:39AM
L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM CLEAR 8-21-19 9:30AM
L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM CLEAR 8-21-19 9:30AM
L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 8-21-19 9:30AM
L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM CLEAR 8-21-19 9:30AM
L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM CLEAR 8-21-19 9:30AM
L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM CLEAR 8-21-19 9:30AM
L 1 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 8-21-19 9:30AM
L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 8-21-19 9:30AM
L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM CLEAR 8-21-19 9:30AM
L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM ALARM 8-21-19 9:29AM
L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 8-21-19 9:29AM
L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM ALARM 8-21-19 9:29AM
L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM ALARM 8-21-19 9:29AM
L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM ALARM 8-21-19 9:29AM
L 1 STP SUMP 91 STP SENSOR OUT ALARM ALARM 8-21-19 9:29AM
L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM ALARM 8-21-19 9:29AM
L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 8-21-19 9:29AM
L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM ALARM 8-21-19 9:29AM
L 8 DISP PAN UDC 7-8 FUEL ALARM CLEAR 8-21-19 9:28AM
L 8 DISP PAN UDC 7-8 FUEL ALARM ALARM 8-21-19 9:27AM
L 7 DISP PAN UDC 5-6 FUEL ALARM CLEAR 8-21-19 9:27AM
L 7 DISP PAN UDC 5-6 FUEL ALARM ALARM 8-21-19 9:26AM
L 5 DISP PAN UDC 1-2 FUEL ALARM CLEAR 8-21-19 9:25AM
L 5 DISP PAN UDC 1-2 FUEL ALARM ALARM 8-21-19 9:25AM
L 6 DISP PAN UDC 3-4 FUEL ALARM CLEAR 8-21-19 9:24AM
L 6 DISP PAN UDC 3-4 FUEL ALARM ALARM 8-21-19 9:24AM
L 1 STP SUMP 91 STP FUEL ALARM CLEAR 8-21-19 9:23AM
L 1 STP SUMP 91 STP FUEL ALARM ALARM 8-21-19 9:23AM
L 2 PIPE 91 FILL SUMP FUEL ALARM CLEAR 8-21-19 9:22AM
L 2 PIPE 91 FILL SUMP FUEL ALARM ALARM 8-21-19 9:22AM
L 4 PIPE 87 FILL SUMP FUEL ALARM CLEAR 8-21-19 9:19AM
L 4 PIPE 87 FILL SUMP FUEL ALARM ALARM 8-21-19 9:19AM
L 9 ANNULAR ANNULAR 87-91 FUEL ALARM CLEAR 8-21-19 9:17AM
L 9 ANNULAR ANNULAR 87-91 FUEL ALARM ALARM 8-21-19 9:17AM
E 1 OTHER COMMUNICATION ALARM CLEAR 8-19-19 2:06AM
E 1 OTHER COMMUNICATION ALARM ALARM 8-19-19 2:04AM
E 1 OTHER COMMUNICATION ALARM CLEAR 8-12-19 2:07AM
E 1 OTHER COMMUNICATION ALARM ALARM 8-12-19 2:05AM
E 1 OTHER COMMUNICATION ALARM CLEAR 8-05-19 7:04AM
E 1 OTHER COMMUNICATION ALARM ALARM 8-05-19 7:02AM
E 1 OTHER COMMUNICATION ALARM CLEAR 8-05-19 2:10AM
E 1 OTHER COMMUNICATION ALARM ALARM 8-05-19 2:07AM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-29-19 2:06AM
E 1 OTHER COMMUNICATION ALARM ALARM 7-29-19 2:03AM
I11200
AUG 21, 2019 11:24 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-19-19 2:06PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 8-16-19 10:47AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 8-16-19 7:17AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 8-13-19 10:12PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-12-19 5:36AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 8-10-19 6:29PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 8-09-19 4:57AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-09-19 4:51AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 8-08-19 8:42PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 8-07-19 7:16AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 8-05-19 3:23PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-05-19 3:23PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 8-05-19 7:23AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 8-03-19 2:40PM
SYSTEM PRINTER ERROR CLEAR 8-03-19 7:56AM
SYSTEM PRINTER ERROR ALARM 8-03-19 7:56AM
SYSTEM PRINTER ERROR CLEAR 8-03-19 7:56AM
SYSTEM PRINTER ERROR ALARM 8-03-19 7:56AM
SYSTEM PRINTER ERROR CLEAR 8-03-19 7:54AM
SYSTEM PAPER OUT CLEAR 8-03-19 7:54AM
SYSTEM PRINTER ERROR ALARM 8-03-19 7:54AM
SYSTEM PAPER OUT ALARM 8-03-19 7:54AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 8-02-19 2:12AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 8-02-19 2:05AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 8-01-19 9:40PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-31-19 1:24PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-29-19 4:59PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 7-29-19 4:34PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 7-29-19 5:56AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-28-19 6:42AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-25-19 4:31PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-24-19 7:45PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 7-23-19 12:22PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-23-19 12:15PM
SYSTEM PRINTER ERROR CLEAR 7-23-19 8:54AM
SYSTEM PRINTER ERROR ALARM 7-23-19 8:54AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 7-22-19 4:54PM
SYSTEM PRINTER ERROR CLEAR 7-22-19 12:27PM
SYSTEM PAPER OUT CLEAR 7-22-19 12:27PM
SYSTEM PAPER OUT ALARM 7-22-19 12:27PM
SYSTEM PRINTER ERROR ALARM 7-22-19 12:27PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-21-19 12:27AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 7-19-19 12:48PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-19-19 12:40PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 7-19-19 7:33AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-17-19 7:23PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-14-19 2:47PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-13-19 7:22PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 7-10-19 7:49PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 7-08-19 10:03AM
I20600
AUG 21, 2019 11:24 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
TANK ALARM HISTORY
TANK 1 PREM 91
DELIVERY NEEDED AUG 13, 2019 10:12 PM
AUG 10, 2019 6:29 PM
AUG 7, 2019 7:16 AM
TANK 2 UNLEADED 87
OVERFILL ALARM OCT 19, 2018 9:00 PM
SEP 2, 2018 9:30 AM
JUN 7, 2018 5:09 PM
LOW PRODUCT ALARM MAY 18, 2019 7:09 AM
JAN 14, 2019 5:41 PM
JAN 14, 2019 9:37 AM
DELIVERY NEEDED AUG 16, 2019 7:17 AM
AUG 8, 2019 8:42 PM
AUG 5, 2019 7:23 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
AUG 21, 2019 11:24 AM
I30200
AUG 21, 2019 11:24 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 91 STP
AUG 21, 2019 9:29 AM SENSOR OUT ALARM
AUG 21, 2019 9:23 AM FUEL ALARM
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
2 91 FILL SUMP
AUG 21, 2019 9:29 AM SENSOR OUT ALARM
AUG 21, 2019 9:22 AM FUEL ALARM
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
3 87 STP
AUG 21, 2019 10:00 AM FUEL ALARM
AUG 21, 2019 9:50 AM FUEL ALARM
AUG 21, 2019 9:39 AM SENSOR OUT ALARM
4 87 FILL SUMP
AUG 21, 2019 9:29 AM SENSOR OUT ALARM
AUG 21, 2019 9:19 AM FUEL ALARM
AUG 28, 2018 10:51 AM FUEL ALARM
5 UDC 1-2
AUG 21, 2019 9:29 AM SENSOR OUT ALARM
AUG 21, 2019 9:25 AM FUEL ALARM
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
6 UDC 3-4
AUG 21, 2019 9:29 AM SENSOR OUT ALARM
AUG 21, 2019 9:24 AM FUEL ALARM
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
7 UDC 5-6
AUG 21, 2019 9:29 AM SENSOR OUT ALARM
AUG 21, 2019 9:26 AM FUEL ALARM
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
8 UDC 7-8
AUG 21, 2019 9:29 AM SENSOR OUT ALARM
AUG 21, 2019 9:27 AM FUEL ALARM
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
9 ANNULAR 87-91
AUG 21, 2019 9:29 AM SENSOR OUT ALARM
AUG 21, 2019 9:17 AM FUEL ALARM
AUG 28, 2018 9:56 AM SENSOR OUT ALARM
I31600
AUG 21, 2019 11:24 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VAPOR PRESSURE
DEC 22, 2017 10:25 AM COMMUNICATION ALARM
DEC 22, 2017 9:52 AM COMMUNICATION ALARM
DEC 22, 2017 9:49 AM COMMUNICATION ALARM
2 FLOW METER 1-2
DEC 22, 2017 10:00 AM COMMUNICATION ALARM
3 FLOW METER 3-4
DEC 22, 2017 10:00 AM COMMUNICATION ALARM
AUG 21, 2017 2:18 PM COMMUNICATION ALARM
4 FLOW METER 5-6
DEC 22, 2017 10:00 AM COMMUNICATION ALARM
AUG 22, 2017 10:48 AM COMMUNICATION ALARM
AUG 21, 2017 2:18 PM COMMUNICATION ALARM
5 FLOW METER 7-8
DEC 22, 2017 10:00 AM COMMUNICATION ALARM
AUG 21, 2017 2:18 PM COMMUNICATION ALARM
I40200
AUG 21, 2019 11:24 AM
I40300
AUG 21, 2019 11:24 AM
I34200
AUG 21, 2019 11:24 AM
I34700
AUG 21, 2019 11:24 AM
IV0100
AUG 21, 2019 11:24 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
1-661-833-8553
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
19-06-06 10:08:18 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 0.60
19-05-25 10:05:07 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 0.54
19-03-08 10:03:03 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 BLKD
18-09-18 10:06:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 6 BLEND3 0.60
18-08-06 10:08:38 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 0.56
18-06-15 10:07:19 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 BLKD
18-06-10 10:07:03 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 BLKD
18-05-16 10:05:32 SENSOR OUT SELFTEST E 1
18-03-11 10:04:55 FLOW PERFORMANCE HOSE BLOCKAGE FP 6 BLEND3 0.59
18-02-26 10:06:06 SENSOR OUT SELFTEST E 1
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
18-08-07 10:08:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3
18-06-12 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
18-06-11 10:06:56 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
17-12-27 10:04:24 SENSOR OUT SELFTEST E 1
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
19-07-28 10:05:26 READINESS ISD:PP EVR:PP ISD & EVR READY
19-07-27 12:24:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING
19-07-27 12:24:39 ISD STARTUP
19-07-27 12:20:51 ISD SHUTDOWN
19-05-13 10:06:16 READINESS ISD:PP EVR:PP ISD & EVR READY
19-05-12 14:40:12 READINESS ISD:PP EVR:NN EVR READINESS PENDING
19-05-12 14:40:12 ISD STARTUP
19-05-12 14:23:07 ISD SHUTDOWN
19-04-04 10:05:04 READINESS ISD:PP EVR:PP ISD & EVR READY
19-04-03 21:21:04 READINESS ISD:PP EVR:NN EVR READINESS PENDING
&(56 &DOLIRUQLD(QYLURQPHQWDO5HSRUWLQJ6\VWHP,' ,GHQWLILFDWLRQ867 8QGHUJURXQG6WRUDJH7DQN,&& ,QWHUQDWLRQDO&RGH&RXQFLO
81 ZZZXQLGRFVRUJ5HY
81'(5*5281'6725$*(7$1.
63,//&217$,1(57(67,1*5(3257)2503DJHRI
7\SHRI$FWLRQ,QVWDOODWLRQ7HVW5HSDLU7HVW0RQWK7HVW
, )$&,/,7<,1)250$7,21
&(56,''DWHRI6SLOO&RQWDLQHU7HVW
%XVLQHVV1DPH(Same as Facility Name or DBA-Doing Business As)
%XVLQHVV6LWH$GGUHVV &LW\ =,3&RGH
,, 81'(5*5281'6725$*(7$1.6(59,&(7(&+1,&,$1,1)250$7,21
1DPHRI8676HUYLFH7HFKQLFLDQ3HUIRUPLQJWKH7HVW(Print as shown on the ICC Certification.) 3KRQH
&RQWUDFWRU7DQN7HVWHU/LFHQVH ,&&&HUWLILFDWLRQ ,&&&HUWLILFDWLRQ([SLUDWLRQ'DWH
6SLOO&RQWDLQHU7HVWLQJ7UDLQLQJDQG&HUWLILFDWLRQV(List applicable certifications.)
,,, 63,//&217$,1(57(67,1*,1)250$7,21
7HVW0HWKRG8VHG0DQXIDFWXUHU*XLGHOLQHV(Specify)
,QGXVWU\&RGHRU(QJLQHHULQJ6WDQGDUG (Specify)
(QJLQHHUHG0HWKRG(Specify)
Attach the testing procedures and all documentation required to determine the results.RI$WWDFKHG3DJHV
7$1.,'(By tank number, stored product, etc.)
6SLOO&RQWDLQHU0DQXIDFWXUHU
0HWKRGRI&DWKRGLF3URWHFWLRQ1RQ0HWDOOLF1RQ0HWDOOLF1RQ0HWDOOLF1RQ0HWDOOLF
,VRODWLRQ,VRODWLRQ,VRODWLRQ,VRODWLRQ
2WKHU(Specify in V.)2WKHU(Specify in V.)2WKHU(Specify in V.)2WKHU(Specify in V.)
,QVLGH'LDPHWHURI6SLOO&RQWDLQHU(Inches)
'HSWKRI6SLOO&RQWDLQHU(Inches)
'RHVWKHVSLOOFRQWDLQHUKDYHDJDOORQFDSDFLW\"<HV1R<HV1R<HV1R<HV1R
0HWKRGWR.HHS6SLOO&RQWDLQHU(PSW\'UDLQ9DOYH'UDLQ9DOYH'UDLQ9DOYH'UDLQ9DOYH
2QVLWH3XPS2QVLWH3XPS2QVLWH3XPS2QVLWH3XPS
2WKHU(Specify in V.)2WKHU(Specify in V.)2WKHU(Specify in V.)2WKHU(Specify in V.)
,9 6800$5<2)7(67,1*5(68/76
6SLOO&RQWDLQHU7HVW5HVXOWV3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO
9 &200(176
Any items marked “Fail” above must be explained in this section. Any additional comments may also be provided here.
9, &(57,),&$7,21%<8676(59,&(7(&+1,&,$1&21'8&7,1*7+,67(67,1*
,KHUHE\FHUWLI\WKDWWKHVSLOOFRQWDLQHUVZHUHWHVWHGLQDFFRUGDQFHZLWK&DOLIRUQLD&RGHRI5HJXODWLRQV7LWOH'LYLVLRQ
&KDSWHU6HFWLRQDQGDOOWKHLQIRUPDWLRQFRQWDLQHGKHUHLQLVDFFXUDWH
8676HUYLFH7HFKQLFLDQ6LJQDWXUH
If the facility has more components than this form accommodates, additional copies of this page may be attached.
Bakersfield 93304
804904 9118985 3/30/2021
OPW 0123282
PEI 1200
1
T1;87
OPW
10.50”
13.00”
T2;91
OPW
10.50”
12.50”
Matthew Story (800) 339-9930
10026730 8/21/2019
Circle K (Mobil)
2601 White Lane
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: Date of Testing:
Facility Address:
Facility Contact: Phone:
Date Local Agency Was Notified of Testing :
Name of Local Agency Inspector (if present during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name:
Technician Conducting Test:
Credentials1: CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) __________________
License Number(s):
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: Hydrostatic Vacuum Other
Test Equipment Used: Equipment Resolution:
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1234
Bucket Installation Type: Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Bucket Diameter:
Bucket Depth:
Wait time between applying
vacuum/water and start of test:
Test Start Time (TI):
Initial Reading (RI):
Test End Time (TF):
Final Reading (RF):
Test Duration (TF –TI):
Change in Reading (RF -RI):
Pass/Fail Threshold or
Criteria:
Test Result: Pass Fail Pass Fail Pass Fail Pass Fail
Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician’s Signature:________________________________________________ Date:_________________________
1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
Circle K (Mobil)8/21/2019
2601 White Lane Bakersfield 93304
Bassem Azzi (805) 217-0610
8/5/2019
Peter Bakersfield Fire Department
Confidence UST Services, Inc.
Matthew Story
804904 9118985
Hydrostatic lake test 0.00625”
T1;87 T2;91
10.50” 10.50”
13.00” 12.50”
5 mins 5 mins
9:10 am 9:10 am
11.00” 11.00”
10:10 am 10:10 am
11.00” 11.00”
1 hour 1 hour
0.00” 0.00”
0.00625” 0.00625”
8/21/2019
✔✔
✔
✔✔
✔✔