UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM (Page 1 of 6)
This form must be used to document testing and servicing of underground storage tank (UST) monitoring equipment. A copy of this form
must be provided to the UST owner or operator. The owner or operator must submit a copy of this form to the local agency regulating the
USTs within 30 days of the date of the monitoring system certification.
I. FACILITY INFORMATION
CERS ID
10132183
Date of Monitoring System Certification
8/13/2019
Business Name (Same as Facility Name or DBA – Doing Business As.)
Gasko Food Mart
Building #
Business Site Address
430 East California Ave
City
Bakersfield
ZIP Code
93306
II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION
Name of Company Performing the Certification
Advanced Compliance
Phone #
(661) 706 - 4321 Ext.
Mailing Address
3704 Littlefalls Ct Bakersfield, Ca. 93312
Name of UST Service Technician Performing the Certification (Print as shown on the ICC Certification.)
Bradley Hinsley
Contractor/Tank Tester License #
971259
ICC Certification #
8373948
ICC Certification Expiration Date
8/23/2019
Monitoring System Training and Certifications (List all applicable certifications.) Expiration Date
ICC Service Techican 8/10/2021
Veeder-root 2/8/2020
Redjacket LLD 5/23/2021
VMI 1/18/2020
III. RESULTS OF TESTING/SERVICING
Indicate and attach the following reports if the monitoring equipment is capable of generating either. Y N NA Monitoring System Set-up Alarm History Report
Was any monitoring equipment replaced?
(If “Yes,” identify the specific devices replaced and list the manufacturer and model for all replacement parts in section IV below.)
Was damage, debris, or liquid found inside any secondary containment systems?
(If “Yes,” describe what was found in section IV below.)
Is all monitoring equipment operational per manufacturer’s specifications?
(If “No,” describe why in section IV below.)
IV. COMMENTS
If directed to use this section, describe how and when the issues were or will be corrected.
V. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING
I hereby certify that the equipment identified in this document was inspected/serviced in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2638 and all information contained herein is true and accurate. Attached to
this certification is information (e.g., manufacturers' checklists, monitoring system set-up, alarm history report, etc.) necessary
to verify that this information and the site plan showing the layout of UST system is complete and accurate.
UST Service Technician Signature
ID = Identification, SW = Single-walled, VPH = Vacuum/Pressure/Hydrostatic, LLD = Line leak detector
UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM (Page 2 of 6)
VI. INVENTORY OF EQUIPMENT CERTIFIED
A separate Monitoring System Certification Form must be prepared for each monitoring system control panel.
Make of Monitoring System Control Panel
Veeder-Root
Model of Monitoring System Control Panel
TLS-350
Software Version Installed
335.00
Check the appropriate boxes to indicate specific equipment inspected/serviced.
Monitoring Device Used Device Model # Monitoring Device Used Device Model #
Tank ID: 87
(By tank number, stored product, etc.)
Tank ID: 91
(By tank number, stored product, etc.)
In-tank Gauging (SW Tank) MAG In-tank Gauging (SW Tank) MAG
Annular Space or Vault Sensor 794390-420 Annular Space or Vault Sensor 794390-420
VPH Sensor VPH Sensor
Product Piping Product Piping
Mechanical LLD 99 LD-2000 Mechanical LLD FX-1V
Electronic LLD Electronic LLD
VPH Sensor (Piping) VPH Sensor (Piping)
Sump Sensor 794380-208 Sump Sensor 794380-208
VPH Sensor (Sump) VPH Sensor (Sump)
Fill Piping Fill Piping
VPH Sensor (Piping) VPH Sensor (Piping)
Sump Sensor 794380-208 Sump Sensor 794380-208
VPH Sensor (Sump) VPH Sensor (Sump)
Vent Piping Vent Piping
VPH Sensor (Piping) VPH Sensor (Piping)
Sump Sensor Sump Sensor
VPH Sensor (Sump) VPH Sensor (Sump)
Vapor Recovery Piping Vapor Recovery Piping
VPH Sensor (Piping) VPH Sensor (Piping)
Sump Sensor Sump Sensor
VPH Sensor (Sump) VPH Sensor (Sump)
Monitoring Device Used Device Model # Monitoring Device Used Device Model #
Tank ID:
(By tank number, stored product, etc.)
Tank ID:
(By tank number, stored product, etc.)
In-tank Gauging (SW Tank) In-tank Gauging (SW Tank)
Annular Space or Vault Sensor Annular Space or Vault Sensor
VPH Sensor VPH Sensor
Product Piping Product Piping
Mechanical LLD Mechanical LLD
Electronic LLD Electronic LLD
VPH Sensor (Piping) VPH Sensor (Piping)
Sump Sensor Sump Sensor
VPH Sensor (Sump) VPH Sensor (Sump)
Fill Piping Fill Piping
VPH Sensor (Piping) VPH Sensor (Piping)
Sump Sensor Sump Sensor
VPH Sensor (Sump) VPH Sensor (Sump)
Vent Piping Vent Piping
VPH Sensor (Piping) VPH Sensor (Piping)
Sump Sensor Sump Sensor
VPH Sensor (Sump) VPH Sensor (Sump)
Vapor Recovery Piping Vapor Recovery Piping
VPH Sensor (Piping) VPH Sensor (Piping)
Sump Sensor Sump Sensor
VPH Sensor (Sump) VPH Sensor (Sump)
ID = Identification, VPH = Vacuum/Pressure/Hydrostatic, UDC = Under-dispenser containment
UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM (Page 3 of 6)
Monitoring Device Used Device Model # Monitoring Device Used Device Model #
Vent/Transition Sump ID: Vent Pan Vent/Transition Sump ID:
Sump Sensor 794380-208 Sump Sensor
VPH Sensor VPH Sensor
UDC ID: 1/2 UDC ID: 3/4
Electronic Sensor 794380-208 Electronic Sensor 794380-208
Mechanical Device Shear Valve Mechanical Device Shear Valve
VPH Sensor VPH Sensor
UDC ID: 5/6 UDC ID:
Electronic Sensor 794380-208 Electronic Sensor
Mechanical Device Shear Valve Mechanical Device
VPH Sensor VPH Sensor
UDC ID: UDC ID:
Electronic Sensor Electronic Sensor
Mechanical Device Mechanical Device
VPH Sensor VPH Sensor
UDC ID: UDC ID:
Electronic Sensor Electronic Sensor
Mechanical Device Mechanical Device
VPH Sensor VPH Sensor
Other Monitored Component ID: Other Monitored Component ID:
Other (Specify in section VII.) Other (Specify in section VII.)
Other Monitored Component ID: Other Monitored Component ID:
Other (Specify in section VII.) Other (Specify in section VII.)
Other Monitored Component ID: Other Monitored Component ID:
Other (Specify in section VII.) Other (Specify in section VII.)
Include information for every underground storage tank component monitored by this monitoring system control panel. If the monitoring
system control panel monitors more components than this form accommodates, additional copies of these pages may be attached.
VII. COMMENTS
Use this section to provide any additional comments about the inventory of the equipment certified.
Y = Yes, N = No, NA = Not Applicable
UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM (Page 4 of 6)
VIII. MONITORING SYSTEM AND PROGRAMMING
This section must be completed if a monitoring panel is used to perform leak detection monitoring. Y N NA
Are the visual and audible alarms operational?
Were all sensors visually inspected for kinks and breaks in the cables and for residual buildup to ensure that floats move freely,
functionally tested, and confirmed operational?
Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their
proper operation?
Was monitoring system set-up reviewed to ensure proper settings?
Was the monitoring panel’s backup battery visually inspected, functionally tested, and confirmed operational?
Does the flow of fuel stop at the dispenser if a leak is detected in the under-dispenser containment?
Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected?
Does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak? Which sensors initiate positive shut down? (Check all that apply.) Sump Under-dispenser containment
If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
For any answer of “N” above, describe in section IX how and when these deficiencies were or will be corrected.
IX. COMMENTS
X. IN-TANK GAUGING TESTING Check this box if tank gauging is used only for inventory control. (Do not complete this section.) Y N NA Check this box if NO tank gauging equipment is installed. (Do not complete this section.)
This section must be completed if in-tank gauging is used to perform leak detection monitoring.
Has all input wiring been inspected for kinks and breaks in the cables and for proper entry and termination, including testing for ground
faults?
Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested,
and confirmed operational?
Was accuracy of system’s product level readings tested?
Was accuracy of system’s water level readings tested?
Were all probes reinstalled properly?
Were all items on the equipment manufacturer’s maintenance checklist completed?
For any answer of “N” above, describe in section XI how and when these deficiencies were or will be corrected.
XI. COMMENTS
GPH = Gallons per hour, Y = Yes, N = No, NA = Not applicable, VPH = Vacuum/Pressure/Hydrostatic, ID = Identification
UNDERGROUND STORAGE TANK
MONITORING SYSTEM CERTIFICATION FORM (Page 5 of 6)
XII. LINE LEAK DETECTOR TESTING Check this box if line leak detectors (LLD) are NOT installed. (Do not complete this section.) Y N NA This section must be completed if LLDs are installed.
Was a leak simulated to verify LLD performance? (Check all that apply.) Simulated leak rate verified: 3 GPH 0.1 GPH 0.2 GPH
Was the testing apparatus properly calibrated?
For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected?
For mechanical LLDs, does the LLD restrict the flow through the pipe when a leak is detected?
For electronic LLDs, does the turbine automatically shut off when a leak is detected?
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test?
For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks?
Were all items on the equipment manufacturer’s maintenance checklist completed?
Were all LLDs confirmed operational within regulatory requirements?
For any answer of “N” above, describe in section XIII how and when these issues were or will be corrected.
XIII. COMMENTS
XIV. VACUUM / PRESSURE/ HYDROSTATIC MONITORING EQUIPMENT TESTING
Check this box if VPH monitoring is NOT used. (Do not complete this section.)
This section must be completed if VPH monitoring is used to perform leak detection monitoring.
System Type (Mark all that apply.) Vacuum Pressure Hydrostatic
Sensor ID Component(s) Monitored by this Sensor Sensor Functionality
Test Interstitial Communication
Test
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
Pass Fail Pass Fail
How was interstitial communication verified? Simulated leak at far ends of the interstitial space. Visual Inspection
Other (Describe the method in section XV below.) Gauge
Was the vacuum or pressure restored to operating levels in all interstitial spaces? Yes No (Describe the reason in section XV below.)
For any answer of “FAIL” above, describe in section XV how and when these issues were or will be corrected.
XV. COMMENTS
Advanced Compliance
3704 Littlefalls Ct.
Bakersfield, Ca. 93308
661-706-4321 Fax# 661-589-9329
VAPORLESS MANUFACTURING, INC.
LDT-890 Leak Detector Test Record
Contractor: Advanced Compliance Customer: Gasko
Date: 8/13/2019 Location: 430 E California Bakersfield, Ca.
Product: 87 UL Technician: Bradley W. Hinsley
Submersible Pump Identification
Manufacturer: Redjacket Model No.:
Serial No.: Notes:
Leak Detector Identification
Manufacturer: VMI Description: 99 LD-2000
Diaphragm-type: Piston-type:
Tamper-proof seal installed: Other Style Leak Detector:
Notes:
Leak Detector in Submersible Pump Test at Dispenser
Operating Pump Pressure (psi): 26 (para. 15)
Gallons per hour rate: 3.0 (para. 22)
Line pressure with pump shut off (psi): 18 (para. 23)
Bleed-back Test with pump off (ml): 150 (para. 26)
Step-through time to full flow (secs): 3 (para. 30)
Leak detector stays in leak search position (Yes/No): Yes (para. 42)
Leak Detector Test
Pass / Fail Notes:
Pass
*Complete thermal expansion test before failing leak detector
Advanced Compliance
3704 Littlefalls Ct.
Bakersfield, Ca. 93308
661-706-4321 Fax# 661-589-9329
VAPORLESS MANUFACTURING, INC.
LDT-890 Leak Detector Test Record
Contractor: Advanced Compliance Customer: Gasko
Date: 8/13/2019 Location: 430 E California Bakersfield, Ca.
Product: 91 UL Technician: Bradley W. Hinsley
Submersible Pump Identification
Manufacturer: Redjacket Model No.:
Serial No.: Notes:
Leak Detector Identification
Manufacturer: Veeder-Root Description: FX-1V
Diaphragm-type: Piston-type:
Tamper-proof seal installed: Other Style Leak Detector:
Notes:
Leak Detector in Submersible Pump Test at Dispenser
Operating Pump Pressure (psi): 32 (para. 15)
Gallons per hour rate: 3.0 (para. 22)
Line pressure with pump shut off (psi): 20 (para. 23)
Bleed-back Test with pump off (ml): 115 (para. 26)
Step-through time to full flow (secs): 3 (para. 30)
Leak detector stays in leak search position (Yes/No): Yes (para. 42)
Leak Detector Test
Pass / Fail Notes:
Pass
*Complete thermal expansion test before failing leak detector
CERS = California Environmental Reporting System, ID = Identification, UST = Underground storage tank, ICC = International Code Council
UNDERGROUND STORAGE TANK
SPILL CONTAINER TESTING REPORT FORM (Page 1 of 1)
Type of Action Installation Test Repair Test 12 Month Test
I. FACILITY INFORMATION
CERS ID
10132183
Date of Spill Container Test
8/13/2019
Business Name (Same as Facility Name or DBA-Doing Business As.)
Gasko Food Mart
Business Site Address
430 East California Ave
City
Bakersfield
ZIP Code
93306
II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION
Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.)
Bradley Hinsley
Phone #
(661) 706 - 4321 Ext.
Contractor/Tank Tester License #
971259
ICC Certification #
8373948
ICC Certification Expiration Date
8/10/2021
Spill Container Testing Training and Certifications (List applicable certifications.)
8/10/2021
III. SPILL CONTAINER TESTING INFORMATION
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify) Industry Standard
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Tank ID: (By tank number, stored product, etc.) 87 91
Spill Container Manufacturer: Phil-Tite Phil-Tite
Method of Cathodic Protection
Non-Metallic Non-Metallic Non-Metallic Non-Metallic
Isolation Isolation Isolation Isolation
Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.)
Inside Diameter of Spill Container: (Inches) 15" 15"
Depth of Spill Container: (Inches) 20" 20"
Does the spill container have a 5 gallon capacity? Yes No Yes No Yes No Yes No
Method to Keep Spill Container Empty
Drain Valve Drain Valve Drain Valve Drain Valve
Onsite Pump Onsite Pump Onsite Pump Onsite Pump
Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.)
IV. SUMMARY OF TESTING RESULTS
Spill Container Test Results Pass Fail Pass Fail Pass Fail Pass Fail
V. COMMENTS
All items marked “Fail” above must be explained in this section. Any additional comments may also be provided here.
VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING
I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section
2637.1 and all the information contained herein is accurate.
UST Service Technician Signature
If the facility has more components than this form accommodates, additional copies of this page may be attached.