Loading...
HomeMy WebLinkAboutSB-989 2019CERS = California Environmental Reporting System, ID = Identification, UST = Underground storage tank, ICC = International Code Council, NA = Not applicable, UDC = Under-dispenser containment UNDERGROUND STORAGE TANK SECONDARY CONTAINMENT TESTING REPORT FORM (Page 1 of 6) Type of Action Installation Test Repair Test Six Month Test 36 Month Test I. FACILITY INFORMATION CERS ID Date of Secondary Containment Test Business Name (Same as Facility Name or DBA-Doing Business As) Business Site Address City ZIP Code II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.) Phone # ( ) - Ext. Contractor/Tank Tester License # ICC Certification # ICC Certification Expiration Date III. SUMMARY OF SECONDARY CONTAINMENT TESTING RESULTS Tank ID: (By tank number, stored product, etc.) A B C D Tank Containment Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Product Piping Containment Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Communication Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Remote Fill Piping Containment Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Communication Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Vent Piping Containment Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Communication Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Vapor Recovery Piping Containment Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Communication Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Turbine / Product Piping Sump Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Fill Riser Sump Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA Vent / Transition Sump ID: a b c d Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA UDC ID: 1 2 3 4 Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA UDC ID: 5 6 7 8 Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA UDC ID: 9 10 11 12 Tightness Test Result Pass Fail NA Pass Fail NA Pass Fail NA Pass Fail NA All items marked “Fail” or “N/A” must be explained in their respective “COMMENTS” section. IV. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING I hereby certify that the secondary containment was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637 and all the information contained herein is accurate. UST Service Technician Signature UDC = Under-dispenser containment, ID = Identification UNDERGROUND STORAGE TANK SECONDARY CONTAINMENT TESTING REPORT FORM (Page 6 of 6) XXI. UNDER-DISPENSER CONTAINMENT TESTING INFORMATION Manufacturer(s): Identify UDC ID from section III for each Manufacturer 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 Test Method Used: Manufacturer Guidelines: (Specify) Industry Code or Engineering Standard: (Specify) Engineered Method: (Specify) Attach the testing procedures and all documentation required to determine the results. # of Attached Pages UDC Testing Training and Certifications (List applicable certifications.) Expiration Date XXII. COMMENTS Provide any additional comments here. If the facility has more components than this form accommodates, additional copies of these pages may be attached. 7tt! gi",!TF' ijrliU!,r anrrf,,1! 1- ft-E I ;'l ft TA 9llr'!E :-E4'ri rat: PEFIIE I .,t:-. +r 41r flf,, 14./ I : /2819 q! fF Fi4 1F rL l i?a l.! E, qE;: I!,