HomeMy WebLinkAboutOVERFILL 2020Testing and Inspection Certificate Tanknology Inc. 11000 North MoPac Expressway, Suite 500, Austin, TX 78759 800-800-4633 www.tanknology.com Page 1 of 1 Test Date 9/14/2020 Tanknology WO#SC1-3452154 Test Purpose COMPLIANCE Customer PO# Customer Location 7-ELEVEN, INC. P.O. BOX 711 DALLAS, TX 75221 7-ELEVEN #32241, MKT 2368 4101 CALLOWAY DRIVE BAKERSFIELD, CA 93312 Attn: ENVIRONMENTAL DEPARTMENT Attn: Iman 5/18/16 (972) 828-7575 (661) 379-5911 Test / Inspection Description Item Tested Date Tested Result Drop Tube/Drain Valve TankT4 RUL - Drain Valve 9/14/2020 Pass Drop Tube/Drain Valve TankT4 RUL - Drop Tube 9/14/2020 Pass Drop Tube/Drain Valve TankT5 PUL - Drain Valve 9/14/2020 Pass Drop Tube/Drain Valve TankT5 PUL - Drop Tube 9/14/2020 Pass Stage I Pressure Decay See test report for details 9/14/2020 Pass CA Overfill Prevention Equipment Inspection Report T4 RUL 4 RUL 9/14/2020 Pass CA Overfill Prevention Equipment Inspection Report T5 PUL 5 PUL 9/14/2020 Pass Overfill Insp OPW Flapper Valve T4 RUL RUL 9/14/2020 Pass Overfill Insp OPW Flapper Valve T5 PUL PUL 9/14/2020 Pass Tanknology Representative: Mark Lindsey Technician: Edwin Pineda Telephone: (800) 666-2176 Technician Certification: (See forms) TP‐201.1C/D Leak Rate of Drop Tube/Drain Valve Assembly and Leak Rate of Drop Tube Overfill Protection Devices and Spill Container Drain Valves Report Form Permit Number: S‐3256‐1‐3 Test Company: TANKNOLOGY INC. Site Name: 7‐ELEVEN #32241, MKT 2368 Technician: Edwin Pineda Site Address: 4101 CALLOWAY DRIVE Certification Number Expiration Date City: BAKERSFIELD Zip: 93312 District: SJV‐0227 4/4/2021 Date/Time of Test: 9/14/2020 DROP TUBE DRAIN VALVE AND OVERFILL PROTECTION DEVICE PRESSURE INTERGITY TEST Straight Drop Tube1 Drop Tube with an Overfill Protection Device2 Drop Tube Drain Valve Pressure Test: Flow rate 80 ml/min Drop Tube Overfill Device Pressure Test: Flow rate 200 ml/min “Corrected” Overfill Device Leak Rate Time to reach 2 in. w.c. at 80 ml/min Drain valve leak rate3 Final pressure Time to reach 2 in. w.c. at 200 ml/min Overfill leak rate3 Final pressure Overfill Device Leak Rate Minus Equals Drain Valve Leak Rate Corrected Leak Rate Tank Grade mins.ml/min in. w.c.mins.ml/min in. w.c.ml/min ml/min ml/min T4 RUL RUL 12 0.00 2.05 149 0.00 2.00 0.00 0.00 0.00 T5 PUL PUL 9 0.00 2.05 185 0.00 2.02 0.00 0.00 0.00 NOTES:1 A straight drop tube must be tested with a bladder in place and using a flow rate of 80 ml/min. 2 The bladder section of TP‐201.1D may be skipped if the entire drop tube passes with a leak rate below 80 ml/min 3 Leak rate = nitrogen flow rate needed to maintain a constant pressure (at least 2 in. w.c.) for 30 seconds. I declare, under penalty of perjury under the laws of the state of California that based on information and belief formed after reasonable inquiry, the statements and information provided in the document are true, accurate, and complete. Signature of Technician:Date:9/14/2020 WO: 3452154 Ver. 1.0 – 12.26.07 2 inch Pressure Decay Test TP201.3 Store Information Testing Company Site Name :7-ELEVEN #32241, MKT 2368 Name :TANKNOLOGY INC. Address :4101 CALLOWAY DRIVE BAKERSFIELD, CA 93312 Address :11000 N. MoPac Expressway Suite 500 Austin, TX 78759 Phone :661-379-5911 Phone :(800) 800-4633 Stage I System?Dual Stage II System?Assit Total # of Nozzles :8 Products per Nozzle :3 Tanks Manifolded ?Yes Drop-Out tank present?No Total # of Tanks Tested :2 Tank Information : Product Grade : Tank Capacity, gallons : Gasoline, gallons : Ullage, gallons : Testing Information : Start Time : Initial Pressure, wcg : Pressure @ 1 minute(s) : Pressure @ 2 minutes : Pressure @ 3 minutes : Pressure @ 4 minutes : Pressure @ 5 minutes : Allowable Final Pressure : Pass/Fail (Enter "GF" Gross Failure) T4 RUL RUL 14544 12387 2157 13:20 2.00 2.00 2.00 2.00 2.00 2.00 1.83 Pass T5 PUL PUL 9695 5889 3806 Total 24239 18276 5963 All 13:20 2.00 2.00 2.00 2.00 2.00 2.00 1.83 Pass Comments: Tester :Edwin Pineda Test Date :9/14/2020 Signature :Work Order :3452154 WO: 3452154 UNDERGROUND STORAGE TANK OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Page 1 of 1) Type of Action Installation Test Repair Test 36 Month Test I. FACILITY INFORMATION CERS ID 10024393 Date of Overfill Prevention Equipment Inspection: 9/14/2020 Business Name (Same as Facility Name or DBA-Doing Business As.) 7-ELEVEN #32241, MKT 2368 Business Site Address 4101 CALLOWAY DRIVE City: BAKERSFIELD Zip: 93312 II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.) Edwin Pineda Phone # (800) 800-4633 Contractor/Tank Tester License # Class A General Engineering 743160 ICC Certification # 8373052 ICC Certification Expiration Date 6/17/2021 Spill Container Testing Training and Certifications (List applicable certifications.) ICC - CA UST Service Technician 8373052 06/17/2021 OPW - EVR Phase 1 100776 01/05/2021 III. OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION Test Method Used: Manufacturer Guidelines (Specify) Industry Code or Engineering Standard (Specify) PEI RP 1200 Engineered Method (Specify) Attach the testing procedures and all documentation required to determine the results. # of Attached Pages: 1 Tank ID: (By tank number, stored product, etc.) What is the tank inside diameter? (Inches) Is the fill piping secondarily contained? Is the vent piping secondarily contained? Overfill Prevention Equipment Manufacturer(s) What is the overfill prevention equipment response when activated? (Check all that apply.) Are flow restrictors installed on vent piping? At what level in the tank is the overfill prevention set to activate? (Inches from bottom of tank.) What is the percent capacity of the tank at which the overfill prevention equipment activates? Is the overfill prevention in proper operating condition to respond when the substance reaches the appropriate level? IV. Overfill Prevention Inspection Results T4 RUL 91.63 in. Yes No Yes No Unknown OPW Shuts Off Flow Restrict Flow A/V Alarm Yes No 80.75" 93.55% Yes No (Specify in section V) T5 PUL 91.63 in. Yes No Yes No Unknown OPW Shuts Off Flow Restrict Flow A/V Alarm Yes No 80.75" 93.13% Yes No (Specify in section V) Yes No Yes No Shuts Off Flow Restrict Flow A/V Alarm Yes No Yes No (Specify in section V) Yes No Yes No Shuts Off Flow Restrict Flow A/V Alarm Yes No Yes No (Specify in section V) SUMMARY OF TESTING RESULTS Pass Fail Pass Fail Pass Fail Pass Fail V. COMMENTS All items marked failed above must be explained in this section. Any additional comments may also be provided here. VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1 and all the information contained herein is accurate. UST Service Technician Signature If the facility has more components than this form accommodates, additional copies of this page may be attached. CERS=California Environmental Reporting System, ID=Identification, UST=Underground storage tank, ICC=International Code Council Overfill Prevention Equipment Inspection OPW 61 and 71 Series Overfill Prevention Device Inspection Date:9/14/2020 Customer Name:7-ELEVEN, INC. Location #:7-ELEVEN #32241, MKT 2368 Location Address:4101 CALLOWAY DRIVE ,BAKERSFIELD ,CA , 93312 OPW Model Number:61SO PART 1) Proper height setting calculation Maximum Tank Volume per: Tank Chart A gallons Max shut off requirement for Flapper is 95% B 95% Multiply Maximum tank volume by 95% C gallons Use tank chart to determine height of calculated volume D inches Measure top of fill riser threads, or face seal adapter when used, to tank top E inches Tank diameter From Chart F inches Upper Tube in tank (G) F - D = G G inches Subtract 2 inches from upper tube in tank G - 2"= H H inches Calculated minimum upper tube length (I) H + E = I I inches Actual measured upper tube length (Without fill adapter) (J) J inches PART 2) Device certification criteria evaluation Criteria 1 Does the overfill prevention device meet the 95% requirement? Criteria 1a If the final shutoff volume is installed greater than 95%, is there at least 250 gallons of ullage above the overfill device activation point to ensure that none of the tank top fittings are exposed to product, meeting the criteria established in EPA 280.20iic and per OPW installation guidelines. Criteria 2 Is the Actual measured upper tube length 6.5 inches or more than the fill riser? (J must be 6.5" or more than E) Criteria 3 Does the overfill prevention device function as required? (Inspect the device for damage, contamination, freedom of movement, weakening due to wear and corrosion) PART 3) Device Certification PASS / FAIL Technician certifies that the device is operationally compliant. T4 RUL 14544.000 0.95 13816.800 82.500 60.875 91.625 9.125 7.125 68.000 69.250 Yes NA Yes Yes Pass T5 PUL 9695.000 0.95 9210.250 82.375 58.125 91.625 9.250 7.250 65.375 67.125 Yes NA Yes Yes Pass 0.95 0.95 Comments: Signature of Technician: Date: 9/14/2020 Edwin Pineda WO: SC1- 3452154 Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:3452154 Site ID / Name:32241 / 7-ELEVEN #32241, MKT 2368 Address:4101 CALLOWAY DRIVE City:BAKERSFIELD State:CA Zip:93312 W.O.# SC1-3452154 OVF W.O.# SC1-3452154 TAPES W.O.# SC1-3452154