HomeMy WebLinkAboutFMC 2020Appendix VI Underground Storage Tank  Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION Installation Repair 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3.TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4.CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages Underground Storage Tank  Monitoring System Certification Form Page 2 of 6 5.MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; Monitoring System Set-up Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? Secondary containment systems are free of damage, debris, or liquid? Are the audible and visual alarms operational? All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? The monitoring system set-up was reviewed, and proper settings confirmed? Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) Sump UDC If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Underground Storage Tank  Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Underground Storage Tank  Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) 3 GPH 0.1 GPH 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? For electronic LLDs, does the turbine automatically shut off when a release is detected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? Were all items on the equipment manufacturer’s maintenance checklist completed? Were all LLDs confirmed operational within regulatory requirements? LLD ID LLD Model Lines Monitored Pass Fail Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Underground Storage Tank  Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING Check this box if tank gauging is used only for inventory control. Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? Was accuracy of system’s product level readings tested? Was accuracy of system’s water level readings tested? Were all probes reinstalled properly? Were all items on the equipment manufacturer’s maintenance checklist completed? Probe ID Probe Model Tanks Monitored Pass Fail 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. UDC-1UDC-2 U D C - 3 U D C - 4 1234 5 6 7 8 Diesel 91 Premium 87 Unleaded 22,000 GALLONS UST-1 8 , 0 0 0 G A L L O N S U S T - 2 20,000 GALLONS UST-3 TS-3 TS-1TS-2 FS-1 F S - 2 FS-3 AA V VVV DISPENSER U D C 1 - 2 536 SENSO R D I S P E N S E R U D C 3 - 4 5 3 6 S E N S O R D I S P E N S E R U D C 5 - 6 5 3 6 S E N S O R D I S P E N S E R U D C 7 - 8 5 3 6 S E N S O R 87 TURBINE SUMP536 SENSOR480 SENSOR99LD LINE LEAK DETECTORVACUUM SENSOR KIT #11-2-3-4-5-6-7-8 PRODUCT LINEDIESEL TURBINE SUMP536 SENSOR480 SENSOR99LD LINE LEAK DETECTORVACUUM SENSOR KIT #31-2-7-8 PRODUCT LINE91 TURBINE SUMP536 SENSOR480 SENSOR99LD LINE LEAK DETECTORVACUUM SENSOR KIT #21-2-3-4-5-6-7-8 PRODUCT LINE87 FILL SUMP536 SENSORDIESEL FILL SUMP536 SENSOR P R E M I U M F I L L S U M P 5 3 6 S E N S O R DIESEL ANNULAR303 SENSOR 8 7 9 1 A N N U L A R 3 0 3 S E N S O R HEALY CLE A N A I R S E P E R A T O R V E N T S U M P T R A N S I T I O N S U M P 5 3 6 S E N S O R ZONE # 1-87 REGULARZONE#4- 91 PREMIUM ZONE #2- 87 VAPOR LINE Z O N E # 3 - 8 7 V E N T L I N E Z O N E # 7 - D I E S E L V E N T L I N E Z O N E # 5 - 9 1 V E N T L I N E SLOPE 18" P E R F O O T M I N . T O T A N K S S T O R E E L E C T R I C A L T I E I N FIRE HYDRANT E S T O P T L S H A G E M A N R D COFFEE RD30K SPLIT TANK L E G E N D V A C U U M S E N S O R K I T # 1 - 8 7 T U R B I N E Z O N E 1 8 7 B R U G G P R O D U C T Z O N E 2 8 7 V A P O R L I N E Z O N E 3 8 7 V E N T L I N E V A C U U M S E N S O R K I T # 2 - 9 1 T U R B I N E Z O N E 4 9 1 B R U G G P R O D U C T Z O N E 5 9 1 V E N T L I N E V A C U U M S E N S O R K I T # 3 - D I E S E L T U R B I N E Z O N E 6 D I E S E L B R U G G P R O D U C T Z O N E 7 D I E S E L V E N T L I N E V E E D E R R O O T S E N S O R , P R O B E S , L E A K D E T E C T O R S 4 D I S P E N S E R + U D C U D C 1 , 2 , 3 , 4 3 3 0 0 2 0 - 5 3 6 H Y D R O S T A T I C D I S P E N S E R P A N S E N S O R 2 A N N U L A R S 3 0 K S P L I T + 2 0 K 3 3 0 0 2 0 - 5 3 6 H Y D R O S T A T I C D I S P E N S E R P A N S E N S O R 7 9 4 3 8 0 - 3 0 3 B R I N E S E N S O R 3 T U R B I N E S U M P S 8 7 , 9 1 , D I E S E L P R O D U C T S 3 3 0 0 2 0 - 5 3 6 H Y D R O S T A T I C D I S P E N S E R P A N S E N S O R 3 3 0 0 2 0 - 4 8 0 V A C U U M S E N S O R 1 1 6 - 0 5 7 - 5 L I N E L E A K D E T E C T O R 3 F I L L S U M P S 8 7 , 9 1 , D I E S E L 3 3 0 0 2 0 - 5 3 6 H Y D R O S T A T I C D I S P E N S E R P A N S E N S O R 1 V E N T S U M P H E A L Y T A N K 3 3 0 0 2 0 - 5 3 6 H Y D R O S T A T I C D I S P E N S E R P A N S E N S O R 3 T A N K P R O B E S 8 7 , 9 1 , D I E S E L 8 4 6 3 9 0 - 1 1 0 M A G P R O B E 3 L E A K D E T E C T O R S 8 7 , 9 1 , D I E S E L 9 9 L D - 2 0 0 0 V M I L I N E L E A K D E T E C T O R 6 " X 7 F O O T B O L L A R D S H B P R O P A N E T A N K SITE MAP = P e n e t r a t i o n s B R A V O F - 7 5 - P E - B R G - D ( 6 5 ) F O R P R O D U C T = P e n e t r a t i o n s B R A V O F - 3 2 - T S - D B R A V O F B ( 5 1 ) F O R V A P O R / V E N T NORTHZONE# 6- DIESELPRICE SIGN AIR /WATER S I T E H A Z M A T I N V E N T O R Y C A R B O N D I O X I D E L I Q U I D A B S O R B A N T P A D S C I M - T E K F I L T E R S L I Q U E F I E D P E T R O L E U M G A S ( L P G ) G A S O L I N E A L L G R A D E S D I E S E L F U E L N O . 2 C O 2 C O 2 F I R E S U P R E S S I O N C I R C U I T B R E A K E R WATER METER SHUTOFF O V E R F I L L A L A R M C I M - T E K F I L T E R S O U T S I D E A B S O R B A N T P A D S O U T S I D E Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ☐ Installation ☐ Repair ☐ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ☐ Manufacturer ☐ Industry Standard ☐ Professional Engineer Test Type ☐ Pressure ☐ Vacuum ☐ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other Is the spill container minimum capacity five gallons excluding riser volume? ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* Method to keep spill container empty ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other Spill Container Test Results ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other Is the spill container minimum capacity five gallons excluding riser volume? ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* Method to keep spill container empty ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other Spill Container Test Results ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] < I20100NOV 17, 2020 2:08 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 IN-TANK INVENTORY TANK PRODUCT VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP 1 87 UNLEADED 11608 11543 9959 63.18 0.00 68.00 2 91 PREMIUM 6092 6043 2439 80.30 0.00 71.43 3 DIESEL 3564 3560 16387 28.68 0.00 83.31 > <I90500 NOV 17, 2020 2:08 PMSOFTWARE REVISION LEVEL VERSION 335.00SOFTWARE# 346335-100-A CREATED - 18.08.27.10.22 S-MODULE# 330160-004-aSYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM >< I50201NOV 17, 2020 2:08 PM SHIFT TIME 1 : 1:00 AM > <I50202 NOV 17, 2020 2:08 PM SHIFT TIME 2 : DISABLED >< I50203NOV 17, 2020 2:08 PM SHIFT TIME 3 : DISABLED > file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] < I50204NOV 17, 2020 2:08 PM SHIFT TIME 4 : DISABLED > <I54600 NOV 17, 2020 2:08 PM TANK PER TST NEEDED WRN: DISABLED >< I54900NOV 17, 2020 2:08 PM TANK ANN TST NEEDED WRN: DISABLED > <I55300 NOV 17, 2020 2:08 PM LINE RE-ENABLE METHODALARM ACKNOWLEDGE > <I55600 NOV 17, 2020 2:09 PM LINE PER TST NEEDED WRN: DISABLED >< I55900NOV 17, 2020 2:09 PM LINE ANN TST NEEDED WRN: DISABLED > <I51400 NOV 17, 2020 2:09 PM H-PROTOCOL DATA FORMATHEIGHT > <I51A01 NOV 17, 2020 2:09 PM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] DAYLIGHT SAVING TIMEENABLED OFF > <I51B00 NOV 17, 2020 2:09 PM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM >< I51600NOV 17, 2020 2:09 PM RE-DIRECT LOCAL PRINTOUT DISABLED >< I50400NOV 17, 2020 2:09 PM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED >< I21900NOV 17, 2020 2:09 PM TANK CHART SECURITY DISABLED >< I5BD00NOV 17, 2020 2:09 PM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] CUSTOM ALARM LABELS DISABLED > <I56000 NOV 17, 2020 2:09 PM MASS/DENSITY DISABLED >< I88101NOV 17, 2020 2:09 PM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : ODD STOP BIT : 2 STOP DATA LENGTH: 7 DATARS-232 SECURITY CODE : DISABLED >< I88102NOV 17, 2020 2:09 PM PORT SETTINGS: COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATARS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH > <I88103 NOV 17, 2020 2:09 PMPORT SETTINGS: COMM BOARD : 3 (EDIM ) RS-232 SECURITYCODE : DISABLED > < file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] I60100 NOV 17, 2020 2:09 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 87 UNLEADED ON 2 91 PREMIUM ON 3 DIESEL ON 4 OFF >< I60200NOV 17, 2020 2:09 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 87 UNLEADED 2 91 PREMIUM 3 DIESEL 4 >< I60300NOV 17, 2020 2:09 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 87 UNLEADED 1 2 91 PREMIUM 2 3 DIESEL 3 4 4 >< I60900NOV 17, 2020 2:09 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 87 UNLEADED 0.000700 2 91 PREMIUM 0.000700 3 DIESEL 0.000045 4 0.000000 >< I60700NOV 17, 2020 2:09 PM TANK DIAMETER file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] TANK PRODUCT LABEL INCHES 1 87 UNLEADED 120.00 2 91 PREMIUM 120.00 3 DIESEL 120.00 4 0.00 >< I60A00NOV 17, 2020 2:09 PM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 87 UNLEADED 4 PTS 21567 2 91 PREMIUM 4 PTS 8531 3 DIESEL 4 PTS 19951 4 1 PT 0 >< I60400NOV 17, 2020 2:10 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 21567 2 91 PREMIUM 8531 3 DIESEL 19951 4 0 >< I60500NOV 17, 2020 2:10 PM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 21567 17567 10858 4125 2 91 PREMIUM 8531 6888 4294 1692 3 DIESEL 19951 16262 10044 3804 4 0 0 0 0 > <I60600 NOV 17, 2020 2:10 PM TANK 20 POINT VOLUMES file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 21567 0 0 0 0 17567 0 0 0 0 10858 0 0 0 0 4125 0 0 0 0 2 91 PREMIUM 8531 0 0 0 0 6888 0 0 0 0 4294 0 0 0 0 1692 0 0 0 0 3 DIESEL 19951 0 0 0 0 16262 0 0 0 0 10044 0 0 0 0 3804 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 >< I61500NOV 17, 2020 2:10 PM TANK PRODUCT LABEL METER DATA 1 87 UNLEADED NO 2 91 PREMIUM NO 3 DIESEL NO 4 NO > <I62F00 NOV 17, 2020 2:10 PM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 87 UNLEADED 4.0 IN. 2 91 PREMIUM 2.0 IN. 3 DIESEL 4.0 IN. > <I62700 NOV 17, 2020 2:10 PM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] 1 87 UNLEADED 1.5 2 91 PREMIUM 1.5 3 DIESEL 1.5 >< I64200NOV 17, 2020 2:10 PM WATER ALARM FILTER TANK PRODUCT LABEL 1 87 UNLEADED LOW 2 91 PREMIUM LOW 3 DIESEL LOW >< I62400NOV 17, 2020 2:10 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 87 UNLEADED 2.0 2 91 PREMIUM 2.0 3 DIESEL 2.0> <I62800 NOV 17, 2020 2:10 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 21567 2 91 PREMIUM 8531 3 DIESEL 19951 4 0> <I62300 NOV 17, 2020 2:10 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 19410 2 91 PREMIUM 7678 3 DIESEL 17956 4 0> <I62200 NOV 17, 2020 2:10 PM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 20489 2 91 PREMIUM 8104 3 DIESEL 18953 4 0> <I62900 NOV 17, 2020 2:10 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 2157 2 91 PREMIUM 853 3 DIESEL 1995 4 0> <I62100 NOV 17, 2020 2:10 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 1000 2 91 PREMIUM 500 3 DIESEL 1000 4 0> <I62600 NOV 17, 2020 2:10 PM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 99 2 91 PREMIUM 99 3 DIESEL 99 4 99> <I62500 NOV 17, 2020 2:11 PM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 99 2 91 PREMIUM 99 file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] 3 DIESEL 99 4 99> <I60800 NOV 17, 2020 2:11 PM TANK TILT TANK PRODUCT LABEL INCHES 1 87 UNLEADED 0.00 2 91 PREMIUM 0.00 3 DIESEL 0.00 4 0.00> <I60B00 NOV 17, 2020 2:11 PM STICK HEIGHT OFFSET ENABLE STATUSDISABLED > <I60C00 NOV 17, 2020 2:11 PM TANK STICK HEIGHT OFFSETTANK PRODUCT LABEL INCHES 1 87 UNLEADED 0.00 2 91 PREMIUM 0.00 3 DIESEL 0.00 4 0.00 >< I61200NOV 17, 2020 2:11 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 87 UNLEADED NONE NONE 2 91 PREMIUM NONE NONE 3 DIESEL NONE NONE 4 NONE NONE >< I63600NOV 17, 2020 2:11 PM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 0 file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] 2 91 PREMIUM 0 3 DIESEL 0 4 0 >< I62A00NOV 17, 2020 2:11 PM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 0 2 91 PREMIUM 0 3 DIESEL 0 4 0 >< I62C00NOV 17, 2020 2:11 PM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 87 UNLEADED STANDARD 2 91 PREMIUM STANDARD 3 DIESEL STANDARD 4 STANDARD > <I62D00 NOV 17, 2020 2:11 PM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 87 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 91 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED > file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] < I63100NOV 17, 2020 2:11 PM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 87 UNLEADED OFF OFF 2 91 PREMIUM OFF OFF 3 DIESEL OFF OFF 4 OFF OFF > <I63000 NOV 17, 2020 2:11 PM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 87 UNLEADED OFF 2 91 PREMIUM OFF 3 DIESEL OFF 4 OFF >< I63200NOV 17, 2020 2:11 PM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 87 UNLEADED OFF 2 91 PREMIUM OFF 3 DIESEL OFF 4 OFF > <I61000 NOV 17, 2020 2:11 PM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 87 UNLEADED 5 2 91 PREMIUM 5 3 DIESEL 5 4 1> <I63A00 NOV 17, 2020 2:11 PM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 87 UNLEADED 10.00% 2 91 PREMIUM 10.00% 3 DIESEL 10.00% 4 10.00% >< I61100NOV 17, 2020 2:11 PM LEAK TEST METHOD - - - - - - - - - - - -TEST ON DATE : ALL TANK AUG 27, 2018START TIME : DISABLED TEST RATE :0.20 GAL/HRDURATION : 2 HOURS TST EARLY STOP:DISABLED > <I61300 NOV 17, 2020 2:12 PMCSLD PROBABLITY OF DETECTION >< I61400NOV 17, 2020 2:12 PM CSLD CLIMATE FACTOR > <I61600 NOV 17, 2020 2:12 PM TANK PRODUCT LABEL CAL UPDATE 1 87 UNLEADED IMMEDIATE 2 91 PREMIUM IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE >< I61A00NOV 17, 2020 2:12 PM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 87 UNLEADED DISABLED 2 91 PREMIUM DISABLED 3 DIESEL DISABLED 4 DISABLED >< I61B00NOV 17, 2020 2:12 PM IN-TANK LEAK GROSS TEST AUTO-CONFIRM >< I61C00NOV 17, 2020 2:12 PM CSLD REPORT ONLY >< I63400NOV 17, 2020 2:12 PM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 0 2 91 PREMIUM 0 3 DIESEL 0 4 0 >< I63500NOV 17, 2020 2:12 PM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 1 2 91 PREMIUM 1 3 DIESEL 1 4 1 >< I78700NOV 17, 2020 2:12 PM > < file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] I70200 NOV 17, 2020 2:12 PM LIQUID LABEL DEVICE LABEL 1 87 STP 2 87 FILL 3 91 STP 4 91 FILL 5 DIESEL STP 6 DIESEL FILL 7 UNLEADED ANNULAR 8 DIESEL ANNULAR 9 1-2 UDC 10 3-4 UDC 11 5-6 UDC 12 7-8 UDC 13 VENT BOX 14 15 16 >< I70300NOV 17, 2020 2:12 PM LIQUID TYPE SENSOR LOCATION TYPE 1 87 STP DW SUMP 2-1 2 87 FILL DW SUMP 2-1 3 91 STP DW SUMP 2-1 4 91 FILL DW SUMP 2-1 5 DIESEL STP DW SUMP 2-1 6 DIESEL FILL DW SUMP 2-1 7 UNLEADED ANNULAR DUAL POINT HYDROSTATIC 8 DIESEL ANNULAR DUAL POINT HYDROSTATIC 9 1-2 UDC DW SUMP 2-1 10 3-4 UDC DW SUMP 2-1 11 5-6 UDC DW SUMP 2-1 12 7-8 UDC DW SUMP 2-1 13 VENT BOX DW SUMP 2-1 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) > <I70400 NOV 17, 2020 2:12 PM LIQUID CATEGORY file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] SENSOR LOCATION CATEGORY 1 87 STP STP SUMP 2 87 FILL PIPING SUMP 3 91 STP STP SUMP 4 91 FILL PIPING SUMP 5 DIESEL STP STP SUMP 6 DIESEL FILL PIPING SUMP 7 UNLEADED ANNULAR ANNULAR SPACE 8 DIESEL ANNULAR ANNULAR SPACE 9 1-2 UDC DISPENSER PAN 10 3-4 UDC DISPENSER PAN 11 5-6 UDC DISPENSER PAN 12 7-8 UDC DISPENSER PAN 13 VENT BOX OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS > <I80700 NOV 17, 2020 2:12 PM RELAY LABEL DEVICE LABEL 1 87 STP 2 91 STP 3 DIESEL STP 4 TEST 5 DISP 1-2 6 DISP 3-4 7 DISP 5-6 8 DISP 7-8 9 10 11 12 OVERFILL >< I80900NOV 17, 2020 2:13 PM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 87 STP NORMALLY OPEN 2 91 STP NORMALLY OPEN 3 DIESEL STP NORMALLY OPEN 4 TEST NORMALLY OPEN 5 DISP 1-2 NORMALLY OPEN 6 DISP 3-4 NORMALLY OPEN file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] 7 DISP 5-6 NORMALLY OPEN 8 DISP 7-8 NORMALLY OPEN 9 NORMALLY OPEN 10 NORMALLY OPEN 11 NORMALLY OPEN 12 OVERFILL NORMALLY OPEN >< I80B00NOV 17, 2020 2:13 PM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 87 STP 1 2 91 STP 2 3 DIESEL STP 3 4 TEST NONE 5 DISP 1-2 NONE 6 DISP 3-4 NONE 7 DISP 5-6 NONE 8 DISP 7-8 NONE 9 NONE 10 NONE 11 NONE 12 OVERFILL NONE > <I80A00 NOV 17, 2020 2:13 PM RELAY TYPE RELAY DESIGNATION TYPE 1 87 STP PUMP CONTROL OUTPUT 2 91 STP PUMP CONTROL OUTPUT 3 DIESEL STP PUMP CONTROL OUTPUT 4 TEST STANDARD 5 DISP 1-2 STANDARD 6 DISP 3-4 STANDARD 7 DISP 5-6 STANDARD 8 DISP 7-8 STANDARD 9 STANDARD 10 STANDARD 11 STANDARD 12 OVERFILL STANDARD >< I80800NOV 17, 2020 2:13 PM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] RELAY SETUP REPORT R 1:87 STP TYPE: PUMP CONTROL OUTPUT TANK #: 1 IN-TANK ALARMS T 1:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:FLOW COLLECT FAIL R 2:91 STP TYPE: PUMP CONTROL OUTPUTTANK #: 2 IN-TANK ALARMS T 2:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 3:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 3:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:FLOW COLLECT FAIL R 3:DIESEL STP TYPE: PUMP CONTROL OUTPUT TANK #: 3 IN-TANK ALARMS T 3:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 5:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM R 4:TEST TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] R 5:DISP 1-2 TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 6:DISP 3-4 TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 7:DISP 5-6 TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 8:DISP 7-8 TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 9: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R10: TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] R11: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R12:OVERFILL TYPE: STANDARDNORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ><I79000 NOV 17, 2020 2:14 PM EDIM:1 VR:349643-001-B TD:97.10.27.11.25 >< I72300NOV 17, 2020 2:14 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 87 PRODUCT VAC SENSOR02 UNKNOWN 03 VAPOR RETURN VAC SENSOR04 91 PRODUCT VAC SENSOR 05 ALL VENTS VAC SENSOR06 DIESEL PRODUCT VAC SENSOR 07 UNKNOWN08 ATM ATM P SENSOR 09 1-2 FLOWMETER AIR FLOW METER10 3-4 FLOWMETER AIR FLOW METER 11 5-6 FLOWMETER AIR FLOW METER file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] 12 7-8 FLOWMETER AIR FLOW METER 13 UNKNOWN14 UNKNOWN 15 UNKNOWN16 PRESSURE SENSOR VAPOR PRESSURE 17 UNKNOWN18 UNKNOWN 19 UNKNOWN20 UNKNOWN 21 UNKNOWN22 UNKNOWN 23 UNKNOWN24 UNKNOWN 25 UNKNOWN26 UNKNOWN 27 UNKNOWN28 UNKNOWN 29 UNKNOWN30 UNKNOWN 31 UNKNOWN32 UNKNOWN 33 UNKNOWN34 UNKNOWN 35 UNKNOWN36 UNKNOWN 37 UNKNOWN38 UNKNOWN 39 UNKNOWN40 UNKNOWN > <IV4F00 NOV 17, 2020 2:14 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 >< IV4000NOV 17, 2020 2:14 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 VAPOR PROCESSOR TYPE file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] NONE > <IV4700 NOV 17, 2020 2:14 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 ASSESSMENT TIME START TIME: 9:00 AMTIME DELAY MINUTES: 1 > <IV5200 NOV 17, 2020 2:14 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 ACCEPT HIGH ORVR: NO >< IV4A00NOV 17, 2020 2:14 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 02 BLEND3 02 02 02 01 02 BLEND3 03 03 03 02 02 BLEND3 04 04 04 02 02 BLEND3 05 05 05 03 02 BLEND3 06 06 06 03 02 BLEND3 07 07 07 04 02 BLEND3 08 08 08 04 02 BLEND3 > <IV4B00 NOV 17, 2020 2:14 PM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 xx/xx 02/01 01/01 xx/xx02 01 02/02 xx/xx 09/02 01/02 03 02 02/03 09/03 01/03 xx/xx04 02 02/04 01/04 09/04 xx/xx 05 03 02/05 01/05 09/05 xx/xx06 03 02/06 09/06 01/06 xx/xx 07 04 02/07 01/07 09/07 xx/xx08 04 02/08 01/08 xx/xx 09/08 > <IV4900 NOV 17, 2020 2:14 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 LABEL TABLE ID LABEL01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 >< IV1000NOV 17, 2020 2:14 PM ISD VERSION: 01.05 > <I90200 NOV 17, 2020 2:14 PMSOFTWARE REVISION LEVEL VERSION 335.00 file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] SOFTWARE# 346335-100-A CREATED - 18.08.27.10.22 S-MODULE# 330160-004-aSYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM >< I11100NOV 17, 2020 2:14 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 PRIORITY ALARM HISTORYID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 5 STP SUMP DIESEL STP LOW LIQUID ALARM CLEAR 11-17-20 12:23PML 5 STP SUMP DIESEL STP LOW LIQUID ALARM ALARM 11-17-20 12:23PM L 5 STP SUMP DIESEL STP LOW LIQUID ALARM CLEAR 11-17-20 12:23PML 5 STP SUMP DIESEL STP LOW LIQUID ALARM ALARM 11-17-20 12:23PM T 2 TANK 91 PREMIUM HIGH WATER ALARM CLEAR 11-17-20 12:15PMT 2 TANK 91 PREMIUM PROBE OUT CLEAR 11-17-20 12:12PM T 1 TANK 87 UNLEADED PROBE OUT CLEAR 11-17-20 11:58AMT 1 TANK 87 UNLEADED PROBE OUT ALARM 11-17-20 11:57AM T 3 TANK DIESEL PROBE OUT CLEAR 11-17-20 11:57AMT 2 TANK 91 PREMIUM PROBE OUT ALARM 11-17-20 11:57AM T 3 TANK DIESEL PROBE OUT ALARM 11-17-20 11:56AMT 2 TANK 91 PREMIUM PROBE OUT CLEAR 11-17-20 11:56AM T 2 TANK 91 PREMIUM PROBE OUT ALARM 11-17-20 11:55AMT 2 TANK 91 PREMIUM OVERFILL ALARM CLEAR 11-17-20 11:55AM L 8 ANNULAR DIESEL ANNULAR HIGH LIQUID ALARM CLEAR 11-17-20 11:54AML 8 ANNULAR DIESEL ANNULAR HIGH LIQUID ALARM ALARM 11-17-20 11:54AM L 8 ANNULAR DIESEL ANNULAR LOW LIQUID ALARM CLEAR 11-17-20 11:54AML 8 ANNULAR DIESEL ANNULAR LOW LIQUID ALARM ALARM 11-17-20 11:54AM L 7 ANNULAR UNLEADED ANNULAR LOW LIQUID ALARM CLEAR 11-17-20 11:54AML 7 ANNULAR UNLEADED ANNULAR LOW LIQUID ALARM ALARM 11-17-20 11:54AM L 7 ANNULAR UNLEADED ANNULAR HIGH LIQUID ALARM CLEAR 11-17-20 11:54AML 7 ANNULAR UNLEADED ANNULAR HIGH LIQUID ALARM ALARM 11-17-20 11:54AM L 7 ANNULAR UNLEADED ANNULAR LOW LIQUID ALARM CLEAR 11-17-20 11:53AML 7 ANNULAR UNLEADED ANNULAR LOW LIQUID ALARM ALARM 11-17-20 11:53AM T 2 TANK 91 PREMIUM HIGH WATER ALARM ALARM 11-17-20 11:52AMT 2 TANK 91 PREMIUM OVERFILL ALARM ALARM 11-17-20 11:49AM T 2 TANK 91 PREMIUM MAX PRODUCT ALARM CLEAR 11-17-20 11:49AMT 2 TANK 91 PREMIUM MAX PRODUCT ALARM ALARM 11-17-20 11:49AM T 1 TANK 87 UNLEADED OVERFILL ALARM CLEAR 11-17-20 11:35AML 6 PIPE DIESEL FILL SENSOR OUT ALARM CLEAR 11-17-20 11:35AM L 2 PIPE 87 FILL SENSOR OUT ALARM CLEAR 11-17-20 11:35AML12 DISP PAN 7-8 UDC SENSOR OUT ALARM CLEAR 11-17-20 11:35AM L 4 PIPE 91 FILL SENSOR OUT ALARM CLEAR 11-17-20 11:35AM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] L 8 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM CLEAR 11-17-20 11:35AM L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-17-20 11:35AML 7 ANNULAR UNLEADED ANNULAR SENSOR OUT ALARM CLEAR 11-17-20 11:35AM L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 11-17-20 11:35AML11 DISP PAN 5-6 UDC SENSOR OUT ALARM CLEAR 11-17-20 11:35AM L 5 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 11-17-20 11:35AML10 DISP PAN 3-4 UDC SENSOR OUT ALARM CLEAR 11-17-20 11:35AM L 9 DISP PAN 1-2 UDC SENSOR OUT ALARM CLEAR 11-17-20 11:35AML13 OTHER VENT BOX SENSOR OUT ALARM CLEAR 11-17-20 11:34AM L13 OTHER VENT BOX SENSOR OUT ALARM ALARM 11-17-20 11:34AML12 DISP PAN 7-8 UDC SENSOR OUT ALARM ALARM 11-17-20 11:34AM L 4 PIPE 91 FILL SENSOR OUT ALARM ALARM 11-17-20 11:34AML11 DISP PAN 5-6 UDC SENSOR OUT ALARM ALARM 11-17-20 11:34AM L10 DISP PAN 3-4 UDC SENSOR OUT ALARM ALARM 11-17-20 11:34AML 8 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM ALARM 11-17-20 11:34AM L 2 PIPE 87 FILL SENSOR OUT ALARM ALARM 11-17-20 11:34AML 7 ANNULAR UNLEADED ANNULAR SENSOR OUT ALARM ALARM 11-17-20 11:34AM > <I11200 NOV 17, 2020 2:14 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIMET 2 TANK 91 PREMIUM HIGH WATER WARNING CLEAR 11-17-20 12:15PM T 2 TANK 91 PREMIUM LOW TEMP WARNING CLEAR 11-17-20 12:12PMT 2 TANK 91 PREMIUM LOW TEMP WARNING ALARM 11-17-20 12:12PM T 1 TANK 87 UNLEADED LOW TEMP WARNING CLEAR 11-17-20 12:00PMT 1 TANK 87 UNLEADED LOW TEMP WARNING ALARM 11-17-20 11:58AM T 2 TANK 91 PREMIUM HIGH WATER WARNING ALARM 11-17-20 11:52AMT 2 TANK 91 PREMIUM HIGH PRODUCT ALARM CLEAR 11-17-20 11:49AM T 2 TANK 91 PREMIUM HIGH PRODUCT ALARM ALARM 11-17-20 11:49AMT 1 TANK 87 UNLEADED HIGH PRODUCT ALARM CLEAR 11-17-20 11:31AM T 1 TANK 87 UNLEADED HIGH PRODUCT ALARM ALARM 11-17-20 11:29AMT 2 TANK 91 PREMIUM DELIVERY NEEDED CLEAR 11-17-20 11:22AM T 2 TANK 91 PREMIUM DELIVERY NEEDED ALARM 11-17-20 11:22AMT 3 TANK DIESEL DELIVERY NEEDED CLEAR 11-17-20 11:22AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 11-17-20 11:21AM SYSTEM PAPER OUT CLEAR 11-17-20 11:17AM SYSTEM PAPER OUT ALARM 11-17-20 11:17AM SYSTEM PAPER OUT CLEAR 11-17-20 11:16AM SYSTEM PAPER OUT ALARM 11-17-20 11:15AMs 5 OTHER ALL VENTS VACUUM WARNING CLEAR 9-10-20 11:44AM s 5 OTHER ALL VENTS VACUUM WARNING ALARM 9-10-20 11:24AMs 5 OTHER ALL VENTS VACUUM WARNING CLEAR 9-10-20 10:37AM s 5 OTHER ALL VENTS VACUUM WARNING ALARM 9-10-20 10:36AMs 5 OTHER ALL VENTS VACUUM WARNING CLEAR 9-04-20 2:23PM s 5 OTHER ALL VENTS VACUUM WARNING ALARM 9-04-20 1:28PM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] SYSTEM PAPER OUT CLEAR 7-03-20 5:12AM SYSTEM PAPER OUT ALARM 7-02-20 2:04PM SYSTEM PRINTER ERROR CLEAR 6-30-20 4:54PM SYSTEM PRINTER ERROR ALARM 6-30-20 4:54PM OTHER ISD VAPOR LEAK WARN CLEAR 5-06-20 2:01PM SYSTEM PAPER OUT CLEAR 5-06-20 9:09AM SYSTEM PRINTER ERROR CLEAR 5-06-20 9:09AM SYSTEM PRINTER ERROR ALARM 5-06-20 9:09AM SYSTEM PAPER OUT ALARM 5-06-20 9:06AM OTHER ISD VAPOR LEAK WARN ALARM 5-06-20 9:06AMT 3 TANK DIESEL DELIVERY NEEDED CLEAR 4-30-20 3:41PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 4-29-20 2:55PM SYSTEM PRINTER ERROR CLEAR 4-15-20 11:10AM SYSTEM PRINTER ERROR ALARM 4-15-20 11:10AM SYSTEM PAPER OUT CLEAR 3-11-20 11:26AM SYSTEM PAPER OUT ALARM 3-11-20 11:25AM SYSTEM PRINTER ERROR CLEAR 2-01-20 8:10AM SYSTEM PRINTER ERROR ALARM 2-01-20 8:10AM SYSTEM PAPER OUT CLEAR 1-30-20 5:10AM SYSTEM PRINTER ERROR CLEAR 1-30-20 5:06AM SYSTEM PRINTER ERROR ALARM 1-30-20 5:06AM SYSTEM PAPER OUT ALARM 1-29-20 3:42AM SYSTEM PAPER OUT CLEAR 12-05-19 7:19AM SYSTEM PAPER OUT ALARM 12-05-19 1:00AM OTHER ISD VAPOR LEAK WARN CLEAR 11-15-19 2:39PM OTHER ISD VAPOR LEAK WARN ALARM 11-15-19 9:02AM >< I20600NOV 17, 2020 2:15 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 TANK ALARM HISTORY TANK 1 87 UNLEADED SETUP DATA WARNING OCT 9, 2019 2:20 PM HIGH WATER ALARM OCT 10, 2019 7:39 AM OVERFILL ALARM NOV 17, 2020 11:29 AM OCT 10, 2019 11:45 AM LOW PRODUCT ALARM OCT 10, 2019 7:35 AM OCT 9, 2019 2:18 PM HIGH PRODUCT ALARM NOV 17, 2020 11:29 AM OCT 10, 2019 11:54 AM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] PROBE OUT NOV 17, 2020 11:57 AM NOV 17, 2020 11:23 AM OCT 10, 2019 12:21 PM HIGH WATER WARNING OCT 10, 2019 7:39 AM DELIVERY NEEDED OCT 10, 2019 7:35 AM OCT 9, 2019 2:18 PM MAX PRODUCT ALARM NOV 17, 2020 11:30 AM LOW TEMP WARNING NOV 17, 2020 11:58 AM OCT 10, 2019 12:22 PM TANK 2 91 PREMIUM SETUP DATA WARNING OCT 9, 2019 2:20 PM HIGH WATER ALARM NOV 17, 2020 11:52 AM OCT 9, 2019 3:09 PM OCT 9, 2019 2:24 PM OVERFILL ALARM NOV 17, 2020 11:49 AM JAN 29, 2020 3:42 AM OCT 10, 2019 12:04 PM LOW PRODUCT ALARM NOV 17, 2020 11:22 AM OCT 9, 2019 2:40 PM SUDDEN LOSS ALARM NOV 17, 2020 11:23 AM HIGH PRODUCT ALARM NOV 17, 2020 11:49 AM OCT 9, 2019 2:18 PM PROBE OUT NOV 17, 2020 11:57 AM NOV 17, 2020 11:55 AM NOV 17, 2020 11:23 AM HIGH WATER WARNING NOV 17, 2020 11:52 AM OCT 9, 2019 3:09 PM OCT 9, 2019 2:24 PM DELIVERY NEEDED NOV 17, 2020 11:22 AM OCT 9, 2019 2:40 PM MAX PRODUCT ALARM NOV 17, 2020 11:49 AM OCT 9, 2019 2:18 PM LOW TEMP WARNING NOV 17, 2020 12:12 PM TANK 3 DIESEL SETUP DATA WARNING AUG 27, 2018 8:19 AM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] HIGH WATER ALARM OCT 10, 2019 8:36 AM OCT 10, 2019 7:37 AM OVERFILL ALARM NOV 17, 2020 11:27 AM OCT 10, 2019 11:41 AM OCT 10, 2019 8:33 AM LOW PRODUCT ALARM OCT 10, 2019 7:33 AM AUG 27, 2018 8:05 AM HIGH PRODUCT ALARM OCT 10, 2019 11:41 AM OCT 10, 2019 7:52 AM INVALID FUEL LEVEL AUG 27, 2018 8:05 AM PROBE OUT NOV 17, 2020 11:56 AM NOV 17, 2020 11:21 AM OCT 10, 2019 12:20 PM HIGH WATER WARNING OCT 10, 2019 7:56 AM OCT 10, 2019 7:37 AM DELIVERY NEEDED NOV 17, 2020 11:21 AM APR 29, 2020 2:55 PM OCT 10, 2019 7:33 AM LOW TEMP WARNING OCT 10, 2019 12:21 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] > <I38200 NOV 17, 2020 2:15 PM >< I30200NOV 17, 2020 2:15 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 STP NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:43 AM FUEL ALARM NOV 17, 2020 10:19 AM LOW LIQUID ALARM 2 87 FILL NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:54 AM FUEL ALARM NOV 17, 2020 10:20 AM LOW LIQUID ALARM 3 91 STP NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:44 AM FUEL ALARM NOV 17, 2020 10:20 AM LOW LIQUID ALARM 4 91 FILL NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:49 AM FUEL ALARM NOV 17, 2020 10:20 AM LOW LIQUID ALARM 5 DIESEL STP NOV 17, 2020 12:23 PM LOW LIQUID ALARM NOV 17, 2020 12:23 PM LOW LIQUID ALARM NOV 17, 2020 11:34 AM SENSOR OUT ALARM 6 DIESEL FILL NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:49 AM FUEL ALARM NOV 17, 2020 10:20 AM LOW LIQUID ALARM 7 UNLEADED ANNULAR NOV 17, 2020 11:54 AM LOW LIQUID ALARM NOV 17, 2020 11:54 AM HIGH LIQUID ALARM NOV 17, 2020 11:53 AM LOW LIQUID ALARM 8 DIESEL ANNULAR NOV 17, 2020 11:54 AM HIGH LIQUID ALARM NOV 17, 2020 11:54 AM LOW LIQUID ALARM NOV 17, 2020 11:34 AM SENSOR OUT ALARM 9 1-2 UDC NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:29 AM FUEL ALARM NOV 17, 2020 10:21 AM LOW LIQUID ALARM file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] 10 3-4 UDC NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:33 AM FUEL ALARM NOV 17, 2020 10:21 AM LOW LIQUID ALARM 11 5-6 UDC NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:36 AM FUEL ALARM NOV 17, 2020 10:21 AM LOW LIQUID ALARM 12 7-8 UDC NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:39 AM FUEL ALARM NOV 17, 2020 10:21 AM LOW LIQUID ALARM 13 VENT BOX NOV 17, 2020 11:34 AM SENSOR OUT ALARM NOV 17, 2020 10:49 AM FUEL ALARM NOV 17, 2020 10:20 AM LOW LIQUID ALARM >< I31600NOV 17, 2020 2:15 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 87 PRODUCT NOV 17, 2020 11:11 AM HIGH LIQUID ALARM NOV 17, 2020 11:10 AM NO VACUUM ALARM OCT 10, 2019 12:06 PM HIGH LIQUID ALARM 3 VAPOR RETURN NOV 17, 2020 11:17 AM HIGH LIQUID ALARM NOV 17, 2020 11:17 AM NO VACUUM ALARM OCT 10, 2019 12:06 PM HIGH LIQUID ALARM 4 91 PRODUCT NOV 17, 2020 11:06 AM HIGH LIQUID ALARM NOV 17, 2020 11:05 AM NO VACUUM ALARM SEP 4, 2020 9:20 AM NO VACUUM ALARM 5 ALL VENTS NOV 17, 2020 11:09 AM HIGH LIQUID ALARM SEP 10, 2020 11:24 AM VACUUM WARNING SEP 10, 2020 10:37 AM NO VACUUM ALARM 6 DIESEL PRODUCT NOV 17, 2020 11:19 AM HIGH LIQUID ALARM NOV 17, 2020 11:19 AM NO VACUUM ALARM OCT 10, 2019 12:07 PM HIGH LIQUID ALARM 8 ATM 9 1-2 FLOWMETER AUG 27, 2018 9:34 AM COMMUNICATION ALARM 10 3-4 FLOWMETER file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] AUG 27, 2018 9:34 AM COMMUNICATION ALARM 11 5-6 FLOWMETER AUG 27, 2018 9:34 AM COMMUNICATION ALARM 12 7-8 FLOWMETER AUG 27, 2018 9:34 AM COMMUNICATION ALARM 16 PRESSURE SENSOR AUG 27, 2018 9:34 AM COMMUNICATION ALARM > <I10200 NOV 17, 2020 2:15 PM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 4952047 4931112 2 UNUSED 4939418 4929592 3 4 PROBE / G.T. 165562 165527 4 INTERSTITIAL BD 204254 203985 5 INTERSTITIAL BD 204109 203791 6 7SMARTSENSOR BD 516304 516154 7 8SMARTSENSOR BD 39981 39950 8 UNUSED 4932980 4924157 9 RELAY BOARD 15141 15119 10 RELAY BOARD 15141 15142 11 RELAY BOARD 15163 15142 12 STP SENSE BOARD 33612 33593 13 UNUSED 4942637 4931262 14 UNUSED 4938220 4926275 15 UNUSED 4936444 4927595 16 UNUSED 4938753 4924017 COMM 1 RS232 SERIAL BD 15186 15164 COMM 2 SERIAL SAT BD 488306 487493 COMM 3 ELEC DISP INT. 102294 102312 COMM 4 UNUSED 4940528 4928333 COMM 5 RS485 MODBUS BD 84872 84735 COMM 6 RS232 SERIAL BD 15208 15187 > <I90200 NOV 17, 2020 2:15 PMSOFTWARE REVISION LEVEL VERSION 335.00SOFTWARE# 346335-100-A CREATED - 18.08.27.10.22 S-MODULE# 330160-004-a file:///C/Users/jerryr/Desktop/Riverlakes%20Monitor/Riverlakes%20setup.txt[12/4/2020 11:33:56 AM] SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM >