HomeMy WebLinkAbout5625 Gosford Road Final ELD 10-24-20 UST System Post Installation Test Report
ELD Test Date:
Customer:
Location:
Tested By: CGRS, Inc.
5444 Dry Creek Road
Sacramento, CA 95838
Project No:61-21860
Jauregui & Culver Inc.
Sam's Club #4819
959 W. Mission Ave.
Escondido, CA 92025
5625 Gosford Rd.
Bakersfield, CA 93313
October 24, 2020
®
Location:CGRS Project No :
Test Date:
CGRS Techs:
IOTA Tech Signature:
Sergio L. Nunez CA Tank Tester #06-1727
Reviewed by:
Chris Murphy Director of CA Services
Test Certification
Post Installation Enhanced Leak Detection (ELD)
October 24, 2020
61-21860
Sam's Club #4819
5625 Gosford Rd.
Bakersfield, CA 93313
Sergio L. Nunez
Date
VR
Date
Primary Containment System PASS
87 PL North/South Primary Containment System PASS
91 PL North/South Primary Containment System PASS
Post Installation ELD Test Results
10/24/2020
10/26/2020
This document certifies that the product lines listed below at the above referenced location have been
tested and passed the iota®VaporTite V005 tightness test.CGRS further certifies that the iota®VaporTite
V005 meets the post installation testing requirements for post installation testing for newly installed
underground storage tank systems as per the California Health and Safety Code,Chapter 6.7,section
25290.1(j)(1).
Final Test Date:IOTA Technicians:
Site Information CGRS Project No :61-21860 Installation Contractor Information
Facility:Customer Name:
Address:Address:
City, State, Zip:City, State, Zip:
County:Contact:
CUPA Contact:Phone/Email:
CUPA Email:
Tank No.Capacity (gal.)Product Type Manufacturer Brine Test Result
Tank 1 20,000 87 Octane DW Fiberglass Xexes Yes N/A
Tank 2 20,000 87 Octane DW Fiberglass Xexes Yes N/A
Tank 3 12,000 91 Octane DW Fiberglass Xexes Yes N/A
Tank Top Sumps Diameter (in.)Depth (in.)Volume (gal.)Description Test Result
S1 42 50 299.88 87 TS1 PASS
S2 42 50 299.88 87 FS1 PASS
S3 42 50 299.88 87 TS2 PASS
S4 42 50 299.88 87 FS2 PASS
S5 42 50 299.88 91 TS PASS
S6 42 50 299.88 91 FS PASS
Junction Boxes with Tank Connection Description Test Result
S1 Tank Probe and Turbine J-Box Open During Test PASS
S3 Tank Probe and Turbine J-Box Open During Test PASS
S5 Tank Probe and Turbine J-Box Open During Test PASS
UDCs Length (in.)Width (in.)Depth (in.)Volume (gal.)Description Test Result
UDC1 42 22 32 128.00 Bravo PASS
UDC2 42 22 32 128.00 Bravo PASS
Transition Sump Length (in.)Width (in.)Depth (in.)Volume (gal.)Description Test Result
N/A N/A N/A N/A N/A N/A N/A
Product Piping Manufacturer Type Size (in.)Length (ft.) Test Result
87 PL North NOV DW Fiberglass 2 75 PASS
87 PL South NOV DW Fiberglass 2 75 PASS
91 PL North NOV DW Fiberglass 2 75 PASS
91 PL South NOV DW Fiberglass 2 75 PASS
Vent Piping Manufacturer Type Size (in.)Length (ft.)Test Result
N/A N/A N/A N/A N/A PASS
Vapor Piping Manufacturer Type Size (in.)Length (ft.)Test Result
VR NOV DW Fiberglass 3 100 PASS
Reviewed By Date IOTA Tech Signature Date
Final ELD Test Project Worksheet
10/24/2020
Sam's Club #4819 Jauregui & Culver Inc.
Sergio L. Nunez
kkarns@bakersfieldfire.us; hwines@bakersfieldfire.us
PIPING
TANKS
5625 Gosford Rd.959 W. Mission Ave.
Escondido, CA 92025
COMPONENTS IN CONTAINMENT
Kern Matt Jauregui
Bakersfield FD; Howard Wines; Kris Karns 760-743-0518/matt@jcincorp.net
Leak Logs / Repair
Bakersfield, CA 93313
10/24/2020
CA License No.
10/26/2020 06-1727
Location:CGRS Project No :
Test Date:
CGRS Techs:
IOTA Tech Signature:
Sergio L. Nunez CA Tank Tester #06-1727
Reviewed by:
Chris Murphy Director of CA Services
VR PASS
10/26/2020
Date
10/24/2020
Date
87 PL PASS
91 PL PASS
COMPONENTS RESULTS
Piping Secondary Communication Confirmation
5625 Gosford Rd.Sergio L. Nunez
Bakersfield, CA 93313
Secondary Flow Communication Test Certification
61-21860
Sam's Club #4819 October 24, 2020
CGRS certifies that at the time the final ELD testing was performed, air flow communication was confirmed
throughout the secondary piping components listed below.