HomeMy WebLinkAbout4800 White Lane ELD 2021Providers for MDleak® MSleak® DPleak®, MCleak® and
PHDleak® Testing Technologies
Page 1 of 3
Test Type:
Facility Name: Job #: 4364
Prepared For: PO #: NA
Site Address:
City: Primary Test Leak Rate: 0.005 gph
State and Zip: CA 93309 Secondary Test Leak Rate: N/A
Start Date:End Date:
SYSTEM TK-1-87 TK-2-89 TK-3-91 TK-4-Dsl
Product Primary MDleak:PASS PASS PASS PASS
Product Secondary:NA NA NA NA
Vent Primary MDleak:PASS PASS PASS PASS
Vent Secondary:NA NA NA NA
VR Primary MDleak:PASS PASS PASS NA
VR Secondary:NA NA NA NA
MCleak ELD Tank:NA NA NA NA
72 Hr. Out of Service:NA NA NA NA
MDleak ELD Tank:PASS PASS PASS PASS
Turbine Sump MDleak:PASS PASS PASS PASS
Turbine Head MDleak:PASS PASS PASS PASS
F/Vapor Sump MDleak:NA NA NA NA
UDC's MDleak:PASS PASS PASS PASS
Fill Bucket MDleak:PASS PASS PASS PASS
Vapor Bucket MDleak:PASS PASS PASS NA
Vent Box MDleak:NA NA NA NA
Fill Spill Bucket Hydo:PASS PASS PASS PASS
Vapor Bucket Hydro:PASS PASS PASS NA
STP Sump Elect DPleak:PASS PASS PASS PASS
Certifying Field Technician: Ricardo Gonzalez State Lic. # :
Certification Leak Rate: 0.005 gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date: 1/19/2021
Office use only
I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National
Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is
true and correct to the best of my knowledge.
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
04-1695
This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak
sensitivity listed above by using one or more of the following DPleak®,MDleak®,MCleak and PHDleak®EPA aproved
Methods.These Methods are the most versatile and comprehensive testing procedures offered to the petroleum
industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®,MCleak,and PHDleak®Method can
be assured that their facility has passed the Nation's highest standard in preventative leak detection.
1/18/2021
1/18/20211/6/2021
4800 White Lane
Bakersfield
Fast Break Mobil
Facility Certification CONFIDENTIAL
California ELD Well Proximity Test GCleak
Fast Break Mobil
Providers for MDleak® MSleak® DPleak®, MCleak® and
PHDleak® Testing Technologies
Page 2 of 3
4800 White Lane Log of Repaired Leak/s
CONFIDENTIAL
TK-1-87 TK-2-89 TK-3-91 TK-4-Dsl
Tank Volume:10000 10000 10000 10000
Manufacture:Unknown Unknown Unknown Unknown
Interstice:Single Wall Single Wall Single Wall Single Wall
Depth To Tank:52"52"52"54"
Tank Dia:8 ft 9 ft 10 ft 11 ft
Depth of Liquid:95"127"127"130"
Tank Sump Boots Turbine
Unknown Unknown Red Jacket
6
Wayne
OPW
Unknown
Smith
Smith
Teflon Flex Connectors
PhilTite
EVR: Veeder-Root
Reference #Date Time Status System Component Manufacture
23 1/6/21 10:51 Leak Pretest TK-3-91 Fill bucket Swivel in fill bucket leaking.
38 1/6/21 12:25 Leak Pretest TK-2-89 ATG Conduit/Pull Box Cap and brass adaptor appear to be leaking
Reference #Date Time Status System Component Manufacture
None
Log of Repaired Leaks
Log of Unrepaired Leaks
Tank Information
Containment Boots:
Piping Information
Manufacture
Spill Buckets:
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Flex:
Product Lines:
Vapor Return / Vent:
UDC/Dispensers Information
Depth to Ground Water:
Manufacture:
>10'
Providers for MDleak® MSleak® DPleak®, MCleak® and