HomeMy WebLinkAbout4800 White Lane ELD 2021Providers for MDleak® MSleak® DPleak®, MCleak® and PHDleak® Testing Technologies Page 1 of 3 Test Type: Facility Name: Job #: 4364 Prepared For: PO #: NA Site Address: City: Primary Test Leak Rate: 0.005 gph State and Zip: CA 93309 Secondary Test Leak Rate: N/A Start Date:End Date: SYSTEM TK-1-87 TK-2-89 TK-3-91 TK-4-Dsl Product Primary MDleak:PASS PASS PASS PASS Product Secondary:NA NA NA NA Vent Primary MDleak:PASS PASS PASS PASS Vent Secondary:NA NA NA NA VR Primary MDleak:PASS PASS PASS NA VR Secondary:NA NA NA NA MCleak ELD Tank:NA NA NA NA 72 Hr. Out of Service:NA NA NA NA MDleak ELD Tank:PASS PASS PASS PASS Turbine Sump MDleak:PASS PASS PASS PASS Turbine Head MDleak:PASS PASS PASS PASS F/Vapor Sump MDleak:NA NA NA NA UDC's MDleak:PASS PASS PASS PASS Fill Bucket MDleak:PASS PASS PASS PASS Vapor Bucket MDleak:PASS PASS PASS NA Vent Box MDleak:NA NA NA NA Fill Spill Bucket Hydo:PASS PASS PASS PASS Vapor Bucket Hydro:PASS PASS PASS NA STP Sump Elect DPleak:PASS PASS PASS PASS Certifying Field Technician: Ricardo Gonzalez State Lic. # : Certification Leak Rate: 0.005 gph Certifying Technician Signature: Date: Statement Confirmed by: Date: 1/19/2021 Office use only I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is true and correct to the best of my knowledge. If you have any questions on the testing please do not hesitate to call. @ 855-255-5325. 04-1695 This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak sensitivity listed above by using one or more of the following DPleak®,MDleak®,MCleak and PHDleak®EPA aproved Methods.These Methods are the most versatile and comprehensive testing procedures offered to the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®,MCleak,and PHDleak®Method can be assured that their facility has passed the Nation's highest standard in preventative leak detection. 1/18/2021 1/18/20211/6/2021 4800 White Lane Bakersfield Fast Break Mobil Facility Certification CONFIDENTIAL California ELD Well Proximity Test GCleak Fast Break Mobil Providers for MDleak® MSleak® DPleak®, MCleak® and PHDleak® Testing Technologies Page 2 of 3 4800 White Lane Log of Repaired Leak/s CONFIDENTIAL TK-1-87 TK-2-89 TK-3-91 TK-4-Dsl Tank Volume:10000 10000 10000 10000 Manufacture:Unknown Unknown Unknown Unknown Interstice:Single Wall Single Wall Single Wall Single Wall Depth To Tank:52"52"52"54" Tank Dia:8 ft 9 ft 10 ft 11 ft Depth of Liquid:95"127"127"130" Tank Sump Boots Turbine Unknown Unknown Red Jacket 6 Wayne OPW Unknown Smith Smith Teflon Flex Connectors PhilTite EVR: Veeder-Root Reference #Date Time Status System Component Manufacture 23 1/6/21 10:51 Leak Pretest TK-3-91 Fill bucket Swivel in fill bucket leaking. 38 1/6/21 12:25 Leak Pretest TK-2-89 ATG Conduit/Pull Box Cap and brass adaptor appear to be leaking Reference #Date Time Status System Component Manufacture None Log of Repaired Leaks Log of Unrepaired Leaks Tank Information Containment Boots: Piping Information Manufacture Spill Buckets: Number of Dispensers: Manufacture: Shear Valve Manufacture: Flex: Product Lines: Vapor Return / Vent: UDC/Dispensers Information Depth to Ground Water: Manufacture: >10' Providers for MDleak® MSleak® DPleak®, MCleak® and PHDleak® Testing Technologies Page 3 of 3 4800 White Lane Reference Addendum CONFIDENTIAL Site Photo