Loading...
HomeMy WebLinkAboutARCO Taft Hwy 3-5-2021 Diesel LLDAdvanced Compliance 3704 Littlefalls Ct. Bakersfield, Ca. 93308 661-706-4321 Fax# 661-589-9329 VAPORLESS MANUFACTURING, INC. LDT-890 Leak Detector Test Record Contractor: Advanced Compliance Customer: ARCO AMPM Date: 3/5/2021 Location: 2051 Taft Hwy. Bakersfield, Ca. Product: DIESEL Technician: Bradley W. Hinsley Submersible Pump Identification Manufacturer: Redjacket Model No.: Serial No.: Notes: Leak Detector Identification Manufacturer: Veeder-Root Description: FX 1DV Diaphragm-type: Piston-type: Tamper-proof seal installed: Other Style Leak Detector: Notes: Leak Detector in Submersible Pump Test at Dispenser Operating Pump Pressure (psi): 36 (para. 15) Gallons per hour rate: 3.0 (para. 22) Line pressure with pump shut off (psi): 18 (para. 23) Bleed-back Test with pump off (ml): 105 (para. 26) Step-through time to full flow (secs): 3 (para. 30) Leak detector stays in leak search position (Yes/No): Yes (para. 42) Leak Detector Test Pass / Fail Notes: Pass *Complete thermal expansion test before failing leak detector