HomeMy WebLinkAboutAPSA 3-2-21BAKERSFIELD FIRE DEPARTMENT
2101 H STREET, BAKERSFIELD., CA 93301
A IDate: 3/Z/ I, Inspector: Peter Armagost
Business Name: Jim Burke Ford
Business Address: 5300 Gasoline Alley
Aboveground Petroleum Storage Tank Program -Tier 11 Qualified Facility Inspection Report (v 3.0)
Violation
Compliance
Number
Program Requirement
Citations
YorN
Class
Comments
Requirement to Prepare and Implement
4010001
SPCC has been prepared
HSC 6.6725270.4.5(a);
40 CFR 1112.3, 112.6
4010057
SPCC plan has been prepared that meets all
HSC6.672. 70.4.5(a);
applicable requirements
40 CFR 1112.3, 112.6
4030038
SPCC has been implemented
HSC 6.6725270.4.5(a);
40 CFR 1112.3
4010008
SPCC onsite If facility staffed 4 hrs/day, or at
HSC 6.6725270.4.5(a);
the nearest field office if not so attended
40 CFR 1 112.3(e)(1)
4010047
Qualified Facility's SPCC plan has been self or
HSC 6.6725270.4.5(a);
PE certified.
40 CFR 1 112.6(a)(1),
112.6(b)
4010035
Facility prepared appropriate SPCC when no
HSC 6.6725270.4.5(a);
,longer meeting Tier 1/11 requirements
40 CFR 1112.3(9)
SPCC Amendments
4010010
Facility has amended SPCC as necessary
HSC 6.6725270.4.5(a);
40 CFR 1 112.5(a),
112.5(b)
A
4030039
SPCC has been implemented within 6 months
HSC 6.6725270.4.5(a);
of amendment
40 CFR 1 112.5(a),
112.5(b)
4010052
Tech amendments certified when a change in
HSC 6.6725270.4.5(a);
facility design/operations occurs, & by PE
40 CFR 1 112.6(b)(2);
lwhen
required
112.6(b)(2)N
1A
Five Year Review
4010009
5 year review performed on SPCC and
HSC 6.6725270.4.5(a);
documented
40 CFR 1 112.5(b)
General SPCC Requirements
4010012
igood
SPCC in writing, follows code seq/cross ref,—
HSC 6.6725270.4.5(a);
eng practice, mgt approval, items not in
40 CFR 1112.7
place
4010013
SPCC Plan discusses conformance with all SPCC
HSC 6.6725270.4.5(a);
rule requirements., & state
40 CFR 1 112.7(a)(1),
rules/regs/guidelines.
112.7(1)
4010014
Environmental Equivalence, if claimed, is
HSC 6.6725270.4.5(a);
addressed in SPCC, other than for secondary
40 CFR 1 112.7(a)(2)
containment.
4010050
PE certified enviro equivalence,
HSC 6.67 25270.4.5(a);
impracticability, and produced water
40 CFR 1112.6(b)(3);
containers/piping, if needed
112.6(b)(4)(iii)
4010051
PE required attestations in the SPCC Plan for
HSC 6.6725270.4.5(a);
alternative measure claim at a Tier 11 facility
40 CFR 1 112.6(b)(4)N
4010016
Physical layout of the facility is adequately and
HSC 6.6725270.4.5(a);
accurately described in SPCC
40 CFR 1 112.7(a)(3)
4010041
SPCC Plan addresses the type of oil and
HSC 6.6725270.4.5(a);
storage capacity for all fixed and portable
40 CFR 1 112.7(a)(3)N
lcontainers
Violation
6 7
Impracticability of containment/diversionary HSC 6.6725270.4.5(a);
Compliance
Number
Program Requirement Citations
SPCC contains an adequate facility diagram HSC 6.67 25270.4.5(a);
YorN
Class
4010015
Y
certified
40 CFR I 112.7(a)(3)
4010030
SPCC adequately addresses discharge HSC 6.6725270.4.5(a);
prevention measures for routine handling, 40 CFR 1 112.7(a)(3)(ii)
impracticability claim 40 CFR 1112, 7(d)
loading/unloading
4010005
If claiming impracticability of
4010042
SPCC Plan addressed countermeasures for HSC 6.6725270.4.5(a);
discharge discovery, response and cleanup 40 CFR 1 112.7(a)(3)(iv)
40 CFR 1 112.7(d)(1)
4010043
SPCC Plan addresses disposal methods for HSC 6.6725270.4.5(a);
plan has been included
recovered materials 40 CFR 1 112.7(a)(3)(v)
4010017
SPCC contains procedures for reporting a HSC 6.6725270.4.5(a);
HSC 6.6725270.4.5(a);
discharge 40 CFR 1112.7(a}(3)
commitment of manpower, equipment, and
40 CFR 1 112.7(d)(2)
(vi); 112.7(a)(4)
4010018
SPCC organized so discharge procedures are HSC 6.6725270.4.5(a);
readily usable if the facility has no response 40 CFR 1 112.7(a)(5)
4010023
Employee training and spill prevention
HSC 6.67 25270.4.5(a);
plan
4010019
SPCC predicts direction, rate of flow, total HSC 6.6725270.4.5(a);
40 CFR 1 112.7(f)(1},briefings
quantity of oil that could be released from a 40 CFR 1 112.7(b)
112.7(f)(3)
discharge
4010020
SPCC addresses the appropriate general HSC 6.6725270.4.5(a);
HSC 6.6725270.4.5(a);
containment/diversionary 40 CFR 1 112.7(c)
discharge procedures, laws/regs, general fac
40 CFR 1112.7(f}(1)
structures/equipment
4030037
Appropriate (general) HSC 6.67 25270.4.5(a);
containment/diversionary 40 CFR 1 112.7(c)
4010022
Person has been designated as accountable for
HSC 6.67 25270.4.S(a);
-.L-. . -.&. . __ - /_ -. .:- � " -%% rr% �% ^rv% r%rr%%'F;
Comments
4010004
6 7
Impracticability of containment/diversionary HSC 6.6725270.4.5(a);
items, if claimed., is PE demonstrated and 40 CFR 1 112.7(d)
certified
4030033
Periodic integrity/leak testing performed with HSC 6.6725270.4.5(a);
impracticability claim 40 CFR 1112, 7(d)
4010005
If claiming impracticability of
HSC 6.67 25270.4.5(a);
containment/diversionary items a contingency
40 CFR 1 112.7(d)(1)
plan has been included
4010006
If claiming impracticability written
HSC 6.6725270.4.5(a);
commitment of manpower, equipment, and
40 CFR 1 112.7(d)(2)
materials provided
4010023
Employee training and spill prevention
HSC 6.67 25270.4.5(a);
discussed in SPCC plan
40 CFR 1 112.7(f)(1},briefings
112.7(f)(3)
4020001
Training provided for op/maint of equip.,
HSC 6.6725270.4.5(a);
discharge procedures, laws/regs, general fac
40 CFR 1112.7(f}(1)
ops, and SPCC
4010022
Person has been designated as accountable for
HSC 6.67 25270.4.S(a);
discharge prevention and reports to
40 CFR I 112.7(f)(2)
management
4030040
Spill prevention briefings are conducted
HSC 6.67 25270.4.5(a);
annually
40 CFR 1 112.7(f)(3)
4010024
SPCC addresses security measures -lighting,
HSC 6.6725270.4.5(a);
access to hand ling/storage,
40 CFR 1 112.7(8)
valves/pumps/transfer equip
4030001
Handling areas, valves, pumps/starter controls,
HSC 6.67 25270.4.5(a);
:load/unload connections secured, lighting
40 CFR 1 112.7(8)
adequate
4010025
SPCC adequately discusses facility tank car and
HSC 6.6725270.4.5(a);
tank truck loading/unloading rack
40 CFR 1 112.7(h)
4030002
Loading rack containment has capacity to
HSC 6.67 25270.4.5(a);
contain single largest compartment of tank
40 CFR 1 112.7(h)(1)
1car/truck
I n
I
Violation
SPCC discusses procedures to test/inspect
HSC 6.67 25270.4.5(a);
Compliance
Number
Program Requirement
Vehicular departure warning system in place at
Citations
YorN
Class
Comments
4030003
HSC 6.6725270.4.5(a);
facility with a loading/un loading rack
40 CFR 1112.7(h)(2)
HSC6.6725270.4.5(a);
4030034
Oil filled operational equipment containment
HSC6.6725270.4.5(a);
40 CFR 1 112.8(c)(6)
are met
/W
40 CFR 1 112.71rl
HSC 6.6725270.4.5(a);
,standards
SPCC Requirements for Onshore Facilities
4010027
Facility drainage or drainage controls
HSC 6.6725270.4.5(a);
4010021
adequately discussed
40 CFR 1112.7(a)(3)
kept for 3 years and written inspection
(iii); 112.8(b)
4030035
Facility drainage adequately restrained unless
HSC 6.6725270.4.5(a);
4030018
conditions met
40 CFR 1 112.8(b)(1)
4030005
Valves used for drainage are manual (not
HSC 6.6725270.4.5(a);
flapper -type) to prevent a discharge
40 CFR 1 112.8(b)(2)
4030008
Drainage from undiked areas or diversion
HSC 6.6725270.4.5(a);
systems designed to retain final discharge in
40 CFR 1 112.8(b)(3),
container
112.8(b)(4)
4030019
facility
HSC 6.6725270.4.5(a);
4030009
Lift pumps provided for treated drainage
HSC 6.6725270.4.5(a);
waters when more than one treatment unit
40 CFR 1 112.8(b)(5)
4010029
Adequate discussion of all bulk storage
HSC 6.6725270.4.5(a);
containers located at the facility
CFR 1 112.8(c)
4030012
Material and construction of all containers are
HSC 6.6725270.4.5(a);
compatible with the material stored
40 CFR 1112.8(c)(1)
4030010
Adequately sized secondary containment
HSC 6.6725270.4.5(a);
provided and maintained for bulk storage
40 CFR I 112.8(c)(2)
containers
4030013
Containment systems are sufficiently
HSC6.6725270.4.5(a);
impervious to contain oil
40 CFR 1112.8(c)(2)
4030006
Rainwater in diked areas is inspected before
HSC 6.6725270.4.5(a);
draining
40 CFR 1 112.8(c)(3)(i),
112.8(c)(3)(fi),
112.8(c) (3) (iii)'
4010026
Records maintained of drainage from diked
HSC 6.6725270.4.5(a);
40 CFR I 112.8(c)(3)(iv)
areas
4030017 1 Buried section of partially buried or bunKerea jr7.3Lc).o1zDz-1u.4f-j(uj,
metallic tank has corrosion protection 40 CFR 1 112.8(c)(5)
4010028
SPCC discusses procedures to test/inspect
HSC 6.67 25270.4.5(a);
storage containers for integrity per industry
40 CFR 1 112.8(c)(6)
standards
4030014
Tanks inspected and tested by qualified person
HSC6.6725270.4.5(a);
in accordance with industry standards
40 CFR 1 112.8(c)(6)
4030015
Aboveground containers tested or inspected
HSC 6.6725270.4.5(a);
for integrity based on industry standards
40 CFR 1 112.8(c)(6)
4010021
Inspection/integrity testing records signed,
HSC 6.6725270.4.5(a);
kept for 3 years and written inspection
40 CFR 1112.7(e),
112.8(c)(6)
procedures kept
4030018
Steam return/exhaust lines that discharge to
HSC 6.6725270.4.5(a);
watercourse are monitored or have treatment
40 CFR 1112.8(c)(7)
system
4010056
SPCC adequately describes overfill prevention
40 CFR 1 112.8(c)(8);
methods, and devices/systems used for each
HSC 6.6725270.4.5(a)
container
4030019
Each container installation has a liquid level
HSC 6.6725270.4.5(a);
sensing device.
40 CFR 1 112.8(c)(8),
112.8(c)(8)(Nv)
4030022 Liquid level sensing devices regularly tested to HSC 6.6725270.4.5(a);
ensure proper operation 40 CFR 1 112.8(c)(8)(v)
3
Violation
4010037
Oil filled electrical equipment exclusions have
Compliance
Number
Program Requirement
Citations
YorN
Class
Comments
4030023
Discharge from effluent treatment facilities
HSC 6.67 25270.4.5(a);
which discharge to navigable waterways
40 CFR 1 112.8(c)(9)
Valid permit maintained
HSC 6.1125404.1
observed
4010032
Tank Facility Statement or Business Plan has
HSC 6.67 252 70.6(a) (1),
4030021
Visible discharges promptly corrected and any
HSC 6.67 25270.4.5(a);
been submitted
25270.6(a)(2)
accumulation of oil in diked areas promptly
40 CFR 1 112.8(c)(10)
Spills/releases of 42 gallons or more of
HSC 6.67 25270.8
petroleum reported upon discovery to Cal OES
4030020
Adequate secondary containment provided for
HSC 6.6 7 252 70.4.5(a);
& UPA or 911
�j)A
mobile/portable storage containers
40 CFR 1 112.8(c)(11)
APSA program fee paid
HSC 6.67 25270.6(b)
4030025
Buried piping is inspected for deterioration if
HSC6.6725270.4.5(a);
All/any permanently closed tanks are properly
HSC 6.67 25270.4.5(a);
exposed and repaired if corrosion damage is
40 CFR 1 112.8(d)(1)
closed under the definition in 40 CFR 112.2
40 CFR 1 112.1(b)(3),
found
112.2
k)
4030027
Buried piping is corrosion protected with
HSC 6.67 25270.4.5(a),
Substantial Harm Criteria certification
HSC 6.67 25270.4.5(a);
-JA
I -A
protective wrapping, coating, or cathodic
40 CFR 1 112.8(d)(1)
maintained at the facility as required
40 CFR I 112.20(e)
protection
4010
Administration/Documentation - General
40 CFR 1112; HSC 6.67
4030028
Terminal connection capped/blank flanged at
HSC 6.67 25270.4.5(a);
Multiple
transfer point & origin marked if not in
40 CFR 1 112.8(d)(2)
Administration/Documentation - General Local
Ordinance
4030029
Pipe supports designed to minimize abrasion
HSC 6.67 25270.4.5(a);
Training - General
HSC 6.67; 40 CFR 1112
and corrosion, and allow for expansion and
40 CFR 1 112.8(d)(3)
Multiple
contraction
4025
)A
4030026
Aboveground valves, piping, and
HSC 6.67 25270.4.5(a);
Operations/Maintenance - General
HSC 6.67; 40 CFR 1112
appurtenances are regularly inspected
40 CFR 1 112.8(d)(4)
Multiple
4030030
Integrity/leak tested buried piping when
HSC 6.67 25270.4.5(a);
Operations/Maintenance - General Local
installed, modified, constructed, relocated, or
40 CFR 1 112.8(d)(4)
Ordinance
replaced
4040
Release/Leaks/Spills - General
HSC 6.67 Multiple; 40
4030031
Vehicle traffic warned of aboveground piping
HSC 6.67 25270.4.5(a);
I
I CFR 1112
Oil Filled Electrical Equipment
4010037
Oil filled electrical equipment exclusions have
HSC6.6725270.2(a)(4)
been met, and where not met is included in
General Facility Requirements
4010034
Valid permit maintained
HSC 6.1125404.1
4010032
Tank Facility Statement or Business Plan has
HSC 6.67 252 70.6(a) (1),
been submitted
25270.6(a)(2)
4040001
Spills/releases of 42 gallons or more of
HSC 6.67 25270.8
petroleum reported upon discovery to Cal OES
& UPA or 911
�j)A
4010033
APSA program fee paid
HSC 6.67 25270.6(b)
4030036
All/any permanently closed tanks are properly
HSC 6.67 25270.4.5(a);
closed under the definition in 40 CFR 112.2
40 CFR 1 112.1(b)(3),
112.2
k)
4010044
Substantial Harm Criteria certification
HSC 6.67 25270.4.5(a);
-JA
I -A
maintained at the facility as required
40 CFR I 112.20(e)
4010
Administration/Documentation - General
40 CFR 1112; HSC 6.67
Multiple
4015
Administration/Documentation - General Local
Ordinance
4020
Training - General
HSC 6.67; 40 CFR 1112
Multiple
4025
Training - General Local Ordinance
4030
Operations/Maintenance - General
HSC 6.67; 40 CFR 1112
Multiple
4035
Operations/Maintenance - General Local
Ordinance
4040
Release/Leaks/Spills - General
HSC 6.67 Multiple; 40
I
I CFR 1112
4
Violation
Compliance
Number
Program Requirement
Citations
Y or N
Class
Comments
4045
Release/Leaks/Spills - General Local Ordinance
4050
Abandonment/Illegal Disposal/Unauthorized
HSC 6.67 Multiple; 40
Treatment - General
CFR 1 112
4055
Abandonment/Illegal Disposal/Unauthorized
Treatment - General Local Ordinance
Comments:
❑ There were no violations noted for this inspection
❑ This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations. You
are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal
enforcement and/or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner.
(NOTE: If this is a pr 'min�ry report,, a,�nal r port will follow.)
Operator's Nam Operator's Signature: Date:
Inspector's Signature: Date: