HomeMy WebLinkAbout830 Union Final ELD 7-15-2020Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 1 of 3
Test Type:
Facility Name: Job #: 4150
Prepared For: PO #: NA
Site Address:
City: Primary Test Leak Rate: 0.005 gph
State and Zip: CA 93307 Secondary Test Leak Rate: 0.1 gph
Start Date:End Date:
SYSTEM TK-1 87 TK-2 91 TK-3 DSL
Product Primary:PASS PASS PASS
Product Secondary:PASS PASS PASS
Vent Primary:PASS PASS PASS
Vent Secondary:PASS PASS PASS
VR Primary:PASS PASS NA
VR Secondary:PASS PASS NA
MDleak ELD Tank:PASS PASS PASS
Turbine Sump:PASS PASS PASS
Turbine Sump Elect:PASS PASS PASS
Turbine Head:PASS PASS PASS
Fill/Vapor Sump:PASS PASS PASS
UDC's:PASS PASS PASS
Fill Bucket Primary:PASS PASS PASS
Vapor Bucket Primary:PASS PASS NA
Fill Spill Bucket Hydo:PASS PASS PASS
Vapor Bucket Hydro:PASS PASS NA
Vent Box:PASS PASS PASS
Certifying Field Technician: Ricardo Gonzalez State Lic. # :
Certification Leak Rate: 0.005 gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date:
Complete Fueling Solutions
Facility Certification CONFIDENTIAL
California ELD New Construction Test MDleak
Gas N Save
830 Union Ave
Bakersfield
7/15/20207/13/2020
7/15/2020
Office use only
I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National Workgroup on Leak
Detection Evaluations (NWGLDE)organization and that the information contained in this report is true and correct to the best of my
knowledge.
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
04-1695
This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak sensitivity listed
above by using one or more of the following DPleak®,MDleak®and PHDleak®EPA aproved Methods.The DPleak®,MDleak®and
PHDleak®Methods are the most versatile and comprehensive testing procedures offered to the petroleum industry.All petroleum
owners and contractors which utilize the DPleak®,MDleak®and PHDleak®Method can be assured that their facility has passed the
Nation's highest standard in preventative leak detection.
7/15/2020
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 2 of 3
830 Union Ave Log of Repaired Leak/s
CONFIDENTIAL
TK-1 87 TK-2 91 TK-3 DSL
Tank Volume: 10000 5000 10000
Manufacture: Modern Modern Modern
Interstice: Vacuum Vacuum Vacuum
Depth To Tank: 75"78"81"
Tank Dia: 10 ft 10 ft 10 ft
Depth to Fuel: 0"0"0"
Tank Sump Boots Turbine
Bravo Smith Red Jacket
4
Gilbarco
OPW
Smith
Smith
Smith
Fire-Flex
PhilTite
EVR: Healy
Reference #Date Time Status System Component Manufacture
82 7/13/20 10:30 Leak Final TK-1 87 Tank 1st Cap on ATG has no gasket in TS
84 7/13/20 11:05 Leak Final TK-1 87 STP Sump Brass adaptor on ATG leaking.
96 7/13/20 13:01 Leak Final TK-1 87 STP Sump Turbine riser to tank leaking.
97 7/13/20 13:02 Leak Final TK-1 87 Fill Vapor Sump Fill bucket to Face Seal Adaptor.
98 7/13/20 13:03 Leak Final TK-2 91 Fill Vapor Sump Bung plug leaking.
101 7/13/20 13:06 Leak Final TK-3 DSL STP Sump Brass adaptor to Face Seal on ATG leaking
164 7/14/20 12:15 Leak Final TK-1 87 STP Sump ATG brass adaptor to face seal adaptor leaking.
165 7/14/20 12:16 Leak Final TK-1 87 Fill Vapor Sump Bucket to riser leaking on fill & VR.
167 7/14/20 12:18 Leak Final TK-3 DSL STP Sump Bung plug leaking.
169 7/14/20 14:00 Leak Final TK-1 87 Fill Vapor Sump
175 7/14/20 15:20 Leak Final TK-1 87 STP Sump Brass tubing to turbine leaking.
177 7/14/20 15:22 Leak Final TK-3 DSL STP Sump Brass adaptor to Face Seal on ATG leaking.
180 7/14/20 16:00 Leak Final TK-1 87 STP Sump Turbine head leaking.
190 7/15/20 7:01 Leak Final TK-3 DSL STP Sump Turbine head leaking.
195 7/15/20 7:55 Leak Final TK-1 87 STP Sump 30 Minute sample. Cap on ATG leaking.
Reference #Date Time Status System Component Manufacture
None
Depth to Ground Water:
Manufacture:
Tank Information
Containment Boots:
Piping Information
Manufacture
Spill Buckets:
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Flex:
Product Lines:
Vapor Return / Vent:
UDC/Dispensers Information
NA
Log of Repaired Leaks
Log of Unrepaired Leaks
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 3 of 3
830 Union Ave Reference Addendum CONFIDENTIAL
Site Photo