Loading...
HomeMy WebLinkAbout1620 e brundage _envirotech report 6.22.20_98-126DS- 13109 -10 _ BAKERSFIELD TRANSFER, INC. I UNIT 1 SECONDARY CONTAINMENT CALCULATIONS DS- 13109 -10 Revision No.: C Calculated By: Stephen Bahr Da e: 08/08113 Checked By: Jack Collins CALCULATION SHEET PURPOSE: 1) To calculate the secondary containment volume for Unit 1 (Tank Farm) at the Bakersfield Transfer Facility. The Area includes four 20,000 - gallon tanks. The secondary contaiment requirements for Unit 1 equal 20,000 gallons plus the volume of rainfall from a 24 -hour, 25 -year rainstorm. I SITE DESCRIPTION: Bakersfield Transfer, Inc. ; 1620 East Brundage Lane 4 Bakersfield, California 93307 I VOLUME EQUATION: V:= L -W -H INPUT VARIABLES: Containment Area Dimensions L:= 44 W:= 44 A:= L•W A = 1936 H:= 2.5 2.5' Peri rater Wal 00 O20,000 Gallon Tank Length of Containment Area, ft. Width of Containment Area, ft. Surface Area of Unit 1, sq. ft. Height of Perimeter Wall, ft. Vtk := 20000 Holding Volume of each Tank within containment area, gallons. 2.0 Fraction of Holding Tank Volume, or footprint, that occupies secondary f 17 containment volume (2.0' /17')(Height of perimeter wall - Foundation =2.0') f =0.12