Loading...
HomeMy WebLinkAbout2001 oak st_apsa insp 12.18.20BAKERSFIELD FIRE DEPARTMENT 2101 H STREET, B KERSFIELD, CA 93301 I Date: / R 72"_4z�2_0 Inspector: Kris Karns Business Name: Jim Burke Ford Business Address: 2001 Oak Aboveground Petroleum Storage Tank Program-Tier 11 Qualified Facility Inspection Report (v 3.0) Violation VIOL Number Program Requirement Citations Y or N Class Comments Requirement to Prepare and Implement 4010001 SPCC has been prepared HSC 6.6725270.4.5(a); 40 CFR 1112.31 112.6 4010057 SPCC plan has been prepared that meets all HSC 6.6725270.4.5(a); applicable requirements 40 CFR 1112.3,112.6 4030038 SPCC has been implemented HSC 6.6725270.4.5(a); 40 CFR 1112.3 4010008 SPCC onsite If facility staffed 4 hrs/day, or at HSC 6.6725270.4.5(a); the nearest field office if not so attended 40 CFR 1 112.3(e)(1) 4010047 Qualified Facility's SPCC plan has been self or HSC 6.6725270.4.5(a); PE certified. 40 CFR 1 11 2.6(a)(1)., 112.6(b) 4010035 Facility prepared appropriate SPCC when no HSC 6.67 25270.4.5(a), I longer meeting Tier 1/11 requirements 40 CFR 1 112.3(8) SPCC Amendments 4010010 Facility has amended SPCC as necessary HSC 6.6725270.4.5(a); 40 CFR 1 112.5(a)., \Stf 112.5(b) 4030039 SPCC has been implemented within 6 months HSC 6.6725270.4.5(a); of amendment 40 CFR 1 112.5(a), 112.5(b) 4010052 Tech amendments certified when a change in HSC 6.6725270.4.5(a); facility design/operations occurs, & by PE 40 CFR 1 112.6(b)(2); when required . 112.6(b)(2)(i) Five Year Review 4010009 5 year review performed on SPCC and HSC 6.6725270.4.5(a); documented 40 CFR 1 112.5(b) General SPCC Requirements 4010012 SPCC in writing, follows code seq/cross ref; HSC 6.6725270.4.5(a); good eng practice, mgt approval, items not in 40 CFR 1112.7 place 4010013 SPCC Plan discusses conformance with all SPCC HSC 6.6725270.4.5(a); rule requirements., & state 40 CFR 1 112.7(a)(1), rules/regs/guidelines. 112. 7(1) 4010014 Environmental Equivalence, if claimed, is HSC 6.6725270.4.5(a); addressed in SPCC, other than for secondary 40 CFR 1 112.7(a)(2) containment. 4010050 PE certified enviro equivalence, HSC 6.6725270.4.5(a); impracticability, and produced water 40 CFR 1 112.6(b)(3); containers/piping, if needed 112.6(b)(4)(iii) 4010051 PE required attestations in the SPCC Plan for HSC 6.6725270.4.5(a); alternative measure claim at a Tier 11 facility 40 CFR 1 112.6(b)(4)(i) Violation VIOL Number Program Requirement Citations Y or N Class Comments 4010016 Physical layout of the facility is adequately and HSC6.6725270.4.5(a); accurately described in SPCC 40 CFR I 112.7(a)(3) 4010041 SPCC Plan addresses the type of oil and HSC 6.6725270.4.5(a); storage capacity for all fixed and portable 40 CFR 1 112.7(a)(3)(i) containers 4010015 SPCC contains an adequate facility diagram HSC 6.6725270.4.5(a); 40 CFR 1 112.7(a)(3) 4010030 SPCC adequately addresses discharge HSC 6.6725270.4.5(a); prevention measures for routine handling, 40 CFR 1 112.7(a)(3)(ii) loading /unloading 4010042 SPCC Plan addressed countermeasures for HSC 6.6725270.4.5(a); discharge discovery, response and cleanup 40 CFR 1 112.7(a)(3)(iv) 4010043 SPCC Plan addresses disposal methods for HSC 6.6725270.4.5(a); recovered materials 40 CFR 1 112.7(a)(3)(v) 4010017 SPCC contains procedures for reporting a HSC 6.6725270.4.5(a); discharge 40 CFR 1 112.7(a)(3) ro (vi); 112.7(a) (4) 4010018 SPCC organized so discharge procedures are HSC 6.6725270.4.5(a); readily usable if the facility has no response 40 CFR 1 112.7(a)(5) plan 4010019 SPCC predicts direction., rate of flow, total HSC 6.6725270.4.5(a); quantity of oil that could be released from a 40 CFR 1 112.7(b) discharge 4010020 SPCC addresses the appropriate general HSC 6.6725270.4.5(a); containment /diversionary 40 CFR 1 112.7(c) structures/equipment 4030037 Appropriate (general) HSC 6.6725270.4.5(a); containment /diversionary 40 CFR 1 112.7(c) structures/equipment have been provided 4010004 Impracticability of containment /diversionary HSC 6.6725270.4.5(a); items, if claimed., is PE demonstrated and 40 CFR 1 112.7(d) certified 4030033 Periodic integrity/leak testing performed with HSC 6.6725270.4.5(a); impracticability claim 40 CFR 1 112.7(d) 4010005 If claiming impracticability of HSC 6.6725270.4.5(a); contain ment/diversionary items a contingency 40 CFR I 112.7(d)(1) plan has been included 4010006 If claiming impracticability written HSC 6.6725270.4.5(a); commitment of manpower, equipment, and 40 CFR 1 112.7(d)(2) materials provided 4010023 Employee training and spill prevention HSC 6.6725270.4.5(a); briefings discussed in SPCC plan 40 CFR 1 112.7(f)(1)., 112.7ffl(3) 4020001 Training provided for op/maint of equip, HSC 6.6725270.4.5(a); 40 CFR 1 112.7(f)(1) discharge procedures, laws/regs, general fac ops, and SPCC 4010022 Person has been designated as accountable for HSC 6.6725270.4.5(a); discharge prevention and reports to 40 CFR 1 112.7(f)(2) -management I I I I I Violation Adequate discussion of all bulk storage HSC b. / 2521U.4.5 (a); VIOL Number Program Requirement Citations Y or N Class Comments 4030040 Spill prevention briefings are conducted HSC 6.67 25270.4.5(a); compatible with the material stored 40 CFR 1 112.8(c)(1) 4010024 SPCC addresses security measures-lighting, HSC 6.67 25270.4.5(a); access to handling/storage, 40 CFR 1 112.7(g) valves/pumps/transfer equip 4030001 Handling areas, valves, pumps/starter HSC 6.67 25270.4.5(a); controls, load/unload connections secured, 40 CFR I 112.7(g) 4030006 lighting adequate 4010025 SPCC adequately discusses facility tank car and HSC 6.67 25270.4.5(a); tank truck loading/unloading rack 40 CFR 1 112.7(h) 4030002 Loading rack containment has capacity to HSC 6.67 25270.4.5(a); 4010026 HSC 6.67 25270.4.5(a); contain single largest compartment of tank 40 CFR 1 112.7(h)(1) areas 4030003 Vehicular departure warning system in place HSC 6.67 25270.4.5(a); 4030017 Buried section of partially buried or bunkered HSC 6.67 25270.4.5(a); at facility with a loading/u n loading rack 40 CFR 1 112.7(h)(2) metallic tank has corrosion protection 4030034 Oil filled operational equipment containment HSC 6.67 25270.4.5(a); standards are met 11 40 CFR 1 112.7(k) SPCC Requirements for Onshore Facilities 4010027 Facility drainage or drainage controls HSC 6.67 25270.4.5(a); adequately discussed 40 CFR 1 112.7(a)(3) 4030035 Facility drainage adequately restrained unless HSC 6.67 25270.4.5(a); conditions met 40 CFR 1 112.8(b)(1) 4030005 Valves used for drainage are manual (not HSC 6.67 25270.4.5(a); flapper-type) to prevent a discharge 40 CFR 1 112.8(b)(2) 4030008 Drainage from undiked areas or diversion HSC 6.67 25270.4.5(a); systems designed to retain final discharge in 40 CFR 1 112.8(b)(3)., facility 4030009 Lift pumps provided for treated drainage HSC 6.67 25270.4.5(a); 40 CFR 1 112.8(b)(5) waters when more than one treatment unit 4010029 Adequate discussion of all bulk storage HSC b. / 2521U.4.5 (a); containers located at the facility 40 CFR1 112.8(c) 4030012 Material and construction of all containers are HSC 6.67 25270.4.5(a); compatible with the material stored 40 CFR 1 112.8(c)(1) 4030010 Adequately sized secondary containment HSC 6.67 25270.4.5(a); provided and maintained for bulk storage 40 CFR 1 112.8(c)(2) containers 4030013 Containment systems are sufficiently HSC 6.67 25270.4.5(a),- impervious to contain oil Rainwater in diked areas is inspected before 40 CFR 1 112.8(c)(2) 4030006 HSC 6.67 25270.4.5(a); Records maintained of drainage from diked 4010026 HSC 6.67 25270.4.5(a); areas 4030017 Buried section of partially buried or bunkered HSC 6.67 25270.4.5(a); metallic tank has corrosion protection 40 CFR 1 112.8(c)(5) 4010028 SPCC discusses procedures to test/inspect storage containers for integrity per industry ~'`----�~`� |standards | _ Violation VIOL Number Program Requirement Citations Y or N Class Comments 4030014 Tanks inspected and tested by qualified person HSC6.6725270-4.5(a); in accordance with industry standards 40 CFR 1 112.8(c)(6) 4030015 Aboveground containers tested or inspected HSC 6.67 25270.4.5(a); for integrity based on industry standards 40 CFR 1 112.8(c)(6) 4010021 Inspection/integrity testing records signed, HSC 6.67 25270.4.5(a); Mo �IJTH kept for 3 years and written inspection 40 CFR 1 112.7(e), 112.8(c)(6) procedures kept 4030018 Steam return/exhaust lines that dischargeto HSC 6.67 25270.4.5(a); watercourse are monitored or have treatment 40 CFR 1 112.8(c)(7) tA system 4010056 SPCC adequately describes overfill prevention 40 CFR 1 112.8(c)(8); methods, and devices/systems used for each HSC 6.67 25270.4.5(a) container 4030019 Each container installation has a liquid level HSC 6. 67 252 70.4.5(a); sensing device. 40 CFR 1 112.8(c)(8)., 112.8(c)(8)(i-iv) 4030022 Liquid level sensing devices regularly tested to HSC 6.67 25270.4.5(a); ensure proper operation 40 CFR 1 112.8(c)(8)(v) 4030023 Discharge from effluent treatment facilities HSC 6.67 25270.4.5(a); which discharge to navigable waterways 40 CFR 1 112.8(c)(9) observed 4030021 Visible discharges promptly corrected and any HSC 6.67 25270.4.5(a); accumulation of oil in diked areas promptly 40 CFR 1 112.8(c)(10) removed. 4030020 Adequate secondary containment provided for HSC 6.67 25270.4.5(a); mobile/portable storage containers 40 CFR I 112.8(c)(11) 4030025 Buried piping is inspected for deterioration if HSC 6.67 25270.4.5(a); exposed and repaired if corrosion damage is 40 CFR 1 112.8(d)(1) found 4030027 Buried piping is corrosion protected with HSC 6.67 25270.4.5(a); protective wrapping, coating, or cathodic 40 CFR 1 112.8(d)(1) protection 4030028 Terminal connection capped/blank flanged at HSC 6.67 25270.4.5(a); ok- transfer point & origin marked if not in 40 CFR 1 112.8(d)(2) service/standby 4030029 Pipe supports designed to minimize abrasion HSC 6.67 25270.4.5(a); and corrosion, and allow for expansion and 40 CFR 1 112.8(d)(3) contraction 4030026 Aboveground valves, piping, and HSC 6.67 25270.4.5(a),- appurtenances are regularly inspected 40 CFR I 112.8(d)(4) 4030030 Integrity/leak tested buried piping when HSC 6.67 25270.4.5(a); installed, modified, constructed, relocated, or 40 CFR 1 112.8(d)(4) replaced 4030031 Vehicle traffic warned of aboveground piping HSC 6.67 25270.4.5(a); or other oil transfer operations A 40 CFR 1 112.8(d)(5) Oil Filled Electrical Equipment 4010037 Oil filled electrical equipment exclusions have HSC6.6725270.2(a)(4) been met, and where not met is included in SPCC plan Violation VIOL Number Program Requirement Citations 9 Y or N Class Comments General Facility Requirements 4010034 Valid permit maintained HSC 6.1125404.1 4010032 Tank Facility Statement or Business Plan has HSC 6.67 25270.6(a)(1), been submitted 25270.6(a)(2) 4040001 Spills/releases of 42 gallons or more of HSC 6.67 25270.8 petroleum reported upon discovery to Cal OES & UPA or 911 4010033 APSA program fee paid HSC 6.67 25270.6(b) 4030036 All/any permanently closed tanks are properly HSC 6.67 25270.4.5(a); closed under the definition in 40 CFR 112.2 40 CFR I 112.1(b)(3)., 4010044 Substantial Harm Criteria certification HSC 6.67 25270.4.5(a); maintained at the facility as required 40 CFR 1 112.20(e) 4010 Administration/Documentation - General 40 CFR 1112; HSC 6.67 Multiple 4015 Administration/Documentation - General Local Ordinance 4020 Training - General HSC 6.67; 40 CFR 1112 Multiple 4025 Training - General Local Ordinance 4030 Operation s/Ma i nte na nce - General HSC 6.67; 40 CFR 1112 Multiple 4035 Operations/Maintenance - General Local Ordinance 4040 Release/Leaks/Spills - General HSC 6.67 Multiple; 40 CFR 1112 4045 Release/Leaks/Spills - General Local Ordinance 4050 Abandonment/illegal Disposal/Unauthorized HSC 6.67 Multiple; 40 Treatment - General CFR 1112 4055 Abandonment/Illegal Disposal/Unauthorized Treatment - General Local Ordinance Comments: -;� There were no violations noted for this inspection O This report shall serve asa "NOTICE TO COMPLY" for Minor Violations, and a "'NOTICE OF VIOLATION"" for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any violations noted, and for those not inspector's corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) 4 % V 'L -Q�